HomeMy WebLinkAboutM10-0264 Inspection Items for M10-0264 12:33 01/05/2015
Sec Item Id Description ___ A r Re Items Action Inheritable
200 MECH-Rou h Yes O 2 AP No
* 310 MECH-Heatin Yes O 1 AP No
' 315 PLMB-Gas Pi in No O 0 No
_ 320 __ MECH-Exhaust Hoods No O 0 No
330 MECH-Supply Air No O 0 No
* 340 MECH-Misc. No O 0 No
* 390 MECH-Final Yes R 2 AP No
Total Rows: 7
Page 1
RAM'S HORN LODGE TENANT FINISH
NOVEMBER 2011
TESTING Com plete
ADJUSTING Mechanical
TABB CERTIFIED
SYSTEM BALANCING
Balancing, Inc.
PO BOX 27706
DENVER, CO. 80227
FAX 303- 972 -7453
PHONE 303- 948 -5429
i
l PAGE 8179
TESTING COMPLETE P.O. BOX 27706
ADJUSTING MECHANICAL DENVER, CO. 80227
SYSTEM BALANCING BALANCING, INC. FAX 303 - 972 -7453
TABB CERTIFIED PHONE 303 - 948 -5429
GENERAL INFORMATION
PROJECT
RAM'S HORN LODGE TENANT FINISH
LOCATION
ARCHITECT
MECHANICAL ENGINEER
SHEETMETAL CONTRACTOR
M -TECH SYSTEMS, INC.
BALANCING CREW C.CATLETT J.CATLETT G.CATLETT J.FREEMAN DATE NOVEMBER 2011
A.STRUBLE
INSTRUMENTS USED
FLOW HOOD
ALNOR / SHORTRIDGE
ANEMOMETER
DAVIS TYPE LCA 6000
SPEED INDICATOR
BIDDLE TYPE 9915
AMMETER / VOLTMETER
AMPROBE TYPE DIGITAL
INCLINED DRAFT GAGE
DWYER 0- 0.25" 0- 0.50" 400"
MAGNEHELIC GAGE
0- 0.50" 0 -1.0" 0 -2.0" 0 -4.0" 0 -8.0"
PRESSURE GAGE
- 30 - - +30 PSI 0 -60 PSI 0 -100 PSI
PRESSURE GAGE DIFFERENTIAL
BARCO 0 -50" 0 -100" 300" 500" 0 -100'
PYROMETER
ALNOR
THERMOMETERS
FLUKE TYPE 52
MICROMANOMETER
ALNOR TYPE 530
TiatlnG A�9
TABB Technician
Names Michael Struble
TABB W. B81044293T
Exphvdon Dates 12/31/2011
I � Z�
Tastlnp Wq and at=!-
TABB Technician
Names Jimmie Catlett
TABB iDs BB957485T
Expiration Dates 12/31/2011
PROJECT ALTITUDE 8200'
FLOW HOOD CORRECT 1.10 APPLIED TO; AREA (K FACTOR
STATIC PRESSURE CORRECTION 1.21
RECORDED PRESSURE READINGS ARE MEASURED X
Catlett
eeo=mC
0 O 4m
supervisor #0728
Not Valid Unless Sipnad
6�mC C.�
\Exo.12/31/201�
X
CORRECTED
VELOCITY
RAM'S HORN LODGE UNIT # 16
* r
COMPLETE
MECHANICAL
BAIANCING. INC.
AIR SYSTEM RECAP SHEET
JOB:
RANS HORN LODGE TENANT FINISH - UNIT # 16
ZONE OR
REQ'D
ACT'L
% OF
FUNCTION
UNIT NO.
MAIN
CFM
CFM
REQ'D OSA REMARKS
PAGE
SUPPLY
FC -12
1 -3
1270
1241
98
1 -2
SUPPLY
FC -13
4 -7
810
835
103
3 -4
SUPPLY
FC -14
8 -10
990
998
101 602
5 -6
SUPPLY
FC -15
11 -13
1280
1264
99
7 -8
TOTAL
4350
4338
100
EXHAUST
EF- IA
76
75
99
9
EXHAUST
EF -1B
76
75
99
10
EXHAUST
EF -1 C
76
75
99
11
EXHAUST
EF -1 D
76
75
99
12
EXHAUST
EF -lE
76
75
99
13
EXHAUST
EF -1 F
76
75
99
14
TOTAL
456
450
99
� a
Complete Page 8179 -1
Mechanical Date 07 -26 -11
Balancing, In Contrac M -TECH
Balance J.C. & J.F.
EQUIPMENT DATA
A) PROJECT RAMS HORN LODGE UNTr # 16 TENANT FINISH
UNIT NO.
FC -12
PLAN LOC.
MAKE
ENVIRO TEC
MODEL NO.
H 12
SER. NO.
11291056504
RATING
1270 CFM ® 0.5"
E.S.P.
INITIAL RPM
1314
B) MOTOR
WEG
HP.
3/4
FINAL RPM
RATED EFF /PF
1173
NONE GIVEN
TYPE
NONE GIVEN
PH.
1
RATED SPEED
1745
MEASMOLTS (L /L)
204
SF.
1.15
RATED VOLTS
115 - 208/460
INITIAL AMPS
4.6
FR.
B56
RATED AMPS
10.8/5.4 -5.4
MEAS.VOLTS (L /G)
S F AMPS
12.8/6.4
FINAL AMPS
C) STARTER
4.1
SIZE
THERMALS
(EXIST)
AMP. RATING
THERMALS
(REQ'D)
AMP. RATING
OTHER
BUILT IN OVERLOAD PROTECTION
D) DRIVEN
AK49
SHEAVE X BORE
H 3/4"
DRIVER
1VL44
SHEAVE X BORE
5/8"
BELTS
A37
SIZE X NO. BELTS
1
MOT. ADJ. IN /OUT
CL. DIST.
DRIVE CHANGE
NONE
BELT CHANGE
NONE
E) FILTERS IN
-0.05 IN.
OUT
-0.15 IN.
DROP
-0.10 IN.
HEAT COIL IN
-0.15 IN.
OUT
NA IN.
DROP
0.15 IN.
COOL COIL IN
NA IN.
OUT
-0.45 IN.
DROP
-0.45 IN.
FAN IN
-0.45 IN.
OUT
0.16 IN.
DROP
0.61 IN.
G) PUMP IN
PSI
OUT
PSI
RISE
PSI FT
DEAD HEAD IN
PSI
OUT
PSI
RISE
PSI Fr
H) REMARKS
AREA=
SQ. Fr.X
FPM=
CFM
FINAL:
SQ. FT.X
FPM=
CFM
COMPLETE
MECHANICAL PROJECT RAMS HORN LODGE UNIT 16
BALANCING LOCATION VAIL CO
FAN SYSTEM
CONTRACTOR
FC -12
M -TECH SYSTEMS, INC.
PAGE NO 8179 -2
DATE 07 -25 -11
BALANCER J.C. & J.F.
REMARKS
AIRBAL
SIZE
REgUIRED I
TEST 1
TEST 2
TEST 3
FINAL
OPENING
PLAN
4 LCT
AREA
VEL
CFM
VEL
%
VEL
%
VEL
%
VEL
CFM
%
REMARKS
FC -12 -1
22/6
1.16
461
535
450
98
440
5101
95
100% OPEN
2
22/6
1.16
461
535
510
111
465
5391
101
3
12/4
1.16
172
200
220
128
165
1911
96
TOTAL
1270
1241
REMARKS
AIRBAL
Complete Page 8179 -3
Mechanical Date 07 -26 -11
Balancing, Inc. Contrac M -TECH
Balance: J.C. & J.F.
EQUIPMENT DATA
A) PROJECT RAMS HORN LODGE UNIT # 16 TENANT FINISH
UNIT NO. FC -13 PLAN LOC.
MAKE ENVIRO TEC MODEL NO. H 08
SER. NO. 11291056505
RATING 960 CFM ® 0.5" E.S.P. INITIAL RPM 1620
FINAL RPM 1143
B) MOTOR
WEG
HP.
3/4
RATED EFF /PF
NONE GIVEN
TYPE
NONE GIVEN
PH.
1
RATED SPEED
1745
MEAS.VOLTS (L /L)
203
SF.
1.15
RATED VOLTS
115 - 208/460
INITIAL AMPS
4.3
FR.
B56
RATED AMPS
10.8/5.4 -5.4
MEAS.VOLTS (L /G)
AMP. RATING
OTHER
S F AMPS
12.8/6.4
FINAL AMPS
4.3
D) DRIVEN
AK49
C) STARTER
SIZE
THERMALS
(EXIST)
AMP. RATING
THERMALS
(REQ'D)
AMP. RATING
OTHER
BUILT IN OVERLOAD PROTECTION
D) DRIVEN
AK49
SHEAVE X BORE
H 3/4"
DRIVER
1VP56
SHEAVE X BORE
5/8"
BELTS
A41
SIZE X NO. BELTS
1
MOT. ADJ. IN /OUT
CL. DIST.
DRIVE CHANGE
1 VL44
BELT CHANGE
A58
E) FILTERS
IN
-0.10
IN.
OUT
-0.18
IN.
DROP
-0.08 IN.
HEAT COIL
IN
-0.18
IN.
OUT
NA
IN.
DROP
0.18 IN.
COOL COIL
IN
NA
IN.
OUT
-0.39
IN.
DROP
-0.39 IN.
FAN
IN
-0.39
IN.
OUT
0.11
IN.
DROP
0.50 IN.
G) PUMP
IN
PSI
OUT
PSI
RISE
PSI FT
DEAD HEAD
IN
PSI
OUT
PSI
RISE
PSI FT
H) REILZARKS
AREA=
SQ. FT.X
FPM=
CFM
FINAL:
SQ. FT.X
FPM=
CFM
COMPLETE
MECHANICAL
BALANCING
PROJECT
LOCATION
FAN SYSTEM
CONTRACTOR
RAMS HORN LODGE UNIT 16
V AIL CO _
FC -13
M -TECH SYSTEMS, INC.
PAGE NO
DATE
BALANCER
R 1 7A -4
07 - 25 -11
.r r p,.r F
AIRBAL
SIZE
REQUIRED
TEST 1
TEST 2
TEST 3
FINAL
OPENING
PLAN
CT'
AREA
VEL
CFM
VEL
%
VEV 0 Xo
%VEL
CFM
%
REMARKS
FC -13 -4
22/6
1.16
284
330
500
176
295
342
104
100% O PEN
5
22/6
1.16
284
330
330
116
295
342
104
6
6/6
1.16
65
7 5
130
201
65
75
101
7
6/6
1.16
65
75
165
255
65
75
TOT AL
810
835
-
__j+
AIRBAL
Complete Page 8179 -5
Mechanical Date 10 -21 -11
Balancing, Inc. Contrac M -TECH
Balance J.C. & G.C.
EQUIPMENT DATA
A) PROJECT RAMS HORN LODGE UNIT # 16 TENANT FINISH
UNIT NO.
FC -14
PLAN LOC.
DRIVER
- - -- -
MAKE
ENVIRO TEC
MODEL NO.
H- 16 W
SER. NO. _
11291056506
1
-- - --
MOT. A DJ. IN/O
RATING
1470 CFM ® 0.5" E.S.P.
INITIAL RPM
1046
B) MOTOR
WEG HP. 3/4
FIlVAL RPM
RATED EFF /PF
672
NONE GIVEN
TYPE
NONE GIVEN PH. 1
RATED SPEED
1745
MEAS.VOLTS (L /L)
204 SF. 1.25
RATED VOLTS
115/208 -230
INITIAL AMPS
4.1 FR. D56
RATED AMPS
10.8/5.4 -5.4
MEAS.VOLTS (L /G)
DROP
S F AMPS
12.8/6.4
FH4AL AMPS
C) STARTER
3.4
SIZE
— —
THERMALS
(E)(IST)
AMP. RATING
THERMALS
(REQ'D)
AMP. RATING
OTHER
BUILT IN OVERLOAD PROTECTION
D) DRIVEN
AK61
SHEAVE X BORE
H 3/4"
DRIVER
- - -- -
1VL44
'- - -- _ -
SHE AVE X BORE
- -- -
5/8" — - - - - --
BELTS
A
-
SI _X NO. BELTS
-- —
1
-- - --
MOT. A DJ. IN/O
OUT
CL. DIST.
IN.
DRIVE CHANGE
1VL34
BELT CHANGE
A39
E) FILTERS
IN
ATMOS
IN.
OUT
-0.02
IN.
DROP
-0.02 IN.
HEAT COIL
IN
-0.02
IN.
OUT
NA
IN.
DROP
0.02 IN.
COOL COIL
IN
NA
IN.
OUT
-0.15
IN.
DROP
-0.15 IN.
FAN
IN
-0.15
IN.
OUT
0.11
IN.
DROP
0.26 IN.
G) PUMP IN PSI OUT PSI RI SE PSI FT
DEAD HEAD IN PSI OUT PSI RISE PSI FT
H) REMARK
OSA AREA= 1.52 SQ. FT.X 395 FPM= 600 CFM
FINAL: 1.52 SQ. FT.X 396 FPM= 602 CFM 100%
COMPLETE
MECHANICAL PROJECT
BALANCING LOCATION
FAN SYSTEM
CONTRACTOR
RAMS HORN LODGE UNIT 16
VAIL CO
FC -14
M -TE CH SYSTEMS, INC.
PAGE NO 8179 -6
DATE 07 -25 -11
BALANCER J.C. & J.F.
REMAR
AIRBAL
SIZE
REQUIRED
TEST 1
TEST 2
TEST 3
FINAL
OPENING
PLAN
CT'
AREA
VEL
CFM
VEL
%
VEL
%
VEL
%
VEL
CFM
%
REMARKS
FC -14 -8
22/6
1.16
259
300
485
188
260
302
101
9
22/6
1.16
297
345
405
136
295
342
99
100% OPEN
10
22/6
1.16
297
345
530
178
305
354
103
TOTAL
990
998
REMAR
AIRBAL
Complete
Mechanical
Balancing, Inc.
EQUIPMENT DATA
A) PROJECT RAMS HORN LODGE UNIT # 16 TENANT FINISH
Page 8179 -7
Date 07 -26 -11
Contrac M -TECH
Balance J.C. & J. F.
UNIT NO. FC -15 PLAN LOC.
MAKE ENVIRO TEC MODEL NO. H16
S ER. N 1129105650
RATING 1485 CFM @ 0.5" E.S.P. INITIAL RPM _ _1073
FIIVAL RP 107
B) MOTOR
WEG
HP.
3/4
RATED EFF /PF
NONE GIVEN
TYPE
NONE GIVEN
PH.
1
RATED SPE
1745
MEAS.VOLTS (L /L)
203
SF.
1.15
RA VO LTS _
115/208 -230 _
INITIAL AMPS
4.2
FR.
B56
RATED AMPS
10.8/5.4 -5.4
MEAS.VOLTS (L /G)
AMP. RATING
OTHER
S F AMPS
12.8/6.4
FINAL AMPS
4.2
D) DRIVEN
AK61
C) STARTER
SIZE
THERMALS
(EXIST)
AMP. RATING
THERMALS
(REQ'D)
AMP. RATING
OTHER
BUILT IN OVERLOAD PROTECTION
D) DRIVEN
AK61
SHEAVE X BORE
H 3/4"
DRIVER
1VL44
SHEAVE X BORE
5/8"
BELTS
A41
SIZE X NO. BELTS
1
MOT. ADJ. IN /OUT
CL. DIST.
DRIVE CHANGE
NONE
BELT CHANGE
NONE
E) FILTERS
IN
ATMOS
IN.
OUT
-0.04
IN.
DROP
-0.04 IN.
HEAT COIL
IN
-0.04
IN.
OUT
NA
IN.
DROP
0.04 IN.
COOL COIL
IN
NA
IN.
OUT
-0.23
IN.
DROP
-0.23 IN.
FAN
IN
-0.23
IN.
OUT
0.15
IN.
DROP
0.38 IN.
G) PUMP IN PSI OUT PSI RISE PSI FT
DEADHEAD IN PSI OUT PSI RISE PSI FT
H) REMARKS
OSA AREA= S FT. FP CFM
FINAL: SQ. FT.X FPM= CFM
COMPLETE
MECHANICAL PROJECT' RAMS HORN LODGE UNIT 16 PAGE NO 8179 -8
BALANCING LOCATION VAIL CO
FAN SYSTEM
CONTRACTOR
FC -15
M -TECH SYSTEMS, INC.
DATE 07 -26 -11
BALANCER J.C. & J.F.
IV
SIZE
REQUIRED
TEST 1
TEST 2
TEST 3
FINAL
OPENING
PLAN
CT
VEL
CFM
VEL
%
VEL
%
VEL
%
VEL
CFM
%
REMARKS
FC -15 -11
22/6
1.16
328
380
250
76
310
360
95
100% OPEN
12
22/6
1.16
388
450
520
134
390
452
101
13
22/6
1.16
388
450
380
98
390
4521
101
TOTAL
1280
1264
IV
Complete Page 8179 -9
Mechanical Date 07 -25 -11
Balancing, Inc. Contrac M -TECH
Balance: J.C.
EQUIPMENT DATA
A) PROJECT RAMS HORN LODGE UNIT # 16 TENANT FI NISH
UNIT NO.
MAKE
EF -lA
PANASONIC
PLAN LOC.
M O_ NO.
AFV -08VF2
SER. NO.
005
_ DEL
RATING
80 CFM ® 0.375"
E.S.P.
INITIAL RPM
DIRECT DRIVE
B) MOTOR
PANASONIC
HP, NONE GIVEN
FINAL RPM
RATED EFF /PF
DIRECT DRIVE
NONE GIVEN
TYPE
NONE GIVEN
PH. 1
RATED SPEED
NONE GIVEN
MEAS.VOLTS (L /L)
SF. NONE GIVEN
RATED VOLTS
120
INITIAL AMPS
.18
FR. NONE GIVEN
RATED AMPS
.2
MEAS.VOLTS (4/G)
120 -
S F AMPS
NONE GIVEN
FINAL AMPS
C) STARTER
.18
SIZE
THERMALS
(EXIST)
AMP. RATING
THERMAL -- --
OTHER
(REQ'D)
BUILT IN OVERLOAD PROTECTION
AMP. RATING
D) DRIVEN
SHEAVE X BORE
DRIVER
SHEAVE X BORE
—
BELTS
SIZE X NO. BELTS
MOT. ADJ. IN /OUT
CL. DIST.
DRIVE CHANGE
BELT CHANGE
E) FILTERS IN
IN.
OUT IN.
DROP
IN.
HEAT COIL IN
IN.
OUT IN.
DROP
IN.
COOL COIL IN
IN.
OUT IN.
DROP
IN.
FAN IN
ATMOS IN.
OUT NA IN.
DROP
IN.
G) PUMP IN
PSI OUT
PSI RISE PSI FT
DEAD HEAD IN PSI OUT PSI RISE PSI FT
H) REMARKS
AREA= 1. 16 SQ. FT.X 66 FPM= 76 CFM
FINAL: 1.16 SQ. FT.X 65 FPM= 75 CFM 99%
Complete
Mechanical
Balancing, Inc.
EQUIPMENT DATA
A) PROJECT RAM HORN LODGE UNIT # 16 TENANT FINISH
UNIT NO. EF -1B
PLAN LOC.
MAKE PANASONIC MODEL NO. AFV -08VF2
SER. NO. 005 _
RATING 80 CFM ® 0.375" E.S.P. INITIAL RPM DIRECT DRIVE
FINAL RPM DIRECT DRIVE
B) MOTOR PANASONIC HP. NONE GIVEN RATED EFF /PF NONE GIVEN
TYPE NONE GIVEN PH. 1 RATED SPEED NONE GIVEN
MEAS.VOLTS (L /L) SF. NONE GIVEN RATED VOLTS 120
INITIAL AMPS .19 FR. NONE GIVEN RATED AMPS .2
MEAS.VOLTS (L /G) 120 S F AMPS NONE GIVEN
FINAL AMPS .19
C) STARTER SIZE
THERMALS (EXIST) AMP. RATING
THERMALS (REQ'D) AMP. RATING
OTHER BUILT IN OVERLOAD PROTECTION
D) DRIVEN
DRIVER
_ _
SHEAVE X BORE
SHEAVE X BORE
BELTS
SIZE X NO. BELTS
MOT. ADJ. IN /OUT
CL. DIST.
DRIVE CHANGE
BELT CHANGE
E) FILTERS IN
IN.
OUT
IN.
DROP
IN.
HEAT COIL IN
IN.
OUT
IN.
DROP
IN.
COOL COIL IN
IN.
OUT
IN.
DROP
IN.
FAN IN
ATMOS IN.
OUT
NA IN.
DROP
IN.
G) PUMP IN
PSI
OUT
PSI
RISE PSI
FT
DEAD HEAD IN
PSI
OUT
PSI
RISE PSI
FT
H) REMARKS
AREA= 1. 16
SQ. FT.X
66
FPM=
76 CFM
FINAL. 1.16
SQ. FT.X
65
FPM=
75 CFM
99 0 /0
Page 8179 -10
Date 11 -17 -10
Contrac M -TECH
Balance: J.C. & G.C.
r '
Complete Page 8179 -11
Mechanical Date 11 -17 -10
Balancing, Inc. Contract M -TECH
Balance: J.C. & G.C.
EQUIPMENT DATA
A) PROJECT RAMS HORN LODGE UNIT # 16 TENANT FINISH
UNIT NO.
EF -1C
PLAN LOC.
MAKE
PANASONIC
MODEL NO.
AFV -08VF2
SER. NO.
005
RATING
80 CFM @ 0.375" E.S.P.
INITIAL RPM
DIRECT DRIVE
B) MOTOR
PANASONIC
HP.
NONE GIVEN
FINAL RPM
RATED EFF /PF
DIRECT DRIVE
NONE GIVEN
TYPE
NONE GIVEN
PH.
1
RATED SPEED
NONE GIVEN
MEAS.VOLTS (L /L)
SF.
NONE GIVEN
RATED VOLTS
120
INITIAL AMPS
.18
FR.
NONE GIVEN
RATED AMPS
.2
MEAS.VOLTS (L /G)
120
S F AMPS
NONE GIVEN
FINAL AMPS
C) STARTER
.18
SIZE
THERMALS
(EXIST)
AMP. RATING
THERMALS
(REQ'D)
AMP. RATING
OTHER
BUILT IN OVERLOAD PROTECTION
D) DRIVEN
SHEAVE X BORE
DRIVER
SHEAVE X BORE
BELTS
SIZE X NO. BELTS
MOT. ADJ. IN /OUT
CL. DIST.
DRIVE CHANGE
BELT CHANGE
E) FILTERS IN
IN.
OUT
IN.
DROP
IN.
HEAT COIL IN
IN.
OUT
IN.
DROP
IN.
COOL COIL IN
IN.
OUT
IN.
DROP
IN.
FAN IN
ATMOS IN.
OUT
NA IN.
DROP
IN.
G) PUMP IN
PSI
OUT
PSI
RISE
PSI FT
DEAD HEAD IN
PSI
OUT
PSI
RISE
PSI FT
H) REMARKS
AREA= 1. 16
SQ. FT.X
66
FPM=
76 CFM
FINAL: 1.16
SQ. FT.X
65
FPM=
75 CFM
99%
%
Complete
Mechanical
Balancing, Inc.
EQUIPMENT DATA
Page 8179 -12
Date 11 -17 -10
Contrac M -TECH
Balance: J.C. & G.C.
A) PROJECT
RAMS HORN LODGE UNIT # 16 TENANT FINISH
UNIT NO.
EF -1D
PLAN LOC.
MAKE
PANASONIC
MODEL NO.
AFV -08VF2
SER. NO.
005
RATING
80 CFM ® 0.375" E.S.P.
IMTIAL RPM
DIRECT DRIVE
B) MOTOR
PANASONIC
HP.
NONE GIVEN
FINAL RPM
RATED EFF /PF
DIRECT DRIVE
NONE GIVEN
TYPE
NONE GIVEN
PH.
1
RATED SPEED
NONE GIVEN
MEAS.VOLTS (L /L)
SF.
NONE GIVEN
RATED VOLTS
120
INITIAL AMPS
.19
FR.
NONE GIVEN
RATED AMPS
.2
MEAS.VOLTS (L /G)
120
S F AMPS
NONE GIVEN
FINAL AMPS
C) STARTER
.19
SIZE
THERMALS
(EXIST)
AMP. RATING
THERMALS
(REQ'D)
AMP. RATING
OTHER
BUILT IN OVERLOAD PROTECTION
D) DRIVEN
SHEAVE X BORE
DRIVER
SHEAVE X BORE
BELTS
SIZE X NO. BELTS
MOT. ADJ. IN /OUT
CL. DIST.
DRIVE CHANGE
BELT CHANGE
E) FILTERS IN
IN.
OUT
IN.
DROP
IN.
HEAT COIL IN
IN.
OUT
IN.
DROP
IN.
COOL COIL IN
IN.
OUT
IN.
DROP
IN.
FAN IN
ATMOS IN.
OUT
NA IN.
DROP
IN
G) PUMP IN
PSI
OUT
PSI
RISE
PSI FT
DEAD HEAD IN
PSI
OUT
PSI
RISE
PSI FT
H) REMARKS
AREA= 1. 16 SQ. FT.X 66 FPM= 76 CFM
FINAL: 1.16 SQ. FT.X 65 FPM= 75 CFM 99%
Complete
Mechanical
Balancing, Inc.
EQUIPMENT DATA
A) PROJECT RAMS HORN LODGE UNIT # 16 TENANT FINISH
Page 8179 -13
Date 11 -17 -10
Contrau M -TECH
Balance- & G.C.
UNIT NO.
EF -1 E
SHEAVE X BORE
PLAN LOC.
DRIVER
MAKE
PANASONIC
MODEL NO.
AFV -08VF2
SER. NO.
005
SIZE X NO. BELTS
RATING
80 CFM ® 0.375" E.S.P.
INITIAL RPM
DIRECT DRIVE
B) MOTOR
PANASONIC
HP. NONE GIVEN
FINAL RPM DIRECT DRIVE
RATED EFF /PF NONE GIVEN
TYPE
NONE GIVEN
PH. 1
RATED SPEED
NONE GIVEN
MEAS.VOLTS (L /L)
IN.
SF. NONE GIVEN
RATED VOLTS
120
INITIAL AMPS
.18
FR. NONE GIVEN
RATED AMPS
.2
MEAS.VOLTS (L /G)
120
COOL COIL IN
S F AMPS
NONE GIVEN
FINAL AMPS
.18
IN.
FAN IN
ATMOS IN.
C) STARTER SIZE
THERMALS AMP. RATING
THERMALS (REQ'D) AMP. RATING -
OTHER BUILT IN OVERLOAD PROTECTION
D) DRIVEN
SHEAVE X BORE
DRIVER
SHEAVE X BORE
BELTS
SIZE X NO. BELTS
MOT. ADJ. IN/OUT
CL. DIST.
DRIVE CHANGE
BELT CHANGE
E) FILTERS IN
IN.
OUT
IN.
DROP
IN.
HEAT COIL IN
IN.
OUT
IN.
DROP
IN.
COOL COIL IN
IN.
OUT
IN.
DROP
IN.
FAN IN
ATMOS IN.
OUT
NA IN.
DROP
IN.
G) PUMP IN
PSI
OUT
PSI
RISE PSI
FT
DEAD HEAD IN
PSI
OUT
PSI
RISE PSI
FT
H) REMARKS
AREA= 1. 16
SQ. FT.X
66
FPM=
76 CFM
FINAL: 1.16
SQ. FT.X
65
FPM=
75 CFM
990/0
.. I
Complete
Mechanical
Balancing, Inc.
EQUIPMENT DATA
A) PROJECT RAMS HORN LODGE UNIT # 16 TENANT FINISH
Page 8179 -14
Date 11 -17 -10
Contrac M -TECH
Balance: J.C. & G.C.
UNIT NO.
EF -1F
SHEAVE X BORE
PLAN LOC.
DRIVER
MAKE
PANASONIC
MODEL NO.
AFV -08VF2
SER. NO.
005
SIZE X NO. BELTS
RATING
80 CFM ® 0.375"
E.S.P.
INITIAL RPM
DIRECT DRIVE
B) MOTOR
PANASONIC
HP. NONE GIVEN
F04AL RPM DIRECT DRIVE
RATED EFF /PF NONE GIVEN
TYPE
NO NE GI
PH. 1
RATED SPEED
NONE GIVEN
MEAS.VOLTS (L /L)
OUT
OUT
OUT
SF. NON GIVEN
RATED VOLTS
120
INITIAL AMPS
MEAS.VOLTS (L /G)
.19
120
FR. NONE GIVEN
RATED AMPS
S F AMPS
.2
NONE GIVEN
FINAL AMPS
C) STARTER
.19
SIZE
THERMALS
(EXIST)
AMP. RATING
THERMALS
(REQ'D)
AMP. RATING
PSI
OTHER
BUILT IN OVERLOAD PROTECTION
RISE PSI
FT
D) DRIVEN
SHEAVE X BORE
DRIVER
SHEAVE X BORE
BELTS
SIZE X NO. BELTS
MOT. ADJ. IN /OUT
CL. DIST.
DRIVE CHANGE
BELT CHANGE
E) FILTERS IN
HEAT COIL IN
COOL COIL IN
IN.
IN.
IN.
OUT
OUT
OUT
IN.
IN.
IN.
DROP
DROP _
DROP
IN.
IN.
IN.
FAN IN
ATMOS IN.
OUT
NA IN.
DROP
IN.
G) PUMP IN
PSI
OUT
PSI
RISE PSI
FT
DEAD HEAD IN
PSI
OUT
PSI
RISE PSI
FT
H) REMARKS
ARE 1. 16
SQ. FT.X
66
FPM=
76 CFM
FINAL: 1.16
SQ. FT.X
65
FPM=
75 CFM
99%
4 % 4
COMPLETE
MECHANICAL
BALANCING, INC.
WATER BALANCE DATA
PAGE 8179 -15
DATE 07 -26 -11
CONT. M -TECH
BAL. J. C.
CHILL
PROJECT RAMS HORN LODGE LOCATION SYSTE: WATER
STATION
:FLOW
ETER
SIZE
RE9'D RATING
BY -PASS
FINAL
REMARKS
UNIT 16
PD IN
GPM
PD IN
GPM
%
PD IN
GPM
I %
FC -12
FLOPAC
M100
16.00
4.00
11.001
3.32
83
FC -13
FLOPAC
M100
13.00
3.50
9.00
2.91
83
FC -14
FLOPAC
M100
16.00
4.00
15.00
3.87
97
FC -15
FLOPAC
M100
21.00
4.50
15.00
3.80
85
100% OPEN
TOTAL
1 16.00
13.901
87
REMARKS
'_ 4 % to
COMPLETE
MECHANICAL
BALANCING, INC.
WATER BALANCE DATA
PAGE 8179 -16
DATE 07 -26 -11
CONT. M -TECH
BAL. J. C.
HOT
PROJECT RAMS HORN LODGE LOCATION SYSTE: WA
STATION
FLOW
METER
SIZE
REQ'D RATING
BY -PASS
FINAL
REMARKS
UNIT 16
PD IN
GPM
PD IN
GPM
%
PD IN
GPM
%
FC -12
FLOPAC
075RL
55.00
1.00
37.00
0.82
82
100% OPEN
FC -13
FLOPAC
075RL
55.00
1.00
40.00
0.85
85
FC -14
FLOPAC
075RH
23.00
2.001
17.00
1.72
86
FC -15
FLOPAC
075RL
55.00
1.00
40.001
0.85
85
RM -15
FLOPAC
075RH
53.00
3.05
39.00
2.62
86
RM -16
FLOPAC
MB 100
23.00
4.601
17.00
3.95
86
RM -17
FLOPAC
075RH
22.00
1.96
17.00
1.72
88
RM -18
FLOPAC
075RH
37.00
0.83
30.00
0.75
90
PUMP ON HIG
TOTAL-
15.44
13.29
86
REMARKS
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT
Town of Vail, Community Development, 75 South Frontage Road, Vail, Colorado 81657
p. 970 - 479 -2139 f. 970.479.2452 inspections. 970.479.2149
MECHANICAL PERMIT
AMF
Job Address: 416 VAIL VALLEY DR VAIL
Location.....: UNIT 16, RAMSHORN
Parcel No...: 210108258024
OWNER TYM INTERNATIONAL LTD 11/03/2010
416 VAIL VALLEY DR
VAIL
CO 81657
APPLICANT MTECH MECHANICAL TECHNOLOGIE 11/03/2010 Phone: (303) 6504000
7535 HILLTOP CIRCLE, STE 200
DENVER
CO 802213452
License: 281 -M
CONTRACTOR MTECH MECHANICAL TECHNOLOGIE 11/03/2010 Phone: (303) 6504000
7535 HILLTOP CIRCLE, STE 200
DENVER
CO 802213452
License: 281 -M
Desciption: NEW MULTI - FAMILY DWELLING UNIT, UNIT 16
Valuation: $103,200.00
ALL TIMES
Permit #: M10-0264
Project #: PRJ09 -0697
Status ...:
ISSUED
Applied..
11/03/2010
Issued . .:
11103/2010
Expires . .:
05/02/2011
Item: 05100 BUILDING DEPARTMENT
11/03/2010 SBELLM Action: AP
APPROVALS
Item: 05600 FIRE DEPARTMENT
CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 42
(BLDG 2009) CARBON MONOXIDE DETECTORS REQUIRED TO BE INSTALLED PER 2009 IRC R315
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information
as required is correct. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure
according to the towns zoning and subdivision codes, design review approved, International Building and Residential Codes and other ordinances of the Town
applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROM 8:0t
AM - 4 PM. - n .1 n
Signature 9f Owner or Contractor
S
// ^ / 0
Date
m e ch c a n i ca I _pe rm it- 041908
**f # * *«**** # **« * * * *** * * * *f *** SUMMARY ###*#*#**###*###############**##*#**####*#..###......f
fff####...
# #####ffff ##f ### *f*##
Mechanical Permit Fee - ->
$2,080.00 Will Call -- -------- > $4.00
Total Calculated Fees --- >
$2,604.00
Plan Check------ - - - - ->
$520.00 Use Tax Fee -- $0.00
Additional Fees--- - - - - ->
$0.00
Investigation--------- - - - - ->
$0.00
TOTAL PERMIT FEE - ->
$2,604.00
Total Calculated Fees - -> $2,604.00
Payments -------- --- ---- ->
$2,604.00
BALANCE DUE - - - - ->
$0.00
Item: 05100 BUILDING DEPARTMENT
11/03/2010 SBELLM Action: AP
APPROVALS
Item: 05600 FIRE DEPARTMENT
CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 42
(BLDG 2009) CARBON MONOXIDE DETECTORS REQUIRED TO BE INSTALLED PER 2009 IRC R315
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information
as required is correct. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure
according to the towns zoning and subdivision codes, design review approved, International Building and Residential Codes and other ordinances of the Town
applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROM 8:0t
AM - 4 PM. - n .1 n
Signature 9f Owner or Contractor
S
// ^ / 0
Date
m e ch c a n i ca I _pe rm it- 041908
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
TOWN OF VAIL, COLORADO Statement
Statement Number: R100001761 Amount: $2,604.00 11/03/201002:20 PM
Payment Method: Check Init: SAB
Notation: 29983 - MTECH
-----------------------------------------------------------------------------
Permit No: M10 -0264 Type: MECHANICAL PERMIT
Parcel No: 2101 - 082 - 5802 -4
Site Address: 416 VAIL VALLEY DR VAIL
Location: UNIT 16, RAMSHORN
Total Fees: $2,604.00
This Payment: $2,604.00 Total ALL Pmts: $2,604.00
Balance: $0.00
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------- - - - - -- ------------------------ - - - - -- ------ - - - - --
MP 00100003111100 MECHANICAL PERMIT FEES 2,080.00
PF 00100003112300 PLAN CHECK FEES 520.00
WC 00100003112800 WILL CALL INSPECTION FEE 4.00
MECHANICAL PERMIT
Boiler / Furnace & Fireplace Applications MUST include:
• Complete Mechanical Room Floor Plan with Dimensions
• Combustion Air Duct Size and Location
• Flue detail or Vent size, location & termination
• Gas Piping layout including development length calculations
• Heat Loss Calculations
Project Street Address:
(Number) (Street) n (Suite #)
Building /Complex Name: Q - 47w
❑ Boiler size & efficiency
❑ Equipment Cut Sheets for Fireplaces /Log Sets
(Manufacturer's info showing make, model & approval listing)
Office Use:
Project #: P- P J79 o(pq
Building Permit #: aU q d ?2 (Q 7
Mechanical Permit #: M AD' Qd U q
Lot #: Block # Subdivision:
Define Scope and Location of Work:
Contractor Information:
Company M 7-��� 4VSh r .S
Company Address: / n
n AQy '
',SQ -
-
c /A ,
ity. State. Zip. (use additional sheet if necessary)
Contact Name: H A� 1A ezjg6 n
❑ Gas Piping Included
Contact Phone: b u 9 d 3ap, ❑ Gas Piping by Others
E -Mail MP P P Q-- y l, ❑ Wood to Gas Fireplace Conversion
r
Town of Vail
Boiler Location:
Interior ( ) Exterior ( ) Other
Number of Existing Fireplaces:
Contractor Signatures( required)
- ,- Gas Appliances Gas Logs Wood /Pellet
Property Information
Parcel #:
Number of Proposed Fireplaces:
(For parcel #, contact Eagle County Assessors Office at 970 - 328 -8640 or Gas Appliances Gas Logs Wood /Pellet
visit www.eaglecounty.us/patie)