Loading...
HomeMy WebLinkAboutB06-0196 Supplementary Structural Calculations 01/29/08.r SUPPLEMENTARY STRUCTURAL CALCULATIONS for - BULLETINS #001, #002 FOUR SEASONS RESORT AT VAIL . Vail, Colorado r JCL[ rLB 0 4:1908 ~J TOWN OF 1 for i HKS/HILL GLAZIER STUDIOS 925 Alma Street Palo Alto, CA 94301 by NISHKIAN MENNINGER 1200 Folsom Street San Francisco, CA 94103 NM Job No. 7083 January 29, 2008 See response below by Nishkian Mennincrer 1-28-08 Vail Four Seasons: Fourth submittal review KL&A, Inc. DRAWINGS DATED 10/23/2007-BULLETIN #001 DRAWINGS DATED 11/05/2007-BULLETIN #002 Structural Comments: Note: structural comments are numbered S1,S2, and are also given a designation with regards to the topic, as follows: DC = design criteria; F= foundations; D = drawings; C = structural calculations; GS = gravity system; LS = lateral system. General Structural Comment: This review and eventual approval does not permit the violations of any section of the building code, or any other ordinance or State law. CLOSED COMMENTS HAVE BEEN REMOVED FROM THE LIST 5164 LS S2.11 Provide detail of roof diaphragm to concrete cores. ProN ide or indicate detail of steel beams to concrete cores for gravity plus lateral loading, per ASCE 7-02 load combinations. Verify drag loads and chord force detailing at eave framing. Verify diaphragm welding is sufficient for expected shear forces, provide shear and moment diagram at roof deck levels. ASCE 7-02: 9.52.6.2.2. 9.5.2.62.6. 9.5.2.6.2.7. KLcC'.l 111 ON-- CUIc111uii1117,S luili-c' ht1'C Ihc'cn Ir,r r1;1)> c1C"Z"c'1c'1'Ulloll. 170/ 11011 Iol'c~ Dec"c'lel"trllo11pc'1'.1~~(~ 9 5.J.4. c1"ltl' 11 11741 4 /OL'.' 1101 c'o1711,01 ol'c'1' ~ciNIn c 101" 1'0oI "11'C'17 ~11'c'l 1'11111 vl0/)c' U11c11011' 1.1011710 IMO '01000_ c'017711017c171 uI lrin,hr~rr<I unc/Ic~cu'ln<1l1 ul1s. IP(' 16(19.1. Tribulclrl' cnrc'c1 tcc~ll /M. hr~rc'r ~lr~i~17 n7rn' n~11 ucclrrrllc'N ITIlcc'1 .~lijli7c'sv of co11c7'ctc' Core; CM117Alc'c/ 10 I/W 1'001 c8(11)17FU( 117 rc'I01il•c' 10 ~Ic'17c10' hrcu'eJ Ii ~nllr~. 11l(' 1604.4. Response: The roof lateral design force was used based on 2- sta,,e analysis. A flexible structure over a stiff structure. The base shear calc. for roof used was a lower R=3.25 compared to the entire buildin( R=6. M y However, the seismic force is revised to 0.4 Sds Wp (the max. diaphragm force for any structure) See revised calc. The horizontal component of wind load is checked against seismic load and does not govern. (the roof has large footprint but smaller projected area.) Due to the shape and material of the roof. it is reasonable to assume the diaphragm is flexible and force distribution should be independent of the stiffness of resisting elements. S165 LS S2.11 Provide detail of concrete diaphragm to concrete cores. verify shear transfer at each level and comment whether any drags are required. Verify if typical details 12 & 23/S 1.0.3A apply throughout the job. ASCE 7-02: 9.5.2.6.2.2. 9.5.2.6.2.6. r 9.5.2.6.2.7. 9.5.2.6.2.8. Iv1,&_f 1 l1 O : 1'I((tNc dcIiI7c rctlllircd c177bc<1111t,171 of tlr~r;~ holN llllo core' 11 (1//N. lox) bell ( hINN B Np/icc ICII.II117 1170111(1 be IINC'd \11C /I 11701 11101' O.riul /O(Id IN 171111N1rrrcd 10 11(1/1 rcinlr,1c11r~r .1('l 1 ~ Response: Added detail 6/S3.02A to show the drag bar embedment length. S169 LS S3.02A Calculations show a significant force reversal / back-stay effect from Level 6 to Level 5 shear force. i.e. SW 14 & SW 16. Verify this load path has been designed for the loads per 3D analysis. Verify soil plus wind / seismic loading has been used for drag design. Note per plan. S2.05.1, a large hole exists adjacent to wall SW16. and per calculations page 536. (38+57)=95k shear transfer is required. No drags are shown on plan. Please verify. Note, elevations S3.02A show 95 r 14" o.c. at upper levels. calculations shown (2) 45 c 24" o.c., please verify designs match calculations. IBC 1616.1.1. IBC 1604.4. KLc-.-l 6 26 0-: Original cominew culcidatecl (38-57)=95k loud for SIT"14 not STI"16 us notecl holivi,er collector bears hure not been added for ST174. SIT'16 collector load is (86+143) -229k, (4) dw 40 An slrolrn 017 pVarl (11-e not adequate f n- 229k. please r-erielr all collector desV rts. ,r 0 ci.1 1 11 0S.- ('crlc idoiioa /or SIf 5 shoii s (4) =S ca cnd 0/ W(111 CII LCIVI V. 117011Cl'r'r iVC112 52.09. 1 117011s (2) - -Ill 717[' 1701-117 ~iCVe C11r71 (4) = ~tll 117' ~i~lllh ~iIIC. PhAINC (111 t11"t!~ 1101'v 7 ah-h co/cnlotiru7s. Response: Revised plan to show (4)48 sheet S2.09.1 S173 1/S2.08.3 Verify lateral support of the low roof structure for wind and seismic loadin(,; low roof section is not connected to Level 8 PT slab beyond or core Nvalls within the roof area, and braced frames are not shown. Similar at 2/S2.08.3 and other low roof structures. IBC 1604.4. h-Ld-.I 1 1 V ON Occoc %I7slit1 ~1e~i~~7? torcc s hose 47001' /0/' sIA4 cool t1111C1111'rs MV1, 1711111iplc stories. to 7;111~ose[l to 111\11'ib71ICc1 \101'l'/('1'C'C~ /711' ~C1N/ C /()(Os. cs11CC'i4llh 011 ll711111-X101'1 /7'0717C . 1 C 11 112P. CIC..11~o it il]111CC11'S Wi7h17770V (.01111.)1 wvr ~C1~I111C /M. 1'001 ~U'liclll1-Cti. 1'ICUSC l'C1'il.l' s111)21o17111," C017C7'CIC slo>>s C11-r ~1r si~,nr71 /1-;r 1r111i or(A o177171oir11>> c11-71c loucA /i-olll l'Crlicul r C(111711M1071 01 brace /77rccs..1.~:(T y.?_ 5. 4: 1130 1004 100(), 15 Response: use max. diaphragm force for design. Checked slab to support force from braces ith over strencath factor. See calc. for the critical bay. Note that the slab was designed for 100 psf snow load and snow load is not included in the over strenUth combo [1.2D+f1L+Em] S173 11,26.28/S7.OlA Calculations indicate that roof deck is attached to slab edge along line 2 and other locations where deck and floor slab are near the same elevation. Provide a detail for lateral roof to slab connection ,vhere required by lateral analysis. IBC 1604.4. h7111s cis 1-°yirirc71..' jJ)l Ci/l' hl>~1hc 0/71(.171 /0 ,ro1~,e plc7iC. SI)CI. ill' 10v101i17" 01 hC171 16 "c111~(e 1VOIC 10 F(H) lc'ck. • • W Response: detail 5/S7.04 clarified. S174 S2.1 1.1, etc Show roof diaphragm to concrete core connection, consider in- plane collector shear forces and out of plane anchorage forces. IBC 1604.8.2; ASCE 7, 9.5.2.6.2.6, 9.5.2.62.8. h"Lc+.1 I II 1)S..AcClrioiI S1.1)i[3: I'rrifi- 'Icckp 11 c'] c'olOilloa is oc/c'clllcllc' jor !1111 of 1-1(o7c 11-'I// or c"o17c'1'c'Ic' c orr 11 411A ~ptm hors=tm1iifl.i. pc r IM 100-4.N2. 1 CXI7tll7NI.017 c177c'17ol"N orc Odc'cliloic' for c ollihl/lcil roof ('ro "lll' Iocic1111(' m oihl117c1.A717711171 fleck ~17car of 'o c15N11111c'1/ill roof cIi(lphro,,"171 ccrlcl hllio11~_ /B(' 17) 1?-IVI Response: Metal deck parallel to wall is not designed for out of plane wall anchorage. Instead, the beams are anchored to wall. The concrete shearxNall is capable of spanning horizontally. See calc. for combined gravity & shear loading for bolts. S175 S2.11.1 Verify diaphragm continuity at dormers line A5 between upper roof deck and lower roof deck. provide collectors as required for in plane shear and out of plane shear. IBC 1604.4. hLc~"I ] lI ON. AcIll' (1041i/N 10. I S1. ().B. I 'c'Oh, 011 ~lclh~ ~11I7I7rn"ti17~~ ~li~conli1717ou~ ~lc'r1 hrocccllrclnlc'~ urN c/c'~i~r71c'cl101' ~I)i'c"loll ~c'l~'1711c ollli'~~o lockl colllhillalir7ll~. 1hic to ma of p/al7c olf~ci irrc~rtll iritr. Ti lliccll cell hrclre'clli'(IMUN 411]YI collc'clol"v ~71I?I~UI'tC11 h{" v/cl/IN he/olt 170" 17('11' cVlc?l1ol7o17.v- Response: same as 4173. see cal c. S188 S5.03 Revised beams 4138 & 4139 appear too shallow to support one ,vay slab at ramp. Shear ties are spaced careater than d/2. Please review beam sizes for ramp loads. IBC 1604.2. ('iilc ~~(11,A) 171(71111'111. 11 `L l1. i w An r 17011 'ivr /,OIl)III /itIrN IV CTL' I] It I C/ L'i1 il7A/C( It/ U1I( /lIII' h01i. ~I3y IC/v rulllilllrurls a ilh 4131'' WWI 4 coO 16 cirplhc. Response: Beam 4138 is a short-span beam and is adequate as shown. Beam 4139 is analyzed as semi-fixed end beam. Some moment will transferred to column rather than Bear 4138. See attached cale. for 4139 Reinforcement is adequate. The beam having stirrups spacing less than d is when factored shear is less than ! , of shear strength. Some bears are actually thicken PT slab but labeled as beam. Those stirrups are provided for constructability purposes. 1~7.~t.1 1 Il ll.~ (lJ.t/111: A l ll\ .AI.fl l)I.i_l1/_~ l r~L100 • A2.02.1 S: Note "concrete till as required..." at Level 2A and other slabs. Please verify this «as accounted for in dead loading. IBC 1606. Response: the slab design has included 2-1/2" concrete till addition dead weight. Structural drawings: Many new details have been added in Bulletins #001 & #002 which have raised questions. Instead of writing comments for each question xve propose a phone conference to clarify the questions and avoid back and forth comments. Please call James Horne at 303-854-7495 at your earliest convenience. Misc. items on drawing: Bulletin 002 set: Sheet S7.01 H: detail 28, the cross reference near grid 14 should read 24/S7.0313 Sheet S7.01 K: detail 26, added cross reference detail 5 for beam to column connection. Sheet S7.03: detail 9, 19 added steel angle and diagonal braces L5X5 to transfer porte cochere walkwav roof diaphragm force back to level 7 slab. Also sho«n on plan S2.07.1. 9, 14, 24, 27, 29/S7.02A 30/S7.02F Added connection detail 24!S7.02F Revised detail 27 for Nvelding. Sheet S7.03 A: detail 16, 26/ S7.03 )A. added kicker to brace the ridge beam. Sheet 57.0313: detail 11, call out vent. slotted hole. • An Detail 25, added note to reference typ. deck support detail (added 27B/S7.04) Sheet S7.04: Detail 13 14. fixed weld svmbol Detail 14, checked for offset embed and it is adequate. The load from the facia channel is small. Detail 5, re, ised. Bulletin 001 set: Sheet S2.0.0.13 revised footing bars to shovN% hooks. Sheet 52.07.3 added horizontal braces for steel posts near grid i. Sheet S2.10.1 detail cut 6/S701A should read 6/S7.03A Similar for sloped slab. Sheet 56.01 detail 2A. 213 added top bars at balcony slab. - [end] - m +w go r NISHKIAN CONSULTING AND STRUCTURAL ENGINEERS 1200 Folsom Street, San Francisco, CA 94103 Tel: (415) 541-9477 Fax: (415) 543-5071 SHEET NO. CALCULATED BY. CHECKED BY OF DATE DATE 'C~~ ~1 fl P('Pfi 6V I tiC/F~ • i' L ~'S~ ZO~ 51Y~iJ - Zo ~iSI` 17 c, ate. "•,~1 4- 4- f r ' C ) = 7 zap Srz~~x~ ~ I f i f f f f f 1 f f f f 1 f t ! f 672 - -672 - - - - _ - 71.01 _ 6T2 GT2 - 671 ~I ❑ - - io B2 - SLOPING SLAB i~ o 81030°' 72012 - - - - - (SkADED) I #512°T&B EX - X2018_' 14A Z - I ~p ~ 7.03 I I I 72012" I B1 10" POST'-TENSIONEb TYP 6T SLAB W1 #4 0 24"I 4 t 2B TYP.IAT it 2#7x23'-D' DRAG BARS i G .0 10" SLAB I HOOK 3'- INTO WALL 8T4 - 16 1 - HS!; 560/8 \ \ BRACE UP POST OE 14 1018" 1, 1 - - B' Z4 m T201 SW8 SW-12 - TYP. AT WALL I m 3 3 ❑ ❑ 10T4 6+51e BOTTOM E.W. TYP. U.O.N. 12. srrv . 2 ~2" - - 81030' - T2012 ml IEl. S.A.D. I, 873 Ix UP A 8T3 ER r"A. - , I , 8_' ❑I 873 FA] sW6 SW10 1 ❑ #6x6,-0"T&B,TYP. AT OPNG o ,a I - I II ` I Ilfl I X~' I I I \-2#7 T&B,EXTEND 4'x-0" BEYONDIOPNG ~ TYP. AT OPNG m m m _ I ] T3 oi1 o_p , Ils 6.6 ego. j i 201 8T4 SW21 8" - - ~r--- I I~ II I it III I~ T1101f l i ICI 3 3 I III - Fs-W-2-3] v O I' I +6+'i 1074 a 874 ❑A ❑B FS W-179 10" PT SLAG A °I w/#4024"B' W. i ❑ III. ~ ~ ~ ~oo~ VIII, _=2.0 L 7;SF ALo r'K /mil q.&,l - ,r z. Qr= `i ~ p" s L<=~ S'~a F lie , c1, 0 "Z 2, 7 ~ tC_ 01/24/08 Project title: 10:32:49 C:ID000MENTS AND SETTINGSWUIDESKTOPIPT-FOURI10THSLABISLAB.ADB - Dale: 112412008 M - - ADAPT CORPORATION STRUCTURAL CONCRETE SOFTWARE SYSTEM 1733 Woodside Road, Suite 220, Redwood City, California 94061 - ADAPT-PT FOR POST-TENSIONED BEAM/SLAB DESIGN Version 7.10 AMERICAN (ACI 318-02/IBC-03) ADAPT CORPORATION - Structural Concrete Software System 1733 Woodside Road, Suite 220, Redwood City, California 94061 Phone: (650)306-2400, Fax: (650)364-4678 Email: SupportCAdaptSoft.com, Web site: http://www.AdaptSoft.com DATE AND TIME OF PROGRAM EXECUTION: Jan 24,2008 At Time: 10:40 PROJECT FILE: slab P R O J E C T T I T L E: four Season support Bracing of roof 1- USER SPECIFIED G E N E R A L D E S I G N P A R A M E T E R S CONCRETE: STRENGTH at 28 days (fcu), for BEAMS/SLABS 5000.00 psi for COLUMNS 5000.00 psi MODULUS OF ELASTICITY for BEAMS/SLABS 4030.50 ksi for COLUMNS 4030.50 ksi CREEP factor for deflections for BEAMS/SLABS 2.00 CONCRETE WEIGHT NORMAL TENSION STRESS limits (multiple of (f'c)1/2) At Top 6.000 At Bottom 6.000 COMPRESSION STRESS limits (multiple of (f'c)) s At all locations .450 REINFORCEMENT: YIELD Strength 60.00 ksi Minimum Cover at TOP 1.00 in Minimum Cover at BOTTOM 1.00 in POST-TENSIONING: SYSTEM Ultimate strength Average effective Strand area...... Min CGS of tendon UNBONDED of strand 270.00 ksi stress in strand (final) 175.00 ksi .193 in'2 from TOP 1.00 in M Page 2 (slab) ADAPT-PT V- 7.10 ACI-02 Min CGS of tendon from BOTTOM for INTERIOR spans.. 1.00 in Min CGS of tendon from BOTTOM for EXTERIOR spans.. 1.00 in Min average precompression 125.00 psi Max spacing between strands (factor of slab depth) 8.00 Tendon profile type and support widths............ (see section 9) ANALYSIS OPTIONS USED: Structural system ONE-WAY Moment of Inertia over support is NOT INCREASED Moments REDUCED to face of support YES Limited plastification allowed(moments redistributed) NO 2- I N P U T G E O M E T R Y 2.1.1 PRINCIPAL SPAN DATA OF UNIFORM SPANS + S FI TOP BOTTOM/MIDDLEI P OI I FLANGE FLANGE REF I MULTIPLIER A RI LENGTH WIDTH DEPTHI width thick.I width thick.IHEIGHTI left right N MI ft in in I in in I in in I in I dw -1-- ---3-- --4---- ---5--- ----6-- 7------8------9------10----11--- --12----13- 1 1 14.00 144.00 10.00 10.00 .50 .50 2 1 28.00 144.00 10.00 10.00 .50 .50 3 1 14.00 144.00 10.00 10.00 .50 .50 4 1 28.00 144.00 10.00 10.00 .50 .50 5 1 14.00 144.00 10.00 10.00 .50 .50 LEGEND: - _ 1 - SPAN 3 - FORM C = Cantil ever 1 = Rectangular sect ion 2 = T or Inverted L section 3 = I section 4 = Extended T or L section 7 = Joist 8 = Waffle 11 - Top surface to reference line 2.2 - S U P P O R T W I D T H A N D C 0 L U M N D A T A SUPPORT LOWER COLUMN UPPER COLUMN WIDTH LENGTH B(DIA) D CBC* LENGTH B(DIA) D CBC* i' a Page 3 (slab) ADAPT-PT - V- 7.10 ACI-02 JOINT in ft in in ft in in ® --1- -2 -3----- --4 5----- 6------ ---7--- ----8---- - --9---- 1 0--- 1 24.00 12.00 24.00 12.00 (2) .00 .00 .00 (1) 2 24.00 12.00 24.00 24.00 (2) .00 .00 .00 (1) 3 24.00 12.00 24.00 24.00 (2) .00 .00 .00 (1) 4 24.00 12.00 24.00 24.00 (2) .00 .00 .00 (1) 5 24.00 12.00 24.00 24.00 (2) .00 .00 .00 (1) 6 .00 12.00 24.00 24.00 (2) .00 .00 .00 (1) *THE COL UMN BOUNDAR Y CONDITION CODES (CBC) Fixed at both ends ...(STANDARD) = 1 Hinged at near end, fixed at far end = 2 Fixed at near end, hinged at far end = 3 Fixed at near end, roller with rotational fixity at far end = 4 • 3- I N P U T A P P L I E D L 0 A D I N G < CLASS > < TYPE D = DEAD LOAD U = UNIFORM P = PARTIAL UNIFORM L = LIVE LOAD C = CONCENTRATED M = APPLIED MOMENT Li= LINE LOAD _ Intensity ( From To ) ( M or C . ..At) 3otal on Trib SPAN CLASS TYPE k/ft-2 ( ft ft ) (k-ft or k . ..ft) k/ft -1-- ---2----- -3--- -----4------- ---5----- ---6--- ------7----- --8----- -9- 1 L U .020 .00 14.00 .240 1 D U .233 .00 14.00 2.796 2 L U .020 .00 28.00 vlJ .240 2 D U .233 .00 28.00 2.796 2 D C 18.90 8.00 3 L U .020 .00 14.00 .240 3 D U .233 .00 14.00 2.796 4 L U .020 .00 28.00 .240 4 D U .233 .00 28.00 2.796 4 D C 18.90 20.00 5 L U .020 .00 14.00 .240 5 D U .233 .00 14.00 2.796 40 4W Page 8 (slab) ADAPT-PT V- 7.10 ACI-02 9.3 - SELECTED POST-TENSIONING FORCES AND TENDON DRAPE Tendon editing mode selected: FORCE SELECTION < SELECTED VALUES CALCULATED VALUES FORCE DISTANCE OF CGS (in) P/A Wbal Wbal SPAN (k/-) Left Center Right (psi) (k/-) (oDL) --1---- ------2J -----3---- ----4---- ----5----- ------6----- -----7---- ----8-- s 1 380.000 5.00 3.50 9.00 263.89 4.524 162 2 380.000 9.00 1.00 9.00 263.89 2.585 74 3 380.000 9.00 5.50 9.00 263.89 4.524 162 4 380.000 9.00 1.00 9.00 263.89 2.585 74 s 5 380.000 9.00 3.50 5.00 263.89 4.524 162 Approximate weight of strand 794.9 LB 9 . 5 R E Q U I R E D MINIMUM P O S T - T E N S T O N I N G FORCES (kips) BASED ON STRESS CONDITIONS BASED ON MINIMUM P/A SPAN LEFT* CENTER RIGHT* LEFT CENTER RIGHT --1-- --------2--- -------3-- 4----- ----------5---- -----6----- ----7---- 1 .00 .00 227.93 180.00 180.00 180.00 _ 2 173.43 198.45 83.91 180.00 180.00 180.00 3 145.75 38.70 145.75 180.00 180.00 180.00 4 83.91 198.45 173.43 180.00 180.00 180.00 5 227.93 .00 .00 180.00 180.00 180.00 Note: * = face-of-support 9.6 S E R V I C E S T R E S S E S (psi) (tension shown positive) L E F T* C E N T E R R I G H T* SPAN TOP BOTTOM TOP BOTTOM TOP BOTTOM -1--- -------2---- ------3----- --------4----- ----5----------- --6--- ------7---- 1 -263.80 -263.98 123.49 -651.27 61.98 -589.75 2 -99.63 -428.15 -536.32 8.54 - 214.86 -312.92 3 -63.03 -464.75 161.21 -688.99 -63.03 -464.75 4 -214.86 -312.91 -536.32 8.54 -99.63 -428.15 5 r 61.98 -589.75 123.49 -651.27 - 263.90 -263.88 r t' r I I t I I I I I I 1 I 1 t i I 1 1 I Stress Diagrams Pile: slab [(+)'T'ension (Limit=424.3) (-)Compression (Limit=-2250.)] 200 - 100 - 0 -100 -200 - -300 -400 - -500 = -600 -700 -Lill Span 1 Project Name: slab Jan. 24, 2008 10:40 AM ADAPT-PT 7.10 Span 2 Span 3 Span 4 Span 5 Combined stresses factors: 1.0*DL+1.0*LL+1.0*PT I i ! f t f 1 f f 1 i f f i i 1 f 1 i 100 0 -100 -200 a u, -300 -400 -500 -600 -700 Span 1 Span 2 Span 3 Span 4 Span 5 Combined stresses factors: 1.0*DL+1.0*LL+1.0*PT X Project Name: slab Jan. 24, 2008 10:40 AM ADAPT-PT 7.10 Stress Diagrams Pile: slab [(-i-)Tension (Limit=424.3) (-)Compression (1-imit--2250)] Combined Bottom Max-T Combined Bottom Max-C Allowable Stresses ;r LL--j Im Fie Ida l'iew Help Des Eill:e ion ~~~JJJ p ft Units English; s - Properties X = C; E = 3605; I = 9096; X = E = 3605; I = 5096; Moment Releases Supports % = 0, Disp = 0; Rotation = O; = Z?; Dnsp 0; Rotation 0; Sprin7s ~Point o nt1 Loads ..Mart = 0; XEnd = 27; UStart = -3.98; r7End = -3.58. r 'J . Errorif), 0 Uerr,ingis) Punning Pnalps is Iol?01 Nodes Defined, 402 Degrees cf freedom Equilibri,.un error: Vert - -0.000 hips; Rotatior, . 0.000 kiP ft Snalysis Comp lete, the :vrer.t'drin6tarn He s s ~J t~ c _J rxrr lr~ beam.wbni - 6e,tloP- . r y,a r] C 43 ?M Monday, Jan 21, 2008 12:59 PM r. M JsJJ Fie Edit View tielp • ✓ a~ Ea ofi 4J- ~c I=1 Description Moment - kip ft - Units English; Properties X = 0; E = 3605; I = 4096; X = 27; E = 3605; I = 1056; .-185.535515 Moment Releases Supports } X = 0; Disp = 0; X = Z7; Disp = 0; Springs - Point Loads X = C; Moment = -105.7; X = 27; Moment = 158.55; XE-t,art = 0; XEnd = 27; UStarc = -3.43; UEnd = -3.43. f, -158.550000- -IYY 'I T_rroris), 0 Uerninafo) I:IPunning Analysis 0 201 Nodes Defined, 402 Degrees of freedom Y Equilibri= error: Pert . -0.000 kips; Rotation - 0.000 kip ft - Analysis Complete t7 iu Feady _e _~Start w- l~ i ~r3 J~ rto, - Mv, P" ~ beaml.wbm ~ Goy De~13nG...~ 34i Monday, Jan 21, 2008 12:58 PM +r i NISHKIAN CONSULTING AND STRUCTURAL ENGINEERS 1200 Folsom Street, San Francisco, CA 94103 Tel: (415) 541-9477 Fax: (415) 543-5071 JOB J I'k'I ` Cwj V451-, NO. 1 SHEET NO. OF CALCULATED BY DATE CHECKED BY DATE M do 0,51 5 r G2 r~ ~ I rl i r a r NISNKIAN . - CONSULTING AND STRUCTURAL ENGINEERS 1200 Folsom Street, San Francisco, CA 94103 Tel: (415) 541-9477 Fax: (415) 543-5071 I JOB `-f-~1f~ It 1 L..-~` NO. N~I SHEET NO. OF CALCULATED BY DATE CHECKED BY DATE do r Y~1C`1~ t Ile PI 0 - 7 I