Installation Instructions4193SN Serialized Interface Module (SIM)The 4193SN is a serialized two-zone expander used to connect alarm sensing
devices to controls which support serial number polling loop devices (i.e., Vista-
40, Vista-50P, and Vista-100).
The 4193SN can be configured as one supervised zone (10K EOLR) and one
unsupervised zone, or two unsupervised zones (normally closed devices only).
Consult the control panel installation instructions for programming information.
Electrical Specification:
Voltage:7-11VDC (as supplied from the Ademco control panel for
multiplex polling loop)
Current:1.5mA
RED (+)
WHITE (LOOP 1) SUPERVISED EOLR 10K
YELLOW (LOOP 1) UNSUPERVISED
GREEN (LOOP 2) UNSUPERVISED
BLACK (COMMON)BLACK (-)
POLLING
LOOP
Wiring Diagram
For Fire Applications:
The 4193SN must be mounted inside the control panel cabinet or inside a UL-
Listed junction box. Loop 1 must be used in the supervised configuration for
Fire. Loop 2 may be used for Burglary.
For UL Burglary Applications:
If using an unsupervised zone of the 4193SN, the unit must be mounted within 3
feet of the alarm initiating device, with no intervening barriers.
4193SN Serialized Interface Module (SIM)
•For connecting alarm sensing devices and switches to
Ademco multiplex polling loop
Quantity: 1 ea.
Requires control panel with SERIALNUMBER device capability
(e.g. Vista-40, etc.)
Consult control panel instructions for compatibility
N7644V2 Rev. B 11/96