July 7, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (D-O)-(40-42.5) form 0' to 2' and on the Upper Basement Level at Gridlines (B-H)-(28-
31) from 8' to 12' and at Gridlines N-29 from 4' to 8'. We observed the placement of CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder
placement, and the overall condition of the walls. Based on our observations the CMU walls
appeared to be constructed in general accordance with the project plans and specifications.
Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 8, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (D to O)-(40 to 43) from 2' to 4', (N.6 to S)-(34.2 to 36) from 0' to 4' on the north wall
and from 0' to 2' on the south wall, and on the Upper Basement Level at Gridlines G.8-29 from
0' to 2' and at (N to S)-28 from 0' to 2'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the walls. Based on our observations the CMU walls appeared to be placed
in general accordance with the project plans and specifications. Grant with PCL was informed
of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 9, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (D to O)-(40 to 43) from 4' to 8', (N.6 to S)-(34.2 to 36) from 2' to 4' on the south wall,
and on the Upper Basement Level at Gridlines G.8-29 from 2' to 4'. We observed the
placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap
splices, ladder placement, and the overall condition of the walls. Based on our observations the
CMU walls appeared to be placed in general accordance with the project plans and
specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 13, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (O to S)-(40 to 42) from 0' to 2', and on the Upper Basement Level at Gridlines G.8-29
from 4' to 8'. We observed the placement of CMU, mortar, bond beams, reinforcing steel bar
size, spacing, clearances, lap splices, ladder placement, and the overall condition of the walls.
Based on our observations the CMU walls appeared to be placed in general accordance with
the project plans and specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 14, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (O to S)-(40 to 42) from 2' to 4', at Grid�ines N-29.5 from 0' to 4', and on the Upper
Basement Level at Gridlines G.8-29 from 8' to 12'. We observed the placement of CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder
placement, and the overall condition of the walls. Based on our observations the CMU walls
appeared to be placed in general accordance with the project plans and specifications. Grant
with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 15, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (D to O)-(40 to 43) from 8' to 12', (N.6 to S)-(34.2 to 36) from 4' to 8', (O to S)-(40 to
42) from 4' to 8', and on the Upper Basement Level at Gridlines (N to S)-28 from 4' to 8'. We
observed the placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing,
clearances, lap splices, ladder placement, and the overall condition of the walls. Based on our
observations the CMU walls appeared to be placed in general accordance with the project plans
and specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 17, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (O to S)-(40 to 42) from 8' to 12', and on the Upper Basement Level at Gridlines N.3-
28.2 from 0' to 4'. We observed the placement of CMU, mortar, bond beams, reinforcing steel
bar size, spacing, clearances, lap splices, ladder placement, and the overall condition of the
walls. Based on our observations the CMU walis appeared to be placed in general accordance
with the project plans and specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 21, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Upper Basement Level
at Gridlines KK to TT.9 and 7 to 16 from 0' to 2', (M-R)-28 from 8' to 12', and H-31 from 0' to 2'.
We observed the placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing,
clearances, lap splices, ladder placement, and the overall condition of the walls. Based on our
observations the CMU walls appeared to be constructed in general accordance with the project
plans and specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 22 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Upper Basement Level
at Gridlines KK to TT.9 and 7 to 16 from 2' to 4', H-31 from 2' to 4', an on the Terrace Level at
Gridlines (B.9-D)-(43-48) from 0' to 2'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications. Grant with PCL
was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tei:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 24 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Upper Basement Level
at gridlines KK to TT.9 and from 7 to 16 from 4' to 8', H-31 from 4' to 8', and on the Terrace
Level at Gridlines (B.9-D)-(43-48) from 2' to 4'. We observed the placement of CMU, mortar,
bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and
the overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications. Grant with PCL
was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 29, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridline (B-D)-(43-48) from 4' to 8' and on the Upper Basement Level at Gridlines (AAA.2-
EEE.9)-(6-15) from 0' to 2', and H-30 from 8' to 12'. We observed the placement of CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splice, ladder
placement, and the overall condition of the walls. Based on our observations the CMU walls
appeared to be constructed in general accordance with the project plans and specifications.
Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
July 31, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman Wet on the Upper Basement Level
at Gridlines (AAA.2-EEE.9)-(6-15) from 2' to 4'. We observed the p�acement of CMU, mortar,
bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and
the overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and site specifications. Grant with
PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 4, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU by Vogelman West on the Upper Basement Level at
Gridlines (AAA.2-EEE.9)-(6-15) from 4'-8', C.5-49.1 from 4'-8' and TT.5-8 from 8'-12'. We
observed the placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing,
clearances, lap splices, ladder placement, and the overall condition of the walls. Based on our
observations the CMU walls appeared to be constructed in general accordance with the project
plans and specifications. Eric with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 6, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Upper Basement Level
at Gridlines AAA.2-EEE.9, 6-15.2 from 8' to 12'. We observed the placement of CMU, mortar,
bond beam, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and
the overall condition of the walls. The CMU walls appeared to be constructed in general
accordance with the project plans and specifications. Eric with PCL was informed of our
observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 11, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Upper Basement Level
at Gridlines (AAA-GGG.9)-(1.3-3) from 0' to 2' and (HHH-UUU)-(1.2-1.5) from 4' to 8'. We
observed the placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing,
clearances, lap splices, ladder placement, and the overall condition of the walls. Based on our
observations the CMU walls appeared to be constructed in general accordance with the project
plans and specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 12, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Upper Basement Level
at Gridlines (AAA-GGG.9)-(1.3-3) from 2' to 4' and on the Lower Basement at Gridlines (EEE.7-
57.2) from 0' to 4'. We observed the placement of CMU, mortar, bond beams, reinforcing steel
bar size, spacing, clearances, lap splices, ladder placement, and the overall condition of the
walls. Based on our observations the CMU walls appeared to be constructed in general
accordance with the project plans and specifications. Grant with PCL was informed of our
observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721