HomeMy WebLinkAboutA11-0006 SK Heat_spec � •-
SILENT SK-Heat, SK-Heat-HT
KNI�T�T and
by H�o�eyweii SK-Heat-ROR
Addressable thermal heat and rate-of-rise detectors
The SK-Heat, SK-Heat-HT, and SK-Heat-ROR are plug in thermal detectors, with integral communication, that
provide features that surpass conventional detectors. These thermal detectors are for use with Silent Knight
IntelliKnight series Fire Alarm Control Panels (FACPs).
IntelliKnight heat detectors are an essential component in virtually any IntelliKnight installation. The IntelliKnight
panel recognizes each detector by its specific address, so precious seconds are not wasted in determining
location of an alarm.
Description • Dual LED indicators for 360°
SK-Heat, SK-Heat-HT and SK- visibility
Heat-ROR are intelligent sensors • Detector transmits signal to
that utilize a state-of-the art indicate maintenance is required +
thermistor sensing circuit for fast
response. Sensitivity is • Plug-in mounting provides ease
continuously monitored and of installation ��
reported to the FACP. Point ID . Optional remote LED annunciator
capability allows each detector's
address to be set with rotary (System Sensor� PN RA100Z)
address switches, rovidin exact SK-Heat (base included)
P 9 • Tamper-proof feature available on
detector locations for selective mounting bases Thermal Ratings
maintenance when chamber SK-Heat: Fixed temperature alarm
contamination reaches • Rotary address switches for fast 135°F (57°C)
unacceptable levels. installation
SK-Heat is a fixed temperature • UL Listed SK-Heat-HT: High temperature heat
sensor 135°F - 190°F (57°C - 88°C)
sensor that uses a thermistor Specifications
sensing circuit to produce 135°F SK-Heat-ROR: Rate-of-rise
(57°C)fixed temperature alarm. Physical detection 15°F/min (8.3°C/min)
Height: 2.0" (51 mm)
SK-Heat-HT is a variable high Diameter: 6.1" (155 mm)installed in Compatibility
temperature detector that provides B210LP base The SK-Heat, SK-Heat-HT and SK-
high temperature detection at Shipping Weight: 4.8 oz (137 g) Heat-ROR are compatible with the
135°F - 190°F. (57°C - 88°C) followin IntelliKni ht FACP's:
Electrical J 9
SK-Heat-ROR is a rate-of-rise Operating Voltage: 15 to 32 Volts 5700
temperature sensor with 135°F DC Peak 5808
(57°C)fixed temperature alarm. 5820XL
Standby Current: 300�aA @ 24
Features VDC The SK-Heat, SK-Heat-HT and SK-
• Reliable analog communications LED Current: 6.5 mA@ 24 VDC Heat-ROR are compatible with the
following detector bases:
for trouble-free operation Environmental
B210LP (included) 6" base
• Age resistant polymer housing Operating Temperature B501 2 wire base
• Innovative thermistor sensing SK-Heat & SK-Heat-ROR: B224B1 Isolator base
circuit -4°— 100°F (-20°C— 38°C) B224RB Relay base
• Superior EMI resistance for
SK-Heat-HT: -4°— 150°F B200SR Sounder base
reliability (-20°C —66°C)
• Variety of mounting options to Humidity: 10% — 93%
noncondensing
meet any application
� •-
Model SK-Heat, SK-Heat-HT,
SK-Heat ROR Addressable Thermal
and Rate-of-Rise Thermal Detectors
Engineering Specifications
The contractor shall furnish and install where indicated on the plans, Intelligent Thermal Sensor Silent Knight
Model SK-Heat, SK-Heat-HT or SK-Heat-ROR. The base included shall be B210LP.
The Heat detector shall have a flashing status LED for visual supervision. When the detector is activated, the
flashing LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset
switch.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The
locking feature shall be field removable when not required.Voltage and RF/transient suppression techniques
shall be employed to minimize false alarm potential.
�
/� ' �
� s�c
� IN OUT
�
- Compatable FACP
�
—E+ .- + -
RA100Z(Optional)
+ -
� ........................
3 2 3 Z 3 z
1 1 :'� 1
�
EE................................................................................................................................................................................. � .................................6 E
E Class A Optioraal Wiring ' :`
:....................................................................................................................................................................................... ....................................................................,
Wiring SK-Series Detector Mounting Bases
Accessories M02-09-00-Test Magnet with Telescoping Handle.
RA100Z-Remote LED Annunciator. XP-4-Extension Pole for XR2B. Extends from 5—15 ft.
RMK400-Recessed Mounting Kit. Provides low profile for use with T55-127-000-Detector Removal Head.
B501.
XR2B-Detector Removal Tool.A removal and re-placement tool BCK-200B-Black Detector Kit. For SK-series detectors.
for SK plug-in detectors. Includes the T55-127-000. 'Unless otherwise noted, specifications apply to all SK thermal
M02-04-01 -Replacement Test Magnet. detectors.
S��E�.�, This document is not intended to be used for installation purposes.We try to MADE IN AMERICA
keep our product information up-to-date and accurate.We cannot cover all
�+�I�HT specific applications or anticipate all requirements.All specifications are FORM#350120 Rev. C
subject to change without notice. For more information, contact Silent Knight O 2010 Honeywell International Inc.
by Honeywell 12 Clintonville Road Northford, CT 06472-1610 Phone: (800)328-0103,
Fax: (203)484-7118.www.silentknight.com