HomeMy WebLinkAboutA10-0115 fire alarm stamped approved drawings 10-0115
THIS DEVICE IS TO BE MOUNTED WITH IN 3' OF THE PEAK. 16/4 FPLP -SLC 14/4 FPLP -NAC 16/4 FPLP -SLC 14/4 FPLP -NAC 16/4 FPLP -SLC 14/4 FPLP -24VDC RISER FROM DOWN BELOW RISER TO SECOND
FLOOR LOFT 16/4 FPLP -SLC 14/4 FPLP -24VDC 16/4 FPLP -SLC 14/4 FPLP -NAC FROM RISER CLOSET 16/4 FPLP -SLC 16/4 FPLP -24VDC FROM RISER CLOSET 16/4 FPLP -SLC 14/4 FPLP -NAC FIRE ALARM
LEGEND GENTEX 9120H -SINGLE STATION SMOKE DETECTOR -24VDC FUTURE 1224CO -CO DETECTOR AND MONITOR MODULE GENERAL NOTES: *** ALL DETECTORS ARE TO BE MOUNTED IN THE CENTER OF THE ROOM.
*** ALL WIRE TO BE FPLP *** ALL BOXES TO BE 4" DEEP METAL BOXES. CO DETECTORS LOCATIONS TO HAVE A SINGLE GANG "P" RING. *** ALL CO DETECTOR LOCATIONS ARE FOR FUTURE USE. ALL WIRE WILL
BE TIED THROUGH AND A SINGLE GANG COVER PLATE WILL BE INSTALLED. *** ALL GENTEX SMOKE DETECTORS WILL BE REPLACED WITH ADDRESSABLE DEVICES WHEN THE FIRE ALARM SYSTEM IS UPDATED. *** ALL
WIRING SHOWN WILL COMPLY WITH THE NEW SYSTEM REQUIREMENTS. Tim Ward Digitally signed by Tim Ward DN: cn=Tim Ward, o=COMMERCIAL SPECIALISTS, ou=NICET IV #115941, email=CSWC.TIM@CSIGJ.COM,
c=US Date: 2010.12.20 10:29:38 -07'00' M.L. Vaughan, Fire Marshal Digitally signed by M.L. Vaughan, Fire Marshal DN: cn=M.L. Vaughan, Fire Marshal, o=Vail Fire & Emergency Services,
ou=Prevention, email=mvaughan@vailgov.co m, c=US Date: 2010.12.20 10:36:05 -07'00' Installation is required to be in conduit. MLV.