August 13, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Upper Basement Level
at Gridlines (HHH-NNN)-(13-15) from 0' to 4' and at EEE-11.5 from 4' to 8'. We observed the
placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap
splices, ladder placement, and the overall condition of the walls. Based on our observations the
CMU walls appeared to be constructed in general accordance with the project plans and
specifications. Jeff with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 14, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman west at gridlines (EEE.8-JJJ)-23.4
from 0'-4'. We observed the placement of CMU, mortar, bond beams, reinforcing steel bar size,
spacing, clearance, lap splice, ladder placement, and the overall condition of the walls. The
CMU walls appear to be constructed in general compliance with site specifications. Jeff with
PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 17, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines (EEE.8-JJJ)-23.4 from 4' to 8'. We observed the placement of CMU, mortar,
bond beams, reinforcing steel bar size, spacing, clearance, lap splice, ladder placement, and
the overall condition of the wall. Based on today's observations the CMU wall appears to be
constructed in general compliance with the site plans and specifications.
In addition, we observed holes drilled by PCL into existing slab on Terrace Level at
Gridlines S-28.5. PCL utilized a wire brush and vacuum to clean the holes. We observed the
holes for depth, diameter, and overall cleanliness. Due to the thickness of the concrete the
holes were approx. 2.5"-3" in depth for #6 bar where manufacturer specifications call for 4"
depth for#6 bar using Hilty RE500 epoxy. Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 18, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (EEE.8-GGG.9)-23.5 from 0' to 4', Q-34.2 from 0' to 4', and on the Upper Basement
Level at Gridlines (AAA-KKK)-(1.3-3) from 4' to 8'. We observed the placement of CMU, mortar,
bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and
the overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications.
Additionally, we observed holes drilled into the existing slab by PCL on the Terrace Level at
Gridlines (A-D)-(35-42). PCL utilized a wire brush and a shop vacuum to clean the holes. We
observed the holes for depth, diameter, and the overall cleanliness. The holes appeared to be in
general accordance with the project plans and specifications of 3" depth for #4 bars using Hilty
RE500 epoxy. Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 19, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines (EEE.8-GGG.9)-23.5 from 4' to 8'. We observed the placement of CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, and lap splices, ladder
placement, and the overall condition of the wall. The CMU wall appeared to be constructed in
general accordance with the project plans and specifications. Grant with PCL was informed of
our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 20, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Upper Basement Level
at Gridlines (AAA-KKK)-(1.3-3) from 8' to 12'. We observed the placement of CMU, mortar,
bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and
the overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 24, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (A-D)-(35-42) from 0' to 2'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications.
In addition, we observed holes drilled by PCL into the existing slab on the Upper Garage Level
for the pump core block out at gridlines U-35 and for shear wall #5 beam on Level 6. PCL
utilized a wire brush and a shop vacuum to clean the holes. We observed the holes for specified
depth, diameter, and the overall cleanliness of the holes. The holes for the pump core block out
appeared to be in general accordance with the project plans and specifications of 4 '/2" depth for
#4 bar using Hilty HY150 Epoxy. The holes on level 6 appeared to be in general accordance
with the project plans and specifications of 6 3/4" depth for #6 bar using Hilty HY150 Epoxy.
Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 25, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (A-D)-(35-42) from 2' to 4', at Gridlines (T-Z)-(16-29) from 0' to 2', and on the Lower
Garage Level at Gridlines EEE.7-57.2 from 4'-8'. We observed the placement of CMU, mortar,
bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and
the overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications.
In addition, we observed holes drilled by PCL into the existing slab on the Terrace Level at
Gridlines Y-15.5. PCL utilized a wire brush and a shop vacuum to clean the holes. We observed
the holes for specified depth, diameter, and the overall cleanliness of the holes. The holes
appeared to be in general accordance with the project plans and specifications of 4" depth for
#6 bar using Hilty RE500 Epoxy. Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 26, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (T-Z)-(16-29) from 2' to 4'. We observed the placement of CMU, mortar, bond beams,
reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the overall
condition of the walls. Based on our observations the CMU walls appeared to be constructed in
general accordance with the project plans and specifications.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
August 27, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was present to perform
materials testing. We observed CMU placed by Vogelman West on the Terrace Level at
Gridlines (A-D)-(35-42) from 4' to 8'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 1, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines (Z-DDD)-15 at 0' to 2'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the wall. The CMU walls appeared to be constructed in general accordance
with the project plans and specifications. Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Marvin Troxel
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tei:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 2, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines (Z-DDD)-15 at 2' to 4'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the wall. The CMU walls appeared to be constructed in general accordance
with the project plans and specifications. Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tei:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 3, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines (Z-DDD)-15 at 4' to 8' and at Gridlines (GGG.9-NNN.4)-23.5 from 0' to 4'. We
observed the placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing,
clearances, lap splices, ladder placement, and the overall condition of the wall. The CMU walls
appeared to be constructed in general accordance with the project plans and specifications.
Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 4, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines (ZZ.9-DDD)-(23.5-29) from 0' to 2' and at Gridlines (GGG.9-NNN.4)-23.5 from
4' to 8'. We observed the placement of CMU, mortar, bond beams, reinforcing steel bar size,
spacing, clearances, lap splices, ladder placement, and the overall condition of the wall. The
CMU walls appeared to be constructed in general accordance with the project plans and
specifications. Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 8, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines (ZZ.9-DDD)-(23.5-29) from 2' to 4' and at Gridlines DDD-(15-23.5) from 0' to
2'. We observed the placement of CMU, mortar, bond beams, reinforcing steel bar size,
spacing, clearances, lap splices, ladder placement, and the overall condition of the wall. The
CMU appeared to be in general accordance with the project plans and specifications. Andy with
PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 10, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines DDD-(15-23.5) from 2' to 4'. We observed the placement of CMU, mortar,
bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and
the overall condition of the wall. The CMU appeared to be in general accordance with the
project plans and specifications. Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 11, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines (ZZ.9-DDD)-(15-29) from 4' to 8'. We observed the placement of CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder
placement, and the overall condition of the wall. The CMU appeared to be constructed in
general accordance with the project plans and specifications. Andy with PCL was informed of
our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 15, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines AAA-DDD/25.8-29.8 from 8' to 12'. We observed the placement of CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder
placement, and the overall condition of the walls. Based on our observations the CMU walls
appeared to be constructed in general accordance with the project plans and specifications.
Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 17, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Lower
Basement Level at Gridlines N.3/28.5 from 4' to 8' and on the Terrace Level at Gridlines
EEE.9/25.8 from 0' to 2'. We observed the placement of CMU, mortar, bond beams, reinforcing
steel bar size, spacing, clearances, lap splices, ladder placement, and the overall condition of
the walls. Based on our observations the CMU walls appeared to be in general accordance with
the project plans and specifications. Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 18, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Upper
Basement Level at Gridlines N.3/28.5 from 8' to 12' and on the Terrace Level at Gridlines
EEE.9/25.8 from 2' to 4'. We observed the placement of CMU, mortar, bond beams, reinforcing
steel bar size, spacing, clearances, lap splices, ladder placement, and the overall condition of
the walls. Based on our observations the CMU walls appeared to be constructed in general
accordance with the project plans and specifications. Andy with PCL was informed of our
observations.
We also picked previous►y cast concrete cylinders and transported them to our laboratory for
future compressive strength testing; results will be forwarded upon completion.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 21, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on Level 1 at
Gridlines JJ-AAA/20-29 from 0' to 4'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications. Grant with PCL
was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 22, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines EEE.9/25.8 from 4' to 8'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the walls. Based on our observations the CMU walls appeared to be
constructed in general accordance with the project plans and specifications. Andy with PCL
was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
September 30, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on Level 1
between Gridlines JJ.O-VV.O/20.0-28.0 from 4' to 8'. We observed the placement of CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder
placement, and the overall condition of the walls. Based on our observations the CMU walls
appeared to be constructed in general accordance with the project plans and specifications.
Andy with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 5, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on Level 1
between Gridlines JJ.O-VV.O/20.0-28.0 from 8' to 12'. We observed the placement of CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder
placement, and the overall condition of the walls. We observed several horizontal bond beam
bars missing at various locations. No one with Vogelman West was present. Grant with PCL
was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721