HomeMy WebLinkAboutF10-0067 1
TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970 - 479 -2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
SPRINKLER PERMIT Permit #: F10-0067
Job Address: 720 W LIONSHEAD CR VAIL Status ...: ISSUED
Location • Applied ..: 09/10/2010
Parcel No...: 210107217001 Issued . .: 10/06/2010
Project No : Expires. .:
OWNER DIAMONDROCK VAIL OWNER LLC 09/10/2010
C/O DIAMONDROCK HOSPITALITY CO
6903 ROCKLEDGE DR STE 800
BETHESDA
( MD 20817
APPLICANT WESTERN STATES FIRE PROTECTI 09/10/2010 Phone: 303 - 792 -0022
7026 S TUCSON WAY
ENGLEWOOD
CO 80112
License: 338 -S
CONTRACTOR WESTERN STATES FIRE PROTECTI 09/10/2010 Phone: 303 - 792 -0022
7026 S TUCSON WAY
ENGLEWOOD
CO 80112
License: 338 -S
Desciption: RELOCATE (17), PLUG (5) EXISTING SPRINKLER HEADS DUE TO
RESTAURANT REMODEL. WILL CHANGE ALL HEADS TO CONCEALERS.
Valuation: $6,235.00
************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** FEE SUMMARY ***************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * ** **
Mechanical - -> $0.00 Restuarant Plan Review - -> $0.00 Total Calculated Fees - - -> $696.99
Plan Check - -> $432.00 DRS Fee- > $0.00 Additional Fees > $0.00
Investigation -> $0.00 TOTAL FEES > $696.99 Total Permit Fee >'
$696.99
WilI CaII >
$0.00 Payments > $696.99
BALANCE DUE > $0.00
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE DEPARTMENT
09/14/2010 mvaughan Action: AP
• CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 53
(FIRE 2007) Monitored fire sprinkler system required and shall comply with NFPA
13 (2007) and VFES Standards.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all
}
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970 - 479 -2252
FROM 8:00 AM - 5 PM.
SIGNA RE OF"O R OR CONTRACTOR FOR HIMSELF O O MSE AND OWNER
I
} �11
t €gg
gg
r
_ g
,
,
1
:
[ ,
t,
,
[
,
-
,
,
I
TOWN OF VAIL, COLORADO Statement
********************************************************************************************
Statement Number: R100001481 Amount: $696.99 10/06/201009:02 AM I
Payment Method: Check Init: SAB 1
Notation: 120510 W.S.F.P i
Permit No: F10-0067 Type: SPRINKLER PERMIT
1
Parcel No: 2101-072-1700-1
Site Address: 720 W LIONSHEAD CR VAIL
i
Location: ;
Total Fees: $696.99 I
1
This Payment: $696.99 Total ALL Pmts: $696.99 i
I
Balance: $0.00 1,
i
ACCOUNT ITEM LIST: i
Account Code Description Current Pmts
1
BP 00100003111100 SPRINKLER PERMIT FEES 264.99
I
PF 00100003112300 PLAN CHECK FEES 432.00 1
i
i
1
i
t
i
i
i
,
; f
:
'
i
,
,
; •
I
I
•
1
1
t
i
i
i
1
I ,
1
.•
.,
t ,
,
I
,
•
1
,
i ,
•
!
!
,
!
i
E
t
1
c
I
!
,
[
'
,
,
1
i
g, Department.of Community Development.
•;"�, -�� r 75 South Frontage Road
►': w 1 . , , _ " .x q Vail, Colorado. 81657
Fait'-'.976
b ' S.
- Va11�0 �e
r
FIRE SPRINKLER PERMIT
Commercial & Residential Fire Alarm shop drawings are required at the time of
application submittal and must include the following information:
1. A Colorado Registered Engineer's stamp or N.I.C.E.T level III (min) stamp
2. Equipment cut sheets of materials
3. Hydraulic calculations
4. A State of Colorado contractor registration number
5. Plans must be submitted by a Registered Fire Protection Contractor
P roject Street Address:
1 - 71 5 W• Lro n 3 l ica. d r✓, Q.c I L
(Number) (Street) (Suite #)
Building /Complex Name: 1fA=tL jM/�QiQio
- - -_ OFF. 3 easoo5 ,__s-g -- -
Contractor Information: p
( Company: L0641> i 5��.{s�F��_ I kD"CVA
!Company Address: So Y1. W+A J
11 city — ekt�ktm t State: t0 Zip:
Office Use:
Project #: P�r� �D -1) (o
Building Permit #: r a c / H
Sprinkler Permit #: V j coca /
Lot #: Block # Subdivision:
Detailed Description of Work: kjocjZ )Z �I�5 >
O)Cest.rtA 5RK;VlLJfA_ eud 5 Due- AD
Contact Name: P kA AVrizV\ {ft, l 4o,,�dk J , 1vi11 ckauv, all heA� S f2 Collc
(use additional sheet if necessary)
Contact Phone: 3 � 3� 5 - 1 a - 57 9 7CL
E -Mail woe,. h,agJen 6A 1 5 F9. U S
Town of Vail Contractor Registration No.: 3 3 1 - s
X Ile--( �7 1, , -
Contra or Signatufe (req red)
Property Information
Detailed Location of Work: OFF $eq&v-
�S cuQAKf
Does a Monitored Fire Alarm Exist? Yes ()a No ( )
Does a Sprinkler System Exist? Yes No ( )
Work Class:
Parcel #: a D - O7a2 - 1 - 7 -601
New ( ) Addition( ) Remodel Repair( )
(For parcel #, contact Eagle County Assessors Office at 970 - 328 -8640 or
visit www.eaglecounty.us /patie) Retro -Fit ( } Other ( )
/�
... _
...,...
Tenant Name: M.AfU A - D FF Sea 5 —t. (&s f J - $ Type of Building:
Owner Name: q y11p ►1�. Rp L 1 Single- Family ( ) Duplex ( ) Multi - Family ( )
Commercial ( Restaurant ( ) Other ( )
Complete Valuation for Fire Sprinkler Permit:
Fire Sprinkler $: P � - 3 5- i Date Receive E V IE
I D
4 (09b,g9 SEP o 9 1010
TOWN OF VAIL
of -Feb-to
Western States
Fire Protection Co.
;v30&e'IM* Z�ued aKd �za�
Material Submittal
FOR
Restaurant
715 W. Lionshead Circle
Vail CO 81657
Tenant Finish
Vail Marriott Off Season
D [EC[EOMIE
SEP 0 9 2010 D
TOWN OF VAIL
Prepared by:
Jeff Hagan
Project Manager
Western States Fire Protection Co.
7026 S. Tucson Way
Centennial, CO 80112
Phone (303) 792 -0022
Fax (303) 792 -9049
Cell (303 -549 -9553
Email jeff.hagan @wsfp.us
WSFP #CS0963
August 26, 2010
MATERIAL INDEX
Description Model
I. Sprinkler Heads
A. Quick Response Concealed Automatic Sprinkler
II. Pipe — 1 -1/4" and smaller threaded
A. Black Schedule 40 Pipe
III. Pipe — 1 -1/2" and larger grooved
A. Black Schedule 10 Pipe
IV. Cast Iron Fittings
V. Pipe Hangers (Per NFPA 13)
A. Top Beam Clamps w/ Lock nut
B. All Thread Rod
C. Adjustable Ring Hanger
D. Drop in Concrete Anchors
G4A
Manufacturer
Reliable
ASTM A 795 Varies"
ASTM A 13 5 Varies"
Varies Varies"
Fig 68
Tolco
Fig. 100
Tolco
Fig. 200
Tolco
HDI -P 3/8
Hilti
"Because of the current escalation occurring with steel, WSFP reserves the right to substitute pipe as required to meet
project schedules.
R 1 0
inble
Bulletin 154 Rev.E
Model G4A
Quick Response
Concealed
Automatic Sprinkler
The Concealer
UL Quick Response
FM Standard Response
Concealed Sprinkler With a
%" (13mm) or 1 %" (38mm) Adjustment
Features
1. Cover plate attachment with %" (13mm)
assembly adjustment.
2. Smooth aesthetic ceiling profile.
3. Factory installed protective cap.
4. Available in brass, chrome or black
plated and white painted finishes.
5. Ordinary temperature rating.
6. Multiple orifices for design flexibility.
Approvals & Listings
1. Underwriters Labortories, Inc. (ULY
Quick Response
2. Underwriters Laboratories of Canada (ULC}-
Quick Response
3. Factory Mutual Research Corp. (FMY
Standard Response
• Light Hazard Occupanicies-
No Limitations
• Ordinary Hazard Occupancies
Groups 1 & 2 Wet Systems Only
4. NYC MEA 258 -93-E - Quick Response
U.S. Patent number 4,880,063.
Application
The Reliable Model G4A
Concealer is the most versatile
quick response concealed sprin-
kler available. It provides the best
form of fire protection while
offering an attractive appearance
and 1 /2" (13mm) of cover adjust-
ment for ease of installation. The
small diameter cover plate as-
sembly is easily attached and
blends into the ceiling, concealing
the most dependable fire protec-
tion available, an automatic
sprinkler system.
The Model G4A ConcealerO is designed for use where
aesthetic appearance is important. Offices, hospitals, motels
and restaurants are but a few of the applications where it can be
used. It is available in different orifice sizes allowing the designer
to optimize system performance, thereby achieving a very
efficient installation.
The Model G4A Concealer" is a UL Listed Quick Response
Concealed sprinkler intended for use in accordance with NFPA
13. FM Approves this sprinkler as a standard response
concealed sprinkler intended for use in accordance with FM
Loss Prevention Data Sheet 2 -8N.
Product Description
The Reliable Model G4A Concealer uses a proven quick
response fusible element in a standard style sprinkler frame
with a drop -down deflector. This assembly is recessed into the
ceiling and concealed by a flat cover plate assembly. The
threaded engagement provides ' /z" (13mm) of cover
adjustment. The flat cover plate is attached to the skirt using
1357 (57 °C) ordinary temperature classification solder.
When the ceiling temperature rises, the solder holding the flat
cover plate melts, the flat cover plate released thus exposing
the sprinkler inside to the rising ambient temperature.
The subsequent fusing of the element opens the waterway
and causes the deflector to distribute the water. Any secure
engagement between the cover plate and cup will assure that
the drop -down deflector is properly located below the ceiling.
CP
Do
m
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York, 10552
Installation
Do not install the G4A Concealer in ceilings which have
positive pressure in the space above.
• Cut a Z inch (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model G4 Wrench, The
wrench has drive tangs which insert into the cup slots.
When installing a sprinkler the wrench is first positioned into
the sprinkler /cup assembly until the wrench tangs engage
the drive slots in the top of the cup (there are two sets of
drive slots in the cup). The sprinkler is then tightened into
the pipe fitting. When inserting or removing the wrench from
the sprinkler /cup assembly, care should be taken to prevent
damage to the sprinkler. DO NOT WRENCH ON ANY
OTHER PART OF THE SPRINKLER /CUP ASSEMBLY.
Install the cover plate by hand turning the cover in the
clockwise direction until it is tight against the ceiling.
A protective cap is provided to protect the drop -down sprinkler
deflector from damage which could occur during construction
before the cover plate is installed. The cap is factory installed
inside the sprinkler cup. Remove cap to install sprinkler, then
re- install cap until the cover plate is installed.
Maintenance
The Model G4A Concealer` should be inspected quarterly
and the sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia or any
other cleaning fluids. Remove any sprinkler that has been
painted (other than factory applied) or damaged in any way. A
stock of spare sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to
installation, sprinklers should be maintained in the original
cartons and packaging to minimize the potential for damage to
sprinklers that would cause improper operation or non - operation.
Technical Data
Ordering Information
1. Sprinkler Model
2. Nominal Orifice
3. Flat Cover Plate
Assembly Finish
4. Inlet Type
Cover Plate Finishes"'
Standard Finishes
Bronze
Chrome
Wh ite alnt
Special Application
Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
Other finishes and colors are
available on special order.
Consult factory for details.
Tempera Rating
I�
l
Model G4 Sprinkler
Wrench
UL Listing Category
Sprinklers, Automatic and
Open
Quick Response Sprinkler
UL Guide Number
VNIV
Classification
Sprinkler
Cover
Plate
Max. Ambient
I Temp.
Ordinary
165 °C
13FF/57 °C
1 100 °F /38 °C
Sprinkler Inlet
Total
Adjustment
Nominal
Orifice
Nominal
K Factor
Thread
Approvals
Sprinkler
Identifcation (SIN)
US
Metric
Non Admustable
1 /2" 13mm
1 12" 15mm
5.6
80
1 /2" NPT RYz
1.2,3.4
R5415
Non Adjustable
Yz" 13mm
' 11 mm
4.2
60
1 /2 "NPT RYz
1,2 , 4
R5413
Non A d'ustable
Ye 13mm
" 0 0mm
2.8
40
'/z "NPT R'' /z
1
R5411
Adjustable
1 Yz" 38mm
'/2" 15mm
5.6
80
1" NPT Male or Female
124
R5418
Ad'ustable
1Yz" 38mm
11mm
4.2
60
1" NPT Male or Female
1,2 4
R5413
Adjustable
1' /2" 38mm )
(10mm)
2.8
1 40
1" NPT Male or Female
1,2,4
R5412
'•. v2• ftWC.V
Fa OR ELWW
i - -IT11 I
i
TR
i
aS L R CUP
_
,f
7 J /B' 90.
19 r FACE Or
f'r✓"G r0 CUM
MwwA .WX.
f26
COWR
ASSENBIY �
COYER a0.lU$/IE"r
J 5116
Fig.1 - 1 12" NPT Non - Adjustable Inlet I Fig. 2 - 1" NPT Male- Adjustable Inlet Fig. 3 - 1" NPT Female- Adjustable Inlet
9
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified
and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured b
Rell able e
T{ I'
T _ J
Ir �r I �� - I =
�JI9J ! ! 111E J =__
Wx.KLU "3ME"r
i 4
r�f �MK &
GN � P ��'[[ N I� NP:<
Snu� � 3 �— n vv E"SiOi.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431 -1588 Sales Offices
(800) 848 -6051 Sales Fax
(914) 668 -3470 Corporate Offices
www.reliablesprinkler.com Internet Address
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in USA 05/05. P/N 9999970150
FM Approved and UL Listed Sprinkler Pipe
Bull Moose Tube Company is a recognized producer
of quality pipe products. Our Schedule 10 and
Schedule 40 are FM Approved and UL Listed (for U.S.
and Canada), even though these products do not
require separate approvals and listings. Bull Moose
Tube made the decision to have them approved and
listed for your peace of mind. Our Sch. 10 and Sch. 40
have been through the same rigorous testing as our
other fine pipe products.
Schedule 10 Pi
Nominal
Pipe Size
(in)
1
1 -1 /d
Bull Moose Tube's Sch. 10 and Sch. 40 pipes are
made to ASTM A135 and ASTM A795. These
products are typically supplied with our protective
coating but can be supplied without the coating so
they can be hot -dip galvanized to meet FM
requirements for use in dry systems in accordance
with the zinc coating specifications of ASTM A795 or
ASTM A53.
O.D.
1. D.
Nom. Wall
Weight/Ft
Bundle
(in)
(in)
(in)
2.375
Size
1.315
1.097
0.109
1.40lbs /ft
91
1 R R n
1 lilt)
n In (I
1 o-1 I L.., r#
r1 4
1 -1/2
1.900
1.682
0.109
2.08lbs /ft
61
70
2
2.375
2.157
0.109
2.64lbs /ft
37
51
L- I /L L.0 t Z) L.b155 U. 12U
3 3.500 3.260 0.120
4 4.500 4.260 0.120
3- b3lbs /ft 30
4.33lbs /ft 19
5.62lbs /ft 19
Schedule 40 Pi
Nominal
Pipe Size O.D. I.D. Nom. Wall Weight/Ft Bundle
(in) (in) linl linl ciao
1 -1/2 1.900 1.610 0.145 2.72lbs /ft 44
2 2.375 2.067 0.154 3.65lbs /ft 30
PIPE PREPARATION
For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak -tight seat for the gasket, pipe surfaces should be
free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt, chips, grease, and rust must be removed prior
to installation. Failure to take these important steps may result in improper coupling assembly, causing leakage. Also, check the manufacturer's
instructions for the specific fitting used.
/1819 Clarkson Road For additional information, c �� us
Chesterfield, MO 63017 contact your salesperson today at
J BULL MOOSE TUBE COMPANY (800) 325 -4467 (800) 325 -4467 or (636) 537 -2600 LISTED
CJ FAX: (636) 537 -2645 in the USA, or from Canada
www.bullmoosetube.com call (800) 882 -4666 FM
A CR 8 O company e -mail: info n bullmoosetube.com
APPROVED
All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation
02/03
1
1.315
1.049
0.133
1.68lbs /ft
70
1 -1/4
1.660
1.380
0.140
2.27lbs /ft
51
1 -1/2 1.900 1.610 0.145 2.72lbs /ft 44
2 2.375 2.067 0.154 3.65lbs /ft 30
PIPE PREPARATION
For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak -tight seat for the gasket, pipe surfaces should be
free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt, chips, grease, and rust must be removed prior
to installation. Failure to take these important steps may result in improper coupling assembly, causing leakage. Also, check the manufacturer's
instructions for the specific fitting used.
/1819 Clarkson Road For additional information, c �� us
Chesterfield, MO 63017 contact your salesperson today at
J BULL MOOSE TUBE COMPANY (800) 325 -4467 (800) 325 -4467 or (636) 537 -2600 LISTED
CJ FAX: (636) 537 -2645 in the USA, or from Canada
www.bullmoosetube.com call (800) 882 -4666 FM
A CR 8 O company e -mail: info n bullmoosetube.com
APPROVED
All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation
02/03
Fig. 68 - Wide Throat Top Beam "C" Clamp w /Locknut
Size Range — 3/8" thru 3/4" rod
Function — For attachment to structural shapes requiring
wider throat especially under roof with bar joist construction.
This clamp may be used in the set screw down position only.
Approvals — Conforms to Federal Specification
WW -H -171 E, Type 23 and Manufacturers Standardization
Society SP -69, Type 19.
Finish — Plain
Note — Available in Electro- Galvanized finish.
Order By — Figure number, rod size and finish
Note — Do not over tighten set screw.
Dimensions • Weights
Rod
Max. Rec.
Approx.
Size
Load Lbs.
Wt. /100
3/8
400
34
1/2
500
50
5/8
600
53
3/4
800
86
f• .
K• °
�• r'r
E
r 0
�- °�.' .\ /•r Jam• /'`
OFFICEIMANUFACTURING FACILITY - 1375 SAMPSON AVE. - CORONA, CA 92879 - PH: 951.737.5599 - FAX: 951.737.0330
CUSTOMER SERVICE - 800386.5266
www.tolco.com
Fig Rod Stiffener
Size Range — Sec 3/8" thru 7/8" hanger rod
Material — Carbon Steel
Function — Secures channel to han rod for vertical seismic bracing.
Approvals — Underwriters Laboratories Lis the USA (UL) and
�
Canada (cUL). Included in our Se ismic Restraints nn annr�vlsri
Finish — Electro Galy r
Note — Avail In HDG finish or Stainless Steel materials.
Ord — Figure number
-a
i
All Thread Rod Cut to Length
Size Range — SecL 8" thru 7/8" rod in
1" increments
Material — Carbon Steel
Maximum Temperature — 750 °F
Finish — Plain
Note — Available in Electro - Galvani d
HDG finish or Stainless S aterials.
Order By — F number, rod diameter, rod
len finish
Fig. 100 -All Thread Rod Full Lenqths
Size Range — Secures 3/8" thru 7/8" rod in
10' lengths
Material — Carbon Steel
Maximum Temperature — 750 °F
Finish — Plain
Note — Available in Electro- Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter
and finish
Dimensions -Weights
Max Rec. Load Lbs.
Rod For Service Temps Approx.
Size 650 °F 750 °F Wt. /100
1/4
240
215
12
3/8
610
540
29
112
117
1010
5
5/8
1810
1610
84
3/4
2710
2420
123
7/8
3770
3 360
169
1 4960 4420 222
1 '/4 8000 7140 360
1 1 h 11630 10370 510
Component of State of
California OSHPD Approved C -LISTED
Seismic Restraints Svste
Dim
nsi'6n - Weights
—1�o_d
Max. Rec. Load Lbs.
Size
For Service Temps
650 °F 750 °F
3/8
610 540
112
1130 1010
5/8
1810 1610
2710 2420
7/8
770 3360
OFFICE /MANUFACTURING FACILITY - 1375 SAMPSON AVE. - CORONA, CA 92879 - PH: 951.737.5599 - FAX: 951.737.0330
- CUSTOMER SERVICE - 800.786.5266
www.tolco.com
Fig. 200 - "Trimline" Adjustable Band Hanger
Size Range — 1/2" thru 8" pipe
Material — Carbon Steel, Mil. Galvanized to G90
specifications
Function — For fire sprinkler and other general pipin
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features —
• (1/2" thru 2 ") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe fro
abrasion. Captured design keeps adjusting nut
from separating with hanger. Hanger is easily
installed around pipe.
• (2'/2" thru 8" Spring tension on nut holds it
securely in hanger before installation. Adjustinc
nut is easily removed.
Approvals — Underwriters' Laboratories listed (1/2"
thru 8 ") in the USA (UL) and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineerir
Approved (3/4" thru 8 "). Conforms to Federal
Specifications WW -H -171 E, Type 10 and Manufacture
Standardization Society SP -69, Type 10.
Maximum Temperature — 650 °F
Finish — Mil. Galvanized. For Stainless Steel materi-
als, order TOLCOTm Fig. 200WON.
Order By — Figure number and pipe size
Dimensions -Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. Length
1/2 3/8 8mm or 10mm 3'A 2 /a 400 11
1 1 /4 3/8 8mm or 10mm 3 2 400 13
1 1 h 3/8 8mm or 10mm 3� 2 400 14
2 3/8 8mm or 10mm 4� 3 400 15
3/4 3/8 8mm or 1Omm 3 2 400 11
1 3/8 8mm or 10mm 3 2 400 12
G UL US LISTED
FM
Zr°
3/6
10mm
5
4'A
600
27
3
3/8
1Omm
5
4
600
29
3
3/8
1Omm
7
5
600
34
4
3/8
10mm
7
5
1000
35
5
1/2
12mm
9�/8
6
1250
66
6
1/2
12mm
10/8
6
1250
73
8
1/2
12mm
13
8
1250
136
OFFICEWANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA. CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.toico.com
— r I uw v nv�i i rirc
EL E Anchoring Systems
4.3.6 1 HDI -P Drop -In Anchor
4.3.6.1 Product Description
The Hihi HDI -P Drop -In anchor is an internally threaded, flush mounted expansion anchor for
solid and hollow concrete.
Product Features
• Optimized 3/4" anchor length to allow reliable fastenings in hollow core panels, precast plank & post tensioned slabs
• Shallow drilling enables fast installation
• Lip provides flush installation, consistent anchor depth and easy rod alignment
• Setting tool leaves mark on flange when anchor is set properly to enable inspection & verification of proper expansion
Guide Specifications
Expansion Anchor. Expansion anchors shall be flush or shell type and zinc plated in accordance with ASTM 8633, SC 1, Type Ill. Anchors shall be Hilti HDI -P
anchors as supplied by Hilti, Inc., Tulsa, OK.
Installation: Install shell or flush type anchors in holes drilled with Hilti carbide tipped drill bits. Install anchors in accordance with manufacturer's
recommendations.
Listings /Approvals
Approvals
• Factory Mutual (FM)
• International Conference of Building Officials (ICBO ES) Evaluation Report No. 5264
• City of Los Angeles (COLA) Research Report No. 25350
4.3.6.2 Material Specifications
HDI -P Carbon Steel material meets the requirements of AISI 111 OM orAlSl 1010
Zinc plated for corrosion protection in accordance with ASTM B633, SC 1, Type III
4.3.6.3 Technical Data
HDI -P Specification Table
Description
Length
in. (mm)
Bit Size
in.
Average Ultimate Loads, lb (kN)
Allowable Loads, lb (kN)
4000 psi (27.6 MPa) Concrete
Hollow Care
4000 psi (27.6 MPS Concrete
Hollow Care
Tension
Shear
Tension
Shear
Tension
Shear
Tension I
Shear
HDI -P 3 /8
3 /4 (19.1)
1 /2'
1900 (8.5)
j 3000 (13.3)
2100 (9.3)
14000 (17.8)
380 (1.7)
600 (2.7)
420 (1.9)
J 800 (3.6)
4.3.6.4 Installation Instructions
see
\S M
1. Set depth gauge 2. Hammer -drill 3. Clean hole. 4. Insert anchor. 5. Insert setting tool and 6. Collar of setting tool will
on drill. hole. strike with hammer leave an indentation on
until anchor is fully set. flange of anchor when
4.3.6.5 Ordering Information property expanded.
HDI -P Products Setting Tools for HDI -P Anchors
Description
Item No.
Box Qty
HDI -P 3 /a
00243554
100
Description
Item No.
HSD -G 3 /e" — 3 /4" Setting Tool w/ hand guard
00247776
HST -P 3 /8" — 3 /4" Setting Tool
00253784
174 U5: 1 -SOD- 879 -8000 / www.us.hilti.com I Hilti Product Technical Guide 2002 1 Canada: 1- 800 - 363 -4458 / www.ca.hilti.com