NAC NAC NAC DEMO DEMO DEMO NAC NAC NAC NAC NAC NAC NAC NAC NAC NAC EAST ELEC 143 24VDC 24VDC 24VDC AUD AUD AUD AUD AUD AUD AUD AUD AUD AUD AUD AUD AUD AUD AUD 120VAC 120VAC 120VAC AUD
AUD AUD SLC SLC SLC SLC SLC SLC SLC SLC SLC SLC SLC SLC SLC CORR. 142 ELEV 7 ELEV 11 TOILET 155 RETAIL 154 ELEV LOBBY 156 STAIR 3 ELEV 8 VEST 157 CLUB LOBBY 162 CONCIERGE 158 BUSINESS
CENTER 159 NAC 0103043P 0103045 P 0103044P 0103048 P 0103138 F F 0103134 F 0103135 (1G-1-2) 15W (1G-1-4) 15W BPS1D BPS1E UIO6R UIO6R SW .5w 0102153 CC1S 0102024 P (1G-1-10) 15W H15/75WP
9'-0" 9'-6" 11'-6" 9'-6" 8'-6" 8'-0" 0103050 135R SLC 0103136 0103137 CT2 F S T S AUD AUD AUD AUD AUD 120VAC 120VAC AUD AUD AUD AUD AUD SLC SLC SLC SLC SLC SLC SLC CT1 0103140 T S SLC
SLC SLC SLC SLC SLC 0103142 CR 0103141 CR 0103056 P 0103055P (1G-1-6) 15W RELOCATE SLC NAC NAC NAC NAC NAC NAC NAC AUD AUD AUD AUD NAC NAC NAC AUD AUD AUD AUD BPS1G NAC P (x-x-x) xxW
(x-x-x) SxxW xw Date: NAC SLC AUD 120VAC 24VDC DEMO AUDA AUDB REFER TO ONE LINE DIAGRAMS AND WIRING DETAILS FOR ADDITIONAL INFORMATION REGARDING WIRE TYPES, RISERS, AND **NOTE** NOT
ALL WIRING TYPES SHOWN IN WIRE LEGEND ARE NECESSARILY USED IN THIS PRTOERJEMCINTA. TLIEOGNESN.D PROVIDED AS ADDITIONAL MEANS OF DRAWING CLARIFICATION. (X-X-X) PROVIDE (1) NEW BPS6A BOOSTER
POWER SUPPLY FOR STROBE CIRCUIT POWER. POWER SUPPLY TO BE TRIGGERED BY EXISTING POWER SUPPLIES. INTERCEPT AND EXTEND EXISTING SLC CIRCUIT TO NEW DEVICES AS SHOWN. INSTALL END OF LINE
RESISTOR. SHOWN DEVICE TO BECOME NEW END OF LINE DEVICE FOR CIRCUIT NAC1D-1. RELOCATE EXISTING DEVICE TO NEW LOCATION SHOWN. ADJUST CANDELA AND SPEAKER SETTINGS AS SHOWN. EXTEND AUDIO
AND STROBE CIRCUITS TO NEW AND RELOCATED DEVICES. SPLICE RETURNING WIRE THROUGH JUNCTION BOX TO NEXT EXISTING DEVICE. RELOCATE EXISTING DEVICE FROM DECK TO DROP CEILING LOCATION SHOWN.
DETAIL NOTES: SIGNATURE SERIES PHOTO-ELECTRIC DETECTORS SHALL BE MOUNTED NO CLOSER THAN 36" TO AN ELECTRONIC BALLAST OR THE WIRING FROM BALLAST FIXTURE RECEPTACLES. ALL DEVICES AND MATERIALS
USED IN THIS PROJECT SHALL BE UL LISTED AND/OR AHJ APPROVED FOR USE IN FIRE ALARM SYSTEMS. IF FIELD CONDITIONS RESULT IN A CHANGE TO THE SHOP DRAWING INSTALLATION IN ANY WAY, CONTACT
FAS SYSTEMS GROUP TO VERIFY PROPOSED CHANGES ARE COMPLIANT WITH NFPA 72 REQUIREMENTS AND PER LOCAL CODES/AMENDMENTS. EACH CONTROL CABINET AND ADDRESSABLE DEVICE SHALL BEAR A TYPED LABEL
INDICATING IT'S ADDRESS OR DESIGNATION, WHICH CAN BE SEEN WITHOUT A LADDER OR LIFT. SMOKE AND HEAT DETECTORS SHALL HAVE THEIR LABEL ON IT'S BASE, DUCT SMOKE DETECTORS SHALL HAVE THEIR
LABEL ON ITS REMOTE TEST STATION. GENERAL NOTES: 1. 2. 3. 4. **NOTE** EXISTING DEVICES SHOWN GREYED, NEW DEVICES SHOWN BOLD. BPS6A/BPS10A -MULTIPLE BOOSTER PANELS WIRING FROM FACP OR
PREVIOUS SLC DEVICE TO NEXT SLC DEVICE BPSX BPSX FROM SIGNATURE CONTROLLER OR PREVIOUS SLC DEVICE SMOKE DETECTOR AND HEAT DETECTOR WIRING TO NEXT SLC DEVICE STANDARD DETECTOR BASE: SIGA-SB,
SIGA-SB4 STANDARD DETECTORS: SIGA-PS, SIGA-PHS, SIGA-IS, SIGA-HRS, SIGA-HFS STROBE CIRCUIT TO NEXT DEVICE OR END OF LINE RESISTOR 25 OR 70Vrms TO NEXT DEVICE OR END OF LINE RESISTOR
25 OR 70Vrms FROM FACP OR PREVIOUS DEVICE STROBE CIRCUIT FROM FACP OR PREVIOUS DEVICE STANDARD GENESIS MODELS: G4-S2VM, G4F-S2VM, G4R-S2VM, G4RF-S2VM, G4-S7VM, G4F-S7VM, G4R-S7VM, G4RF-S7VM
GENESIS SYNCHRONIZED SPEAKER/STROBE WIRING TO NEXT DEVICE OR END OF LINE RESISTOR. FROM FACP OR PREVIOUS DEVICE. STANDARD GENESIS MODELS: GI-VM, G1F-VM, G1R-VM, G1RF-VM, G1-HDVM, G1F-HDVM,
G1R-HDVM, G1RF-HDVM, G1-HD, G1F-HD, G1R-HD, G1RF-HD. GENESIS SYNCHRONIZED HORN, HORN/STROBE, STROBE WIRING KEY PLAN A11-0001 be wary of placement in areas where aerosol products will
be used. Approved. M. Vaughan M.L. Vaughan, Fire Marshal Digitally signed by M.L. Vaughan, Fire Marshal DN: cn=M.L. Vaughan, Fire Marshal, o=Vail Fire & Emergency Services, ou=Prevention,
email=mvaughan@vailgov.com, c=US Date: 2011.01.17 13:34:03 -07'00'