HomeMy WebLinkAbouttube Colmn FP �RVir�n
ENGINEERING C�NSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 3/19/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 1
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Level 1, Gridline NNN,71 Location:
� 4 MEASUREMENTS � Thickness #1 InCheS
AT EACH END OF Thickness #2 inches
� 12-INCH LENGTH �,
'��. /�� Thickness #3 inches
2 4 2 4 Thickness #4 inches
��`-
� �� Thickness #5 inches
3, 3� Thickness #6 inches
Thickness #7 inches
Thickness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 1 7/16 1.) 1 7/16 Thickness #10 inches
2.) 1 6/16 2.) 1 4/16 Thickness #11 inches
3.) 1 1/16 3.) 1 2/16 Thickness #12 inches
4.) 1 7/16 4.) 1 6/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs) 16.2
Average Thickness (inches) 1 5/16 Density (pcf) 28.0
Specified Thickness (inches) min. 1 3/16 Specified density (pc� min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 22 Ibs.
Adhesion (psf) 381.9 Specified adhesion (psf) min. 150
NOtes: Please not Adhesion tests were performed on 4/28/2009.
Field Representative: Eric Mocko
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 3/19/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 2
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Level 2, Gridline NNN/71 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 1 5/16 1.) 1 4/16 Thickness #10 inches
2.) 1 7/16 2.) 1 4/16 Thickness #11 inches
3.) 1 7/16 3.) 1 4/16 Thickness #12 inches
4.) 1 4/16 4.) 1 6/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (g) 24.1
Average Thickness (inches) � 1 5/16 Density (pcf) 20.0
Specified Thickness (inches) min. 1 3/16 Specified density (pc� min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Level 2, Gridline NNN/71 Area of specimen: 0.0576 sq.ft.
Recorded force: 13 /bs.
Adhesion (psf) 226 Specified adhesion (psf) min. 150
Notes: Adhesion tests were performed on 4/28/2009.
Field Representative: Eric Mocko
�RVir�n
ENGINEERING C�NSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 3/19/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 3
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Level 3, Gridline NNN/71 Location:
� 4 MEASUREMENTS � Thickness #1 InCheS
AT EACH END OF Thickness #2 inches
� 12-INCH LENGTH �,
'��. /�� Thickness #3 inches
2 4 2 4 Thickness #4 inches
��`-
� �� Thickness #5 inches
3, 3� Thickness #6 inches
Thickness #7 inches
Thickness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 1 5/16 1.) 1 5/16 Thickness #10 inches
2.) 1 7/16 2.) 1 6/16 Thickness #11 inches
3.) 1 7/16 3.) 1 4/16 Thickness #12 inches
4.) 1 7/16 4.) 1 5/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs) 0.0000
Average Thickness (inches) 1 6/16 Density (pc�
Specified Thickness (inches) min. 1 3/16 Specified density (pc� min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 13 Ibs.
Adhesion (psf) 226 Specified adhesion (psf) min. 150
NOtes: Adhesion tests were performed on 4/28/2009
Field Representative: Eric Mocko
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 4/28/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 4
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Level 4, Gridline NNN/71 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 1 7/16 1.) 1 4/16 Thickness #10 inches
2.) 1 5/16 2.) 1 5/16 Thickness #11 inches
3.) 1 7/16 3.) 1 4/16 Thickness #12 inches
4.) 1 4/16 4.) 1 7/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs) 0.0000
Average Thickness (inches) � 1 5/16 Density (pcf)
Specified Thickness (inches) min. 1 3/16 Specified density (pcf) min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 20 /bs.
Adhesion (psf) 347 Specified adhesion (psf) min. 150
Notes: Please note Adhesion tests were performed on 5/15/2009.
Field Representative: Kevin McClure
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 6/8/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 5
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Level 5, Gridline FF-61 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 1 4/16 1.) 1 4/16 Thickness #10 inches
2.) 1 5/16 2.) 1 5/16 Thickness #11 inches
3.) 1 7/16 3.) 1 4/16 Thickness #12 inches
4.) 1 7/16 4.) 1 7/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs) 0.0000
Average Thickness (inches) � 1 5/16 Density (pcf)
Specified Thickness (inches) min. g/16 Specified density (pcf) min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 14 /bs.
Adhesion (psf) 243 Specified adhesion (psf) min. 150
Notes: Adhesion test performed on 6/18/09
Field Representative: Kevin McClure
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 6/26/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 6
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Level 5, Gridline S-65.8 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 1 12/16 1.) 1 12/16 Thickness #10 inches
2.) 1 13/16 2.) 1 14/16 Thickness #11 inches
3.) 1 12/16 3.) 1 11/16 Thickness #12 inches
4.) 1 13/16 4.) 1 14/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs) 0.0000
Average Thickness (inches) + 1 13/16 Density (pcf)
Specified Thickness (inches) min. 1 11/16 Specified density (pcf) min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 22 /bs.
Adhesion (psf) 381.9 Specified adhesion (psf) min. 150
Notes: Adhesion test performed on 7-7-2009
Field Representative: Kevin McClure
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 9/14/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 7
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Roof, Gridlines JJJ-65.1 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 10/16 1.) 10/16 Thickness #10 inches
2.) 9/16 2.) 11/16 Thickness #11 inches
3.) 10/16 3.) 9/16 Thickness #12 inches
4.) 12/16 4.) 11/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs) 0.0000
Average Thickness (inches) � 10/16 Density (pcf)
Specified Thickness (inches) min. g/16 Specified density (pcf) min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 24 /bs.
Adhesion (psf) 416.6 Specified adhesion (psf) min. 150
Notes:
Field Representative: Kevin McClure
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 9/25/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 8
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Roof, Gridlines H/68 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 9/16 1.) 8/16 Thickness #10 inches
2.) 10/16 2.) 10/16 Thickness #11 inches
3.) 8/16 3.) 9/16 Thickness #12 inches
4.) 8/16 4.) 10/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs) 0.0000
Average Thickness (inches) � 9/16
Specified Thickness (inches) min. 8/16
ADHESION DETERMINATION Diameter of specimen: inches
Location: Area of specimen: 0 sq.ft.
Recorded force: /bs.
Adhesion (psf) Specified adhesion (psf) min.
Notes:
Field Representative: Kevin McClure
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 11/16/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 9
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Level 5 at Gridilnes EEE.9/12.0 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 1 5/16 1.) 1 7/16 Thickness #10 inches
2.) 1 7/16 2.) 1 7/16 Thickness #11 inches
3.) 1 6/16 3.) 1 7/16 Thickness #12 inches
4.) 1 5/16 4.) 1 6/16 Volume of test area: cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs)
Average Thickness (inches) � 1 6/16 Density (pcf)
Specified Thickness (inches) min. 1 3/16 Specified density (pcf) min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 24 /bs.
Adhesion (psf) 416.6 Specified adhesion (psf) min. 150
Notes: Adhesion test was performed on 11/17/2009
Field Representative: Kevin McClure
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 12/3/2009
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 10
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Roof, Gridlines E.1/28.0 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 14/16 1.) 12/16 Thickness #10 inches
2.) 13/16 2.) 13/16 Thickness #11 inches
3.) 14/16 3.) 13/16 Thickness #12 inches
4.) 13/16 4.) 13/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs) 25.4
Average Thickness (inches) � 13/16 Density (pcf) 24.0
Specified Thickness (inches) min. 12/16 Specified density (pc� min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 22 /bs.
Adhesion (psf) 381.9 Specified adhesion (psf) min.
Notes:
Field Representative: Kevin McClure
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 1/11/2010
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 11
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Location: Roof, Gridlines 2.0/12.1 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 11/16 1.) 11/16 Thickness #10 inches
2.) 9/16 2.) 9/16 Thickness #11 inches
3.) 10/16 3.) 10/16 Thickness #12 inches
4.) 9/16 4.) 10/16 Volume of test area: 0.0000 cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (g) 25.4
Average Thickness (inches) � 10/16 Density (pcf) 22.0
Specified Thickness (inches) min. g/16 Specified density (pc� min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 21 /bs.
Adhesion (psf) 365 Specified adhesion (psf) min. 150
Notes:
Field Representative: Kevin McClure
�r�ou�n
ENGINEERING CONSULTRNTS
FIREPROOFING DATA SHEET
Project: Ritz Carlton Residences Date: 1/11/2010
Job Number: 08-6502
Reported to: RCR Vail, LLC Copies to:
953 South Frontage West, Suite 215
Vail, Colorado 81657
Attn: Mr. Cody O'Kelly
Tube Columns Test number: 12
THICKNESS DETERMINATION DENSITY SAMPLE SIZE DETERMINATION
Level 6, Gridlines F.1/24.0 Location:
� 4 MEASUREMENTS � Thickness #1 inches
AT EACH END OF I Tf"11CkIl2SS #2 inches
� 12-INCH LENGTH +
�a
� �\ ThiCkness #3 inches
2 � a � 4 ThiCkness #4 inches
�
ThiCkness #5 inches
` 3� 3f ThiCkness #6 inches
ThiCkness #7 inches
ThiCkness #8 inches
Test Number: Test Number: Thickness #9 inches
1.) 13/16 1.) 12/16 Thickness #10 inches
2.) 11/16 2.) 11/16 Thickness #11 inches
3.) 13/16 3.) 13/16 Thickness #12 inches
4.) 13/16 4.) 12/16 Volume of test area: cubic feet
Length of test area: inches
Width of test area: inches
Average thickness: inches
DENSITY DETERMINATION
Weight of pan (g)
Weight of pan and material (g)
Weight of material (Ibs)
Average Thickness (inches) � 12/16 Density (pcf)
Specified Thickness (inches) min. 11/16 Specified density (pcf) min.
ADHESION DETERMINATION Diameter of specimen: 3.25 inches
Location: Area of specimen: 0.0576 sq.ft.
Recorded force: 28 /bs.
Adhesion (psf) 486.0 Specified adhesion (psf) min. 150
Notes:
Field Representative: Kevin McClure