October 7, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We re-observed CMU placed by Vogelman West on Level 1
between Gridlines JJ.O-YY.O/18.0-28.0 from 8' to 12'. We observed that Vogelman West had
corrected the discrepancies listed on 10/5/2009 report. The CMU walls appeared to be
constructed in general accordance with the site specifications. Andy with PCL was informed of
our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 13, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on Level 1 at
Gridlines SSS.4/40.3-43.0, 34.0-35.0, & 26.0-29.8 from 0' to 4'. We observed the placement of
CMU, mortar, bond beams, reinforcing steel bar size, spacing, clearance, lap splices, ladder
placement, and the overall condition of the walls. We observed that the wall at Gridlines
SSS.4/26.0-29.8 was missing all vertical and horizontal reinforcing steel. The walis at Gridlines
SSS.4/34.0-35.0, and SSS.4/40.3-43.0 appeared to be in general accordance with the project
plans and specifications. No one from Vogelman West was present. We informed Andy with
PCL of our observations and he informed us that he would notify Vogelman West of the
discrepancies.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 19, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU pillars at AAA.O-HHH.O/21.0 Level 1.
Vogelman West was constructing pillars at 4-8'. The CMU walls appeared to be placed in
general accordance with t he project plans and specifications.
Sincerely,
GROUND Engineering Consultants, Inc.
Stephen Buckeridge
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 22, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on Level 1 at
Gridlines SSS.3/31.0 and 37.9 from 0' to 6'. We observed the placement of CMU, mortar, bond
beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the
overall condition of the walls. We observed that Vogelman West had not placed a bond beam
or horizontal reinforcing steel at the 4' elevation of the walls. Based on our observations the
CMU walls were not in general accordance with the site specifications. Andy and Grant with
PCL were informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 23, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on Level 1 at
Gridlines SSS.3/31.0 and 37.9 from 0' to 6'. We observed that Vogelman West had corrected
the discrepancies listed on 10/22/2009 report. Based on our observations the CMU walls
appeared to be in general accordance with the site specifications. Andy with PCL was informed
of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 27, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level balconies at Gridlines UUU.O/7.0-10.0 and UUU.O/R6.0-R7.0 from 0' to 4'. We observed
the placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap
splices, ladder placement, and the overall condition of the walls. Based on our observations the
CMU walls appeared to be in general accordance with the site specifications. Grant with PCL
was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 28, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level balconies at Gridlines UUU.O/7.0-10.0 and UUU.O/R6.0-R7.0 from 4' to 8'. We observed
the placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap
splices, ladder placement, and the overall conditions of the walls. Based on observations the
CMU walls appeared to be constructed in general accordance with the project plans and
specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 29, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level balcony at Gridlines UUU.O/1.5-6.0 from 0'-4'. We observed the placement of the CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder
placement, and the overall condition of the walls. Based on our observations the CMU walls
appeared to be in general accordance with the site specifications. Grant with PCL was
informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
October 30, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level balcony at Gridlines UUU.O/1.5-6.0 from 4' to 8'. We observed the placement of the CMU,
mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap splices, ladder
placement, and the overall condition of the walls. Based on our observations the CMU walls
appeared to be in general accordance with the site specifications. Grant with PCL was
informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
November 3, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines UUU.O/1.3-1.4 and AAA.O-GGG.O/1.3-1.4 from 0' to 4'. We observed the
placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap
splices, ladder placement, and the overall condition of the walls. Based on our observations the
CMU walls appeared to be constructed in general accordance with the project plans and
specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
November 4, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Garden
Level through Gridlines 1.3/UUU.O to 1.4/DDD.O-EEE.O at 4' to 8' high. The CMU walls were
observed for specified bar size, spacing, ladder beams, and overall condition of the walls.
Based on our observations the CMU walls appeared to be constructed in general accordance
with the project plans and specifications. Kristen with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Marvin Troxel
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
November 6, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines AAA.2 and GGG.9/71.0 from 0' to 4', and on Level 1 at Gridlines C.0-
D.0/49.0-54.0 from 0' to 2'. We observed the placement of CMU, mortar, bond beams,
reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the overall
condition of the walls. Based on our observations the CMU walls appeared to be constructed in
general accordance with the project plans and specifications. Grant with PCL was informed of
our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
November 10, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines AAA.2 and GGG.9/71.0 from 4' to 8', and unit 105 balcony from 0' to 4', Level
1 Gridlines C.0-D.0/49.0-54.0 from 2' to 4', and unit 105 balcony from 0' to 4'. We observed the
placement of CMU, mortar, bond beams, reinforcing steel bar size, spacing, clearances, lap
splices, ladder placement, and the overall condition of the walls. Based on our observations the
CMU walls appeared to be constructed in general accordance with the project plans and
specifications. Grant with PCL was informed of our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
November 11, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Terrace
Level at Gridlines AAA.2 and GGG.9/71.0 from 8' to 12' and on Level 1 at Gridlines C.0-
D.0/49.0-54.0 from 4' to 8'. We observed the placement of CMU, mortar, bond beams,
reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, an d the overall
condition of the walls. Based on our observations the CMU appeared to be constructed in
general accordance with the project plans and specifications. Grant with PCL was informed of
our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative
South Metro Office North Metro Office Gypsum Office
41 Inverness Drive East 7393 Dahlia Street, P.O. Box 464
Englewood,CO 80112-5412 Commerce City,CO 80022-1834 Gypsum,CO 81637
Tel:(303)289 1989 TeI:(303)289 1989 Tel:(970)524 0720
Fax: (303)289 1686 Fax:(303)289 6742 Fax:(970)524 0721
������
EN�INEERIIVG C�NSIJLTFINTS
November 13, 2009
Job Name: Materials Testing, Ritz Carlton
Residences, Vail, Colorado
Job Number: 08-6502
Vail Resorts Development Company
953 S. Frontage Rd. West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O' Kelly,
As requested, a GROUND Engineering Consultants representative was on site to perform
construction materials testing. We observed CMU placed by Vogelman West on the Lower
Basement Level for elevator #7 door from 0' to 4' and on the Terrace Level at Gridlines AAA.2
and GGG.9/71.0 from 12' to 16'. We observed the placement of CMU, mortar, bond beams,
reinforcing steel bar size, spacing, clearances, lap splices, ladder placement, and the overall
condition of the walls. Based on our observations the CMU walls appeared to be constructed in
general accordance with the project plans and specifications. Grant with PCL was informed of
our observations.
Sincerely,
GROUND Engineering Consultants, Inc.
Kevin McClure
Field Representative