HomeMy WebLinkAboutVail Lionshead Filing 3 Block 1 Lot 7.PDF Town of Vail Building Safety & Inspection Services Community Development Department 75 South Frontage Road Vail, Co 81657 (970) 479-2325 FAX (970) 479-2452 Plan analysis based on the 1997 Uniform Building Code Project Number: B02-0198 Date: July 8, 2002 Project Name: MARRIOTT TENANT FINISH, PENTHOUSES I, II & III Address: 714 W Lionshead Circle Contractor: Hyder Construction Occupancy: Rl Architect: Gwathmey, Pratt, Schultz Construction: II-FR Engineer: Alvine & Associates,Inc. Report By: Goodell Consulting Project Description: Tenant Finishes for Penthouse I, a 2664-sq-ft, 2-story condominium unit located on the 7th & 8th stories; Penthouse II, a 2175-sq-ft, 1-story condominium unit located on the 7th story; and Penthouse III, a 2,072-sq-ft, 1-story condominium unit located on the 6th story; respectively, of an existing hotel building. NOTE: The code items listed in this report are not intended to be a complete listing of all possible code requirements in the 1997 UBC. It is a guide to selected sections of the code. Report partially created using Plan Analyst software by b w & a. Portions of the material contained in this program are reproduced from the Uniform Building Code (UBC)with the permission of the 6 International Conference of Building Officials (ICBO) . SEPARATIONS The condominiums are required to be separated from other condominium units or hotel rooms adjacent to them or above or below them by approved one-hour fire-resistive construction in accordance with Sec. 310.2.2, 197 UBC. Corridor walls adjacent to condominiums are required to be approved, 1-hour fire-resistive construction in accordance with Sec. 1004.3.4, 197 UBC, including smoke-gasketed 20-minute smoke-and-draft-control door assemblies in accordance with Sec. 1004.3.4.3.2.1. Stair enclosures in this 8-story Type II-FR building are required to be constructed as 2-hour fire-resistive enclosures with 90-minute doors in accordance with Sec. 1005.3.3, 197 UBC. 2 PENTHOUSE I, 7TH & 8TH STORIES: FL NAME AREA MIN.LIGHT MIN.VENT NO.EXITS EGRESS ------------------------------------------------------------------------ 2 Hallway 183 .0 .0 1 No 2 Bedroom #2 249 24.9 12.45 1 No 2 Closet #2 21 .0 .0 1 No 2 Bathroom #2 61 .0 3.05 1 No 2 Bedroom #3 256 25.6 12.8 1 No 2 Closet #3 19 .0 .0 1 No 2 Bathroom #3 68 .0 3.4 1 No TOTAL FOR FLOOR 857 1 1 Entry Hallway 153 .0 .0 1 No 1 Living/Diniing/Kitche 956 95.6 47.8 1 No 1 Entry Closet 24 .0 .0 1 No 1 Entry Powder Room 34 .0 1.7 1 No 1 Master bedroom 294 29.4 14.7 1 No 1 Master bath 181 .0 9.05 1 No 1 Master Closet 64 .0 .0 1 No 1 Pantry/Stairs 76 .0 .0 1 No 1 Living Room Closet 25 .0 .0 1 No TOTAL FOR FLOOR 1807 1 DWELLING TOTAL 2664 1 PENTHOUSE II, 7TH STORY: FL NAME AREA MIN.LIGHT MIN.VENT NO.EXITS EGRESS ------------------------------------------------------------------------ 1 Entry Hallway 191 .0 .0 1 No 1 Entry Closet 30 .0 .0 1 No 1 Entry Powder room 31 .0 1.55 1 No 1 Living/Dining/Kitche 835 83.5 41.75 1 No 1 Washer/Dryer 13 .0 .0 1 No 1 Master bedroom 288 28.8 14.4 1 No 1 Master Closet 108 .0 .0 1 No 1 Master bath 162 .0 8.1 1 No 1 Bedroom #2 216 21.6 10.8 1 No 1 Closet #2 15 .0 .0 1 No 1 Bathroom #2 54 .0 2.7 1 No 1 Bedroom #3 153 15.3 7.65 1 No 1 Closet #3 16 .0 .0 1 No 1 Bathroom #3 63 .0 3.15 1 No TOTAL FOR FLOOR 2175 1 CONDOMINIUM TOTAL 2175 1 PENTHOUSE III, 6TH STORY: FL NAME AREA MIN.LIGHT MIN.VENT NO.EXITS EGRESS ------------------------------------------------------------------------ 1 Living/dining room 678 67.8 33.9 1 No 1 Kitchen 114 .0 5.7 1 No 1 Entry Vestibule 189 .0 9.45 1 No 1 Entry Closet 14 .0 .0 1 No 1 Washer/Dryer 13 .0 .0 1 No 1 Entry Bathroom 49 .0 2.45 1 No 3 1 Master bedroom 234 23.4 11.7 1 No 1 Master bath 145 .0 7.25 1 No 1 Master Closet 66 .0 .0 1 No 1 Bedroom #2 222 22.2 11.1 1 No 1 Closet #2 12 .0 .0 1 No 1 Bathroom #2 64 .0 3.2 1 No 1 Bedroom #3 205 20.5 10.25 1 No 1 Closet #3 11 .0 .0 1 No 1 Bathroom #3 56 .0 2.8 1 No TOTAL FOR FLOOR 2072 1 BUILDING TOTAL 2072 1 FOOTNOTES: 1) EGRESS - Egress windows or doors are not required for sleeping rooms located at or above the fourth story (Sec. 310.4, UBC) . 2) NOTE: The building official has determined that the number of required exits from each individual condominium unit may be based upon an occupant load factor of 300 square feet per occupant. However, two exits are required from each entire story of the building. The building official has also determined that the separation distance for the stair enclosures as proposed is adequate under the circumstances. 3) A mechanical ventilation system may be used in lieu of exterior openings for ventilation. -- Sec. 1203.3 Such system shall be capable of providing two air changes per hour. ROOM DIMENSIONS: Habitable space shall have a ceiling height of not less than 7 feet 6 inches. Kitchens, halls, bathrooms and toilet compartments may have a ceiling height of 7 feet measured to the lowest projection. If the ceiling is sloping, then the minimum height is required in only 1/2 of the area. -- Sec. 310.6.1 Every dwelling unit shall have at least one room which has not less than 120 square feet of floor area. Other habitable rooms except kitchens shall have an area of not less than 70 square feet. -- Sec. 310.6.2 Habitable rooms other than a kitchen shall not be less than 7 feet in any dimension. -- Sec. 310.6.3 STAIR REQUIREMENTS: 1) A stairway in a dwelling must be at least 36 inches wide. -- Sec. 1003.3.3.2 2) The maximum rise of a step is 8 inches and the minimum run is 9 inches -- Sec. 1003.3.3.3, Exception 1 3) A handrail is required on one side a stairway 34 to 38 inches above the nosing if there is 4 or more risers. -- Sec. 1003.3.3.6, Exceptions 4) Provide a guard rail where drop off is greater than 30 inches. The minimum height is 36 .inches and the maximum opening size is 4 inches. -- Sec. 509.1 & 509.2, Exception 1 5) The minimum headroom is 6 ft.- 8 inches. -- Sec. 1003.3.3.4 6) Enclosed usable space under the stairs is required to be protected as required for 1 hr. fire-resistive construction. -- Sec. 1003.3.3.9 GLAZING REQUIREMENTS: All glazing in hazardous locations is required to be of safety glazing material. -- Sec. 2406.3 & 2406.4 Locations: 1) Glazing in ingress and egress doors except ]alousies. ' 4 2) Glazing in fixed and sliding panels of sliding door assemblies and panels in swinging doors other than wardrobe doors. 3) Glazing in storm doors. 4) Glazing in all unframed swinging doors. 5) Glazing in doors and enclosures for hot tubs, whirlpools, saunas, steam rooms, bathtubs and showers. Glazing in any portion of a building wall enclosing these compartments where the bottom exposed edge of the glazing is less than 60 inches above a standing surface and drain inlet. 6) Glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24-inch arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60 inches above the walking surface. 7) Glazing in an individual fixed or operable panel, other than those locations described in items 5 and 6 above, than meets all of the following conditions: A. Exposed area of an individual pane greater than 9 square feet. B. Exposed bottom edge less than 18 inches above the floor. C. Exposed top edge greater than 36 inches above the floor. D. One or more walking surfaces within 36 inches horizontally of the plane of the glazing. 8) Glazing in railings regardless of height above a walking surface. Included are structural baluster panels and nonstructural in-fill panels. 9) Glazing in walls and fences used as the barrier for indoor and outdoor swimming pools and spas when the bottom edges is less than 60 inches above the pool side and the glazing is within 5 feet of the pool or spa water's edge. 10) Glazing in walls enclosing stairway landings or within 5 feet of then bottom and top of stairways where the bottom edge is less than 60 inches above the walking surface. SMOKE DETECTOR REQUIREMENTS: 1) A smoke detector is required on the ceiling or wall at a point centrally located in the corridor or area giving access to each sleeping area. -- Sec. 310.9.1.4 2) A smoke detector is required on the ceiling or wall in each sleeping area. -- Sec. 310.9.1.4 3) A smoke detector is required on all stories. -- Sec. 310.9.1.4 If the upper level contains sleeping room(s) , a smoke detector is required in the ceiling of the upper level close to the stairway. -- Sec. 310.9.1.4 4) Smoke detectors are required to be wired to the building's power source and shall be equipped with a battery backup. -- Sec. 310.9.1.3 5) Detectors shall sound an alarm audible in all sleeping area of the dwelling in which they are located. -- Sec. 310.9.1.4 6) Provide a smoke detector in all sleeping rooms and areas having access to sleeping rooms. -- Sec. 310.9.1.4 7) Provide a smoke detector on all floors that is connected to an alarm audible in all sleeping areas. -- Sec. 310.9.1.4 SHAFT ENCLOSURES: 1) Gas vents and noncombustible piping installed in walls passing through 3 floors or less do not need to be in 2-hour shafts, provided the annular space around the vents or piping is filled at each floor or 5 ceiling with noncombustible materials.-- Sec. 711.3 2) All other shafts are required to be enclosed in a 2-hour assembly. -- Sec. 711.1 & Table 6-A OTHER: 1) The only wood that is permitted to be used for backing within interior walls is approved, fire-retardant-treated wood (Sec. 603.1, UBC, for Type II-FR noncombustible construction) . 2) Kraft paper backing for insulation is not permitted to be used in Type II-FR construction (Sec. 707.3, UBC) . 3) Gas-fired logs or fireplaces installed in bedrooms or sleeping rooms must be specifically listed for installation in a sleeping room and the installation must follow the manufacturer's instructions for installation in a sleeping room. 4) Plywood may not be used as backing for masonry veneer installed on fireplaces in Type II-FR noncombustible construction. Approved cement board or other materials that meet the UBC definition of "noncombustible" must be used (Sec. 603.1, UBC) . 5) Clothes dryer ducts that exceed the prescriptive maximum length requirements of 14' and two 90-degree elbows (Sec. 504.3.2, 197 UMC) must be designed by a qualified mechanical engineer or otherwise meet the requirements of Sec. 504.3.2, UMC. 6) Dishwashers must be equipped with approved backflow prevention devices in accordance with Sec. 807.4, 194 UPC; Sec. 409, 197 IPC and applicable state laws. SEE ALSO THE RESIDENTIAL PLAN REVIEW LIST ATTACHED TO THE APPROVED PLANS FOR ADDITIONAL REQUIREMENTS AND REMINDERS. Town of Vail Building Safety& Inspection Services (970)479-232.5 i RESIDENTIAL PLAN REVIEW LIST Per the Town of Vail Municipal Code, based upon the adoption of the 1997 Uniform Building Code (UBC), 1998 International Mechanical Code (IMC) or 1997 Uniform Mechanical Code (UMC), 1994 Uniform Plumbing Code (UPC) or 1997 International Plumbing Code (IPC), the 1999 National Electrical Code (NEC) and the 1989 Model Energy Code (MEC). OWNER'S NAME: JVIAke—1 ! /7-tr PERMR# g00Z 01 / IMPORTANT NOTICE: THIS LIST IS AN INTEGRAL PART OF YOURAPPROVED PLANS ALL ITEMS CONTAINED ON THIS LIST ARE MINIMUM CODE REQUIREMENTS AND MUSTBE COMPLIED WITHIF YOUR CONSTRUCTION IS TO RECEIVE INSPECTION APPROVALS THE CIRCLED ITEMS ARE THOSE ITEMS WHICH,DURING THE COURSE OF OUR PLAN REVIEW OF YOUR PROJECT, WERE FOUND TO BE INCORRECT, UNCLEAR, OR NOT SHOWN ON YOUR PLANS. SOME ITEMS ARE CIRCLED EVEN IF THEYARE SHOWN CORRECTLY ON THE PLANS SIWLY TO REMIND YOU OF AN IMPORTANT CODE REQUIREMENT SPECIAL NOTE SHOULD BE TARN OF THE CIRCLED ITEMS SO THAT CORRECTIONS CAN BE MADE DURING THE COURSE OF CONSTRUCTION. EVERYEFFORT HAS BEEN MADE TO NOTE ALL NECESSARY CORRECTIONS DURING OUR PLANREVIEWPROCESS. HOWEVER, ULTIMATELY IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PERFORM THE CONSTRUCTION ACCORDING TO MINIMUM CODE REQUIREMENTS, REGARDLESS OF WHETHER OR NOT THE ITEMS ARE CIRCLED ON THIS LIST IF YOU SHOULD HAVE ANY QUESTIONS WHATSOEVER, PLEASE CONTACT BUILDING SAFETY & INSPECTION SERVICES AT 479-2325 BEFORE PROCEEDING THIS SET OF APPROVED PLANS(STAMPED "APPROVED,"DATED&INITIALED)MUST BE AVAILABLE TO THE BUILDING INSPECTOR ON THE SITE WHEN INSPECTIONS ARE MADE FAILURE TO HAVE THESE APPROVED PLANS ON THE JOB SITE WILL RESULT IN 1) NO INSPECTION BEING PERFORMED 2) NO INSPECTION APPROVAL 3) NO APPROVAL TO PROCEED WITH THE CONSTRUCTION 4) PAYMENT OF A $40 00 REINSPECTION FEE AT THE BUILDING SAFETY & INSPECTION SERVICES OFFICES BEFORE THE INSPECTION IS RESCHEDULED (UBC Sec 108.8) I SPECIAL NOTE: LICENSING REQUIREMENTS FOR PLUMBING AND ELECTRICAL WORK Per Colorado law (CRS 12-58-101 et seq & 12-23-101 et seq, respectively), persons performing plumbing or electrical work for hire must be licensed by the State Plumbing or Electrical board, respectively, and must be working under the supervision of persons licensed by the state to operate a plumbing or electrical business For plumbing work,this means that the individual must not only be licensed by the state as a plumber,but must also either hold a Master Plumber's license or be working under the direct supervision of a Master Plumber. For electrical work, the person doing the work must not only be licensed, but must also either hold a Master Electrician's license and an Electrical Contractor's license or be working under the direct supervision of an individual licensed as such The only applicable exception to these laws is that individuals may perform electrical or plumbing work within their own home(see CRS 12-58-113(2) and 12-23-111(2), respectively, for details) 2 APPROVAL OF PLANS AND SPECIFICATIONS DOES NOT PERMIT THE VIOLATION OF ANY PART OF THE TOWN OF VAIL BUILDING CODES OR ANY OTHER ORDINANCE OR LAW OF THE TOWN OF VAIL 1 Foundations supporting wood shall extend at least 6"above the adjacent finished grade(UBC Sec 1806 1) 2 All lumber in contact with concrete or masonry or within 6" of finished grade shall be treated wood or redwood (UBC Sec. 2306.4) 3 Frost depth to the bottom of the foundation footings must be as prescribed on the engineered plans If not noted, the frost depth to the bottom of the footings must be a minimum of 48 inches below finished grade (UBC 1806 1) 4 Wood joists closer than 18"or wood girders closer than 12"to exposed ground within a crawl space are to be treated lumber or wood of natural resistance to decay(UBC Sec 2306 3) Wood used inthe construction of structures and located nearer than 6" to earth shall be of treated wood or wood of natural resistance to decay(UBC Sec 2306 3). 5 Wood girders,that are not treated or of redwood,entering concrete or masonry walls must maintain a'/2"air space(UBC Sec. 2306.6) 6 Under floor vents shall have a net area of not less than 1 sq.ft for each 150 sq ft of under floor area(UBC Sec. 2306 7) 7 Accessible under floor areas shall be provided with a minimum 18" x 24" unobstructed access opening (UBC Sec 2306 3) Where equipment is located in an under floor area the access opening shall be of a height and width sufficient to allow the removal of the largest piece of equipment,but not less than 30"x 22" (UMC Sec 307 4) 8. Provisions shall be made for the control and drainage of surface water around buildings. All building pads will be graded 2% away from buildings(UBC Sec 1804.7& 1806 5 5) 9. Dampproofing or waterproofing of foundations retaining earth and enclosing interior spaces below grade is required (UBC Sec 1402 4) 10. Bond beam required in block foundation walls. 11 Foundation plates or sills shall be bolted to the foundation wall as prescribed on the engineered plans Ifnot noted,bolted with not less than'/2-inch diameter steel bolts embedded at least 7 inches into the concrete or masonry and spaced not more than 6 feet apart There shall be a minimum of 2 bolts for each piece with one bolt located within 12 inches of each end of each piece (UBC Sec 1806 6) 12 Garage floor surface shall be of approved noncombustible materials or asphaltic paving material(UBC Sec. 312.5) 13 All lumber,plywood,fiberboard and structural glued laminated timber must be identified by a grade mark or certificate of inspection issued by an approved agency(UBC Sec 2304.1) 14. All trusses and/or rafters are to be tied to exterior walls with approved hurricane anchors (UBC Sec 1605 2 3) Rafters & ceiling joists exceeding 2" x 6" (3 to 1 ratio) & trusses shall be supported laterally at points of bearing by solid blocking to prevent rotation&lateral displacement (Sec. 2320 12 8) Trusses shall be marked showing the truss manufacturer, design loads and spacing (UBC Sec 2321 4) 15. Trusses shall be designed and fabricated in accordance with ANSI/TPI 1-1995(UBC 2321 1)or a design and details by an engineer must be furnished. Prior to rough framing inspection a truss engineering report detailing the bearing points,bracing requirements,load design and spacing must be on site and attached to the "APPROVED PLANS" 3 16 Ridge beam shall not be less in depth than the end cut of the rafters, and shall be at least 1"nominal thickness(UBC Sec 2320 12 3) 17.Provide attic vapor barrier and ventilation equal to 1 sq. ft. per 300 sq. ft. of attic area and rafter spaces (UBC Sec 1505 3 except#2 ) 18.Provide a minimum 22"x 30" attic access opening with 30" clear headroom in the least dimension as required by UBC Sec 1505 1 19. All roofing to be installed per manufacturer's listing Roofs shall be sloped a minimum of 1 unit vertical in 48 units horizontal for drainage (UBC Sec 1506.1) 20 The interior of the building must be separated from foam plastic insulation by an approved thermal barrier having an index of 15. Within an attic or crawlspace foam plastics shall be protected from ignition by 1 '/2"mineral fiber insulation, 1/4"plywood,hardboard,gypsum wallboard,corrosion- resistant sheet metal having a base thickness not less than .016" at any point, or other approved material installed in such a manner that the foam plastic is not exposed(UBC Sec 2602 4) 21. alcomes,landings,exterior stairs,occupied roofs and similar surfaces exposed to the weather and sealed underneath shall be waterproofed and must be sloped a minimum of 1/4 unit vertical in 12 units horizontal (UBC 1402 3) 22 sulation shall be installec�,per the 1989 MEC A vapor retarder of 4-mil poly or� - acked Batts is a wired n Var, 01-1671 � �/' 61SP/ lw-5f/I����� y/�'64I el)jS 23. atural�i if in abitable rooms to be equal to 10% of the Boor area and natural or met amcal ventilation per UBC Sec 1203 3), (UBC Sec 1203 2) 24. If and/or when the basement is finished, the Town of Vail will enforce the natural light and ventilation requirement This must be a consideration in basement design XEVERY SLEEPING ROOM BELOW THE FOUR STORY MUST HAVE ONE EXTERIOR DOORORESCAPEW1NDOWWIT 5­7 SQ.FT.NET CLEAR OPENING THE MINIMUM HEIGHT OF THIS CLEAR OPENING MUST BE AT LEAST 24" WITH THE MINIMUM WIDTH AT LEAST 20". SILL HEIGHT CANNOT BE GREATER THAN 44" ABOVE FINISHED FLOOR. NOTE THAT BOTH MINIMUMS CANNOT BE USED TO ACHIEVE THE 5 7 SQ FT NET CLEAR OPENING REQUIRED (UBC Sec 310 4) 26. BASEMENTS SHALL BE PROVIDED WITH AT LEAST ONE ESCAPE OR RESCUE WINDOW WINDOW WELLS AT ESCAPE OR RESCUE WINDOWS SHALL COMPLYWITH THE FOLLOWING a The clear horizontal dimensions shall allow the window to be fully opened & provide a minimum accessible net clear opening of 9 sq ft,with a minimum dimension of 36 inches b Window wells with a vertical depth of more than 44 inches shall be equipped with a permanently affixed ladder or stairs that are accessible with the window in the fully open position and do not encroach into the required dimensions by more than 6 inches (UBC Sec 310 4) r(-�7abitable space shall have a ceiling height of not less than 7-6" except as otherwise permitted in this section(UBC Sec 310 6 1) 28 oke detectors shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area When the dwelling has more than one story and in dwellings with basements, a detector shall be installed on each story and in the basement In dwelling units where a story or basement is split into two or more levels, the smoke detector shall be installed on the 3 4 upper level, except that when the lower level contains a sleeping area,a detector shall be installed on each level When sleeping rooms are on an upper level,the detector shall be placed on the ceiling of the upper level in close proximity to the stairway In addition, if the ceiling height of a room open to the hallway serving bedrooms exceeds that of the hallway by 24" or more, smoke detectors shall be installed in the hallway and the adjacent room. Detectors shall be audible in all sleeping areas of the dwelling unit(UBC Sec 310 9 1.4) Smoke Detectors shall receive their primary source from the building wiring and shall be equipped with a battery backup (UBC Sec. 310 9 1 3) 29 Where the valuation of an addition or repair to an existing structure exceeds $1000 00 or when one or more sleeping rooms are added or created in existing dwellings,the entire structure shall be provided with smoke detectors as required for a new structure(UBC Sec. 310 9.1.2). Smoke detectors may be solely battery operated when installed in existing buildings ([IBC Sec. 310.9.1.3) 30 Double keyed dead bolts are not permitted on exit doors from dwellings and guest rooms Night latches, dead bolts and security chains may be used provided such devices are operable from the inside without the use of a key or tool and are mounted at a height not to exceed 48" above the finished floor(UBC Sec 10033 1 8) 31 tt handrail/guardrail to be placed 34" minimum to 38"maximum above the nosing of the treads The hand grip portion of handrails shall not be less than 1 1/4" nor more than 2" in cross sectional area dimension or shall provide an equivalent gripping surface. Handrails shall be continuous the full length of the stair Ends shall be returned or shall terminate in newel posts or safety terminals. (UBC Sec 10033336) 32. TAIRWAY MINIMUM HEADROOM REQUIREMENT IS 6'-8" (UBC Sec. 1003.3.3.4). 33 or private residential stairs, maximum riser height is 8", minimum tread run is 9", and minimum stair width is 36" (UBC Sec. 1003 3.3.3 &.2). For winding stairways the 9"tread must be provided at a point not more than 12" from the side where the treads are narrower, but in no case shall any width of run be less than 6" at any point (UBC Sec. 1003.3.3.3) a ardrails for bale and landings that are more than 30" above grade or floor below shall be a imum hei ht�o 36" for single family dwellings and the interior of individual units of multi-f _buildings an 42 n other occupancies Note that clearanceTbef een rote erm dia a pickets must be such that a 4" dia er sphere cannot pass through(UBC Sec 509 1 & 509 2) 035. andmgs shall have a dimension measured in the direction of travel equal to the width of the stairs(UBC Sec 1003.3.3 5). Landings shall have a width of the stairway or door, whichever is greater(UBC Sec. 10033 1 7) 36 Landings are required at all exterior doors(UBC Sec 1003 3 1.7) o37. nclosed usable space under stairs shall have walls and soffits protected on the enclosed side as required for one-hour fire-resistive construction (UBC Sec. 1003.3 3.9). Fire stop stairs at stringers(UBC Sec. 708 2 1) 38 Skylights shall comply with UBC Sec 2409 for glass skylights and UBC Sec 2603 7 for plastic skylights Glazed skylights shall have screens installed below them Laminated glass with a minimum of 30-mil poly vinyl butyryl interlayer maybe used without screens (UBC Sec 2409 2) See exceptionsf &sh la zing in doors or within 24" adjacent to doors, including windows and glazing in enclosures for owers, saunas,whirlpools, steam rooms and tubs located less than 60"above the floor or drain inlet,and shower doors must be impact resistant safety glazing or tempered glass. Glazing within 18"ofthe floor,in railings, and at stairway landings must also be safety glass(UBC Sec 2406 4) Hinged shower doors shall open outward(UBC Sec 2407) G 40 hower area walls shall be finished with a hard,non-absorbent surface to a height of 70"above the drain = inlet(UBC Sec 807.13) All shower compartments,regardless of shape, shall have a minimum finished interior area of 1024 square inches and shall also be capable of encompassing a 30 inch circle (UPC 410.4) 41 he water closet stool shall be located in a space not less than 30"in width and shall have a clear space in front of the water closet stool of not less than 24" (UBC Sec 2904) 42 Garage walls and/or ceilings adjacent to or under dwellings require the installation of materials approved for one-hour fire-resistive construction on the garage side and a self-closing,tight fitting solid wood door 1-3/8"in thickness or a labeled door with a fire-protection rating of at least 20 minutes(UBC Sec 302.4), exception 3). 43 No openings are permitted between a garage and rooms used for sleeping(UBC Sec 312 4) 44.Do not penetrate"firewall"(occupancy separation wall between garage and dwelling)with plastic pipe or plastic electrical boxes,except those plastic electrical boxes specifically listed for such use(NEC 300-21) Outlets on opposite sides ofwalls&partitions shall be separated by a horizontal distance of24"minimum (UBC Sec. 709 7). 45 When a garage is located under a dwelling, or the ceiling is being used as part of the separation, bearing walls, columns and beams supporting the horizontal separation must be protected by materials approved for one-hour fire resistive construction(UBC Sec. 302.2) 46. dwelling units, at least one wall switch-controlled light fixture or outlet shall be installed in every abitable room,in bathrooms,hallways, stairways and attached garages, and at outdoor entrances(NEC 210-70) 47. rovide ground-fault protection(GFCI)for all 120 volt,single phase 15 and 20 amp receptacles installed n the following locations bathrooms, kitchens,unfinished basements,witm 6 ft of a wetbar, garages, grade level portions of unfinished accessory buildings,crawlspaces, and outdoor receptacles (NEC 210- 8). 48 t least one wall receptacle outlet shall be installed in bathrooms adjacent to each basin Bathroom )receptacles shall be supplied by at least one 20-ampere branch circuit,which have no other outlets(NEC 210-52d) 49 No wall space shall be more than 6'from an outlet, and an outlet is required at all counters 12" wide or more, and on any wall over 2' (NEC 210-52c). 50 At least one lighting outlet and GFCI protected convenience receptacle shall be installed in an attic or crawl space where these spaces contain equipment requiring servicing,or are used for storage(NEC 210- 70, UMC Sec 306 3 & 306 4) 51. ncandescent light fixtures installed in clothes closets must be located at least 12" horizontally from the n edge of shelves Aflush RECESSED fixture with a solid lens or fluorescent fixture maybe installed with a 6"horizontal clearance to the edge of shelves PENDANT FIXTURES MAYNOT BE INSTALLED IN CLOTHES CLOSETS (NEC 410-8) 52 All receptacles, light fixtures, wiring, and equipment installed in wet or damp locations shall be installed so that water cannot enter or accumulate in wireways,lampholders, or other electrical parts All fixtures installed in these locations shall be marked "SUITABLE FOR WET LOCATIONS " (NEC 410-4) 53 At least one receptacle outlet installed not over 6 ft. 6 in. above grade shall be installed at the front and back of the dwelling 54)comply wimming pools,fountains,hot tubs, spas and hydro-massage"jacuzzi"tubs and similar installations shall with all provisions of NEC Article 680,which has severe restrictions on the type and location of switches, outlets and lights. Motors & equipment shall be accessible by a removable panel with an opening size per manufactures specifications Oinrovide %giod vent to the outside for clothes dryer Total combined length, horizontal and vertical cluding 90-degree elbows,shall not exceed 14'. Two feet shall be deducted for each elbow in excess of 2 (UMC Sec 504 3 2). 56 rovide bathroom exhaust fan connected directly to the exterior and capable of 5 air changes per hour ((JBC Sec 1203 3) 57 All habitable rooms shall be provided with heating facilities capable of maintaining a room temperature of 70-degrees F at 3 feet above the floor(UBC Sec 310 11) 58 Provide minimum 1" clearance between Class "B" gas vent and combustible material and 6" clearance from single wall vent connectors to combustible material (UMC Sec 803 1 & Table 3-C) 59.LIQUEFIED PETROLEUM GAS (PROPANE) SHALL NOT SERVE ANY WATER HEATER OR FURNACE LOCATED IN A PIT, CRAWL SPACE OR BASEMENT WHERE HEAVIER THAN AIR GAS MIGHT COLLECT TO FORMA FLAMMABLE MIXTURE (UPC Sec 1213 6) 60 No gas water heater or furnace shall be installed in any room used or designed to be used for sleeping purposes, bathrooms, clothes closets or other confined space opening into any bedroom or bathroom Exception sealed combustion chamber type water heaters, direct vent furnaces, or enclosed furnaces (UMC Sec. 304.5). 61 Provide clearance on combustion air side of furnace and 30"working space in front of all heating controls (UMC Sec 307 2) 62 Solid fuel, oil, and gas fired appliances require adequate combustion air(UMC Secs 701 1) 63. Doors to gas appliances must be a minimum of 36"in width but not less than required for the removal of the largest piece of equipment(UMC Sec 307 2) 64. GAS APPLIANCES LOCATED IN A GARAGE SHALL HAVE IGNITION SOURCE AT LEAST 18" ABOVE THE FLOOR AND MUST BE PROTECTED FROM AUTO MWACT(UMC Sec 303 1 3) 65. In buildings of Type V construction only, laundry& dumbwaiter shafts may be either of approved fire- resistive wall construction or may have the inside layered with not less than No.26 galvanized sheet gauge metal Openings into shafts shall be protected by a self-closing solid-wood door 13/8"thick (UBC Sec 711 6) 66 Installation and venting of EPA approved zero clearance/factory built fireplaces shall conform to manufacturers specifications(UBC Sec. 3102.5.1). 67 No permit shall be issued for the installation of a solid-fuel burning fireplace stove, fireplace insert or wood stove appliance unless the appliance fully conforms with the requirements for emissions testing, certification and labeling found under Title 30, Article 28, Sections 402-405 of the Colorado Revised Statutes and the Town of Vail air pollution ordinance All such appliances to be installed must be certified by the Air Pollution Control Division of the Colorado Department o f Health to meet the emission standards set forth in Section IV of Regulation No 4 of Volume I of the Colorado Air Quality Control Commission as EPA Phase II or Colorado Phase III solid fuel burning devises 68 Provide manufacturer's placement and set up manual for factory-built(manufactured)housing at the time of the rough inspections s , • 69 Hearth must extend 16"in front of and 8"beyond the sides ofthe firebox opening,or for fireboxes 6 sq ft or larger, 20" in front and 12" beyond the sides(UBC 3102 7 12) e 70 fireplaces and barbecues shall comply with UBC Sec 3102 7 Chimneys shall comply with Secs 3102 3, )1024and31025 Chimneys must ext d a minimum of 2 ft. above any art of the building within 10 ft of the chimney C Table 31-B). u ®� /�J10 5 ���1�� �e�<r�l� e /�rc� r�I�so/� v'e4 71 Approved num ers or a dresses shall b provide for all new bu ngs m suc a position as to be plainly visible and legible from the street or road fronting the property(UBC Sec 502) Job sites or driveways to sites must be readily identifiable from public streets 72 o domestic dishwashing machine shall be directly connected to a drainage system or food waste disposer without the use of an approved dishwasher air gap fitting on the discharge side (UPC Sec 807 4) Atmospheric vacuum breakers are required on all hose bibb connections and faucets with hose attachments. (UPC Sec 603 3.7). (7;' ough frame inspection is to be made after the roof, all framing,fire blocking and bracing are in place and all pipes, chimneys and vents are complete and the electrical, plumbing, and heating wires, pipes and ducts are in place 74 Post& beam connections shall be provided to ensure against uplift&lateral displacement (Sec 2324) Connections depending on foists hangers or framing anchors, ties or other mechanical fasteners not otherwise covered may be used where approved by an engineer (UBC Sec 2325 2) 75.Fire blocking shall be installed: i In concealed spaces of stud walls&partitions, including furred spaces, at the ceiling and floor levels& at 10-foot intervals both vertical&horizontal ii At all interconnections between concealed vertical & horizontal spaces such as occur at soffits, drop ceilings and cove ceilings iii. In openings around vents, pipes, ducts, chimneys, fireplaces, and similar openings which afford a passage for fire at ceiling&floor levels,with noncombustible materials (UBC Sec 708 2 1) 76 All openings into a drainage or vent system, except those to which plumbing fixtures are properly connected, shall be permanently plugged or capped in an approved manner, using appropriate materials (UPC 1014 1 1 3) ADDITIONAL CORRECTIONS: l wood ( --Fo ac i i l' 4,-) -k&��ed b d X03.1, - CUB THESE CORRECTIONS ARE PART OF THE"APPROVED"PLANS AND MUST REMAIN ATTACHED TO THEM THE CORRECTIONS NOTED ABOVE AND ALL OTHER APPLICABLE CODE REQUIREMENTS MUST BE COMPLIED WITH IN ORDER TO RECEIVE INSPECTION APPROVALS INSPECTIONS WILL NOT BE MADE UNLESS THE "APPROVED" PLANS AND PLAN CHECK LIST ARE AVAILABLE ON THE JOB SITE. ' Gwathmey Pratt � Schultz I i Are leeb.p.m 0 s I 1000 3 r-101.1 RCL Wear Will,Cokwado 81657 Tel: (970)C6-1147 3 —--------- --— FcDr.(9M 476-1612 ' DECK RAILING i I , - OVERFLOW DRAIN I ALL IDECXS SLOPED I PER FT TO DRAIN U N O ' - --- FLOOR DRAIN i - =al nn �\; V I r all bllr ----- ---- -- - ---- ---- - - ------ --- --- -- -- ------ - -la'-1"--- - ---- - - �, .0! 16',-4 i I a" 43 I O I HR 3 I -- - - -- - - ml I +fx m I ! I i I � s/8.,- i 1 i VERIFY DIMENSIONS 50 I LIVING THAT STONE VENEER ' I ROOM ENDS UP ALMOST FLUSH w/ ! ____- w! I tt1 } DRYWALL BEYOND I ; r' �� MASTER I HR I c(1 t�C1�1'CUUM I I I r l I , i I ' / - -- - -- - - - -- -- - -- - - -- - - -- - - ARCHED- - - - -- -- -- -- - - - - - - - -- --L -- - - - - -- -- -- --- - -- ,-- - -- - _ - -- - _ - I -- - - - - �vl - - - - - - -- -i - -- - - -- - - - - -- - - - HEADER,_ _& - i - j - - DIRECT VENT GA5 APPLIANCE ' I - - - --" - ------- - FIREPLACE - TYPICAL - SEE 43 BUILDING ELEVATIONS FOR HR I LOCATION OF VENT TERMINATION 'rl �, WI C n �I I I V l • = i O � �,{ BEDROOM #3 ; , , 1 - - 18" W1DE HEARTH I 2 Q ( I - m I - ! - „ = TILED I EXTENSION ON I I X I „� - - _-' m FLOOR TO MATCH BENCH \ I ' � I 3s/811 I WIDTH OF MANTEL I X A81 � 6" 41 411 I6 -53/41, g/1. _ 3�„ 35/8 l/ 35/81 s/n _-- ---- - - -- - - - -- - - - - - - - - - - - - -- - - - - - - --- - - - - - -- - -- -- - - - --- - - - -- - --- - - - - -- - - --- -- - --- -- -- --- - --- - - ------ - - - -X5/811 41_a�211 61_811 35/81 i - i - 3/' I T ' lo, 4 u' to ! '.- � I I� °✓ 8 I^I�11 5, 2 I t I - NOTE 5811 TYPE X U - - DRYWALL AT FIREBOX i - T; - - ------- -- ----+ TYPICAL I N I I 2 a ml ' j - ----- --- -- - - - - - +'--- - - ,r VERIFY DIMENSIONS SO I i -T - - __ _-- THAT STONE VENEER - ENDS UP ALMOST FLUSH w/ I I I DRYWALL BEYOND _ ! 9F 4<4 I I - I m j �m ( I T I m I 1 T" �j Ln 35/8n 3 , 3 (� 58u I I HR I 5 1 �5/ 5/" I 5 " 1 n •1 :--- - -- 4 -8/4 -- r ---- - -41_311-- ----- - --------- -- - ----- ------4--Oh' ----- - /8 -- -4'-O��' - - -- - + -- - --- ----- - 6 -8 -- - 8 3/8 -4Y811 31_611' I ' 3/ - - _ l t---- —�- - - -- --- - ---------- ---- --—-- - -- — - ' I - -- --- - - - -- 3 8 3 6, �,p� �---- --- (V, I m —1 !: tn' I I L I ------ - LU < s ; I ENTRY Y ESTI5ULE I O 21_Q1,11 DI N I NG t 1-- I r - --- - -- - - --- -- I ---- ---- -- ----- - - ------- - .r---- -- - - - - -- - - ------r ---- - - -- -- - -- -- - --- ----- --- ------------------ -- --- - ---- - -- -- ----- --�- ROOM i 1 , I I - L ------- ----- —------ --- -- ! Nm i ref - -_ -- -- - - --- - -- --- - ,,;� i 1 �m tf1 r i x � 17'-u%2 - -- - -- -- -- -------------- -- -- ----------�-------- - - -/1, ------- ------ -- ----------------- --- -- 1034 I II �� I T Ti 554'. I I ' DN 3 8 11_3/411 �\` }'-2%411 611 I''-7�/ 51-13/ql 21_45/11 3511 1 l - -- • I I I \� � I --- --- - � -�--� -;- � ---------------- ----------' r BEDROOM #2 KITCHEN - 1 Gwa�thh! /Pratt/5chultz I -� I R -_ I — � i I All RigEs P.G ARCHED I HR I 4 e/,Pp HEADER G I r This document and the tdea3 In m / ( I i and designs Incorporated I. I 1 I !i j -�I pr ofesslonai servlca�Is the I ! pro ertttt,�� of bwothmeyy/Pratt Schultz <Krchltecte, PC and Is m I p not to be used, In whole or Irl l 4 part, for any other ro�ect I I r�ithout the written a thorizat; ` I I OF Edward M bwathmey Jr, T Henry Pratt or Sld y Schultz 1 1 I Date: 03 JUN 02 CONDO ISSUE ' � ----- -- ----� ---- - ;\`\ --- --- -- ------- ---- -1 ----- ---- - - --------- -- - ---- - - - - --- --- -----�- -----_- - ---- ------------ ----- ----------- - ---___-_---_ - - i --------- ---� ��'��..��`� �e�� ------ -----___ - .___ Revised: SOAP SHELF I a2 `° 'i-? , -; , l CORRIDOR WALLS CLOSE TO APPROVE UNDERSIDE OF STRUCTURE -` ABOVE- TYPICAL t Communky Development Department I I ' + d Building Safety 8 InspecHOn T01�1VOF PAIL �� �t1M1�11i�A.'�r VnL.=�htk VA ft r[14h m&The into m a ' Np�ae d a permit of t�pprOVal d Altar.apaddafioaa�Comptttad0a� doN(ter be aetttb-- to be a paean ft of i apptvval of.my viotttior d MW 4(*A ptovid=of thin Code a of aay Cdtet ardinteoe of de jtteitdi dML IlataI ; 1 9 to give aothorlty to violate of Caaod the ptvrisiooa offt I GENERAL NOTES cob orCWer ardmances of the jurisdiction doll not be valid. The iauantx of a permit based on plans.speeif cats s and other data tdttll DIMENSIONS GIVEN ARE TO FACE OF ROUGH ALL INTERIOR WALL CONSTRUCTION I trot prevent the budwng official from thereafter requning the corteedm d STUD, CONCRETE OR FURRING A5 NOTED A55EMBLIES TO BE I HOUR RATED opera in said plans,specifications and other data,ur from preventing ode CONTRACTOR TO FIELD VERIFY ALL PIMEN51ONS CONSTRUCTION PER THE UB.0 UNLESS Operations being tamed on thereunder when to violation of ode at of AND NOTIFY ARCHITECT PROMPTLY OF ANY NOTED OTHERWISE STAIR ENCLOSURE, any other ordmanceso tus 30 i ERRORS OR DISCREPANCIES PRIOR TO SHAFT WALLS AND FLOOR/CEILiN65 TO BE a BEGINNING THE WORK 2 HOUR RATED INITIALS: TE DIMENSIONS GIVEN ARE SUBJECT TO EXISTING CORRIDOR WALLS SHALL EXTEND UP TO AND/OR FIELD CONDITIONS, MATERIALS AND, UNDERSIDE OF STRUCTURE OR DECKING '�!/� �G' l `�G MEANS AND METHODS OF CONSTRUCTION ABOVE ALL OTHER WALLS SHALL U USED CONTRACTOR AND HIS 5U5-CONTRACTORS TERMINATE AT CEILING UND SHALL FIELD VERIFY ALL CRITICAL OR MINIMUM r r Sheet Number i CLEARANCES BEFORE BEGINNING THE WORK SEE BUILDING ELEVATIONS FOR ADDITIONAL �� INFORMATION G (. DO NOT SCALE THE DRAWINGS CONTACT // ��ARCHITECT FOR ANY MISSING OR ILLEGIBLE SEE It" PLANS FOR ADDITIONAL INFORMATION PLAN— ^ I ( I DIMENSIONS ALL STUDS 3�b" U N O 2 . 17 I - " WALL CONSTRUCTION TYPES MAY NOT 51 XTH FLOOR LIST ALL NECESSARY COMPONENTS SEE STEEL COLUMNS TO HAVE 2HR REFERENCED DESIGN SOURCE FOR PROTECTION PER UL #X528 "- �� _ 1- N DETAILED A55EMBLY COMPONENTS SCALE. !� - I O r ° - Gwathmey - ASPHALT ROOFING-INSTALL /- PER MM 5 SPECIFICATIONS I I ` I I Pratt 'V FIRE RESISTANT PLYWOOD \ - �- Exispi,6 N2'&YP SHEATHINS- ' ' _ PATCH AND REPAIR AS NECESSARY i � ! i ! t0 N I Afchltecls,p.m I FULL DEPTH FRICTION-FIT UNFACED � 1,5'DENS-&LA55 SHEATHING- I I E I ! --FIBER6LA55 BATT INSULATION �� ATTACH TO STUDS w/1 144" t ! "� 1000 S Rd.West CORRO51ON RESISTANT TYPE cOe -FULL DEPTH FRICTION-FIT VNFAGED 5 SCREWS AT 8"OL (PERIMETER) t ! I ; I 6°. 5 n' I g r, �6" Vcd,COIOfOdo 81657 ( FIBER&L.A55 BATT INSULATION AND 12"OL.(FIELD) I i -�)/� 1 17 -4/ 25 6AWE MTL STUD FRAMINb AT 25 GAWE MTL STUD FRAMING AT �' rt �) + I _ { 8 Tel; (q7�471147 IV OL-STUD SIZE PER ORAAIN65 �1 IV O.C-5TUD 51ZE PER DRAWIN&5 �) -25 6AUGE MTL STUD FRAMING AT ( ' I - ---' ! - EXTERIOR MTL STUD FRAMING- I I I i I, !' I Fmc t97f�476-1612 y/ IW OL-STUD SIZE PER DRAWIN55 �- SEE EXISTING STUDS FOR SIZE, f FRICTION-FIT ASS FULL DEPTH UNPAGED ) I V- " FIBERGLASS GATT INSULATON-TYPICAL j !) ) \ / SPACING AND ATTACHMENT TO BLDG (, ! �-�- BONE LAYER 4(,"TYPE X DRYWALL ) ONE LAYER 33"TYPE X DRYWALL "\-. (_�` ! ---�DIRECT VENT GAS APP!!IANGE �f' i AT FACE OF WALL-ATTACH TO STUDS ( AT EACH SIDE WITH JOINTS CENTERED t- / FIBER&LA55 BATT INSULATION-FRICTIONGTYPICAL /J //� ONE LAYER ab'TYPE X DRYWALL- ( / W/ I"TYPE 5 DRYWALL SCREWS AT OVER STUDS AND STAGGERED ON ! ! f FIREPLACE - TYPICAL • SEE ATTACER JOINTS ON OPPOSITE SIDES- 8'OL (PERIMETER)AND 12"OL (FIELD) - OPPOSITE SIDES-ATTACH TO STUDS / 6 MIL GOVT POLYETHYLENE BUILDING ELEVATIONS f OR { -ATTACH TO STUDS W/I'TYPE 5 /( TAPE,TEXTURE AND FINISH PER SPECS- w/11/4" TYPE S DRYWALL SCREWS r DRYWALL SCREWS AT W OL (PERIMETER) (�� APPLY GOVT SEALANT AT PERIMETER ` ( VAPOR BARRIER-TYPICAL ! ( I ! AT W OL.(PERIMETER)AND 12.OL (FIELD)- / 7 I I LOCATION OF VENT TERIMINATION AND 12'OL (FIELD)-TAPE TEXTURE AND �_ = f\n FINISH PER SPECS-APPL11 GONT �} SCREWS ALONG SIDE IN1 JOINTS OFFSET - �• %r';'07015 DRYWALL- I SEALANT AT PERIMETER �� TAPE,TEXTURE AND FINISH PER SPECS- 1 i , -- TUDS w/I'TYPE 5 APPLY CONT SEALANT AT PERIMETER ( \ SCREWS AT 8"OL1PERtMETER) ! f I r --- -�18" INIDE HEARTH AND TEXTURE AND IFI�9H AS SPECIFIED ! ! I 1 � ! z---� I I /� � G�RDIE I IOR PARTITION INTERIOR PARTITION 0 D CIM P ARnTION FOAL �}II��JtS WALL { i I ! ' ' ( y p �(0 3, J EXTENSION ON I i ® UL iJ UL DES�GN U4�1 FLOOR TO MATCH I HIR Sim / ( WIDTH OF MANTEL _ - Sim--- �r-------------- -- t j�� -'� '� --1 NOTE 5/8,r TYPE X f ^- EXTERIOR SYSTEM SEE ELEVATIONS i I D I N)NG i i '� i m 1 v v 1 \�; S 1771 NG } a " "` -- i DRiWALL AT FIREBOX f / W/I"FOAM THICKNESS VRO ! i Room i I -- t —! O AREA / I I C//�_) I -CEMENT BOARD SIDING- INSTALL ( I 1 55/8"� (,J [(1 _ " ' �✓ �� PER MFR'S SPEGIFICATION5 I � - - i f - EXISTING 15"GYP SF$ATHiNb- EXISTIN6 GONG WALL - ( 7 ;i` sfi `--- �i = - ! sim `t I �aaM 4 PATCH AND REPAIR AS NECESSARY C FRICTION FIT FULL DEPTH UNPAGED FRICTION-FIT FIR L DEPTH UNPAGED I N - + _ -_ _ O - I r; 'TYPE X DRYWALL ON T6°HAT CHANNELS �'" j 2 I O 1 Sim } -l�"DENS-GLASS SHEATHING- r FIBERGLASS BATT INSULATION FIBERGLASS BATT INSULATION f / ATTACH TO STUDS w/1 144" - ' AT INTERIOR FINISHED SPACES(UN0 IN BOTH WALLS (l Pn" , IN BOTH WALLS Inn`s 1 A82 ( I CORROSION RESISTANT TYPE » 25&AWE 13b"MTL STUD FURRING L SSGREWSATg'OL (PERIMETER) +'- -- ------ ---. -� ---- _----_ ---_ _--_L .-_ __-----_ - ---------- - _ -- - -- AT IV OL-NOTE FURRINb SHALL I 25 bAWE MTL STUD FRAMING AT 16"OG- ( ( 25&AWE MTL STUD FRAMING AT 16"OL- AND 12"OL (FIELD) 1; / _ - }! ) ( ) +-- I I I I - f - - i-- ---NOT TOUGH FACE OF CONG WALL ( STUD 51ZE PER ORAWIN&S-5TUD5 MAY C STUD SIZE PER DRAWINGS-STUDS MAY NOT TOUGH BUT THEY MAY BE BRACED �_ .''� 1 - 1,45/g, 3 i } c = (^ NOT TOUGH BUT THEY MAY BE BRACED 3 I I ( EXTERIOR MTL 5TUD FRAMING- .OR- W/ GYP BD AS NECESSARY W/ GYP BD AS NECESSARY " " 5 -2/e I S -'7/2 �" 3'-3" 1't -61, 8 SEE EXISTING STUDS FOR SIZE .Y ----_� -.-- ----- -- -- y�-- --- _-_ -- - -_ - -- l -_ -------__ ---�----_ D 5PACIN&AND ATTACHMENT TO BLDG --- 76" RAT CHANNELS OR 1142"`Z"FURRING /11 /1 \'") /) I \ n y-� ?� .\ ONE LAYER%,TYPE X DRYWALL ( FULL DEPTH FRICTION-FIT UNPAGED Q l �` - ONE LAYER 34"TYPE X DRYWWLL AT EACH SIDE- ATTACH TO STUDS q �} ( ATE SIDE WiTH JOINTS CENTERED - ' ( 7 y FIBERGLASS BATT INSULATION-TYPICAL FULL DEPTH UNPAGED FIBER6LA55 _ - W/I"TYPE 5 DRYWALL SCREWS AT ! i ! ! 8 10 I t 4 BATT OR BOARD INSULATION OVER STUDS AND STAGGERED ON r r' ) 6"OL (PERIMETER) AND 12"OL _- - - I / 1 " OPPOSITE SIDES-ATTACH TO STUDS , (FIELD)-TAPE,TEXTURE AND I ( I -b MIL GOVT POLYETHYLENE ; s w/IV4 TYPE 5 DRYWALL SCREWS T ) I N I AH2 } VAPOR BARRIER-TYPICAL ONE LAYER 5/8'TYPE X DRYWALL �� FINISH PER SPECS-APPLY CONT O ! \ } 1 5/8'TYPE X DRYYVALL-' r AT INSIDE(5/8'6EOR61A PACIFIC AT VOL, (PERIMETER)AND 12"OL (FIELD)- r ( SEALANT AT PERIMETER I ! 1 ATTACH TO STUDS w/i'TYPE 5 DEN5-`SHIELD AT TILED WALLS)-ATTACH J-� SCREWS ALONG SIDE JOINTS OFFSET 4" - TO STUDS w/I'TYPE 5 SCREYVS AT ? v SCREWS AT 8.OL.(PERIMETER) APPLY G�SEALANT AT PERIMETER I *A� / 12'15H TAPE TEXTURE AND AND IY OL.D FIND-TAPE, FINISH PER SPECS , ) �+ TEXTURE AND FINISH AS$PEGIFIED I ! UE D��IGN-0472 (SIM) W ' '�- IN6 BOTH SIDES 1 DI 5 GN 4Q1 SIM) PULurD�51GNWU�420 (SIM) i \ I i I 1 1 DW i -ICITGH N i { MASTER - DINING BEDROOM ROOM I /- CERAMIC,WALL T1LE OR MATERIAL i- FULL DEPTH FRICTION-FIT UNFAGED ;�- FRICTION-PIT FULL DEPTH UNPAGED v - FRICTION-FIT FULL DEPTH UNPAGED l I = 1 AS SPECIFIED-THINSET APPLICATION / FIBERGLASS BAIT INSULATION ( FISE"LA55 BATT INSULATION j FIBERGLASS BATT INSULATION �� / IN BOTH WALLS IN BOTH WALLS _-_-- �i/ FULL DEPTH FRICTION-FIT ATINSULATION UNPAGED i 25&AWE MTL STUD FRAMIN&AT - t FIBERbLA55 GATT INSULAT10r / 16'OL-STUD SIZE PER DRAWINGS j / / ONE LAYER%"TYPE X DRYWALL- ATTACH TO STUDS W/I"TYPE 5 / \ I ELEG PANEL-- 25 6AWE MTL STUD FRAMING AT / / AS WALL TILE OR MATERIAL ( y ) ,f DRYWALL SGREYe AT b"OL t I \ y i s IW OL-STUD SIZE PER DRAV,11N65 AS SPECIFIED-THINSET APPLICATION �;ti (PERIMETER) AND 12"OL (FIELD)- Y LIVING I / LOCATION ( O i I m�I I TAPE,TEXTURE AND FINISH PER ) ) \ } dJ I ONE LAYER%'TYPE X DRYYIIALL "✓ b MIL POLY VAPOR BARRIER- PEGS-APPLY GONT SEALANT AT ° AT EACH SIDE WITH JOINTS CENTERED ' PERIMETER `- } ROOM (AT STFr4M5HONIER WALLS ONLY) -- OVER STUDS AND STAG6ER ION ; r - - - ---T------- ---- -------- (V 1 (yI f OPPOSITE SIDES-ATTACH TO STU05 f gi _ _ i �- 25 6AUGE MTL STUD FRAMING AT IV OL- i- �- 25 6AWE MTL STUD FRAMING AT IV OL- — `` ) w/11{" TYPE 5 DRYWALL SGJREWS r q 0 5 �j" YpE 5 1�_} ^� ) 5TUO SIZE PER DRAAIW75-STUDS MAY ) ��1 STUD 512E PER DRAWINGS-STUDS MAY - ----`DIRECT VENT GAS APPLIANCE AT 8"OL (PERIMETER)AND 112°OL (FIELD)- ) DRYWALL SCREWS AT 8"OL (PERIMETER) ) ` 1 NOT TOUGH BUT THEY MAY BE BRACED k , NOT TOUGH BUT THEY MAY BE BRACED �- �'� FIREPLACE - TYPICAL - SEE 1 SCREWS ALON6 SIDE JOINTS OFFSET 4" (. � K W/MTL STUDS OR 6YP BO AS NECESSARY ( =� VV MTL STUDS OR GYP BD AS NECESSARY _ { 4'-3 ° 2'-O" AND 12'OL (FIELD) -5TA66ER JOINTS {�) >` t I r BUILDING ELEVATIONS FOR TAPE,TEXTURE AND FINISH PER SPECS- EA WAY -TAPE,TEXTURE AND FINISH ! -^ _ APPLY GOVT SEALANT AT P�RIMI°_TER /� .�oo�v�c..,r en•i••". '� f "^�- _ _ �v PF Y rFM7/IA P i'IFIr °t7F 411F1 P]^ ,�� , r� 1-. � PC Y.GF!]RAIA PArIFV •nF►14�.uIFI r'Y' - LG'G TI G'•�! Gt•' • =1`lT TCri}{I�LtiTICt•I r` AT PERIMETER �' ) ��1 T�E BACKER BOARD-VTTAGH w/ul�ti"RUST -� `) TIL( BAGIGER BOARD EACHIS IDE-ATTACH I (y TYPE X 6EOR&IA PAGIFIG DENS-SHIELD , - , f-Tt RESISTANT TYPE 5 SCREWS AT I2'OG- `- w/1 `RUST RESISTANT TYP 5 SCREWS / IS" WIDE HEARTH - �, TILE BACKER BOARD-'ATTACH TO STUDS 'TYPE X GEORGIA PACIFIC DENS-SHIELD ��_ TAPE JOINTS w/6LA55 FIBER MESH L- AT 12'OL-TAPE JOINTS w/GLASS FIBER w/IV4'RUST RESISTANT.'TYPE 5 SCREWS AT TILE BACKER BOARD-ATTACH TO STUDS TAPE-INSTALL(TILE)FINISH MESH TAPE-INSTALL(TILE)FIN15H ! ' --EXTENSION ON b"OL-TAPE JOINTS w/&LASS FIBER w/IVs'RUST RESISTANT TYPE 5 SCREWS AT MESH TAPE INSTALL.(TILE)FINISH AS SPEG'D 6"OL-TAPE JOINTS w/6L.ASS FIBER ! I �F FLOOR TO MATCH MESH TAPE- INSTALL(TILE)FINISH AS SPEG'D pp WIDTH OF MANTEL TILED CORRIDOR PARTITION s TILED CORRIDOR PARTITION g G F LPL UMBI IS 51 M) b GLADF(L UMBI S K 51 M) ! ' ' i`-2" I I _ O I 1 ® UL DESIGN U4Q1 (SIM) ® UL DESIGN U442 ® ® 5 " 12 T a 10 1/2" ';!I x 1 I I! m� (TILE MAY BE AT OPP SIDE OF WALt) ( r NOTE /e TYPE X � , � v ' 1 I KITCHEN � -DRYWALL AT FIREBOX 13 R ® 8' O 4H TYPICAL UP - -- �- I 1 I I! 5 ,I ' ° ' ! � ! I q'-4" 3'-3/e 6 -5� I 10 615/4'. 6', d S „ 3518' 1 u I ' /3/g ►n 1!3S/" —+ ,I I � I FIBER& ASS FULL DEPTH UNPAGED it u i (,sip FRICTION-FIT FULL DEPTH UNPAGED FIBERGLASS GATT INSULATION , 5 I I O _-_ O • FIBERGLASS BATT INSULATION _i �� IN BOTH WALLS � - I IN BOTH WALLS ? , A AIR GAP BETWEEN 136`MTL STUD � ) , ;6 _ g/„ ! u f "' � " 1-55/4" u ! 1 AND "6YP BOARD ; '✓ 5 4 I -4 �4--2 r 1 -4 3_ T I i LINE OF EXISTING FIRE RATED WALL- shy- ,y -sl-- 4'� - �Y-aY �/8' 1 ! ' 2 25 6AWE 136"MTL STUD FRAMIN&AT 16" �- PATCH AND REPAIR AS NEGE55ARY , -'�- - �- �wv I OL.-5TUD5 MAY TOUCH BUT THEY MAY -25 GAWP 136"MTL STUD FRAMING AT Ib" � 1 _ 1 � 1 NR �pT OL-STUDS MAY NOT TOUGH BUT THEY MAY ( I / M A I 1 N BE BRACED W/ 6YP BD A5 NEGE55ARY BE BRACED W/ GYP BD AS NECESSARY r ' I 1 N } 25 6AWE 2142'MTL STUD FRAMING AT 16" I ! + I �► O ! I ; (n 1 J - - i- EXISTING COLUMN PER STRUCTURAL,WRAPPED x �' r OL-STUDS MAY NOT TOUCH THE EXISTING .q f I I ! I I r - - - " _ ONE LAYER fit'TYPE X&YP BOARD �,� ! S�8 6'-3 - I0" 41-4" -6 % WITH 3b TYPE X GYP HOARD-TYP WALL A 1 J X ONE LAYER �y AT INSIDE OF WALL,JOINTS CENTERED I HR �1Z 1 -- -- - y t-- -- v 1 7 PE X 6YP BOARD WALL Cu OVER STUDS AND STAGGERED WITH OUTER Sim =�I p 51 1 HR 1 HR 1 m fl' .G --- -- tl AT INSIDE S JOINTS CENTERED ! 1 I OVER STUDS AND STAGGERED WITH OUTER } LAYERS-ATTACH TO STUDS w/Iq" TYPE + ONE LAYER 36"TYPE XDRYWALL -JOINTS - - _ - - - Ind - - I - - - ?. i (� y / 5 DRYWALL SCREWS AT b'OL (PERIMETER) at CENTERED OVER STUDS-ATTACH TO 5TVD5 -- - - - - - -- - - �-� - - L T - - �+"� - �D• - - - - -- - -_ -_- !_-_ \ �- - -- �, LAYERS-ATTACH TO STUDS w/14` TYPE 1 ! 1 _ I - - - 3- - T- - -R1 LV � - - ! ` r AND 12'OL (FIELD) \ w/I"TYPE 5 DRYWALL SCREWS AT 8'OL 4 -7/2' S'-3/8' 121-4/2" L� 5 DRYWALL eCREW5 AT V OG (PERIMETER) - - ! _ }- --- ----- ✓✓✓ r AND 12"OL (FIELD) �; `�- \ t j !PERIMETER)AND 12'OL (FIELD) - -1 --p t „ , -� - �{�- ----.P- -- - i t --- - -�, i', u ry r R ONE LAYER 3i,ONE LAYER 36° TYPE X DRYWALL ( T` -AT SHOWER,SUBSTITUTE 36"TYPE X _ 3 W!D I I 6 tJ� 3/8 f I HR O ��'' ` -�-ONE LAYER%",ONE LAYER 3b",TYPE X DRYWALL F WITH JOINTS CENTERED OVER STUDS-STAGGER f�� &EORGIA PACIFIC"DENS-SHIELD"TILE 1 „ /4" !' WITH JOINTS CENTERED OVER STUDS-STAGGER G JOINTS FROM INNER "LAYER ATTACH TO HACKER BOARD-ATTACH W/14♦'RUST 5'-4!/4" 1/ JOINTS FROM INNER 3i"LAYER ATTACH TO } '� STUDS w/IVe TYPE 5 DRYWALL SCREWS AT %� RESISTANT TYPE 5 SCREWS AT 12"OL- - --i-1 �-"`T---- - T' '"d } -- I �D I ' ( !� I` , _ / e STUDS w/IL4" TYPE 5 DRYWALL�GREINS AT 8"OL (PERIMETER)AND f2'OL (FIELD)- TAPE JOINTS W/MASS FIBER MESH TAPE- 4J J W OL (PERIMETER)AND 12'OL (FIELD)- TAPE,TEXTURE AND FINISH PER SPECS- INSTALL(TILE)FINISH r /yam+ ! _� ,O ! `-- 1 /� ��41 ` { f V JI ( I !!/l m 1 1 O TAPE,TEXTURE AND FINISH PER SPECS- APPLY CONT SEALANT AT PERIMETER 7 T✓ 9 APPLY GONT SE�A(LANT AT PERIMETER �,,' � - 5UL IDESI,i UU4gI ((51M) s 5UL IDESIGNP�R 50 1 4 STAIRWIELL. PAR1'ITIDN m `� ' I , /, I ''�' �5�0 } , f +`J, ! 3'-5" } 2'—..I'S/8" L ^ - i (rn U,1� ■ �``, /,• `��j�'/ �\ „� 16,1 _EV� 5 „! aI r�/ _ f �r-� '� �I-- ,- " 1 r� 3� ( In 1 If NALL CONSTRUCTION TYfi�ES - _ 1 _ ,_ " „ s _ ~I I �,�' d1 T �� ! N - ! 3 O i 5/e 4'-83 ,3,g„ _ - __ _ _- CC 5EV NTH FLOOR I a( Ae ` - NOT TO SCALE -_�_"-__._ �.T__- i �{► rL f O 1 I i 1 I c AI j m ¢, �-y �, ,5' - -6" 35ieI' 1 i4„ 3518', cv -- I Sim (U °� ��s ' ! \ .9 ! 6" ,gym{ 1 - - - ! (U 1 im m \/ I HR O O O 5 - I MASTER 4�-il�„ _; ���� i ►�R n� I � -_ � G Lu ENERA NOTES 1- ! -- ' -----i------- �_� BEDROOM #2 N DIMENSIONS 61VEN ARE TO FACE OF ROUGH ALL INTERIOR WALL CONSTRUCTION _m m 1 A - �.� #f-- , STUD, CONCRETE OR FURRING AS NOTED ASSEMBLIES TO BE I HOUR RATED 6 19'-i�ie 8 -3 ! 6 I O 1!1 I U 21 CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS CONSTRUCTION PER THE UBG UNLE55 i -___ _-L � _ r_ �-_-- -_ 35� _ � —__----- m 1 T� I ► i O AND NOTIFY ARCHITECT PROMPTLY OF ANY NOTED OTHERWISE STAIR ENCLOSURE, w ! ! if I �1r N _ I I ERRORS OR DISCREPANCIES PRIOR TO SHAFT WALLS AND FLOOR/CEILINGS TO BE i \� i = 1 - , 6'-O" r BEGINNING THE WORK. 2 HOUR RATED iii m I - } Ir DIMENSIONS GIVEN ARE SUBJECT TO EXISTING CORRIDOR WALLS SHALL EXTEND UP TO I r " %� 2 I 7 I I - _ I J V t AND/OR FIELD CONDITIONS, MATERIALS AND UNDERSIDE OF STRUCTURE OR DECKING I'-7" s I ��I I i ABOVE ALL OTHER WALLS SHALL f MEANS AND METHODS OF GONSTRUGTION ! i 2 ( 1 1 { I 1 ! 1 ✓ 1 V USED CONTRACTOR AND HIS SUB-CONTRACTOR5 TERMINATE AT CEILING URO ! I I ry 1 tl I 1 1 SHALL FIELD VERIFY ALL CRITICAL OR MINIMUM CLEARANCES BEFORE BEGINNING THE WORK SEE BUILDING ELEVATIONS FOR ADDITIONAL ! j() I ! l6"- I INFORMATION. ' DO NOT SCALE THE DRAW IN65 CONTACT ARCHITECT FOR ANY MISSING OR ILLEGIBL)= SEE �" PLANS FOR ADDITIONAL INFORMATION i" 1 _ DIMENSIONS { ! ! ! ' ALL 5TUD5 5%" U N O ` WALL CONSTRUCTION TYPES MAY NOT LIST ALL NEGE55ARY COMPONENTS SEE STEEL COLUMNS TO HAVE 2HR r FENTHOU5E REFERENCED DESIGN SOURCE FOR } F LAN_ 1 4 PENTHOUSE 11 / DETAILED ASSEMBLY COMPONENTS PROTECTION PER UL X528 , i SEVENTH FLOOR { - I SCALE: 14" = 1'-0" I DOOR SCHEDULE bwafhrneyyt/Pratt/Schvitz ' i Archite-fs, PG All Rights Reserved DOORS � M �J �,,.AROAARE OETt''ll (L5 VERIFY PER EXISTING Th 1 1doeument, and the Ideas d GONDITIGTAIS herein as an Imt�'ument of t-�OOt� Professional servir yIS the Tt� ' SchptzrZahftec-ts, PG/dndts TYFE LOCATE 51Z.E (WXH) THICK LABEL TYPE DEPTH FIN15H TYPE HDWR. # ' JAMB REMARKS GENERAL NOTE5 not to be used, In whole or in rlithovt the written outhorizotl port, for any other project of Edward M.6Wothmeyy Jr, A ENTRY 2'-10" X 6'-8" 1 5/4 " 20 MIN WD STAIN 6 SEAL ENTRY I/ A62 Henry Pratt or Sidney Schultz B ENTRY 2'-10" X 6'-8" 1 5/4 „ QO MIN HM (D PRIME 8 PAINT/STAIN d SEAL ENTRY I ALL DOORS, FRAMES, GLAZING, 2/ A62 I ETC., ARE SUBJECT TO THE REOUIREMENT5 OF THE UNIFORM G CLOSET (2) 2'-0" X 6'-8" I`5/8 " AD STAIN 8 SEAL DUMMY W/ BALLGATGH 5/ A62 ! BUILDING GODS AND ALL STATE AND LOCAL REGULATIONS D CLOSET (2) 1'-6" X 6'-8" 1 5/8 1, WD STAIN 6 SEAL DUMMY W/ BALLGATGH I/ A62 Date: 03 JUN '02 BATH (2) !'-6" X 6'-8" 15/511 WD STAIN $ SEAL BATH 02A I/ A62 HARDWARE TYPES GIVEN ARE ,CONDO 15SUE F BATH 2'-10" X 6'-8" 15/4 " WD STAIN 8 SEAL PRIVACY INTENDED FOR USE A5 A Revised I/ A62 � GENERIC INDICATION OF TYPE- - SEE HAREWARE SCHEDULE AND IJ A62 SPECIFICATIONS FOR ALL G BEDROOM 2'-10" X 6'-8" 1 5/4 " WD STAIN 4 SEAL PRIVACY HARDWARE REQUIRED r , CONNECTION 2'-1O" X 6'-8" 1 5/4 " 20 MIN WD STAIN I SEAL ROOM CONNECTION" 05 4/ A&2 *5HARE5 FRAME WITH ADJACENT DOOR **SMOKE SEALS FOR SOUND, NO CLOSER REa'D CONTRACTOR SHALL VERIFY ALL STAI0 5'-0" X 6'-8" 1 5/4 " QO MIN HMO PRIME 8 PAINT/STAIN d SEAL STAIR 10 5/ A62 51M* *FIELD VERIFY FRAME DEPTHS AND TYPES OF FRAME ANCHORAGE LETTER 5/ A62 DESIGNATION FOLLOWING FRAME CORRIDOR 21-10" X ' '-10" X 6'-8" 13/4 " I HR HM O PRIME 4 PAINT/STAIN d SEAL CORRIDOR 25 DEPTH GIVEN HERE IS TO INDICATE TYPE OF WALL GORRIDD} 3'-O" X 6'-8" 15/4 " q0 MIN HMO PRIME 8 PAINT/STAIN 8 SEAL CORRIDOR 25 5/ A62 51M* *FIELD VERIFY PROVIDE MAGNETIC HOLD-OPEN CONSTRUCTION ADJACENT TO FRAME G=GONGRET'E, 5=MTL ELEVATOR (2) 2'-6" X 6'-8" 1 514 " 20 MIN WD STAIN 8 SEAL ELEVATOR LOBBY 1'7 5/ A62 51M* *FIELD VERIFY STUD5/DRYWALL, M=MASONRY SERVICE i 5'-0" X 6'-8" 1 5/4 " I HR HM O PRIME d PAINT/STAIN 8 SEAL SERVICE II 5/ A62 SiM* *FIELD VERIFY EXISTING PATCH AND REPAIR FRAME AS NEGE55ARY HARDWARE SCHEDULE SHALL BE PREPARED BY THE SUB-CONTACTOR UTILITY 3'-O" X 6'-8" 13!4 " I HR HMO PRIME dPAINT/STAIN SEAL UTILITY 21 5I A62 51M* *FIELD VERIFY AND SHALL BE SUBMITTED TO ARCHITECT IN TIME TO UTILITY 4'-0" X 6'-8" 1 5/4 " I HR HM O PRIME 8 PAINT/STAIN d SEAL UTILITY 21 5/ A62 SIM* *FIELD VERIFY ALLOW TIMELY REVIEW BY ARCHITECT AND OWNER " * ELEVATOR (Z .21-6' X &'-8" i 3/4 QO MIN HMO PRIME 8 PAINT/STAIN d SEAL ELEVATOR LOBBY {� � , 5/ A62 SIM *FIELD VERIFY + , CONNECTION (2) f'-5" X 6'-8" 1 5/4 " 20 MIN WD STAIN It SEAL ROOM CONNECTION** TBD 4/ A62 *SHARES FRAME WITH ADJACENT DOOR **SMOKE SEALS FOR SOUND, NO CLOSER REa'D T BATH it 2'-6" X 6'-8" 1 5/4 " WD STAIN 4 SEAL PRIVACY I/ A62 ► NOTE: E: — U OL05ET ; 2'-6" X 6'-8" 1 5/4 " WD STAIN 4 SEAL PASSAGE I/ A62 ALL HOLLOW METAL FRAME Sheet Number V BEDROOM 2'-6" X 6'-8" 1 5/4 " WD STAIN 6 SEAL PRIVACY 1/ A62 DIMENSIONS A55UME A RETURN TO FiNISH MATERIAL, UNO BEDR00M 2'-8" X 6'-8" 1 5/4 " AD STAIN $ SEAL PRIVACY A2 . 185 X CLOSET 2'-6" X 6'-8" 1 5/8 1, WD STAIN 8 SEAL _ � POCKET DOOR Y PANTRY 2'-10" X 6'-8" 1 5/8 1, WD STAIN $ SEAL DUMMY W/ BALLGATGH Cft ' + Z CL05ET (2) 2'-6" X 6'-8" 1 5/4 " WD STAIN SEAL DUMMY WI BALLGATGH i EXTERIOR SIDING , SEE ELEVATIONS I - ASPHALT ROOFING - INSTALL -EiF5 SYSTEM AS SPECIFIED I , - PER MFR'S SPECIFICATIONS - - - w... __ _ W/ I"FOAM THICKNESS U.NO r ,, _..__ _ _ _.,. _ _. , -GW�m® -CEMENT BOARD SIDING - INSTALL 1 J T n y r— 14"FIRE RESISTANT f'1-YWOOD PER MFR'5 SPECIFICATIONS Prcft / - EXISTING 1-� Ht;A" GYP 5THING / -- EXISTING W GYP SHEATHING - EXISTING GONG WALL �hu PATCH AND REPAIR AS NEGE55ARY PATCH AND REPAIR AS NECESSARY 5 �.-� FRICTION-FIT FULL DEPTH UNPAGED / � ?-- FRICTION-FIT FULL DEPTH UNPAGED 8�; _ FIBERGLASS BATT INSULATION � /6" TYPE X DRYWALL ON It" HAT CHANNELS / ' FIBERGLASS BULL INSULATION � FULL DEPTH FRICTION-FIT UNPAGED DENS-GLAS5 5HEATHING- t h" DEN5-GLASS SHEATHING- ( ( i ( s�� Ard tods, a 'f� ATTACH TO STUDS w/ 1 1" i f�-ATTACH TO STUDS w! 1 %a• c IN BOTH WALLS ( IN BOTH WALLS P - -FIBERGLASS BATT INSULATION ( AT INTERIOR i=1NI5HED SPACES (UNO) ('� �, ({ } — FULL DEPTH FRICTION-FIT UNPAGED CORROSION RE515TANT TYPE t; t / CORROSION RESISTANT TYPE 5 25 GAUGE 1 " MTL STUD FURRING t ' �`x FIBERGLASS BATT INSULATION 5 SCREWS AT 8" OG (PERIMETER) 5 5GREWS AT 8" 00,(PERIMETER) r " { ( r 100013.Frontage Rd West " AT I6 OG- NOTE FURRING SHALL ) ) ��- 25 GAUGE MTL STUD FRAMING AT fb O.G- ,r ) 25 GAUGE MTL STUD FRAMING AT 16" 00- Vd,Cdorado 8166! 25 GAUGE MTL STUD FRAMING AT �� 25 GAUGE MTL STUD FRAMING A7 ( -S� AND 12" DG, (FIELD) AND 12" O.G (FIELD) ( STUD SIZE PER DRAWIN65-STUDS MAY / ! rr- �� STUD SIZE PER DRAWINGS (\.' �" ) i NOT TOUGH FACE OF GONG WALL ( i i STUD SIZE PER DRAWINGS-STUDS MAY t /^I6" O.G- STUD SIZE PER DRAWINGS / (, t Tel: MC)476-1147 u --- 25 GAUGE MTL STUD FRAMING AT EXTERIOR MTL STUD FRAMING- ., EXTERIOR MTL STUD FRAMING- r (''�;� NOT TOUCH BUT THEY MAY BE BRACED NOT TOUGH BUT THEY MAY BE BRACED „ t 4761612 }�_ 1 ib" OG- STUD SIZE PER DRAWINGS ��� SEE EXISTING STUDS FOR SIZE, ' SEE EXISTING STUDS FOR SIZE, -OR- W/, GYP $D AS NECESSARY _ W/ GYP BD AS NECESSARY ; ' FRICTION-FIT FULL DEPTH UNPAGED j , SPACING AND ATTACHMENT TO BLDG SPACING AND ATTACHMENT TO BLDG r• ) ^ FIBERGLASS BATT INSULATION- TYPICAL K „ t ONE LAYER 5�"TYPE X DRYWALL ( t T5" HAT CHANNELS OR Ih" Z" PURRING �� / r r ' }) ! ' J ONE LAYER fib" TYPE X DRYWALL ONE LAYER /a TYPE XDRYWALL — FULL DEPTH FRICTION UNPAGED I ( �" ` ' ONE LAYER V TYPE X DRYWALL f ! '�- i ✓ ) AT PAGE OF WALL -ATTACH TO STUDS `�� !�—AT EACH SIDE WITH JOINTS CENTERED C ( FULL DEPTH FRICTION-FIT UNPAGED Q AT EACH SIDE - ATTACH TO STUDS ONE LAYER W TYPE X DRYWALL - 'mil W/ 1" TYPE 5 DRYWALL SCREWS AT l 1 FIBERGLASS BATT INSULATION- TYPICAL %x\ J FiBERGLA55 BAIT INSULATION- TYPICAL FULL DEPTH UNPAGED FIBERGLASS J 1 ��;_ AT EACH SIDE WITH JOINTS CENTERED i } � � % - r OVER STUDS AND STAGGERED ON W/ I" TYPE 5 DRYWALL SCREWS AT OVER STUDS AND STAGGERED ON x $ATT OR BOARD INSULATION k Sti I ) 8" O.G (PERIMETER) AND 12" Of, ( I STAGGER JOINTS ON OPPOSITE SIDES 8" OG (PERIMETER) AND 12" Of, (FIELD) - t,, OPP051TE SIDES- ATTACH TO STUDS OPPOSITE SIDES-ATTACH TO STUDS -(;i` ATTACH TO STUDS W/ I' TYPE 5 TAPE, TEXTURE AND FINISH PER SPECS- x; - w/ 11'a" TYPE 5 DRYWALL 5CREA5 6 MIL GOUT POLYETHYLENE" - 6 MIL GOUT POLYETHYLENE '`�� %• 'TYPE 5 DRYWALL SCREWS ) 1 (FIELD)- TAPE,TEXTURE AND DRYWALL SCREWS AT 8" OG (PERIMETER) APPLY CONT SEALANT AT PERIMETER ( VAPOR BARRIER- TYPICAL {' VAPOR BARRIER- TYPICAL ? ONE LAYER 5/8" TYPE X DRYWALL ' '� , ti"/ 1 a (� t ,� FIN15H PER SPECS-APPLY CONT ( ,. AND 12" O.0 (FIELD)- TAPE, TEXTURE AND ( � "`�a AT 8" OG (PERIMETER) AND 12" O.G (FIELD)- ,` / AT IN51DE (5/8" GEORGIA PACIFIC ) AT 8" OC (PERIMETER) AND 12" OG. (FIELD)- t SEALANT AT PERIMETER FINISH PER SPECS- APPLY GOVT >l- > SCREWS ALONG 51DE JOINTS OFFSET 4" '5/8" TYPE X DRYWALL- lr 5/8"TYPE X DRYWALL- < 5GREW5 ALONG 51DE JOINTS OFFSET 4" t TAPE, TEXTURE AND FINISH PER SPECS- ( ATTACH TO STUDS w/ I"TYPE 5 l �" / ATTACH TO STUDS w/ I" TYPE 5 DENS-SHIELD AT TILED WALLS)- ATTACH �> ' ) TAPE, TEXTURE AND FINISH PER SPECS- 7 r SEALANT AT PERIMETER ) / -` TO STUDS w/ I" TYPE S 5CREW5 AT APPLY CONT SEALANT AT PERIMETER (> SCREWS AT 8" O.G(PERIMETER) ✓) SCREWS AT 8" OG(PERIMETER) 12" O.G- TAPE TEXTURE AND APPLY CONT SEALANT AT PERIMETER AND 12" O.G.(FIELD)- TAPE, AND 12" OL(FIELD)- TAPE, FINISH PER SijECS TEXTURE AND FIN15H AS SPECIFIED p�TEXTURE AND FINISH AS SPECIFIED L r' l RD�DSOIGRN I Uhl4T lOR PARTITION 2 INTERIOR PARTITION UGORDR PARTITION ASPDESTGNNU4�2 (5 j � U DE)S IGNMU4 2 (5 iM} 6 CO� KALLS- FURRING BOTH SIDES ORRIO iMPLUMBI(51F-1)S7 I`LL 3 P{LUl D I�WA4LL HR HR 1 HR ��,--FRICTION-FIT FULL DEPTH UNFAGED CERAMIC WALL TILE OR MATERIAL ,. FIBERGLASS BATT INSULATION FULL DEPTH FRICTION-FIT UNFAGED FRICTION-FIT FULL DEPTH UNFAGED FRICTION-FIT FULL DEPTH UNFAGED i _ IN BOTH WALLS — FIBER6 N-FIT FULL DEPTH UNFAGED r AS SPECIFIED- 7}fINSET APPLICATION FIBER6LA55 BATT INSULATION <�' ' FIBERGLASS BAIT INSULATION �% FIBERGLASS GATT INSULATION FRICTION-FIT FULL DEPTH UNFAGED FIBERGLASS GATT INSULATION i IN BOTH WALLS IN BOTH WALLS `-� FIBERGLASS BATT INSULATION - i g i�J IN BOTH WALLS FULL DEPTH FRICTION-FIT UNFAGED K - �" AIR GAP BETWEEN I�" MTL STUD - 25 GAUGE MTL STUD FRAMING AT IN BOTH WALLS AND 5/q" GYP BOARD -- LINE OF EXISTING FIRE RATED WALL- �/ FIBERGLASS BATTIINSULATION / ONE LAYER fig" TYPE X DRYWALL - _ / I6" O.C- STUD SIZE PER DRAWINGS ( �" ' ( t �� i"� t � � ATTACH TO STUDS W/ I" TYPE 5 � � 25 GAUGE 1V MTL STUD FRAMING AT I6" %- ,-� = ' PATCH AND REPAIR AS NECESSARY — 25 GAUGE MTL STUD FRAMING AT �— CERAMIC WALL TILE OR MATERIAL t �` -, i DRYWALL SCREWS AT 8" OG ,�� } t , OG- STUDS MAY NOT TOUGH BUT THEY MAY _ — -25 GAUGE 1511," MTL STUD FRAMING AT I6" } i' -� y (PERIMETER) AND 12" OG (FIELD)- 00- STUDS MAY NOT TOUGH BUT THEY MAY Ib" O.G- STUD SIZE PER DRAWINGS AS SPECIFIED- THIN5ET APPLICATION _ r ( BE BRACED W/ GYP BD AS NECESSARY , i :> TAPE,TEXTURE AND FINISH PER r\�� � BE BRACED W/ GYP BD AS NECESSARY { `��) �— 25 GAUGE 2%5" MTL STUD FRAMING AT I6" ONE LAYER 5/a" TYPE X DRYWALL 6 MIL POLY VAPOR BARRIER- ' �a SPECS- APPLY CONT SEALANT AT (,� ✓y; EXISTING COLUMN PER STRUCTURAL, WRAPPED 3 ' ' �' OG- STUDS MAY NOT TOUGH THE EXISTING AT EACH SiDE WITH JOINTS CENTERED (AT STEAMSHOWER WALLS ONLY) PERIMETER 1 ( / WITH " TYPE X GYP BOARD - TYP �� -- ONE LAYER 5/a" TYPE X GYP BOARD WALL OVER STUDS AND STAGGERED ON ti✓ I k ��' AT INSIDE OF WALL, JOINTS CENTERED "� OPPOSITE SIDES- ATTACH TO STUDS (j, 5 �; �— 25 GAUGE MTL STUD FRAMING AT I6" OG- - -' ��-- " - ONE LAYER g/" TYPE X GYP BOARD w/ II/a" TYPE 5 DRYWALL SCREWS r 3 ,� ONE LAYER b" TYPE XDRYWALL - -� -i'` 25 GAUGE MTL STUD FRAMING AT I6 OG- -� OVER STUDS AND STAGGERED WITH OUTER ATTACH TO STUDS W/ I" TYPE 5 `�-} STUD 51ZE PER DRAWIN65-5TUD5 MAY > STUD SIZE PER DRAWINGS-STUDS MAY AT INSIDE OF WALL, JOINTS CENTERED Y LAYERS- ATTACH TO STUDS w/ k" TYPE {�"1 ONE LAYER %"TYPE X DRYWALL - JOINTS AT 8" OG (PERIMETER) AND 12" OG (FIELD)- ) fix; NOT TOUGH BUT THEY MAY BE BRACED r OVER STUDS AND STAGGERED WITH OUTER - ( SCREWS ALONG SIDE JOINTS OFFSET 4" DRYWALL SCREWS AT 8" OG (PERIMETER) Al MTL STUDS OR GYP BD AS NEGE55ARY NOT TOUGH BUT THEY MAY BE BRACED LAYERS- ATTACH TO STUDS w/ IiV TYPE 5 DRYWALL 5GREW5 AT 8. 0.0 (PERIMETER) ;<-�� CENTERED OVER STUDS -ATTACH TO STUDS t AND 12" OG (FIELD) - STAGGER JOINTS S s _,i .l , W/ MTL STUDS OR GYP $D AS NECESSARY ' �(�; S DRYWALL SCREWS AT 8" OG (PERIMETER) i` AND 12" OG (FIELD) ,�} w/ I" TYPE 5 DRYWALL SCREWS AT 8' O.G � TAPE, TEXTURE AND FINISH PER SPECS- �`Y1 -a! t <' (PERIMETER) AND 12" O.G (FIELD) " J EA WAY - TAPE, TEXTURE AND FINISH --R f (''-� AND 12" OjC (FIELD) i APPLY GOUT SEALIANT AT PERIMETER PER SPECS- APPLY GOUT SEALANT ' V TYPE X GEORGIA PACIFIC "DENS-SHIELD" t-��l ��� --- V TYPE X GEORGIA PACIFIC, "DENS-SHIELD" �- ONE LAYER 5/4", ONE LAYER 5/1,", TYPE X DRYWALL 1, i� -AT SHOWER, SUBSTITUTE 3g" TYPE X 5 AT PERIMETER TILE BACKER BOARD-ATTACH w/ Ida" RUST t ) TILE BACKER BOARD EACH SIDE ATTACH { -a--ONE LAYER 5/a", ONE LAYER 5.g", TYPE X DRYWALL r>> i� WITH JOINTS CENTERED OVER STUDS -STAGGER ( ' GEORGIA PACIFIC "DENS-SHIELD" TILE - - - TYPE X GEORGIA PAGIFIG DENS-SHIELD x - RE515TANT TYPE S SCREWS AT 12" OG- } �- w/ l5/a" RU57 RESISTANT TYPE 5 SCREWS �; I( �! WITH JOINTS CENTERED OVER STUDS -STAGGER s JOINTS FROM INNER 5/" LAYER ATTACH TO BACKER BOARD- ATTACH W/ 15/4" RUST �\ ) TILE BACKER BORD- ATTACH TD STUDS 5)j" TYPE X GEORGIA PACIFIC DEN5-SHIELD TAPE JOINTS w/ GLA55 FIBER MESH �` AT 12" OG- TAPE JOINTS w/ GLASS FIBER JOINTS FROM INNER 5ja' LAYER ATTACH TO < STUDS w/ I%a" TYPE 5 DRYWALL SCREWS AT ± w/ I VV RUST RESISTANT TYPE 5 5GREW5 AT �\ TILE BACKER BOARD- ATTACH TO 5TUD5 TAPE- IN5TALL(TILE) FIN15H MESH TAPE- INSTALL(TILE) FINISH STUDS w/ 1%a" TYPE 5 DRYWALL SCREWS AT 8" O.0 (PERIMETER) AND 12" OG (FIELD)- I RESISTANT TYPE 5 SCREWS AT 12" H TA TAPE JOINTS Al GLA55 FIBER MESH TAPE- 6" O.C- TAPE JOINTS w/ 6LA55 FIBER w/ Ida" RUST RESISTANT TYPE 5 SCREWS AT 5' I �' 8"p.G (PERIMETER) AND 12" O.0 (FIELD)- TAPE, TEXTURE AND FINISH PER SPECS- INSTALL (TILE) FINISH MESH TAPE- INSTALL (TILE) FINISH AS 5PEC'D b" O.C- TAPE JOINTS w/ GLASS FIBER -� TAPE, TEXTURE AND FINISH PER SPECS- APPLY CONT SEALANT AT PERIMETER I MESH TAPE- INSTALL (TILE) FINISH AS SPEG'D APPLY CONT SEALANT AT PERIMETER TILED CORRIDOR' PARTITION TILED CORRIDOR PARTITION s TILED PLUMBING WA b TILED PLUMBING WA a� STAIRWELL PARTITION q STAIRWELL PARTITION q4 STAIRWELL PARTITION aR UL DESIGN U4g1 (SIM) I HR UL DESIGN U442 , GA FILE WP 50 0 � l lR GA FILE WP 50-10 �SiM) UL DESIGN U4gl (SIM) UL DESIGN U4( fI (SIM) (TILE MAY BE AT OFF SIDE OF WALL) ' WALL G0NS UGTION TYPES a ` Sr1yr--NTH FLOOR SCALE: t'-O" 2 3 4 O � ' u , l GENERAL NOTES DIMENSIONS GIVEN ARE TO FAGS OF ROUGH ALL INTERIOR WALL CONSTRUCTION ' i ( STUD,CONCRETE OR FURRING AS NOTED A55EMBLIE5 TO BE I HOUR RATED l i CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS CONSTRUCTION PER THE UBG UNLESS } I AND NOTIFY ARCHITECT PROMPTLY OF ANY NOTED OTHERWISE STAIR ENCLOSURE, i I l i ERRORS OR DISCREPANCIES PRIOR TO SHAFT WALL5 AND FLOOR/GEILING5 TO BE BEGINNING THE WORK 2 HOUR RATED I I ? I I I I DIMENSIONS GIVEN ARE SUBJECT TO EXISTING CORRIDOR WALLS SHALL EXTEND UP TO I AND/OR FIELD CONDITIONS, MATERIALS AND UNDERSIDE OF STRUCTURE OR DECKING MEANS AND METHODS OF CONSTRUCTION ABOVE ALL OTHER WALLS SHALL i ! l USED, CONTRACTOR AND HIS 51.15-CONTRACTOR5 TERMINATE AT CEILING UNO i SHALL FIELD VERIFY ALL CRITICAL OR MINIMUM i CLEARANCES BEFORE BEGINNING THE WORK SEE BUILDING ELEVATIONS FOR ADDITIONAL , I INFORMATION DO NOT SCALE THE DRAWINGS CONTACT ARCHITECT FOR ANY M1551N6 OR ILLEGIBLE SEE W PLAN5 FOR ADDITIONAL INFORMATION i DIMENSIONS W ALL STUDS 5%" UN.O l ALL CONSTRUCTION TYPES MAY NOT - i I I LIST ALL NECESSARY COMPONENTS SEE I I STEEL COLUMNS TO HAVE 2HR REFERENCED DESIGN SOURCE FOR I I I I I I I I I I OPEN TO DETAILED ASSEMBLY COMPONENT'S_ PROTECTION PER UL #X528 i , , i r , i i 4 BLOW , - - i 1 I i I I I lil Ila OPEN TO I ! '' sil , „/ l HR - ------ --�1 0 i \ BELOW i �f 16� � �3'-0511,' �� ,_0318, 2._l,. ,/ I6'-4511,„ all LINE OP 5'-O" I I I i 0 1 SPRING POINT ' fy i N fR sim I i 4 -CI 11, „ I m i BEDROOM #2 i I _ / — IIA82 `� `f l I - sim a m " Il 2'-8r4„ I 16-45/8„ \ 8 I 1 i I i 6 T ® IONI/2, U� \ Z I t l I I , \ I I ; 0 Clopyright i I Wa BEDROOM #3 I I \ I ' Gwathmey/Pratt/5chultz Architecfs, P.G. m All Rights Reserved I r�i� n� 1 I I 12 TREADS �� ry I } I I This document, and the ideae • �'\ dee,9.,- ,..��r,.s,-..ass ! 12 T ® 1n0 1/2111 l I — I herein, as an Instrument AF i n 13 R VII I , 1 I u , t�/ u r l I gropes of service, is the I 13' 5" 3518 31-05'" �,_ 3 „ 351 2, I,. I I6�-4�g„ A — Y - _ propertts�� of tarts, eq/Pratt Schultz fCrchitects, P,C, and is' part, for any othar pro ect not to be used, in whole or In without the wrltten authd-rizatl tD bI i I HR r of Edward M.6wathm Jr I � 1,y 5 4'-101/8' Henry Pratt or Sidnay Schultz. �� � - i T Date: 03 JUN 02 CONDO 15SUE. r Revised: ! 1 l \ E PLAN-LOFT � Fr-NTHOU5r . I Sheet,Number' - ' �I GHTH FLOOR SCALE: �" = I'_O" A2 .1 :::I , ` - e 3 ' ' i • , , , s 6 GwathrhO } Prafit c t 4 Schultz } Architects,p c 1000 S.Frontage Rd West + I Vall,Colorado 81657 ( j Tel (970)476-1147 { # Fax:(970)476.1612 ! I I + 1 1 I ! I I I ( I I ! i j k j ati �D 1 F =7 _- I ! FLAT 5OFFIT 5EE ! ! ! i ELEVATIONS FOR j f i l 5TARTING POINT I ' ___ I ! I RIDGE I a— � _ -^; RIDGE I i 1:2'-10 3/4' AFF } r I 12'-10 3/4 AFF I SPRING 512 512 512_ i 5PRING } _ 5 12 _ I I/2" AI=F •.r 5LOPE DN _SLOPE DNS SLOPE DN 5LOPE DN q'-"7 1/2" AFF + - I j A RCH , 1 I } I CEILING I I U V-O" AFF Q ! CEILING CEILING r q'-4" AFF I z N q'-4" AFF � t � i ' � OA� CEILING , ( N `0 S'-O" AFF 1 iI it + 1L I I ! I t= t tL 1 1; 'V Q II I �I I CEILING it q'-4" AFF ,! r _ �I 11 it i 1 �i ! sil 11� - -- - - = CEILING j rt w f i' II II li ! CEILING f_�r»_�_ =�- q'-4" AFF 0) p 1+t1 I q'-4" AFF I +III G CEILING IIL ti II y I� ! 1 I I Z ! CEILING CEILING 8'-O" AFF Vi LU 8'-O" AFF I II'l l f 1 m' 8'-O" AFF I n u Ip I , I I,t,li i } I �---1 LL LHI 'lii � ( I �� i- Z 4 u.1 Q F I i��ll 1 i II �I it i it ! o �L l!II I I �GEILING I I't ,I I I 1'-4" AFF i Il 7 1!I - tl iZ > f i�t�ll � I iI;;II Ni W t 'p itu t If it ! s I 11 ! u 11 ! , it it Ll i n 5A q It 1 I fill t I Jill 1I it n i I I it a ' ; � , I I iE � _ �>✓EI�.ING ,111'1 ! , AFF i iit'il 1 t CEILING ' 8 -O" AFF - 11;11 t m Copyright jj/ I ' „ 1 Gwafhmeyy/Pratt/Schultz CEILING ! I 1," ArchitocEo, PG I ! 8'-0" AFF i ! } This documen and the Woos { i GCILit�O I _ _ � I cinct ctvo,gn irvr-Pvratva =Z7-= - t herein, as on instrument oP AFF f -j profeestonai service, to the CEILING / f ! pproper of 6wothmey/Pratt 5chuttz �r4hltecto,P G and is 8'-O" AFF ! not to be veod,-In whole or in j t j port, for my other protect ' I ! ARCH without the written autehyorizati i ! Hanr� Prat or y 5 hvltz' , 1L Z Q i I ! t� �� j �`� j Date: 05 JUN 02 ` CONDO 15SUE i! , i a - _ ___ Revised: I ROF- Ff=NTH0U5T= I I i 5IXTH FLOOR Sheet Number A20,25 „ SCALE: ! " = 1`—O" i ire + ., r t x ♦ 3 r a _ 1 u k ' Y r _ , , R` r v - Gwathmpy 1 Schultz Architects,p c , 1000 S Frontage Rd Vilest ' Vail,Colorado 81657 ' Tel' (470)476-1147 y Fax.(470)476.1612 , r 4 Q , I I 2.3 , f ! D , { I s=_--*="'L.-1L x--._-••-y--=� ALL s--T---,_r°=z � ' —FLAT SOFFIT SEE i I /~ ELEVATIONS FOR I d I I I l ( STARTING POINT SPRING I _ - , I j 12'-5" AFF 2 AF J= I l t I ' • ; j i i I 1 � �_='==`= _-- °tom________- I 1612_-- - 1612-___-•- � ,I i ' I { I ( f I SLOPE DN SLOPE ON ' • _ ___ I l' i 4 1612 — FLAT SOFFIT SEE---- I--- SLOPE ON SLOPE DN RIDGE t ELEVATIONS FOR �Z iI AFF 5TARTIN6 POINT I ? RIDGE I 1 I Grr�iric I 5n'-a ZI Ai -A r== i I t { 12'-D" AFF 13 c.t F'—f= ! I '-2" AFF I I ABOVE { I I 4 Y ' , I II j GEILING I ` I j rr I 3 4 s 1 f 10'-4" FF l A8J �z GEILING I i i t LL ? l 10'-6" AFF I r+lul � 1 LOWER CEILING- n �z l ( �—HEIGHT TO BE i �°° �4p Q Q / DETERMINED ' k BY LANDING ABOVE f �-- I 5'-0" AFF t lQ � l w 1 i � I° w � . GEILING l • I ! �I� ! �0 O w 5'-0" AFF ; Q I 4, ° t j STAIR VAR IES I pQ j ( i , I It CL0 l ? t s O 5'-0" AFF I GEILING ? l ! I - 10'-6" AFF GEILING GEILING II ' E I q'-0" AFF FLAT SOFFIT SEE --- E ! ' ~ t I GEILtING ELEVATIONS FOR { 8'-9" AFF RGH 5TARTIN6 POINT I l GEILING i I CEILING " �{ I GEILING j 8�O" AFF j 10 -b AFF ----- q'-O" AFF j t ? ( - GEILING 3 CEILING AFF w q'-O" AFF l I �7 l I 1 t I J GEILING l j 1 G�EiILING 8'-O" AFF ? ( I GEILING r II O' AFF t GEILING ? 8'-O'�AFF I t , 10'-6" AFF p g bwaChrrne4/Pratt/5chvttz, i w cl' 10L" AFF Ail Rights f2eserved 1 l I I = I i Mnis document, and the Ideas and destans Incorporated herein, as on instrument oP I FE: prol"esst t er Ice Is the propertt�yT o '�wa�hmey/Pratt GEILING Schvitz , rchItects, PG. and Is i CEILING r 1 i u ;a „ not to be wed, In whole or in li p - I; II -O AFF i art, for other ro It ` 10 -6" AFF ? P P J I l � II I' ` I, GEILING without the written avthortzatt i I t q'-O" AFF I of Edward M bwathmey Jr., y y ' I � Henr Pratt or Stdne 5chvitz. 1 I , r ? CEILING 5'-O' AFF t AFF i 1 ' Date: 03 JUN 02 a I I ? CONDO 155UE i - - - - - - - -- - - - - - - -- -- -- - --- - - - - --- - - - - -- - - -_ - - - - -- - - - -- - - - _ _ - -- -- - - ---- ---- - - -'-- - ------- -- - - ------ _ - - - Revised: I f RCF - IOENTHOU5E 1 4 Ft=NTH0U5t= I I SEVENTH FLOOR i Sheet Number A2 , 2 ' 'v , I' , .. , , , ' ' - l ' , z x ' - ' ' .. , i r ..- v ' ' . ' ..,w s. .. r ' _ _ ..,a... i r _ _ r .. _ _<. .... __._..,.i,--.. _ ..- _ .s .. ,. .._ . , . .. ' ..,a..x . i a• ,. 1 ... a, ,..r-x-,.a..,..._.e.... v_. a.L.m ._.,a.. v.. _ u - _ __ nJd .. .a..w.. _ x _` . ., .. ..,.. _ i r-.. ._-...s ,... u-f .. 1, ... _,.._f Gwathmpy-,�,.. f 1 Pratt Schultz Archiltects,p c 1000&Frontage Rd West Vail,Colorado 81657 j + Tel (970)476.1147 i Fmc-(970)476-1612 r I i I I �I I • I , Q O E j I i I I I SEE DRAWING A224 FOR SOFFIT INFORMATION Slt— (, r ! SEE DRAWING A224 FOR ! j I �/G• SOFFIT INFORMATION t I SEE VYiIN& A,224 FOR GEILINNG INFORMATION IN —� THI5 AREA LH C, IL Z LL C1 LU ( ! I I rhOEILINC7 `�j r XI10 i I I IN SPRING I 8'-q" AFF l N t- iJ I SPRING ! 5'-10 1/2" AFF " _ I 4'-4" AFF L { ++ tNCEILIN& LL 4%F LL Z< 461 SLoPE�i O, • I --- ---�--- _ ----- u_, CEILING r4 i ! j i F j — Q } 12'-2" AFF LL ' j !p I U- —�O _� I A8.2 { n w +yl Q fN N`r p �1 CEILING ! alp t 41 -A 8'-q" AFF G�FILING -- PEAK OF PYRAMID l Iz � Z i 8''-q" AFF �,r m �s D / N W ;1f 4 // n�a I� ! r G�lLlNS I `DI9J r ! AFF - t A jet i � �� I J I j 1 1612_ 1 ! m I t GEILING j SLOPE DMA m Gwat`,rTrri�et/Pratt/Schultz i i GEILING Ii 8 - " AFF yy i Ar¢hiteGfs, P.G 8'-�(' AFF i� ( All Rights Reserved ( SPRING N SPRING 5'-10 V2" AFF i IL �Z } 4'-4" AFF This docvment, and the Ideas L— ILL (� } and designs Incorporated herein as an instrument of professtiyonal service, is the ` not to be vsed, in Mole 01, in Sehuitz Arehiteats, P.0 and Is j it{1 part, for any other protect l I I i without the written authorizatl z -- - - -- _ - - - — - — - - - r- oP Edward K bwathmey Jr Henry Pratt or Sidney Schultz. Date: 05 JUN 02 CONDO 155UE Revised: f t I I I i I ROF -LOFT C� PENTHOU5r I • �1&HTH FLOOR SCALE: !4° = I'-D" ---- ----- - Sheet Number A 14 t T , __ ' I F , , ._ ....._. .. _ _ .' .uv, ,, .. , _ .v..W.w _ .._ _ -_ _ ,_._.. _ _ - .._. _- ..._..y,.. ,. ,._.. ,_ ` .. ' ., W. ..s x_._ .. .,. ., W- _. ,... _ ., ,_ .... .._., .., <,x .. ,.._,. , .....o-d,. __, s... -u— __. -„. ... , . ,. -.. .. W ,-._... ..__ a. „_.•.... ._.may..,...,..,,,�.....z .. _�..,. .. ..w... .. .w .-_1., ... ..,a_,_-__. Gwathm pY DOOR 5GHEDUL.E d � # Pratt Schultz t ; a DOOR5 FRAME5 HARDWARE DETA I L5 VERIFY PER EXISTING I Architects.coND1TIONS p c. DOOR,J 1000 S Frontage Rd West " TYPE LOCATE 5 IZ E (WXH) TH I GK LABEL TYPE DEPTH E I N 15H TYPE I DWR. # JAMB REMAR 5 1 T�.Colorado, 657 GENERAL NOTES Fmc•(970)476-1612 1 A ENTRY 2'-10" X 6'-8" 1 3/4 " 20 MIN WD STAIN 8 SEAL ENTRY If A62 i B ENTRY 2'-10" X 6'-8" 1 3/4 " q0 MIN HM O PRIME 6 PAINT/STAIN 4 SEAL ENTRY 2/ A62 ; a ALL DOORS, FRAMES, GLAZING, s ETC, ARE SUBJECT TO THE G CLOSET (2) 2'-0" X 6-8" 13/8 " WD STAIN d SEAL DUMMY W/ BALLGATGH •3/ A62 , REQUIREMENTS OF THE UNIFORM BUILDING CODE AND ALL D CLOSET (2) I'-6" X b'-8" 1 318 " WD STAIN 4 SEAL DUMMY W/ BALLGATGH I/ A62 STATE AND LOCAL REGULATIONS. a BATH (2) I'-6" X 6'-8" 15/51, WD STAIN 4 SEAL BATH 02A V HARDWARE TYPES GIVEN ARE A62 � , INTENDED FOR USE AS A •" - F BATH 2'-10" X 6`-8" 1 3/4 " WD STAIN 4 SEAL PRIVACY I/ A62 (1 GENERIC INDICATION OF TYPE- F VV L AND C7 BEDROOM 2'-10" X 6'-8" 1 314 " WD STAIN ,4 SPECIFICATIONS, FOR AL SEAL _ PRIVACY I/ A62 I HARDWARE REQUIRED. CONNECTION 21-10" X 6'-8" i 3/4 " 20 MIN WD STAIN 8 SEAL ROOM CONNECTION** 03 4/ A62 *SHARES FRAME WITH ADJACENT DOOR **SMOKE SEALS FOR SOUND, NO CLOSER REQ'D STAIR CONTRACTOR SHALL VERIFY ALL 3'-O" X rot 314 " q0 MIN HM I PRIME $ PAINT/STAIN S SEAL STAIR 10 5/ A6.2 SIM* *FIELD VERIFY FRAME DEPTHS AND TYPES OF FRAME ANCHORAGE LETTER CORRIDOR 2'-10" X 6'-8°' 1 3/4 " 1 HR HMO PRIME 4 PAINT/STAIN d SEAL CORRIDOR 25 5/ A62 DESIGNATION FOLLOWING FRAME DEPTH GIVEN HERE 15 TO CORRIDOR 3'-O" X 6'-8" 1 3/4 " 5/ A62 SIM* INDICATE TYPE OF HALL q0 M!N HM�I PRIME d PAINT/STAIN 8 SEAL CORRIDOR 25 *FIELD VERIFY PROVIDE MAGNETIC HOLD-OPEN CONSTRUCTION ADJACENT TO FRAME- G=CONCRETE, S=MTL ELEVATOR ; (2) 2'-6" X 6'-8" 1 3/4 " 20 MIN WD STAIN S SEAL ELEVATOR LOBBY 1-1 5/ A62 51M* *FIELD VERIFY STUDS/DRYWALL, M=MA50NRY, SERVICE 3'-0" X 6'-8" 1 3/4 " 1 HR HM O PRIME d PAINT/STAIN d SEAL SERVICE II 5/ A62 51M* *FIELD VERIFY EXISTING PATCH AND REPAIR FRAME AS NECESSARY HARDWARE SCHEDULE SHALL BE UTILITY 3'-0" X 6'-8" 1 3/4 " I HR HM O PRIME 8 PAINT/STAIN $ SEAL UTILITY 21 * PREPARED BY THE 5UB-CONTACTOR 5/ Ab2 SIM *FIELD VERIFY AND SHALL BE SUBMITTED UTILITY - 4'-0" X 6-8" 1 3/4 " I HR HM O PRIME 8 PAINT/STAIN 8 SEAL UTILITY 21 5/ Ab2 SIM* * TO ARCHITECT IN TIME TO FIELD VERIFY ALLOW TIMELY REVIEW BY ARCHITECT AND OWNER. LEI( ELEVATOR (2) .2'-(5" X 6-8" 1 3/4 " qO MIN HM O PRIME ,$ PAINT/STAIN 8 SEAL ELEVATOR LOBBY 1'7 5/ A62 SIM* *FIELD VERIFY CONNECTION (2) 1'-5" X 6'-8" 1 3/4 " 20 MIN WD STAIN 8 SEAL ROOM CONNECTION""' TBD I, I 4/ A62 *SHARES FRAME WITq ADJACENT DOOR **SMOKE 5EAL5 FOR SOUND, NO CLOSER REQ'D T BATH 2'-6" X 6'-8" 1 3/4 " WD STAIN d SEAL PRIVACY I/ A6.2 ' U CLOSET 2'-6" X 6'-8" 13/4 " WD STAIN 4 SEAL PASSAGE I/ A62 NOTE: HO W A L FRAME LLO MET ' V BEDROOM � 2'-6" X 6'-8" 13/4 " WD STAIN d SEAL PRIVACY I/ A62 DIMENSIONS A55UME A 'ib" f W BEDROOM 2'-8" X 6'-8" RETURN TO FIN15H MATERIAL, UNO 13/4 " WD STAIN d SEAL PRIVACY - ' f X CLOSET 2'-6" X 6-8" 1 3/8 " INi� STAIAI s G1=AL rCGNCT �OOF� i Y PANTRY 2'-10" X 6'-8" 1 318 " WD STAIN B SEAL DUMMY W/ BALLGATGH Z CLOSET (2) .2'-6-1 X 6-8" 1 3/4 " WD STAIN d SEAL DUMMY W/ BALLGATGH 4 ' 7 ` SEE DOOR TRIM ELEV. • i SEE DOOR TRIM, � s/8" DRYWALL ' 7 ELEV. i _ 35/8" or 2%2" METAL STUD __ _,_ ___ >-��� �'`,•' x - 8 " META,L STUD --- _ _ _ HOLLON METAL. FRAME 5/8 DRYWALL -- -------- -"- -, 5/8" DRYWALL , y ' TYPE I NOT TO SCALE J-La F SINGLE RABBETED --- - . _ %'� DOUBLE RABBETED ---- " �� �'f' ' ... WOOD FRAME .- � WOO F R�A ME WOOD TRIM WOOD TRIM j V JAMB DETAIL JAMB DETAIL r IW x 1W. 5/4" x 5/2-1- - —-1 z --_-----A 'ie' x 4"- -\ I I ! HOLLOW MTL -- --- HOLLOW MTL - / M / DOOR FRAME �\ DOOR FRAME �`'� 3 OV2" 4" 1 /4.. DRYWALL — --__ — 5i8" DRYWALL i 35/8" METAL STUD -------- _ _ - '��,� 1 8" OR 35/e" or 2%2" !METAL STUD i Q/ 0 Copyyright _ IU 6wathmeyy/1°rott/schvitz I T' � I i , ArchitecEs, P.G B/4" _—� _—°-- _ u` 1 " I All Rights Reserved DRYWALL _ ._ 5/e DRYWALL - — "' i ,r,a aocum�c,anc: zne Iaeas - - ' ( "74(," FRAME - -` ----- " W -° -!� i I I and designs Incorporated herein, as an instrument oP � -I „ �/ proFesotonal service, is the _ �b FRAME - --� -" / propert�,� of 5wathm yy/Pratt RETURN - TYP --' - Schultz /{rchitects, Pe.G and is RETURN TYP ' ( ' noot to oe "sot echo o actin without thew itten aLpth6rizatT /J - Or Edward M bwathm Jr DOOR .IAMB TRIM -� ----- JAMB DETAIL DOOR JAMB TRIM — - I m ay MODIFY TO FIT OVER / ` m� Homy Pratt or Sidney Schultz MTL FRAME 2 MODIFY TO FIT OVER � JAMB DETAIL , MTL FRAME Date: 03 JUN 02 I l CONDO ISSUE ' Revised; SEE DOOR TRIM . I V4" CHAMFERED--` EDGE AS SHOWN � - 5/a" DRYWALL- __ -_�_ 'ter ---_ 5/a" 2%2" METAL STUD m ---__-- ` ' m 6 " METAL STUD 9/4' x 5/2" OGEE--, EDGE PROFILE 1 r 5/8" DRYWALL ---- - ` ------I j WOOD JAMB---- __ ___ _ i-� SINGLE RABBETED NOTE: ALL DIMENSIONS ARE FINISHED NOT NOMINAL WOOD TRIM ; ALL EDGES EASED UNLESS NOTED OTHERWISE JgMB DETAIL WOOD FRAME �-�''� WOOD TRIM ' - __ POCKET DOOR DETAIL - TY P I GA L DOOR TRIM DETAIL- CALE: 1" = 1'-0" Sheet Number A &.2 " f I Gwathmpy Y Pratt Schultz Architects.p C 1000 S Frontage Rd West Vail,Colorado 81657 A � Tel. (970)476-1147 SLOPE //� //^�` ��LINE OF CEILING Fmc (970)476-1612 SEVEN TH FLOOR TfV•�ORE6ROUND - EL 153' ' `� �� —--- ----- — SEVENTH FLOOR EL 153'-4" ' O 1 SIXTH FLOOR EL 141'-b" _ - SIXTH FLOOR EL 141'-6" 1 INTERIOR ELr\/AT10N ` SCALE 1/4" , I � { I f ` 1 1 Y ' r � v SLOPE j SLOPE t SLOPE I` 1 ONDO LOFT �-- -- -- ---- --- - -- - -- -- -----� �� --- --- CEL 165'-b�,l O Z ,-+,CONDO LOFT `_ - - ---- - -- ------ - -- --� - - - - -�--- - -I , - - - I '- --- -- ' - --------- -- — - � -- --- `� EL 165'-bi�fl 0Hi? O _ SEVENTH FLOOR I I EL 153'-4" F SEVENTH FLOOR EL 153'-411 INTERIOR ELEVATION 0 �► SCALE I/4" INTERIOR ELEVATION 4 � , SCALE. I/4.1 , ' d Of SLOPE LINE OF 5'-0" GLG HGT SLOPE P I I� O G op y rl g ht Gwaf P t/5chvltz Arch1tes ;T All Rlc3ht5 ,Reserved v� cThIs nd desf;:1 nt, and the ideas proPesstl ys al servpce nt.of _ hpperelri,as an Instrument of the --_- — }Z CONDO LOFT GV Schutz/Gr�tteGts P G/pi s EL 165 -61 part, Par any other protect i h '�qJI► not to be used, iM wholedor to v• ` �j � oP Edward M 6wathme Jr, Hienr auth rtzatl 0� y Pratt or�nay chvitz pe/ i Date, 03 JUN 02 � CONDO 155UF revised: V 1 r ; - —_ SEVENTH FLOOR EL 153'-4" SEVENTH FLOOR EL 153'-4" a , , INTERIOR ELEVATION j SCALE 1/411 Sheet Number,' umbe ; 1 , 1 c Gwathme Pratt, Schultz r , s � l Architects,p c 1000 8 Frontage Rd West 7 i Val[,Colorado 81657 f Tel (970)476-1147 Fax (970)476-1612 i SLOPE � r ' __, CONDO LOFT i EL 165'-6 c v f CD ` �-w Q� CONDO LOFT ` t -� - -- T EL I __ SEVENTH FLOOR - _ EL 153'-4" SEVENTH FLOOR 4 8 I z SLOPE CONDO LOFT (I ' EL 165'-6 �--1 UA D � IL o SEVENTH FLOOR � EL 153'-4" INTERIOR ELEVATION O5r-ALE- 1/4" = P-O" m G66oa�p rrghLt �.,� Alw'Ghl Mots, P,Gt/S�h,iIF= All Rights Reserved This document, and the Ideas and designs Incorporated herein, os on Instrument of professional service, is the Sroue Gwthmoyy/Pratt chptz r teats, P-r- and is not to be used, in whole or in ti part, for any other pro ect wtthovt the written avthriza of Edward K bwathmey Jr, Henry Pratt or 5ldney Schultz i— LINE OF GLG 9 BEDROOM ENTRY Date: 03'JUN 02 , VERIFY IF PROBLEM W/ TRIM CONDO 155UE d NOTIFY ARCHITECT Revised: • 5LOPE SLOPE (� ,CONDO LOFT TEL 165'-6 r INTERIOR E SCALE 1/4" Sheet Number A a2-1 ;�