HomeMy WebLinkAboutF11-0001TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970 - 479 -2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
SPRINKLER PERMIT Permit #
Job Address: 728 W LIONSHEAD CR VAIL Status ... :
Location.....: RITZ CARLTON RETAIL SPACE 3 (POSH HAIRS Applied .. :
Parcel No...: 210107223120 Issued. . .
Project No Expires. .:
OWNER RCR LLC
PO BOX 959
AVON
CO 81620
APPLICANT WESTERN STATES FIRE
7026 S TUCSON WAY
ENGLEWOOD
CO 80112
License: 338 -S
CONTRACTOR WESTERN STATES FIRE
7026 S TUCSON WAY
ENGLEWOOD
CO 80112
License: 338 -S
01/13/2011
PROTECTI 01/13/2011
PROTECTI 01/13/2011
Fl 1 -0001
ISSUED
01/13/2011
01/25/2011
Phone: 303 - 792 -0022
Phone: 303 - 792 -0022
Desciption: RELOCATE TWELVE SPRINKLER HEADS WITH SEMI - RECESSED DUE TO
NEW TENANT REMODEL.
Valuation: $3,630.00
************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** FEE SUMMARY ************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Mechanical --- >
$0.00 Restuarant Plan Review - ->
$0.00
Total Calculated Fees --- >
$586.28
Plan Check --- >
$432. 00 DRB Fee --------------------- >
$0.00
Additional Fees------ - - - - ->
$0.00
Investigation ->
$0.00 TOTAL FEES--------- - - - - ->
$586.28
Total Permit Fee ---------- >
$586.28
Will Call - - - - ->
$0.00
Payments ------------------- >
$586.28
BALANCE DUE --------- >
$0.00
**************************************************************************************************************
* * * *
* * * * * * * * * * * * * * * * * * * * * * * * * **
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE
DEPARTMENT
01/17/2011
mvaughan Action: AP
pending
use approval from
council
CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 53
(FIRE 2007) Monitored fire sprinkler system required and shall comply with NFPA
13 (2007) and VFES Standards.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970 - 479 -2252
FROM 8:00 AM - 5 PM.
SIGNATUfE OF /OWNED OR 0ONTRACTOR FOR HIMSELF AND OWNEF
TOWN OF VAIL, COLORADO Statement
Statement Number: R110000065 Amount: $586.28 01/25/201111:45 AM
Payment Method: Check Init: SAB
Notation: 120632
W.S.F.P.
-----------------------------------------------------------------------------
Permit No: Fll -0001 Type: SPRINKLER PERMIT
Parcel No: 2101 - 072 - 2312 -0
Site Address: 728 W LIONSHEAD CR VAIL
Location: RITZ CARLTON RETAIL SPACE 3 (POSH HAIR S
Total Fees: $586.28
This Payment: $586.28 Total ALL Pmts: $586.28
Balance: $0.00
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------- - - - - -- ------------------------ - - - - -- ------ - - - - --
BP 00100003111100 SPRINKLER PERMIT FEES 154.28
PF 00100003112300 PLAN CHECK FEES 432.00
ant of Community Development
75 South Frontage Road
Vail, Colorado, 816570,
Tel:. 970- 479 -2128x
�?
Fax 970- 479 -2452/
Web: www.vailgov:c
� e i C rrii
FIRE SPRINKLER PERMIT
Commercial & Residential Fire Alarm shop drawings are required at the time of
application submittal and must include the following information:
1. A Colorado Registered Engineer's stamp or N.I.C.E.T level III (min) stamp
2. Equipment cut sheets of materials
3. Hydraulic calculations
4. A State of Colorado contractor registration number
5. Plans must be submitted by a Registered Fire Protection Contractor
Project Street Address:
1031 South Frontage Road Space C
(Number) (Street)
Building /Complex Name: V Rit Ca rlt o n
Contractor Information:
Company: Western States Fire Protection
Company Address: 7026 S. Tuscan Way
City: Centennial
Contact Name: Joe Hayden
(Suite #)
Office Use: 0( - -- V07 - 000( 1 0
Project #: PR, / d — 0 ,
Building Permit #:
Sprinkler Permit #: DOC
Lot #: Block # Subdivision:
Detailed Description of Work: Relocate (12) sprinkler
State: CO Zip : 80112 heads with semi - recessed due to new tenant remod
Contact Phone: 303 - 549 -8979
E -Mail joe.hayden @wsfp.us
Town of Vail Contractor Registration No.: 338 -S
X a
Contractor Signature (required) Jum
Property Information
Parcel #: 210107223120
(For parcel #, contact Eagle County Assessors Office at 970 - 328 -8640 or
visit www.eaglecounty.us /patie)
Tenant Name: Posh Hair Salon
Owner Name: Vail Resorts
Complete Valuation for Fire Sprinkler Permit:
Fire Sprinkler $:
$3,630.00
(use additional sheet if necessary)
Detailed Location of Work: Work will be preformed in
retail space C f�f LSi MR i,- SfjLD,:
Does a Monitored Fire Alarm Exist? Yes ( ,,) No ( )
Does a Sprinkler System Exist? Yes(. No( )
Work Class:
New ( ) Addition ( ) Remodel Repair ( )
Retro -Fit ( ) Other ( )
Type of Building:
Single - Family ( ) Duplex ( ) Multi - Family ( )
Commercial Restaurant ( ) Other ( )
Date Received:
oI \9 c
13
JAN iW 2011
M
TOWN OF VAIL
01- Feb -l0
I///\ Western States
v Fire Protection Co.
p .dufea acsd Sao
Material Submittal
FOR
POSH HAIR SALON
VAIL RITZ CARLTON
1031 SOUTH FRONTAGE ROAD
VAIL, CO 81658
Tenant Finish
Prepared by:
Jeff Hagan
Project Manager
Western States Fire Protection Co.
7026 S. Tucson Way
Centennial, CO 80112
Phone (303) 792 -0022
Fax (303) 792 -9049
Cell (303 -549 -9553
Email jeff.hagan @wsfp.us
WSFP #CS11097
January 13, 2011
11
Model F1 FR Recessed Sprinkler Types
Recessed Pendent
Listings & Approvals
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters' Laboratories of Canada (ULC)
3. Certified by FM Approvals
4. Loss Prevention Council (LPC, UK)
5. NYC BS &A No. 587 -75 -SA
6. Meets MIL- S -901C and MIL -STD 167 -1
7. Verband der Schadenversicherer (VdS, Germany)
8. NYC MEA 258 -93 -E
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number
VNIV
Patents: US Patent No. 6,374,920 Applies to
Model F1 FR Vertical Sidewall Sprinklers.
Product Description
Reliable Models F1 FR and F1 FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a
standard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models F1 FR and F1 FR Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers. This
quick response enables the Model F1 FR and F1 FR Recessed
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response. The balance of
parts are made of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid ex-
Bulletin 136 Rev.M
Model F1 FR Recessed
Quick Response
Sprinklers
Recessed Pendent
(Model FP Shown)
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
c
m
1
The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
MATERIAL INDEX
"Because of the current escalation occurring with steel, WSFP reserves the right to substitute pipe as required to meet
project schedules.
Description
Model
Manufacturer
1.
Sprinkler Head
A. Standard Spray Quick Response Semi - Recessed Pendant Sprinkler
FIFR
Reliable
II.
Pipe — 1 -1/4" and smaller threaded
A. Black Schedule 40 Pipe
ASTM A 795
Varies"
III.
Cast Iron Fittings
Varies
Varies"
IV.
Pipe Hangers (Per NFPA 13)
A. Concrete Drop in Anchors
HDI -P 3/8
Hilti
B. All Thread Rod
Fig. 100
Tolco
C. Adjustable Ring Hanger
Fig. 200
Tolco
"Because of the current escalation occurring with steel, WSFP reserves the right to substitute pipe as required to meet
project schedules.
Model F1 FR Quick Response Recessed Pendent Sprinkler
I Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor
Sprinkler Approval Sprinkler Identification
Height Organizations Number (SIN)
HOLE IN CEILING
us
Metric
?2' (15mm)
y" NPT (RYz)
5.6
80
2.2" (5 6mm)
1,2,3,4,5,7,8
R3615
_ 1 CEI!lNfi l
" (20mm)
Y NPT (R
8.0
115
2.3" (58mm)
1,2,3,8
R3612
(11 mm)
y "NPT(RI/2)
4.2
60
22'(56mm)
1,2,8
R3613
38' (10mm)
y"" NPT (R'/1)
2.8
40
2.2" (56mm) --
1,2,8
R3611
10mm
F%
4.2
60
56mm
4,7
R3614
I' Refer to escutcheon data table for approvals and dimensions.
1/8
13.1mm1 1 _0.
? 17131 - DM
j71.1mm1 136FG01 _ f
(1) RCFEP T^ FI d F2 ESCUTCHEON DATA TABLE FOR APPROVALS AND DMENSONS.
1 1 14• HOLE DA.
371mmJ
IS /16• pA
jA9.ZmmJ
HOLE IN CEILING
TURN COLLAR
UN k DCHT
AC4NST SPRINKLER
WRCNYH Bp55
!' x 112• REDUCER
CUP
fl
I
i
I I
FACE OF fll11AC IL
ADJUS TMENT hl
_ 1 CEI!lNfi l
0'J vs
1/8
13.1mm1 1 _0.
? 17131 - DM
j71.1mm1 136FG01 _ f
(1) RCFEP T^ FI d F2 ESCUTCHEON DATA TABLE FOR APPROVALS AND DMENSONS.
2.
1 518" DIA. [66.7mm1
HOLE IN CEILING
1 5116 DLA, [58.7mml
CUP
r
I 112' REDUCER
� I
L _J
CEILING
00 da
FACE OF F ?T/NG
TO FACE OF CEILING
DIUENSION,,�
1
r}
A T1
ADJUSTAlfNT
IJEi':05_A
(1) REFER TO FP ESCUTCHEON DATA THOLE FOR APPROVALS AND DIMENSIONS.
2.
Installation
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Model F1 FR Recessed Quick Response Sprinklers are to
be installed as shown. The Model F1 or F2 Escutcheons illus-
trated are the only recessed escutcheons to be used with the
Model F1 FR Sprinklers. The use of any other recessed escutch-
eon will void all approvals and negate all warranties.
When installing Model F1 FR Sprinklers, use the Model D Sprin-
kler Wrench. When installing Model F1 FR Recessed Pendent or
Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any
other type of wrench may damage these sprinklers.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation. RE-
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Re-
moval of the protectors before this time may leave the bulb vul-
nerable to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PROTECTORS
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS
TO REMOVE THE PROTECTORS.
Temperature Ratings
A
(1) Not available for recessed sprinklers.
Escutcheon Data
•I
Foridr," An Face of Fitting
Modal Approvals Adjustment DI n sion to Calling or
Wall Dimension
Sprinkler
Escutcheon
z
Classification
Temperature
Max. Ambient
Bulb
F1
Temp.
Color
'C
'F
1 Y116 "
(5mm - 17mm)
Ordinar
Min Recess
Y. "
(5mm - 24mm)
FP
Ordinary
68
155
10o'F(38 °C)
Red
Intermediate
93
200
150- F(66'C)
Green
High (t)
14
286
225'F(1o7'C)
Blue
A
(1) Not available for recessed sprinklers.
Escutcheon Data
•I
Foridr," An Face of Fitting
Modal Approvals Adjustment DI n sion to Calling or
Wall Dimension
No Dimensional Figure for FP
Maintenance
The Models F1 FR and F1 FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non - operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1
Recessed Pendent
Recessed Horizontal Fl
Finishes (1)(2)
Standard Finishes
Sprinkler
Escutcheon
z
1y „
F2
1,2,3,4,5,7,8
Max Recess
F1
1,2,4,8
Max Recess
(38.1 mm)
3;8`
1 Y116 "
(5mm - 17mm)
Min Recess
Y. "
(5mm - 24mm)
FP
1,2
Max Recessed
j mm
1y" (38.1 mm)
19.1mm
No Dimensional Figure for FP
Maintenance
The Models F1 FR and F1 FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non - operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1
Recessed Pendent
Recessed Horizontal Fl
Finishes (1)(2)
Standard Finishes
Sprinkler
Escutcheon
z
Brass
Chrome Plated (3)
White Painted (3)
F2
1,2,3,4,5,7,8
Max Recess
(38.1 mm)
Ye - 'Y,a ll
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Min Recess
1 Y116 "
(5mm - 17mm)
24mm
FP
1,2
Max Recessed
j mm
1y" (38.1 mm)
1
PushoN
Thread -off
1,2
Min Recessed
1 "(25.4mm)
(24 m s m)
No Dimensional Figure for FP
Maintenance
The Models F1 FR and F1 FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non - operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1
Recessed Pendent
Recessed Horizontal Fl
Finishes (1)(2)
Standard Finishes
Sprinkler
Escutcheon
Bronze
Brass
Chrome Plated (3)
White Painted (3)
Chrome Plated
White Polyester Coated
S pecial A p Ip icatl Finishes
Sprinkler
Escutcheon
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
( Other finishes and colors are available on special order.
Consult the factory for details.
( FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
( FP Push- on/Thread -off escutcheon
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Note: When Model F1 FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable
The Reliable Automatic Sprinkler Co., Inc.
(800)431 -1588 Sales Offices
(800)848 -6051 Sales Fax
(914)668 -3470 Corporate Offices
www.reliablesprinkler.com Internet Address
® Recycled
Paper
Revision lines indicate updated or new data
EG. Printed in U.S.A. 7105 PIN9999970027
FM Approved and UL Listed Sprinkler Pipe
Bull Moose Tube Company is a recognized producer
of quality pipe products. Our Schedule 10 and
Schedule 40 are FM Approved and UL Listed (for U.S.
and Canada), even though these products do not
require separate approvals and listings. Bull Moose
Tube made the decision to have them approved and
listed for your peace of mind. Our Sch. 10 and Sch. 40
have been through the same rigorous testing as our
other fine pipe products.
Bull Moose Tube's Sch. 10 and Sch. 40 pipes are
made to ASTM A135 and ASTM A795. These
products are typically supplied with our protective
coating but can be supplied without the coating so
they can be hot -dip galvanized to meet FM
requirements for use in dry systems in accordance
with the zinc coating specifications of ASTM A795 or
ASTM A53. All Schedule 10 and Schedule 40 pipe
has a pressure rating of 300 PSI.
Schedule 40 Pipe
1
1.315
1.049
1.68 Ibs /ft
70
1 1/4
1.660
1.380
2.27 Ibs /ft
51
1 1/2
1.900
1.610
2.72 Ibs /ft
44
2
2.375
2.067
3.66 Ibs /ft
30
PIPE PREPARATION
For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak -tight seat for the gasket, pipe surfaces should be
free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt, chips, grease, and rust must be removed prior
to installation. Failure to take these important steps may result in improper coupling assembly, causing leakage. Also, check the manufacturer's
instructions for the specific fitting used.
n 1819 Clarkson Road For additional information, C �L us
( v� Chesterfield, MO 63017 contact your salesperson
J t BULL MOOSE TUBE COMPANY (800) 325 -4467 today at (800) 325 -4467 or ltsrEo
CJ FAX: (636) 537 -2645 (636) 537 -2600 in the USA,
www.bullmoosetube.com or from Canada FM
ACA A company e-mail: salesO)bullmoosetube.com call (800) 882 -4666
APPROVED
All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation.
12/09
ill PICTORIAL TABLE OF CONTENTS
Cast Iron (Continued)
CAST IRON DRAINAGE FITTINGS
ra I &
Fig. 701 Fig. 7018
90" Short Turn Elbow 90" Reducing Short Turn Elbow
Size Range: 1' 12* thru 4" Sizes: 1 & 2"
vi
Fig. 722 Fig. 723
Tee Reducing Tee
Sizes: 1 12' & 2" Size: 2" x 2" x 1'/i
www.anvilind.com 9
MMIM"
4.3.9 HDI -P Drop -In Anchor
4.3.9.1 Product Description
4.3.9.2 Material Specifications
4.3.9.3 Technical Data
4.3.9.4 Installation Instructions
4.3.9.5 Ordering Information
Listinas /Aoarovals
ICC -ES (International Code Council)
ESR -1291
COLA (City of Los Angeles)
Research Report No. 25350
Factory Mutual (FM)
Pipe Hanger Components for Automatic
Sprinkler Systems
4.3.9.1 Product Description
The Hilti HDI -P Drop -In anchor is an
internally threaded, flush mounted
expansion anchor for solid and
hollow concrete.
Product Features
Guide Specifications
• Optimized 3/4" anchor length to
allow reliable fastenings in hollow
core panels, precast plank & post
tensioned slabs
• Shallow drilling enables fast
installation
• Lip provides flush installation,
consistent anchor depth and easy
rod alignment
• Setting tool leaves mark on flange
when anchor is set properly to
enable inspection & verification of
proper expansion
Expansion Anchor Expansion anchors
shall be flush or shell type and zinc
plated in accordance with ASTM B 633,
SC 1, Type III. Anchors shall be Hilti
HDI -P anchors as supplied by Hilti.
Installation Install shell or flush type
anchors in holes drilled with Hilti carbide
tipped drill bits. Install anchors in
accordance with manufacturer's
recommendations.
4.3.9.2 Material Specifications
The HDI -P is manufactured from mild carbon steel, which is zinc plated for
corrosion protection in accordance with ASTM B 633, SC 1, Type III
4.3.9.3 Technical Data
HDI -P Specification Table
Desc.
Length
in. (mm)
Bit Size'
in.
Average Ultimate Loads, lb (kN)
Allowable Loads, lb (kN)
4000 psi Concrete
(27.6 MPa)
Hollow Core
(Spancrete)
4000 psi Concrete
(27.6 MPa)
Hollow Core
(Spancrete)
Tension
Shear
Tension
j Shear
Tension
Shear
Tension
Shear
HDI -P 3/8
3/4(19.1)
1/2
1900 (8.5)
3000 (13.3)
2100 (9.3)
4000 (17.8 )
380 (1.7)
600 (2.7)
420 (1.9)
800 (3.6)
1 For Hilti matched tolerance carbide tipped drill bits, see section 8.4.1.
4.3.7.4 Installation Instructions
1. Set depth 2. Hammer -drill 3. Clean hole. 4. Insert anchor. 5. Insert setting 6. Collar of set -
gauge on drill. hole. tool and strike ting tool will
with hammer leave an
until anchor is indentation
fully set. on flange of
4.3.9.5 Ordering Information anchor when
HDI -P Anchor properly
expanded.
Item No. Description Box City
00283611 HDI -P 3/8 100
Setting Tools for HDI -P Anchors
Item No. Description
00283611 HSD -G 3/8" - 3/4" Setting Tool w/ hand guard
00253784 HST -P 3/8" - 3/4" Settina Tool
256 Hilti, Inc. (US) 1- 800 - 879 -8000 1 www.us.hilti.com I en espanol 1 -800- 879 -5000 1 Hilti (Canada) Corp. 1- 800 - 363 -4458 1 www.ca.hilti.com 1 Product Technical Guide 2006
Component of State of
California OSHPD Approved C � ps LIMB
Seismic Restraints System
Fig. 100 - All Thread Rod Full Lengths
Size Range — Secures 3/8" thru 7/8" rod in
10' lengths
Material — Carbon Steel
Maximum Temperature — 750 °F
Finish — Plain
Note —Available in Electro- Ga Ivan ized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter
and finish
® OFFICEIMANUFACTURING FACILITY - 1375 SAMPSON AVE. - CORONA, CA 92879 - PH: 951.737.5599 - FAX: 951.737.0330
CUSTOMER SERVICE - 800.786.5266
www.tolco.com
Dimensions - Weights
Max Rec. Load Lbs.
Rod
For Service Temps
Approx.
Size
650 °F 750 °F
Wt. /100
1/4
240 215
12
3/8
610 540
29
1/2
1130 1010
53
5/8
1810 1610
84
3/4
2710 2420
123
7/8
3770 3360
169
1
4960 4420
222
1 1 /4
8000 7140
360
1
11630 10370
510
® OFFICEIMANUFACTURING FACILITY - 1375 SAMPSON AVE. - CORONA, CA 92879 - PH: 951.737.5599 - FAX: 951.737.0330
CUSTOMER SERVICE - 800.786.5266
www.tolco.com
Fig. 200 - "Trimline" Adjustable Band Hanger
Size Range — 1/2" thru 8" pipe
Material — Carbon Steel, Mil. Galvanized to G90
specifications
Function — For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features —
• (1/2" thru 2 ") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
abrasion. Captured design keeps adjusting nut
from separating with hanger. Hanger is easily
installed around pipe.
• (2 thru 8" Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals — Underwriters' Laboratories listed (1/2"
thru 8 ") in the USA (UL) and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8 "). Conforms to Federal
Specifications WW -H -171 E, Type 10 and Manufacturers
Standardization Society SP -69, Type 10.
Maximum Temperature — 650 °F
Finish — Mil. Galvanized. For Stainless Steel materi-
als, order TOLCOTm Fig. 200WON.
Order By — Figure number and pipe size
c UL us usTEo
FM
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
• CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Dimensions • Weights
Pipe
Rod Size
Max. Rec.
Approx.
Size
Inch
Metric
A
B
Load Lbs.
Length
1/2
3/8
8mm or 10mm
3
2
400
11
3/4
3/8
8mm or 10mm
3
2 +h
400
11
1
3/8
8mm or 10mm
3Y8
2
400
12
1 1 /4
3/8
8mm or 1 Omm
3 8 /4
2
400
13
11/1
3/8
8mm or 10mm
3
2
400
14
2
3/8
8mm or 10mm
4
3
400
15
c UL us usTEo
FM
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
• CUSTOMER SERVICE • 800.786.5266
www.tolco.com