HomeMy WebLinkAboutA11-0010 plans WIRE AND CONDUIT CHARACTERISTICS Wire Schedule Cable /Wire Desigination Conductor size Insulation Number of Conductors Conductor Dia. (in) Conductor /Cable Area (sq-in) Conduit Size (in) Conduit ID (in) Area (sq-in) A (SLC) 16AWG CABLE 2 Con Cable 0.176 0.0243 1/2 0.622 0.304 B (Strobes) 14AWG THHN 2 0.111 0.0194 3/4 0.824 0.533 C (Speakers) 16AWG CABLE 2 Con Cable 0.178 0.0249 1 1.049 0.864 D (24VDC) 14AWG CABLE 2 0.111 0.0194 E (RS-485) 16AWG CABLE 2 Con Cable 0.178 0.0249 1-1/4 1.380 1.496 G (IDC) 16AWG THHN 2 0.096 0.0145 1-1/2 1.610 2.036 2 2.067 3.356 I (Sounder Base Interconnect) 16AWG THHN 1 0.096 0.0072 2-1/2 2.731 5.858 3 3.356 8.846 Fire alarm cable for Signaling Line Circuit (SLC) type "A" shown in wire schedule is : Non Plenum 16awg, non shielded, 2cond, solid, TYPE FPLR. OD = 0.176 Each B circuit consists of 2 #14 conductors Fire alarm cable for Speaker Circuit type "C" shown in wire schedule is : Non Plenum 16awg, OA shielded, 2cond, solid, TYPE FPLR. OD = 0.178 Each D circuit consists of 2 #14 conductors Fire alarm cable for RS-485 Circuit type "E" shown in wire schedule is : Non Plenum 16awg, OA shielded, 2cond, solid, TYPE FPLR. OD = 0.178 Each G circuit consists of 2 #16 conductors Each I circuit consists of 1 #16 conductor CONDUIT FILL CALCULATION TABLE CONDUIT SIZE CONDUCTORS IN CONDUIT SEGMENT 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 1A 8.0% 4.6% 2.8% 1.6% 1.2% 0.7% 0.4% 1A,1D 14.4% 8.2% 5.1% 2.9% 2.1% 1.3% 0.7% 2A,2D 28.8% 16.4% 10.1% 5.8% 4.3% 2.6% 1.5% 3A,2D 36.8% 20.9% 12.9% 7.5% 5.5% 3.3% 1.9% 1A,1D,1I 16.8% 9.5% 5.9% 3.4% 2.5% 1.5% 0.9% 2A,2D,2I 31.1% 17.7% 10.9% 6.3% 4.6% 2.8% 1.6% 1B,1C 14.6% 8.3% 5.1% 3.0% 2.2% 1.3% 0.8% 2B,2C 29.1% 16.6% 10.2% 5.9% 4.3% 2.6% 1.5% 3B,3C 43.7% 24.9% 15.4% 8.9% 6.5% 4.0% 2.3% 4B,4C 58.2% 33.2% 20.5% 11.8% 8.7% 5.3% 3.0% 1G 2.4% 1.4% 0.8% 0.5% 0.4% 0.2% 0.1% 2G 4.8% 2.7% 1.7% 1.0% 0.7% 0.4% 0.2% 3G 7.1% 4.1% 2.5% 1.5% 1.1% 0.6% 0.4% 4G 9.5% 5.4% 3.4% 1.9% 1.4% 0.9% 0.5% 5G 11.9% 6.8% 4.2% 2.4% 1.8% 1.1% 0.6% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 1D,1E 11.1% 6.3% 3.9% 2.3% 1.7% 1.0% 0.6% 1D,2E 15.9% 9.1% 5.6% 3.2% 2.4% 1.4% 0.8% 2D,1E 17.5% 10.0% 6.2% 3.6% 2.6% 1.6% 0.9% 2D,2D 22.3% 12.7% 7.8% 4.5% 3.3% 2.0% 1.2% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% M.L. Vaughan, Fire Marshal Digitally signed by M.L. Vaughan, Fire Marshal DN: cn=M.L. Vaughan, Fire Marshal, o=Vail Fire & Emergency Services, ou=Prevention, email=mvaughan@vailgov.com, c=US Date: 2011.04.06 09:21:09 -06'00' M.L. Vaughan, Fire Marshal Digitally signed by M.L. Vaughan, Fire Marshal DN: cn=M.L. Vaughan, Fire Marshal, o=Vail Fire & Emergency Services, ou=Prevention, email=mvaughan@vailgov.co m, c=US Date: 2011.04.06 09:22:14 -06'00' Project Name Solaris Date 3/15/2011 Circuit Number Remote Power Supply #6 /RPS6-7 Voltage Voltage Voltage Location Second Level Retail 207 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.885 245 0.97 0.885 245 1.383 0.885 245 0.692 Minimum Device Voltage 16 End of Line Voltage 19.43 End of Line Voltage 19.02 End of Line Voltage 19.71 Total Circuit Current 0.885 Wire Ohm's Percent Drop 4.73% Percent Drop 6.78% Percent Drop 3.39% Gauge Per 1000 Distance from source to 1st device 100 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.165 100 19.84 0.565 2.77% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.165 30 19.70 0.702 3.44% Device 3 0.165 30 19.59 0.809 3.96% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.060 25 19.53 0.871 4.27% Device 5 0.165 30 19.47 0.934 4.58% Candela Candela Device 6 0.165 30 19.43 0.966 4.73% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 19.43 0.966 4.73% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.43 0.966 4.73% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.43 0.966 4.73% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.43 0.966 4.73% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.43 0.966 4.73% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.43 0.966 4.73% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.43 0.966 4.73% END 19.43 0.966 4.73% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.43 0.966 4.73% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.43 0.966 4.73% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.43 0.966 0.966 4.73% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.43 0.966 4.73% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.43 0.966 4.73% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.43 0.966 4.73% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.885 245 End of Line Voltage 19.43 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.885 OUT SPARE CAPACITY = 41% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Totals Totals Totals End of Line and Load Centering Methods use only the wire guage for the first device to source CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Load Centering Method PS-6 BATTERY CAPACITY CALCULATION FOR RPS6 OPERATION ON BATTERY BACKUP POWER DEVICE TYPE QTY STAND-BY CURRENT QTY ALARM CURRENT EACH TOTAL EACH TOTAL RPS6-1 1 0.000 0.000 1 0.225 0.225 RPS6-2 1 0.000 0.000 1 0.349 0.349 RPS6-3 1 0.000 0.000 1 0.385 0.385 RPS6-4 1 0.000 0.000 1 0.812 0.812 RPS6-5 1 0.000 0.000 1 0.385 0.385 RPS6-6 1 0.000 0.000 1 0.272 0.272 RPS6-7 1 0.000 0.000 1 0.885 0.885 RPS6-8 1 0.000 0.000 1 0.000 0.000 MAIN PC BOARD 1 0.129 0.129 1 0.129 0.129 Number of Slave power Supplys 0 0.006 0.000 0 0.006 0.000 0 0.000 0.000 0 0.000 0.000 0 0.000 0.000 0 0.000 0.000 TOTAL CURRENT 0.129 3.442 TOTAL CURRENT -STANDBY OPERATION 0.129 HOURS REQUIRED FOR OPERATION 24.00 BATTERY STANDBY REQUIREMENTS 3.10 TOTAL CURRENT -ALARM OPERATION 3.442 HRS REQUIRED FOR OPERATION 0.250 (15 MIN) BATTERY ALARM REQUIREMENT 0.86 TOTAL BATTERY REQUIREMENTS 3.96 BATTERY REQUIRED WITH 20% FACTOR 4.75 7 AMP-HOUR BATTERIES INSTALLED AMPS AVAILABLE CURRENT 8 TOTAL CURRENT 3.442 SPARE CAPACITY 56.98% M.L. Vaugha n, Fire MarshalDigitally signed by M.L. Vaughan, Fire Marshal DN: cn=M.L. Vaughan, Fire Marshal, o=Vail Fire & Emergency Services, ou=Prevention, email=mvaughan@va ilgov.com, c=US Date: 2011.04.06 09:21:46 -06'00' IFC-320 FIRE ALARM CONTROL PANEL -FAP5 Calculation Column 1 Primary, Non-Fire Alarm Current (amps) Calculation Column 2 Primary, Fire Alarm Current (amps) DEVICE QTY. AMPS. TOTAL QTY. AMPS. TOTAL IFC-320 1 0.2500 0.2500 1 0.2300 0.2300 KDM-R2 DISPLAY 1 0.1000 0.1000 1 0.1000 0.1000 ACPS-2406 0 0.1287 0.0000 0 0.0000 0.0000 BACNet Gateway 0 0.3600 0.0000 0 0.3600 0.0000 LCD-80,LCD-80TM 0 0.1000 0.0000 0 0.1000 0.0000 JNCA 0 0.4000 0.0000 0 0.5000 0.0000 LDM-32 0 0.0400 0.0000 0 0.0000 UZC-256 0 0.0350 0.0000 0 0.0850 0.0000 AMG-1,AMG-E 0 0.0600 0.0000 0 0.0600 0.0000 FFT-7,FFT-7S 0 0.0600 0.0000 0 0.1200 0.0000 AA-30 0 0 AA-100,AA-120 0 0 M302MJ,M502MJ 0 0.0094 0.0000 0 0.0900 0.0000 XPIQ 0 0.0000 0 0.0000 RPT-W,RPT-WF,RPT-F,NCM-W 1 0.0170 0.0170 1 0.0170 0.0170 UDACT Communicator 0 0.0400 0.0000 0 0.1000 0.0000 Notification Appliance 1 1 2.9410 2.9410 SOUNDER BASES 13 0.0010 0.0130 13 0.0150 0.1950 Power Supervision Relays 1 0.0200 0.0200 1 0.0200 0.0200 DH500,DH502 Duct Detectors 0 0.0000 0 0.0000 CHG-120 Battery Charger 0 0 SLC #1 Totals 1 0.2000 0.2000 1 0.2000 0.2000 TOTAL 0.60 3.70 TOTAL CURRENT -STANDBY OPERATION 0.600 HOURS REQUIRED FOR OPERATION 24 BATTERY REQUIREMENTS FOR 4 HRS 14.40 TOTAL CURRENT -ALARM OPERATION 3.703 HOURS REQUIRED FOR OPERATION (15min) 0.25 BATTERY REQUIREMENTS FOR 5 MIN 0.93 TOTAL BATTERY REQUIREMENTS 15.33 BATTERY REQUIRED WITH 20% FACTOR 18.39 BATTERY TO BE INSTALLED 18 AMP-HR