FINAL REPORT OF SPECiAL INSPECTIONS
Project: Ritz Carlton Residences PermitNumber: B06 0352
Project Location: 728 West Lionshead Circle
Owner RCR Va i 1 , LLC
Address953 S Frontage Rd West , # 215C�{�,: Vail , CO Z�p: g1657
Design Professional In Charge:Ground Engineering Consultants , Inc ( Special Inspectors )
Address: PO Box 464 , 101A Airpark Drive # 9
�ity; Gypsum State: CD Zip: 81637 phone: 970 - 524 - 0720
� g_7n - � � 4 - n � � i � ...... ��, milrc�unnr�� ir� i-7cr� rr . �" eFCI
To the best of my information, knowledge, and belief, the special inspections and/or testing required for
this project, have been completed in accordance with the con#ract documents.
Interim reports submitted prior to this Final Report of Special fnspections form a basis for, and are to be
considered an integral part of tnis fna[ report. Any discrepancies that were noted in all interim reports
have been corrected.
Prepared by: , ;�~ ,
� : ,�_
r , �� ° ����
Michael K . Wariner , P . E � �� � `� �.� �;�� �
i Type or Print �Iame ����;� '�4 , ��- `D
i � �� - � �� � i�
1 � �� _� �;;��; , . ;s . � i�
o �s � � �
0
� Sigaature >> ���� �`" ` �
j� `� �< � � �a
���1 �d � �
� e � �
� � � � �t ..
�� _ . � �������d � � ' -�
Date � �> � �
Preparer's Seal and Signature Required
_ � 2 _
_ _ . _ . _ _
August 2 , 2010
Subject : Summary of Materials Testing and
Special Inspection Services , Ritz Carlton
Residences , Vail , Colorado
Job Number: 08-6502
RCR Vail LLC
953 S . Frontage Rd . West , Suite 215
Vail , Colorado 81657
Attn : Mr. Cody O ' Kelly ,
This letter summarizes the materials testing GROUND Engineering Consultants , Inc .
(GROUND) performed during the construction of the Ritz Carlton Residences building ,
located at 728 West Lionshead Circle in Vail , Colorado . The special inspection and
materials testing services were perFormed at times scheduled by the Owner, Contractor =�
and/or Subcontractors between January 16 , 2008 and May 27 , 2010 . � ����-�-
c �
_<��,z
_ , ,,o� T
' ` ,.�n � ,-
Representatives of our office were present on a part time basis to periodically observe � �-
the footing subgrade and during the placement of backfill for the footings and for the . -
floor slab . Nuclear-moisture density testing was periodically performed on the processed '
soils .
During construction , representatives of our office periodically observed reinforcing steel
placement , post-tension tendon placement and performed periodic testing on the
structural concrete placed for the foundation , foundation walls , slabs on deck and other
structural elements . Samples of the structural concrete were periodically tested to
determine physical properties and compressive strength .
Representatives of our office periodically observed reinforcing steel placement and
grouting operations as scheduled by the Owner, Contractor or Subcontracfor during
masonry operations . At the time of our visits , representatives of our office observed the
placement of sections of reinforcing steel and the general construction of the masonry
walls . Mortar, grout , and masonry prism specimens were cast periodically during
construction . Samples of the mortar, grout and masonry prisms specimens were tested
for compressive strength .
Structural steel welded and bolted connections were observed during construction by a
certified welding inspector (CWI ) . These observations were completed at times
scheduled by the Owner, Contractor or Subcontractor.
ROUHn
ENGINEERING CONSULTIaNTS INC .
101A Airpark Dr. , Unit 9, PO Box 464, Gypsum , CO 81637 Phone (970) 524-0720 Fax (970) 524-0721 www,groundeng .com
Office Locations: Englewood • Commerce City • Loveland • Granby • Gypsum
Ritz Carlton Residences
Vail, Colorado
The spray applied fireproofing (SFRM) was periodically observed for coverage and
measured for thickness . Adhesion tests were periodically performed and samples were
collected periodically to determine the in-place density.
Based on the final test results to date , field observations , RFI 's received and other
project documentation received from the design team , it is our opinion that the materials
tested and/or observed for the foundation soils , structural concrete , reinforcing steel ,
post-tension tendons , masonry, structural steel and spray applied fireproofing were in
general accordance with project plans , specifications , or applicable RFI 's .
The observations and materials testing as indicated above were performed periodically
to provide data to the Owner, Contractor and Subcontractors to assist them in
evaluating the general compliance of the tested materials and/or work with the contract
documents at the times of our observation and testing . We did not supervise , direct or
have any control over any of the Contractor's or Subcontractor' s work. We were not
responsible for the Contractor's or Subcontractor's scheduling of our services , means ,
° methods , procedures , techniques , or sequences of construction , nor responsible for
ensuring that any Contractor or Subcontractor performed or completed the work in
'� � ^ �'���� accordan
;,f, ; � v -� ;
ao�� \
���o ��� �
F°`°c ' � If ou have an
, , ��� y y questions concerning this letter, please contact our office .
�;: �. � � i,�
,cc� �
� �� �r Sincerely ,
, : = «
�� ,� ;� . ��
"�F�� GROUND Engineering Consultants, Inc .
Evan E . Kuhn
�;.�: ---�r..��,
�:_ � � . ,-ur � ,' -:
r�-' �� �a�� �C`;,
,=7� �50��:;, . r, .,, n = o %� ��''��
�r��� ��� Y�:`�° �� ` `
f r ��a � - � o �u �
�� �' _ �� �°° ' .�
, �'a
� C � � H ,'u A { ._� AiC ;
f C
� � � � ��
_` _ �
�i. �
� 1 1 �� � I _' '
-/ � � t� r
- ;J
_
LI
,�..`� ��_ _ �
Reviewed by Michael K. Wariner, P . E .
Job No. 08-6502 GROUND Engineering Consultants, Inc. Page 2 of 2