HomeMy WebLinkAboutB11-0068 I
�������i�� i���� �� �������� ��{�� ���������€�
��„��
(r�a� itom id w�.� F9�e�a�i�ior�� .._ _.�.�: �.A,� ��g_ It�m� X�tiefl �lnhu�i��le .._.,
* 91 PW-Fir�al d�iv���rade � Yes F� 1 AP' �_ No
` 532� �W-1'�MP.C/C? Y�� F� � A� �NQ- --
r EJ�� ��5� �����..�'i��_ ��� '� '� �� """.. �Q '�.
" 90 �1.�� �'�E��`INi� �1���_ �� �� �,� �� Na
�' �p�' �L��x���r���t���f�i��i ��'�� �i � �P ��,�...✓ �� .,�....
k �1 114� _���L����r���p � -���,��i������,�,�_ �.�.�. ��w �� ! ��� ....
�_�._.�. ��..._.__ �..
' 92�� �l.�� i��u h _.,.,_,� .jt�� �.,� ���- ��! ��____.���:�.��,
� ,....._.__ °
" �OQ _����hi,��u�,�,_,__ ��1�� �� & � �� �
r` 31� I M��i�t t i��ti�� �Y�� ��_�_ t �� .� �� � � �__ �1a
r _. __ _� .__,_�_
G` �3AQ .. �f���Ei��Y���� - , ., W �_ � __.w.� ✓t .._ ._,__
� _�. � C5[� �����i����i(�et�i��3WF�6� _ .w_ ;�I`�� ,���� 9� F�� .�, �����.._
��� —___�_���._ ' ���iE� t�����i�t��d V__, ..� � r�� _I i� 1� �►� I� _. �� __._�.
��� I 239 __��1.R9� �t���Hr�u�t�e__._ �`��� (�_ .�� ��� r � �,��_....�
�� �d6�� � �6�P�������3�,ih f`��� I I��� � _� N�� � �I�
���__�__ _�� �i���;����a�����+_ _�`� f��� �e�_._ �� , �,� � . ' ��:___�_.��
,
�` ?�_ �������� ����r����€������.�......._.�'��� ��.� � ; �� � �o .�
• �Q f �€�L�t�=f r�;*,+���_ � '�a� �.___ � 4 �� � �� �
�' S� ,a..e � �1-��'ii��;�l��iu� � _�. '�fi�� ���-_ �.�. � �� � ��
�.. _� _ ,»,
* �'��+J ,_.��L��=:�k,��ti�rkt��il,_ . ��r�� �� �_t ,���� � ��,� .
_w_. � - -
��:� `��� Y_ .. ��.i������ µ 'Y�� � �,d � A� 1 .��.-, �
_:r.�,.,.� � . s
�" ��1 � �tAf�-il.�t�ie�sa�t��n_f�f�-�...,.,,.,,� �Yd� ��.,.�.,_. :j }��.��� ;~ ���,._ a
�______._.� _,__. _ .
� �.
• 2� � C�i,�h� EL�ri�F,1�Nt�� �'��� � � �'u. � �� F�+�.._... _..J
* �9�u ���L��•����i �..M-- ����� -.. �i�...._-.�.��-.M �� 4
__� .��,�__
�
�� i�2� i�IR� �4n�� _. _ m._ -�'��� I � 9� �� �I�
__ �-�- _�. ��� � � _.��_�_._.. �_...�. -
�" � t�l —
�_._ 1�3t3.� _._,.M:l f�l�utt���,��! �_ ���� �F$ ,� l_ � I�P � __. h��i: n
l_`._ � 3�� � �JI��I���`���I ..�,.�- }Y�� � � �-__-�- t �� �.�.._ ��__� ..��_.!
_ ___ -� �
�*�_ 53�_ � �LtS�--T�r��i �t�i �'��� �� .,�.. 9 � �� �� i
__ �._ . ��.
�' �ac� __i�LI��I h�r��i 4�1f� ._-a 1fe� � ,_ l� �,P �J�
w_ _ ,,,
, ��9�,u_ ( qLk�h1_�'�iv1E�_�t� � � Y�� � �t � �AP t�'..r�fda�.�
�"� 5�� �trAhl-�i�lA���1�3 _'� � � i��� �€3 �� �� �A� �t�....,..� �
_. .���.� r _r
�_ �. p .�_�.�._..._.�._._. --
• �0 �l,t����in�l Y� �,,.�._.�-.n �� � RI�
�..._,. .�.._..__. __�_._._.. n „-�-� _ -��..-. .
'�4��f��r�ai€c�;d'�
���� �
Community Development Department
75 South Frontage Road
Vail, Colorado USA 81657
,.
CERTIFICATE OF OCCUPANCY
This certificate is issued pursuant to the requirements of Title 10, Section 10 -1 -2, ADOPTED CODES of the Vail Town
Code certifying that, at the time of issuance, this structure was found to be substantially in compliance with the various
ordinances of the town regulating building construction or use for the following:
Name and description of project SECONDARY SIDE/ SOUTH SIDE OF DUPLEX
Address of project: 1456 WESTHAVEN CIRCLE
Owner name and address 1456 VAIL LLC, PO BOX 745 VAIL CO. 81658
IBC Edition: 2009 Occupancy Group(s): R3 Type(s) of Construction: VB
Permit Number(s): B11 -0068 Occupant Load:_ Sprinkler System Y/ N Type: -13
2S Z.
Martin Haeberle, Chief Building Official Date
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
MR OF oyta
Town of Vail, Community Development, 75 South Frontage Road, Vail, Colorado 81657
p. 970.479.2139, f. 970.479.2452, inpsections 970.479.2149
COMBINATION BLDG PERMIT Permit #: B11 -0068
Job Address
Location......
Parcel No....
OWNER 1456 VAIL LLC
PO BOX 745
VAIL
CO 81658
APPLICANT SUNDER INC
PO BOX 1393
EDWARDS
CO 81632
License: 789 -B
CONTRACTOR SUNDER INC
PO BOX 1393
EDWARDS
CO 81632
License: 789 -B
1456 WESTHAVEN CR VAIL
SECONDARY SIDE /SOUTH SIDE
210312402006
04/18/2011
04/18/2011 Phone: (970) 926 -2777
04/18/2011 Phone: (970) 926 -2777
Description:
NEW SECONDARY SIDE /SOUTH SIDE
Occupancy: R -3 Type Construction: VB
Project #:
Applied.....:
Issued...
PRJ11 -0117
04/18/2011
07/20/2011
Valuation: $930,600.00
........................ . .................. ...............................
FEE SUMMARY ,,,,......,,,.....,,».....,....,......... ..............,.,.......,,..,..
Building Permit ------ - - - - ->
$5,281.00
Bldg Plan Check ----- - - - - -> $3,432.65
Use Tax Fee------------------ - - - - ->
$18,412.00
Electrical Permit ---- - - - - ->
$391.00
Elec Plan Check ------ - - - - -> $254.15
Restuarant Plan Review--- - - - - ->
$0.00
Mechanical Permit - - - - - ->
$1,120.00
Mech Plan Check ---- - - - - -> $280.00
Additional Fees--------------- - - - - ->
$0.00
Plumbing Permit --- - - - - ->
$900.00
Plmb Plan Check ---- - - - - -> $225.00
Recreation Fee--------------- - - - - ->
$507.60
Investigation------------------ - - - - ->
$0.00
Will Call ------------------------------ >
$20.00
TOTAL PERMIT FEES --- ---------- >
$30,933.40
Payments -- ---------------------------- >
$30,933.40
BALANCE DUE------------------ - - - - ->
$0.00
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information
as required is correct. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure
according to the town's zoning and subdivision codes, design review approved, International Building and Residential Codes and other ordinances of the Town
applicable thereto.
REQUESTS FO INSP�TION SHALL BE
8:00 AM - 4�6 PM.
Signature of Owner or C tractor
Print
combination permit_012811
TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROM
Dat
T T1 N 001
RR** fifififififi* RfififiRR* RRRR* R* R***** fifififififififififififififi* fiRRRRR** RR* RRfiRfifififififififiRfifiR*** k* RRRfi* fi* fififi* fiRRfififi* RfiRRRRR* RRRRRR* R** fififififififi* R* RR* R* R* fififififififi *fiRRRRRRRR * * * * * *fififififiRRRRR ** *fifi * *fififiRRRRRRR
CONDITIONS OF APPROVAL TO BE MET PRIOR TO FINAL SIGN OFF
Permit #: B11 -0068 Address: 1456 WESTHAVEN CR VAIL
Owner: 1456 VAIL LLC Location: SECONDARY
SIDE /SOUTH SIDE
* RRRRRRRRR** fi** fi *fififififififififififiRRRR *RxRRRRRRR * * ** fifi *fififiR *Rfifi fifi *fiRR *RRRRRR *fifi* fifififififififi *RRRRRRRRRRR * * * * * * * * * *fi *fi * * *fiRR fifi* RR *RRRR * *fifififiRfiRfifiRRRRRRRR * * * * ** fifi* fifi *fiRfiRRRRRR * *fifififififiRR *RRRRRfiR
Cond: CON0011944
Prior to footing inspection, the applicant shall submit
revised plans lowering the roof pitch to comply with the 33
foot building height limit.
Entry: 06/17/2011 By: bgibson Action: AP
combination permit_012811
OVARLTON
Permit #: 611 -0068
Owner: 1456 VAIL LLC
SIDE /SOUTH SIDE
REQUIRED INSPECTIONS AND STATUSES
Address: 1456 WESTHAVEN CR VAIL
Location: SECONDARY
Item: 00010 BLDG - FOOTING
06/16/2011 By: JRM Action: AP Comments:
SECONDARY SIDE FOOTERS COMPLETE
07/11/2011 By: sgremmer Action: PI Comments: see
highlighted plans for progress
Item: 00020 BLDG - Foundation /Steel
06/29/2011 By: sgremmer Action: AP Comments: see
highlighted plans for progress
07/11/2011 By: sgremmer Action: PI Comments: see
highlighted plans for progress
Item: 00110 ELEC- Service
Item: 00120 ELEC -Rough
Item: 00140 ELEC -Misc.
Item: 00200 MECH -Rough
Item: 00310 MECH- Heating
Item: 00320 MECH- Exhaust Hoods
Item: 00330 MECH - Supply Air
Item: 00340 MECH -Misc.
Item: 00210 PLMB- Underground
Item: 00220 PLMB- Rough /D.W.V.
Item: 00230 PLMB- Rough/Water
Item: 00240 PLMB -Gas Piping
Item: 00260 PLMB -Misc.
Item: 00224 FIRE -ALARM ROUGH
Item: 00225 FIRE - SPRINKLER ROUGH
Item: 00030 BLDG - Framing
Item: 00050 BLDG - Insulation
Item: 00060 BLDG - Sheetrock Nail
Item: 00070 BLDG -Misc.
Item: 00022 PLAN -ILC FRAMING
Item: 00021 PLAN -ILC Foundation Plan
Item: 00190 ELEC -Final
Item: 00228 FIRE - Final
Item: 00290 PLMB -Final
Item: 00390 MECH -Final
Item: 00530 BLDG -Temp. C/O
Item: 00540 BLDG -Final C/O
Item: 00534 PLAN - FINAL C/O
Item: 00090 BLDG -Final
combination permit_012811
TOWN OF VAIL, COLORADO Statement
Statement Number: R110000812 Amount: $110.00 07/20/201112:07 PM
Payment Method:Credit Crd Init: SAB
Notation: MC - JOHN
�yiliU)al ii►_ \ih7
-----------------------------------------------------------------------------
Permit No: Bll -0068 Type: COMBINATION BLDG PERMIT
Parcel No: 2103- 124 - 0200 -6
Site Address: 1456 WESTHAVEN CR VAIL
Location: SECONDARY SIDE /SOUTH SIDE
Total Fees: $30,933.40
This Payment: $110.00 Total ALL Pmts: $30,933.40
Balance: $0.00
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------- - - - - -- ------------------------ - - - - -- ------ - - - - --
PF 00100003112300 PLAN CHECK FEES 110.00
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
MO OF
Town of Vail, Community Development, 75 South Frontage Road, Vail, Colorado 81657
p. 970.479.2139, f. 970.479.2452, inpsections 970.479.2149
COMBINATION BLDG PERMIT Permit #: B11 -0068
Job Address: 1456 WESTHAVEN CR VAIL
Location......: SECONDARY SIDE /SOUTH SIDE
Parcel No....: 210312402006
OWNER 1456 VAIL LLC
PO BOX 745
VAIL
CO 81658
APPLICANT SUNDER INC
PO BOX 1393
EDWARDS
CO 81632
License: 789 -B
CONTRACTOR SUNDER INC
PO BOX 1393
EDWARDS
CO 81632
License: 789 -B
04/18/2011
04/18/2011 Phone: (970) 926 -2777
Description:
NEW SECONDARY SIDE /SOUTH SIDE
04/18/2011 Phone: (970) 926-2777
Occupancy: R -3 Type Construction: VB
Project #:
Applied.....:
Issued...:
PRJ11 -0117
04/18/2011
05/20/2011
Valuation: $930,600.00
..... .............. .. ................. »..,........�. ..._.....,,, ... ,,..... FEE SUMMARY .........,= a.................,.... ..,.......,..,...,.,.........., ...,.........
Building Permit ------ - - - - ->
$5,281.00
Bldg Plan Check ----- - - - - ->
$3,432.65
Use Tax Fee------------------ - - - - ->
$18,412.00
Electrical Permit ---- - - - - ->
$391.00
Elec Plan Check ------ - - - - ->
$254.15
Restuarant Plan Review--- - - - - ->
$0.00
Mechanical Permit - - - - - ->
$1,120.00
Mech Plan Check ---- - - - - ->
$280.00
Additional Fees--------------- - - - - ->
$0.00
Plumbing Permit --- - - - - ->
$900.00
Plmb Plan Check ---- - - - - ->
$225.00
Recreation Fee--------------- - - - - ->
$507.60
Investigation------------------ - - - - ->
$0.00
Will Call ------------------------------ >
$20.00
TOTAL PERMIT FEES -- ----------- >
$30,823.40
Payments -- ---------------------------- >
$30,823.40
BALANCE DUE------------------ - - - - ->
$0.00
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information
as required is correct. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure
according to the town's zoning and subdivision codes, design review approved, International Building and Residential Codes and other ordinances of the Town
applicable thereto. -1--,
REQUESTS FOR INSPECTION
8:00 AM - 4:00 PM. `y
Signature of Owner
Print N<
combination permit_012811
E TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROM
S-170111
Date
•, rxxxxxxxx, r,. wxwrwxwxxxxxxxxxxwxxwrnx; rxxxxxxxxxxxxxwxxxxxxxxxxxxxxxxxxxrxxrrwr.« vrvrxv. vrwxxxxxxxxxxxxxx, rxr+ xr. v. xxrrxxxxx+ xxxxxxxxxxxxw, rx> v.+ xe «wwxrxxxxxxxxxxxxxxxxxxxxxxxxxx +xxx+ +xxx +rxxv.xx+
CONDITIONS OF APPROVAL TO BE MET PRIOR TO FINAL SIGN OFF
Permit #: 1311 -0068 Address: 1456 WESTHAVEN CR VAIL
Owner: 1456 VAIL LLC Location: SECONDARY
SIDE /SOUTH SIDE
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx xxx. xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
Cond: CON0011944
Prior to footing inspection, the applicant shall submit
revised plans lowering the roof pitch to comply with the 33
foot building height limit.
combination permit_012811
WN OVAIL
Permit #: B11 -0068
Owner: 1456 VAIL LLC
SIDE /SOUTH SIDE
REQUIRED INSPECTIONS AND STATUSES
Address: 1456 WESTHAVEN CR VAI L
Location: SECONDARY
Item: 00010 BLDG - FOOTING
Item: 00020 BLDG - Foundation /Steel
Item: 00110 ELEC - Service
Item: 00120 ELEC -Rough
Item: 00140 ELEC -Misc.
Item: 00200 MECH -Rough
Item: 00310 MECH- Heating
Item: 00320 MECH- Exhaust Hoods
Item: 00330 MECH - Supply Air
Item: 00340 MECH -Misc.
Item: 00210 PLMB- Underground
Item: 00220 PLMB- Rough /D.W.V.
Item: 00230 PLMB- Rough/Water
Item: 00240 PLMB -Gas Piping
Item: 00260 PLMB -Misc.
Item: 00224 FIRE -ALARM ROUGH
Item: 00225 FIRE - SPRINKLER ROUGH
Item: 00030 BLDG - Framing
Item: 00050 BLDG - Insulation
Item: 00060 BLDG - Sheetrock Nail
Item: 00070 BLDG -Misc.
Item: 00022 PLAN -ILC FRAMING
Item: 00021 PLAN -ILC Foundation Plan
Item: 00190 ELEC -Final
Item: 00228 FIRE - Final
Item: 00290 PLMB -Final
Item. 00390 MECH -Final
Item. 00530 BLDG -Temp. C/O
Item: 00540 BLDG -Final C/O
Item: 00534 PLAN - FINAL C/O
Item: 00090 BLDG -Final
combination permit_012811
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
TOWN OF VAIL, COLORADO
Statement
************************************************************* * * * * * * * * * * * *
* * * * * * * * * * * * * * * * * **
Statement Number:
R110000512 Amount: $30,823.4005/20 /201102:02 PM
Payment Method:
Check Init: SAB
Notation:
11475 SUNDER
INC
-----------------------------------------------------------------------------
Permit No:
Bll -0068 Type: COMBINATION BLDG PERMIT
Parcel No:
2103 -124- 0200 -6
Site Address:
1456 WESTHAVEN CR VAIL
Location:
SECONDARY SIDE /SOUTH SIDE
Total Fees:
$30,823.40
This Payment:
$30,823.40 Total ALL Pmts:
$30,823.40
Balance:
$0.00
ACCOUNT ITEM LIST:
Account Code
--------------
Description
Current Pmts
- - -
00100003111100, GFPO
- -- ------------------------ - - - - --
ELEC PERMIT FEES- GFP012
------ - - - - --
323.00
BP 00100003111100
BUILDING PERMIT FEES
5,281.00
EP 00100003111100
ELECTRICAL PERMIT FEES
68.00
MP 00100003111100
MECHANICAL PERMIT FEES
1,120.00
PF 00100003112300
PLAN CHECK FEES
4,191.80
PP 00100003111100
PLUMBING PERMIT FEES
900.00
RF 11100003112700
RECREATION FEES
507.60
UT 11000003106000
USE TAX 4%
18,412.00
WC 00100003112800
WILL CALL INSPECTION FEE
20.00
May 17, 2011
Mr. Bill Gibson
Town of Vail
Department of Community Development
75 South Frontage Road West
Vail, CO 81657
RE: JAFFE DUPLEX, LOT 3, 1456 WESTHAVEN, VAIL, CO
Dear Bill:
In response to your May 17, 2011 e -mail regarding the building
height of the duplex, we will be revising all 8:12 roof pitches to
7 1/2:12. This revision will keep all effected ridge heights below
the 33 feet height limit. We will adjust our drawings and copy
you on the revisions.
Also included is the May 5, 2011 report prepared by HP
Geotech addressing the debris flow conditions.
Please let me know if you have any further questions. We look
forward to getting started with construction.
Sincerely,
SEGERBERG, MAYHEW & ASSOCIATES, ARCHITECTS
Kurt A. Segerberg, A.I.A.
President
KAS /Irt
enc.
MAY 18 2011
TOWN OF VAIL
Segerberg, Mayhew & Associates Architects, P.C., A.I.A.
Mail: P.O. Box 4700 Vail, CO 81658 e-mail: info @smarchs.com http: / /www.smarchs.com
Main Office: Eagle -Vail 101 Eagle Road Bldg. 6 Avon, CO 81620 phone: 970 476 4433 fax: 970 476 4608
Denver Office: 12600 West Colfax Avenue, Suite A -140 Lakewood, CO 80215 phone: 303 623 3355 fax: 303 623 2262
DRQII D1y7
►JEE.VOPT14- PAWLAK GEOTEC111%
May 5, 2011 FMAY Tom Jaffe 1 S 2 011
1815 West Gore Creek Drive, #E
Vail, Colorado 81657
OF VAIL JJob No. 110 364A
Subject: Evaluation of Potential Debris Flow Impacts to Proposed Duplex
Residence, Lot 3, Glen Lyon Subdivision, Westhaven Circle and Greenhill
Court, Vail, Colorado
Dear Mr. Jaffe:
As requested by Kurt Segerberg with Segerberg .Mayhew Architects, we have evaluated
the debris flow conditions at the subject site with respect to the proposed Site Plan dated
April 22, 2011 and more recent rough grading plan provided by Glenn Palmer of Alpine
Engineering on May 3, 2011. We previously conducted a subsoil study for design of
foundations at the site and presented our findings in a report dated November 29, 2010,
Job No. 110 364A.
The proposed building footprint is similar to that shown in our previous report but has
shifted slightly to the west and rotated slightly counterclockwise. The shift and rotation
provides a little more room along the east side to work with grade changes and surface
drainage. The grade change between the uphill Lot 2 and the subject site is proposed to
be handled by a combination of retaining walls and fairly deep swales. We suggested to
Glenn Palmer to revise the upper retaining wall of the spa area to be 1 foot above the
drainage swale for freeboard. The driveway entrance for the uphill, primary unit has been
shifted downhill to the west and the ground floor level has been raised somewhat which
will provide at least one foot of fall from. the building to the drainage pan of Westhaven
Circle. Because potential debris flow impact to the lot will be from uphill across
Westhaven Circle, we recommended that a civil engineer design the grading for the
project. We understand that Alpine Engineering has been retained and is working to
complete the grading plan started by the architect.
The subject site is located in a moderate debris flow hazard area according to Town of
Vail (2000). The potential flood impact to the property is from the drainage basin above
the Glen Lyon Subdivision and flow across the alluvial fan upon which the property is
located. Considering the property location in the lower part of the moderate hazard area,
and that considerable development has occurred uphill in the subdivision, it appears that
the potential impact to the property would be mainly from mud flood rather than debris
flow. Mitigation of this type of flow can usually consist of on-site drainage features to
route the mud flood flows down Westhaven Circle and around the east side of the lot by
Tom Jaffe
May 5, 2011
Page 2
earth berms, well defined swales and retaining structures. We recommend these features
have a minimum depth or height of at least 2 feet and be designed to deflect flows
downhill rather than intercept flows that could cause flow material to backup on the
property. Based on these conditions and the rough grading plan provided by Glenn
Palmer, in our opinion, the grading plan and building layout for the project can be
designed such that the development will not increase the hazard to adjacent public or
private properties including buildings, structures and road and utility right -of -ways.
If you have any questions or need further assistance, please call our office.
Sincerely,
HEPWORTH — PAWLAK G&kQCHNICAL, INC.
a r at
Steven L. Pawlak, P. F 2 " ` ;
Rev. by: DEH ? ,t'l;a iorrt�t U:ot
SLPJksw
cc: Segerberg Mayhew Architects — Kurt Segerberg (kse erbergsmarchs.corn)
Reference:
Town of Vail, 2000, Ojjicaal Debris Flow Hazard Map, Town of Vail, prepared by Town
of Vail, Vail, Colorado (adopted by Town Council on October 17, 2000).
Alpine Engineering — Glenn Palmer, PE �alil�erulecivil.ct�_m)
Job No. i 10 364x1
TFfech
May 9, 2011
Mr. Martin Haeberle
Chief Building Official
Town of Vail
75 South Frontage Road West
Vail, CO 81657
RE: JAFFE DUPLEX, LOT 3, 1456 WESTHAVEN, GLEN LYON SUBDIVISION, RESPONSE
TO BUILDING DEPARTMENT COMMENTS DATED APRIL 14, 201 1.
Dear Martin:
Per your request, enclosed are four sets of revised construction documents. The
most notable changes to the duplex have been the modifications to the site and
grading plan and some slight adjustments to the primary and secondary floor
elevations. We raised the entry level and upper level of the primary unit by 1' -6 ".
The primary entry drive was moved to the west to provide better drainage for this
unit. The secondary unit was raised 6" and a site retention wall system is being
designed for the east side of the secondary unit. The building footprint locations
on the site remain the same.
The revisions and responses to your April 14, 2011 letter are as follows:
Architectural Comments:
1. Heat tape will be used on all gutters and downspouts. See note on Sheet
A1.0 snow fence retention devices will not be used.
2. Attic ventilation will be provided though gable roof at secondary unit. See
Sheet A5.1. Five hundred (500) square feet will be ventilated with a
minimum vent size of 1.6 square feet per 1203.2 IBC.
3. Attic access will be provided as shown on Sheet A3.4.
Sheet Survev:
1. Attached are four stamped surveys as revised by Eagle Valley Engineering
per Public Works request dated April 5, 2011.
Sheet A2.0:
The grading plan has been reviewed by Alpine Engineering and HP
Geotechnical Inc. The plan has addressed the moderate debris hazard
flow.
Segerberg, Mayhew & Associates Architects, P.C., A.I.A.
Mail: P.O. Box 4700 Vail, CO 81658 e-mail: info @smarchs.com http: / /www.smarchs.com
Main Office: Eagle -Vail • 101 Eagle Road, Bldg. 6 Avon, CO 81620 • phone: 970 476 4433 • fax: 970 476 4608
Denver Office: 12600 West Colfax Avenue, Suite A- 40 Lakewood, CO 80215 phone: 303 623 3355 fax: 303 623 2262
Mr. Martin Haeberle
May 9, 2011
Page Two
2. Retaining walls will be reviewed by structural engineer and geotechnical
engineer. Design is being coordinated.
Sheet A7.0:
1. Party wall has been extended to under side of roof sheathing. See Detail
4/A7.0.
2. Gable separation requires 5/8" Type "X" Gyp. Bd. at ceiling and wall
separations. See Detail 1 /A6.0.
3. Regarding spa cover, see Detail 5/A7.0. Also see attached Specification.
Spa to be provided by "Hot Springs Company ".
Sheet A8.0:
1. All windows and glazed doors to have .30 U.factor. See Window Schedule
note Sheet A8.0.
2. See stone veneer attachment clarification note on masonry addendum
Detail 1 W.O.
3. See note for weep location in stone veneer. Detail 1 W.O.
Sheet A8.1:
1. See clarification for corner insulation detail 14/A8.1 and 15/ A8.1.
Sheet A9.0 thru 9.4:
l . See notes on Sheet A9.0 and A9.3 of Electrical Plans for locating permanent
certificate per ResCheck requirement.
2. See located carbon monoxide detectors on Electrical Plans. Typical shown
outside all bedrooms. Sheets 19.0, A9.2, A9.3 and A9.4.
Structural Comments:
1. See attached response dated April 18, 2011 from S.A. Miro Structural
Engineers.
Mr. Martin Haeberle
May 9, 2011
Page Three
2. Foundation drainage will be reviewed during the excavation and
foundation work. Generally, drainage will be installed at all perimeter
footings.
Plumbing Comments:
I . Please refer to civil engineering drawings and notes.
Mechanical Comments:
l . See Mechanical Sheet A3.0.
Electrical Comments:
1. See notes on Sheet A9.0 by New Electrical.
2. See notes on Sheet A9.0 by New Electrical.
3. See notes on Sheet A9.0 by New Electrical.
Load Calculations:
1. See attached load calculations per 220 -80 for heat tape.
Please let me know if you need any further clarifications. We look forward to
getting started with construction.
Sincerely,
SEGERBERG, MAYHEW & ASSOCIATES, ARCHITECTS
Kurt A. Segerberg, A.I.A.
President
KAS /Irt
enc.
cc: Bill Gibson
P.O. Box 4700
VAIL, COLORADO 81658
(970) 476 -4433
Fax (970) 476 -4608
TO Martin Haeberle
Chief Building Official
Town of Vail
75 South Frontage Road West
Vail, CO 81657
WE ARE SENDING YOU ® Attached
❑ Shop drawings ® Prints
❑ Copy of letter ❑ Change order
LETTER OF TRANSMITTAL
DATE 05 -09 -11 JOB No. 33006.00
ATTENTION Martin
RE: Jaffe Duplex — Lot 3 Permit Set
❑ Under separate cover via the following items:
❑ Plans ❑ Samples ❑ Specifications
❑ Transparencies
COPIES I DATE I NO. I DESCRIPTION
4 05 -03 -11 1 1 Jaffe Duplex — Lot 3 Permit Set 05 -03 -11
❑ For approval
❑ Approved as submitted
❑ Resubmit copies for approval
® For your use
❑ Approved as noted
❑ Submit copies for distribution
❑ As requested
❑ Returned for corrections
❑ Return corrected prints
❑ For review and comment
❑
❑ FOR BIDS DUE
❑ PRINTS RETURNED AFTER LOAN TO US
REMARKS
COPY TO File
SIGNED: Kurt
If enclosures are not as noted, kindly notify us at once
[E [Eae[ED
MAY 10 2011
TOWN OF VAIL
G( HP
h
HEPWORTH- PAWLAK GEOTECHNICAL
May 5, 2011
Hepkorth -Paw IA Geotechnical; Inc.
5070 County Reti d 154
Getrncxxi Springs, Colorado 81601
Phone: 970 -945 -7988
Fax: 970-945,8454
email: 11pRet4hNeolecle c,M,
Tom Jane
1815 West Gore Creek Drive, #E
Vail, Colorado 81657
Job No. 110 364A
Subject: Evaluation of Potential Debris Flow Impacts to Proposed Duplex
Residence, Lot 3, Glen Lyon Subdivision, Westhaven Circle and Greenhill
Court, Vail, Colorado
Dear Mr. Jaffe:
As requested by Kurt Segerberg with Segerberg Mayhew Architects, we have evaluated
the debris flow conditions at the subject site with respect to the proposed Site Plan dated
April 22, 2011 and more recent rough grading plan provided by Glenn Palmer of Alpine
Engineering on May 3, 2011. We previously conducted a subsoil study for design of
foundations at the site and presented our findings in a report dated November 29, 2010,
Job No. 110 364A.
The proposed building footprint is similar to that shown in our previous report but has
shifted slightly to the west and rotated slightly counterclockwise. The shift and rotation
provides a little more room along the east side to work with grade changes and surface
drainage. The grade change between the uphill Lot 2 and the subject site is proposed to
be handled by a combination of retaining walls and fairly deep swales. We suggested to
Glenn Palmer to revise the upper retaining wall of the spa area to be 1 foot above the
drainage swale for freeboard. The driveway entrance for the uphill, primary unit has been
shifted downhill to the west and the ground floor level has been raised somewhat which
will provide at least one foot of fall from the building to the drainage pan of Westhaven
Circle. Because potential debris flow impact to the lot will be from uphill across
Westhaven Circle, we recommended that a civil engineer design the grading for the
project. We understand that Alpine Engineering has been retained and is working to
complete the grading plan started by the architect.
The subject site is located in a moderate debris flow hazard area according to Town of
Vail (2000). The potential flood impact to the property is from the drainage basin above
the Glen Lyon Subdivision and flow across the alluvial fan upon which the property is
located. Considering the property location in the lower part of the moderate hazard area,
and that considerable development has occurred uphill in the subdivision, it appears that
the potential impact to the property would be mainly from mud flood rather than debris
flow. Mitigation of this type of flow can usually consist of on -site drainage features to
route the mud flood flows down Westhaven Circle and around the east side of the lot by
Parker 303-841-7119 • Colorado Springs 719 -633- 5562 • Silverthorne 970 -468 -1989
Tom Jaffe
May 5, 2011
Page 2
earth berms, well defined swales and retaining structures. We recommend these features
have a minimum depth or height of at least 2 feet and be designed to deflect flows
downhill rather than intercept flows that could cause flow material to backup on the
property. Based on these conditions and the rough grading plan provided by Glenn
Palmer, in our opinion, the grading plan and building layout for the project can be
designed such that the development will not increase the hazard to adjacent public or
private properties including buildings, structures and road and utility right -of -ways.
If you have any questions or need further assistance, please call our office.
Sincerely,
HEPWORTH – PAWLAK GE CHNICAL, INC.
�N�L. P
1i. s • .
Steven L. Pawlak, P. gyp. 5222
o�o5'f� /CIS
Rev, by: DEH "-%.. `S'SONA L�;•St�Qq�
SLP/ksw
cc: Segerberg Mayhew Architects – Kurt Segerberg (ksegerbg1rQo-,marclis.com)
Reference:
Town of Vail, 2000, Official Debris F1owHazard Map, Toitn of Pail, prepared by Town
of Vail, Vail, Colorado (adopted by Town Council on October 17, 2000).
Alpine Engineering – Glenn Palmer, PE (palmer (alpiiecivil com)
Job No. 110 364A
GecStech
April 18, 2011
Kurt Segerberg
Segerberg Mayhew Architects
101 Eagle Road, Bldg. 6
Avon, CO 81620
Denver RE: Jaffe Duplex — Lot 3 Glen Lyon
TOV Building Department Review Comment Responses
Abu Dhabi S. A. Miro Project No. 10 -146
Summit County
Dear Kurt:
Architecture
Engineering Following are my responses to the Town of Vail building department review comments dated April
Project Management 14, 2011 related to the structural drawings.
Sheet S1.0
1. Both continuous and periodic special inspections of the soils are included in the schedule of
special inspections. These are listed in Table 1704.7 near the bottom of the sheet. We have
reviewed the soils report and it appears that the inspections listed in this table satisfy the
requirements of the soils report.
2. Additional information pertaining to the reporting of discrepancies has been added to the
statement of special inspections.
3. Owner /Contractor to address.
4. Concrete general note "A" has been revised to indicate ACI 318 -08.
Sheet S2.0
1. Architect to address.
Soils Report
1. The requirement for inspection of the bearing soils is shown in Table 1704.7 on sheet S1.0.
2. Architect to address.
3. Architect to address.
If you have any questions please call.
Sincerely,
S. A. Miro, Inc.
Steven J. Marshall, P.E, S.E.
Associate
S. A. MIRO,, INC. www.samiro.com 610 :Main St_ Suite 11, Frisco, CO 970 - 668 -0747
CNJ(REScheck Software Version 4.4.0
Compliance Certificate
Project Title: Jaffe Duplex
Energy Code:
2009 IECC
49.0
Location:
Vail, Colorado
Orientation: Unspecified
Construction Type:
Single Family
0.0
Building Orientation:
Bldg. orientation unspecified
1692
Glazing Area Percentage:
26%
Heating Degree Days:
9248
Climate Zone:
6
Orientation: Unspecified
Construction Site:
Owner /Agent:
Designer /Contractor:
Lot 3
Glen Lyon Division
Tom Jaffe
Kurt Segerberg
Vail, CO 81658
Segerberg Mayhew & Associates
Orientation: Unspecified
P.O. Box 4700
0.500
68
Vail, CO 81658
Compliance: 4.8% Better Than Code Maximum UA: 1502 Your UA: 1430
The % Better or Worse Than Code index reflects how close to compliance the house is based on code trade -off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
- - -,
Wall 1: Wood Frame, 16" D.C.
401113
49.0
0.0
100
Orientation: Unspecified
7425
21.0
0.0
306
Window 2: Wood Frame:Double Pane with Low -E
1692
SHGC: 0.26
0.300
508
Orientation: Unspecified
Door 1: Solid
135
Orientation: Unspecified
0.500
68
Door 2: Glass
222
SHGC: 0.21
0.300
67
Orientation: Unspecified
Basement Wall 1: Solid Concrete or Masonry
695
Orientation: Unspecified
15.0
0.0
33
Wall height: 10.0'
Depth below grade: 10.0'
Insulation depth: 10.0'
Floor 1: All -Wood Joist/Truss:Over Unconditioned Space
1180
Floor 2: All -Wood Joist/Truss:Over Outside Air
38.0
0.0
31
Floor 3: Slab- On- Grade:Unheated
125
38.0
0.0
3
Insulation depth: 4.0'
210
5.0
156
Floor 4: Slab -On- Grade: Heated
212
Insulation depth: 4.0'
5.0
158
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed buildin has been designed to meet the 2009 IECC requirements in
�REScheck Version 4.4.0 and to comply with the mandatory requAW:9; sp tion Checklist.
��" �• �'cEFd� -g, fir. Name -Title Dat
Project Title: Jaffe Duplex
Data filename: F: \prj \jaffe2- Lot3FromSarah\ Archive \Progressl2- 16- 10 \ResCheck \Jaffe- Lot3.rck Report date: 02/15/11
Page 1 of 4
CNJ(
Ceilings:
REScheck Software Version 4.4.0
Inspection Checklist
❑ Ceiling 1: Cathedral Ceiling (no attic), R-49.0 cavity insulation
Comments:
Above -Grade Walls:
❑ Wall 1: Wood Frame, 16" o.c., R -21.0 cavity insulation
Comments:
Basement Walls:
❑ Basement Wall 1: Solid Concrete or Masonry, 10.0' ht / 10.0' bg / 10.0' insul, R -15.0 cavity insulation
Comments:
Windows:
❑ Window 2: Wood Frame:Double Pane with Low -E, U- factor: 0.300
For windows without labeled U- factors, describe features:
#Panes Frame Type Thermal Break? Yes No
Comments:
Doors:
❑ Door 1: Solid, U- factor: 0.500
Comments:
Up to 40 sq.ft. of this door is exempt from the U- factor requirement.
❑ Door 2: Glass, U- factor: 0.300
Comments:
Floors:
❑ Floor 1: All -Wood Joist/Truss:Over Unconditioned Space, R -38.0 cavity insulation
Comments:
Floor insulation is installed in permanent contact with the underside of the subfloor decking.
❑ Floor 2: All -Wood J oist/Truss: Over Outside Air, R -38.0 cavity insulation
Comments:
Floor insulation is installed in permanent contact with the underside of the subfloor decking.
❑ Floor 3: Slab- On- Grade:Unheated, 4.0' insulation depth, R -5.0 continuous insulation
Comments:
Slab insulation extends down from the top of the slab to at least 4.0 ft. OR down to at least the bottom of the slab then horizontally for a
total distance of 4.0 ft.
❑ Floor 4: Slab -On- Grade: Heated, 4.0' insulation depth, R -5.0 continuous insulation
Comments:
Slab insulation extends down from the top of the slab to at least 4.0 ft. OR down to at least the bottom of the slab then horizontally for a
total distance of 4.0 ft.
Air Leakage:
❑ Joints (including rim joist junctions), attic access openings, penetrations, and all other such openings in the building envelope that are
sources of air leakage are sealed with caulk, gasketed, weatherstripped or otherwise sealed with an air barrier material, suitable film or
solid material.
❑ Air barrier and sealing exists on common walls between dwelling units, on exterior walls behind tubs /showers, and in openings between
window /door jambs and framing.
❑ Recessed lights in the building thermal envelope are 1) type IC rated and ASTM E283 labeled and 2) sealed with a gasket or caulk
between the housing and the interior wall or ceiling covering.
Project Title: Jaffe Duplex Report date: 02/15/11
Data filename: F: \prj \jaffe2- Lot3FromSarah\Archive \Progress12- 16- 10 \ResCheck \Jaffe- Lot3.rck Page 2 of 4
Access doors separating conditioned from unconditioned space are weather- stripped and insulated (without insulation compression or
damage) to at least the level of insulation on the surrounding surfaces. Where loose fill insulation exists, a baffle or retainer is installed
to maintain insulation application.
❑ Wood - burning fireplaces have gasketed doors and outdoor combustion air.
Air Sealing and Insulation:
❑ Building envelope air tightness and insulation installation complies by either 1) a post rough -in blower door test result of less than 7
ACH at 33.5 psf OR 2) the following items have been satisfied:
(a) Air barriers and thermal barrier: Installed on outside of air - permeable insulation and breaks or joints in the air barrier are filled or
repaired.
(b) Ceiling /attic: Air barrier in any dropped ceiling /soffit is substantially aligned with insulation and any gaps are sealed.
(c) Above -grade walls: Insulation is installed in substantial contact and continuous alignment with the building envelope air barrier.
(d) Floors: Air barrier is installed at any exposed edge of insulation.
(e) Plumbing and wiring: Insulation is placed between outside and pipes. Batt insulation is cut to fit around wiring and plumbing, or
sprayed /blown insulation extends behind piping and wiring.
(f) Comers, headers, narrow framing cavities, and rim joists are insulated.
(9) Shower /tub on exterior wall: Insulation exists between showers /tubs and exterior wall.
Sunrooms:
❑ Sunrooms that are thermally isolated from the building envelope have a maximum fenestration U- factor of 0.50 and the maximum
skylight U- factor of 0.75. New windows and doors separating the sunroom from conditioned space meet the building thermal envelope
requirements.
Materials Identification and Installation:
❑ Materials and equipment are installed in accordance with the manufacturer's installation instructions.
❑ Insulation is installed in substantial contact with the surface being insulated and in a manner that achieves the rated R- value.
F-1 Materials and equipment are identified so that compliance can be determined.
❑ Manufacturer manuals for all installed heating and cooling equipment and service water heating equipment have been provided.
❑ Insulation R- values and glazing U- factors are clearly marked on the building plans or specifications.
Duct Insulation:
F-1 Supply ducts in attics are insulated to a minimum of R -8. All other ducts in unconditioned spaces or outside the building envelope are
insulated to at least R -6.
Duct Construction and Testing:
Building framing cavities are not used as supply ducts.
❑ All joints and seams of air ducts, air handlers, filter boxes, and building cavities used as return ducts are substantially airtight by means
of tapes, mastics, liquid sealants, gasketing or other approved closure systems. Tapes, mastics, and fasteners are rated UL 181A or
UL 181 B and are labeled according to the duct construction. Metal duct connections with equipment and /or fittings are mechanically
fastened. Crimp joints for round metal ducts have a contact lap of at least 1 1/2 inches and are fastened with a minimum of three
equally spaced sheet -metal screws.
Exceptions:
Joint and seams covered with spray polyurethane foam.
Where a partially inaccessible duct connection exists, mechanical fasteners can be equally spaced on the exposed portion of the
joint so as to prevent a hinge effect.
Continuously welded and locking -type longitudinal joints and seams on ducts operating at less than 2 in. w.g. (500 Pa).
❑ Duct tightness test has been performed and meets one of the following test criteria:
(1) Postconstruction leakage to outdoors test: Less than or equal to 673.9 cfm (8 cfm per 100 ft2 of conditioned floor area).
(2) Postconstruction total leakage test (including air handler enclosure): Less than or equal to 1010.9 cfm (12 cfm per 100 ft2 of
conditioned floor area) pressure differential of 0.1 inches w.g.
(3) Rough -in total leakage test with air handler installed: Less than or equal to 505.4 cfm (6 cfm per 100 ft2 of conditioned floor area)
when tested at a pressure differential of 0.1 inches w.g.
(4) Rough -in total leakage test without air handler installed: Less than or equal to 337.0 cfm (4 cfm per 100 ft2 of conditioned floor area).
Heating and Cooling Equipment Sizing:
❑ Additional requirements for equipment sizing are included by an inspection for compliance with the International Residential Code.
Cj For systems serving multiple dwelling units documentation has been submitted demonstrating compliance with 2009 IECC Commercial
Building Mechanical and /or Service Water Heating (Sections 503 and 504).
Circulating Service Hot Water Systems:
Project Title: Jaffe Duplex Report date: 02/15/11
Data filename: F: \prj \jaffe2- Lot3FromSarah\ Archive \Progress12- 16- 10 \ResCheck \Jaffe- Lot3.rck Page 3 of 4
• ❑ Circulating service hot water pipes are insulated to R -2.
Lj Circulating service hot water systems include an automatic or accessible manual switch to turn off the circulating pump when the
system is not in use.
Heating and Cooling Piping Insulation:
❑ HVAC piping conveying fluids above 105 degrees F or chilled fluids below 55 degrees F are insulated to R -3.
Swimming Pools:
❑ Heated swimming pools have an on /off heater switch.
LJ Pool heaters operating on natural gas or LPG have an electronic pilot light.
F1 Timer switches on pool heaters and pumps are present.
Exceptions:
Where public health standards require continuous pump operation.
Where pumps operate within solar- and /or waste - heat - recovery systems.
F] Heated swimming pools have a cover on or at the water surface. For pools heated over 90 degrees F (32 degrees C) the cover has a
minimum insulation value of R -12.
Exceptions:
Covers are not required when 60% of the heating energy is from site - recovered energy or solar energy source.
Lighting Requirements:
Fi A minimum of 50 percent of the lamps in permanently installed lighting fixtures can be categorized as one of the following:
(a) Compact fluorescent
(b) T -8 or smaller diameter linear fluorescent
(c) 40 lumens per watt for lamp wattage <= 15
(d) 50 lumens per watt for lamp wattage > 15 and <= 40
(e) 60 lumens per watt for lamp wattage > 40
Other Requirements:
1-1 Snow- and ice - melting systems with energy supplied from the service to a building shall include automatic controls capable of shutting
off the system when a) the pavement temperature is above 50 degrees F, b) no precipitation is falling, and c) the outdoor temperature is
above 40 degrees F (a manual shutoff control is also permitted to satisfy requirement's').
Certificate:
L] A permanent certificate is provided on or in the electrical distribution panel listing the predominant insulation R- values; window
U- factors; type and efficiency of space- conditioning and water heating equipment. The certificate does not cover or obstruct the visibility
of the circuit directory label, service disconnect label or other required labels.
b zo
� NOTES TO FIELD: (Building Department Use Only)
V,
Lon
V
Project Title: Jaffe Duplex Report date: 02/15/11
Data filename: F: \prj \jaffe2- Lot3FromSarah\ Archive \Progress12- 16- 10 \ResCheck \Jaffe- Lot3.rck Page 4 of 4
2009 IECC
Energy
Efficiency
Certificate
Insulation .
Ceiling / Roof
49.00
Wall
21.00
Floor / Foundation
38.00
Ductwork (unconditioned spaces):
Glass & Door Rating
U-Factor SHGC
Window
0.30 0.26
Door
Cooling Heating &
0.30 0.21
Heating System:
Cooling System:
Water Heater:
Name:
Date:
Comments:
i
vs
v�
C
GH
tech
HEPWORTH- PAWLAK GEOTECHNICAL
Hepworth- Pawlak Geotechnical, Inc.
5020 County Road 154
Glenwood Springs, Colorado 81601
Phone: 970-945-7988
Fax: 970-945-8454
email: hpgeo @hpgeotech.com
SUBSOIL STUDY
FOR FOUNDATION DESIGN
PROPOSED DUPLEX
LOT 3, GLEN LYON SUBDIVISION
VAIL, COLORADO
JOB NO. 110 364A
NOVEMBER 29, 2010
PREPARED FOR:
TOM JAFFE
1815 W. GORE CREEK DRIVE, #E
VAIL, COLORADO 81657
Parker 303 -841 -7119 0 Colorado Springs 719- 633 -5562 • Silverthorne 970 - 468 -1989
TABLE OF CONTENTS
PURPOSE AND SCOPE OF STUDY ......................................... ............................... - I -
PROPOSED CONSTRUCTION .................................................. ............................... - 1 -
SITECONDITIONS .................................................................... ............................... - 2-
GEOLOGIC CONDITIONS ........................................................ ............................... - 2 -
FIELDEXPLORATION ............................................................. ............................... - 2 -
SUBSURFACE CONDITIONS ................................................... ............................... - 3 -
DESIGN RECOMMENDATIONS .............................................. ............................... - 3 -
FOUNDATIONS -
FOUNDATION AND RETAINING WALLS .......................... ............................... -4-
FLOORSLABS ....................................................................... ............................... - 6-
UNDERDRAINSYSTEM ....................................................... ............................... -6-
SITEGRADING ..................................................................... ............................... -7-
SURFACE DRAINAGE -
LIMITATIONS........................................................................... ............................... - 8 -
FIGURE 1 - LOCATION OF EXPLORATORY BORINGS
FIGURE 2 - LOGS OF EXPLORATORY BORINGS
FIGURE 3 - LEGEND AND NOTES
FIGURE 4 - SWELL- CONSOLIDATION TEST RESULTS
TABLE 1- SUMMARY OF LABORATORY TEST RESULTS
PURPOSE AND SCOPE OF STUDY
This report presents the results of a subsoil study for a proposed residential duplex to be
located at Lot 3, Glen Lyon Subdivision, Vail, Colorado. The project site is shown on
Figure 1. The purpose of the study was to develop recommendations for the foundation
design. The study was conducted in accordance with our proposal for geotechnical
engineering services to Tom Jaffe dated December 14, 2009.
A field exploration program consisting of exploratory borings was conducted to obtain
information on the subsurface conditions. Samples of the subsoils obtained during the
field exploration were tested in the laboratory to determine their classification,
compressibility or swell and other engineering characteristics. The results of the field
exploration and laboratory testing were analyzed to develop recommendations for
foundation types, depths and allowable pressures for the proposed building foundation.
This report summarizes the data obtained during this study and presents our conclusions,
design recommendations and other geotechnical engineering considerations based on the
proposed construction and the subsurface conditions encountered.
PROPOSED CONSTRUCTION
The proposed duplex will be a three story wood frame structure stepped into the hillside
with a garage on the first level of the secondary unit and the main level of the primary
unit. Garage floors will be slab -on- grade. Grading for the duplex is assumed to be
relatively minor with cut depths between about 4 to 12 feet. We assume relatively light
foundation loadings, typical of the proposed type of construction.
If building loadings, location or grading plans change significantly from those described
above, we should be notified to re- evaluate the recommendations contained in this report.
Job No. 110 364A
GEOrtech
-2-
SITE CONDITIONS
The site was vacant of structures and snow cover was about one foot at the time of our
exploration. Vegetation consists of sage brush, grass and weeds. The site is located on a
north facing hillside and the ground surface slopes down at a grade of about 20 percent in
the building area.
GEOLOGIC CONDITIONS
The site is located on a large alluvial fan that is shown to have moderate hazard debris
flow according to the official Town of Vail maps of geologic hazards adopted October
17, 2000.
FIELD EXPLORATION
The field exploration for the project was conducted on November 12, 2010. Two
exploratory borings were drilled at the locations shown on Figure 1 to evaluate the
subsurface conditions. The borings were advanced with 4 inch diameter continuous flight
augers powered by a track - mounted CME 45 drill rig. The borings were logged by a
representative of Hepworth - Pawlak Geotechnical, Inc.
Samples of the subsoils were taken with a 2 inch I.D. spoon sampler. The sampler was
driven into the subsoils at various depths with blows from a 140 pound hammer falling 30
inches. This test is similar to the standard penetration test described by ASTM Method
D -1586. The penetration resistance values are an indication of the relative density or
consistency of the subsoils. Depths at which the samples were taken and the penetration
resistance values are shown on the Logs of Exploratory Borings, Figure 2. The samples
were returned to our laboratory for review by the project engineer and testing.
Job No. 110 364A GEUf*t@ch
-3-
SUBSURFACE CONDITIONS
Graphic logs of the subsurface conditions encountered at the site are shown on Figure 2.
The subsoils consist of about one foot of topsoil overlying medium dense, silty sand and
gravel with cobbles and probable small boulders. Drilling in the granular soils with auger
equipment was occasionally difficult due to the cobbles and boulders.
Laboratory testing performed on samples obtained from the borings included natural
moisture content, density and percent finer than sand size gradation analyses. Results of
swell- consolidation testing performed on a relatively undisturbed drive sample, presented
on Figure 4, indicate low to moderate compressibility under conditions of loading and
wetting. The laboratory testing is summarized in Table 1.
No free water was encountered in the borings at the time of drilling and the subsoils were
slightly moist to moist.
DESIGN RECOMMENDATIONS
FOUNDATIONS
Considering the subsurface conditions encountered in the exploratory borings and the
nature of the proposed construction, we recommend the building be founded with spread
footings bearing on the natural granular soils below topsoil. The soils could tend to
compress when wetted and precautions should be taken to prevent wetting below the
building. �—
The design and construction criteria presented below should be observed for a spread
footing foundation system.
1) Footings placed on the undisturbed natural granular soils should be
designed for an allowable bearing pressure of 2,000 ps£ Based on
experience, we expect initial settlement of footings designed and
Cp
Job NO. 11U J04A ygtecn
M
constructed as discussed in this section will be about 1 inch or less. There
could be on the order of 1 inch of additional settlement if the bearing soils
FOUNDATION AND RETAINING WALLS
Foundation walls and retaining structures which are laterally supported and can be
expected to undergo only a slight amount of deflection should be designed for a lateral
earth pressure computed on the basis of an equivalent fluid unit weight of at least 50 pcf
for backfill consisting of the on -site granular soils. Cantilevered retaining structures
which are separate from the duplex and can be expected to deflect sufficiently to mobilize
the full active earth pressure condition should be designed for a lateral earth pressure
Job No. 110 364A G(~cPtech
are wetted.
,\\\2)
The footings should have a minimum width of 16 inches for continuous
walls and 2 feet for isolated pads.
3)
Exterior footings and footings beneath unheated areas should be provided
with adequate soil cover above their bearing elevation for frost protection.
Placement of foundations at least 42 inches below exterior grade is
typically used in this area.
4)
Continuous foundation walls should be reinforced top and bottom to span
local anomalies such as by assuming an unsupported length of at least 14
feet. Foundation walls acting as retaining structures should also be
designed to resist lateral earth pressures as discussed in the "Foundation
and Retaining Walls" section of this report.
5)
The topsoil and any loose or disturbed soils should be removed and the
footing bearing level extended down to the relatively dense natural
granular soils. The exposed soils in footing area should then be moistened
and compacted. If water seepage is encountered in footing areas. we,
should be contacted for additional evaluation.
A representative of the geotechnical engineer should observe all footing
excavations prior to concrete placement to evaluate bearing conditions.
FOUNDATION AND RETAINING WALLS
Foundation walls and retaining structures which are laterally supported and can be
expected to undergo only a slight amount of deflection should be designed for a lateral
earth pressure computed on the basis of an equivalent fluid unit weight of at least 50 pcf
for backfill consisting of the on -site granular soils. Cantilevered retaining structures
which are separate from the duplex and can be expected to deflect sufficiently to mobilize
the full active earth pressure condition should be designed for a lateral earth pressure
Job No. 110 364A G(~cPtech
-5-
computed on the basis of an equivalent fluid unit weight of at least 45 pcf for backfill
consisting of the on -site granular soils.
All foundation and retaining structures should be designed for appropriate hydrostatic and
surcharge pressures such as adjacent footings, traffic, construction materials and
equipment. The pressures recommended above assume drained conditions behind the
walls and a horizontal backfill surface. The buildup of water behind a wall or an upward
sloping backfill surface will increase the lateral pressure imposed on a foundation wall or
retaining structure. An underdrain should be provided to prevent hydrostatic pressure
buildup behind walls.
Backfill should be placed in uniform lifts and compacted to at least 90% of the maximum
standard Proctor density at a moisture content near optimum. Backfill in pavement and
walkway areas should be compacted to at least 95% of the maximum standard Proctor
density. Care should be taken not to overcompact the backfill or use large equipment
near the wall, since this could cause excessive lateral pressure on the wall. Some
settlement of deep foundation wall backfill should be expected, even if the material is
placed correctly, and could result in distress to facilities constructed on the backfill.
The lateral resistance of foundation or retaining wall footings will be a combination of the
sliding resistance of the footing on the foundation materials and passive earth pressure
against the side of the footing. Resistance to sliding at the bottoms of the footings can be
calculated based on a coefficient of friction of 0.45. Passive pressure of compacted
backfill against the sides of the footings can be calculated using an equivalent fluid unit
weight of 375 pcf. The coefficient of friction and passive pressure values recommended
above assume ultimate soil strength. Suitable factors of safety should be included in the
design to limit the strain which will occur at the ultimate strength, particularly in the case
of passive resistance. Fill placed against the sides of the footings to resist lateral loads
should be compacted to at least 95% of the maximum standard Proctor density at a
moisture content near optimum.
Job No. 110 364A HPtF_-Ch
W
FLOOR SLABS
The natural on -site soils, exclusive of topsoil, are suitable to support lightly loaded slab -
on- grade construction. There could be some potential for settlement if the bearing soils
are wetted. To reduce the effects of some differential movement, floor slabs should be
separated from all bearing walls and columns with expansion joints which allow
unrestrained vertical movement. Floor slab control joints should be used to reduce
damage due to shrinkage cracking. The requirements for joint spacing and slab
reinforcement should be established by the designer based on experience and the intended
slab use. A minimum 4 inch layer of free - draining gravel should be placed beneath
basement level slabs to facilitate drainage. This material should consist of minus 2 inch
aggregate with at least 50% retained on the No. 4 sieve and less than 2% passing the No.
200 sieve.
All fill materials for support of floor slabs should be compacted to at least 95% of
maximum standard Proctor density at a moisture content near optimum. Required fill can
consist of the on -site granular soils devoid of vegetation, topsoil and oversized rock.
UNDERDRAIN SYSTEM
Although free water was not encountered during our exploration, it has been our
experience in mountainous areas that local perched groundwater can develop during times
of heavy precipitation or seasonal runoff. Frozen ground during spring runoff can create
a perched condition. We recommend below -grade construction, such as retaining walls
and crawlspace areas, be protected from wetting and hydrostatic pressure buildup by an
underdrain system.
The drains should consist of drainpipe placed in the bottom of the wall backfill
surrounded above the invert level with free - draining granular material. The drain should
be placed at each level of excavation and at least 1 foot below lowest adjacent finish
grade and sloped at a minimum I% to a suitable gravity outlet. Free - draining granular
Job No. 110 364A Ge 9tech
-7-
material used in the underdrain system should contain less than 2% passing the No. 200
sieve, less than 50% passing the No. 4 sieve and have a maximum size of 2 inches. The
drain gravel backfill should be at least 1 %2 feet deep. An impervious membrane such as
30 mil PVC liner could be placed below the drain to help prevent wetting below the
building.
SITE GRADING
The risk of construction - induced slope instability at the site appears low provided cut and
fill depths are limited. We assume that cut and fill depths for the lower levels will not
exceed about 10 to 12 feet. Embankment fills should be compacted to at least 95% of the
maximum standard Proctor density near optimum moisture content. Prior to fill
placement, the subgrade should be carefully prepared by removing all vegetation and
topsoil and compacting to at least 95% of the maximum standard Proctor density. The fill
should be benched into the portions of the hillside exceeding 20% grade.
Permanent unretained cut and fill slopes should be graded at 2 horizontal to 1 vertical or
flatter and protected against erosion by revegetation or other means. Potential debris flow
impact will be from across Westhaven Circle and on -site grading should direct potential
flow down Westhaven Circle and around the proposed building on Lot 3. The grading
should be designed by a civil engineer. This office should review site grading plans for
the project prior to construction.
SURFACE DRAINAGE
The following drainage precautions should be observed during construction and
maintained at all times after the duplex has been completed:
1) Inundation of the foundation excavations and underslab areas should be
avoided during construction.
2) Exterior backfill should be adjusted to near optimum moisture and
compacted to at least 95% of the maximum standard Proctor density in
Job No. 110364A GE PtGCh
pavement and slab areas and to at least 90% of the maximum standard
Proctor density in landscape areas.
3) The ground surface surrounding the exterior of the building should be
sloped to drain away from the foundation in all directions. We
recommend a minimum slope of 12 inches in the first 10 feet in unpaved
areas and a minimum slope of 3 inches in the first 10 feet in paved areas.
Free - draining wall backfill should be capped with at least 2 feet of the on-
site soils to reduce surface water infiltration.
4) Roof downspouts and drains should discharge well beyond the limits of all
backfill.
LIMITATIONS
This study has been conducted in accordance with generally accepted geotechnical
engineering principles and practices in this area at this time. We make no warranty either
express or implied. The conclusions and recommendations submitted in this report are
based upon the data obtained from the exploratory borings drilled at the locations
indicated on Figure 1, the proposed type of construction and our experience in the area.
Our services do not include determining the presence, prevention or possibility of mold or
other biological contaminants (MOBC) developing in the future. If the client is
concerned about MOBC, then a professional in this special field of practice should be
consulted. Our findings include interpolation and extrapolation of the subsurface
conditions identified at the exploratory borings and variations in the subsurface
conditions may not become evident until excavation is performed. If conditions
encountered during construction appear different from those described in this report, we
should be notified so that re- evaluation of the recommendations may be made.
This report has been prepared for the exclusive use by our client for design purposes. We
are not responsible for technical interpretations by others of our information. As the
project evolves, we should provide continued consultation and field services during
construction to review and monitor the implementation of our recommendations, and to
CVO rvo. 11U (J4A . ..,
verify that the recommendations have been appropriately interpreted. Significant design
changes may require additional analysis or modifications to the recommendations
presented herein. We recommend on -site observation of excavations and foundation
bearing strata and testing of structural fill by a representative of the geotechnical
engineer.
Respectfully Submitted,
HEPWORTH - PAWLAK GEOTECHNICAL, INC.
Louis E. Eller
Reviewed by:
Steven L. Pawlak, P
LEE /ksw
cc: Segerberg
Job No. 110 364A
15222
�� oAP
BONA
ttn: Kurt Segerberg
GecPtech
BORING 1
ELEV.= 8074'
S1:
:ISI
8075
8070
a�
c
0
0
w
8065
PROPOSED FLOOR LEVEL = 81
30/5,10/0
WC =7.2
DD =103
- 200 =40
50/4
PROPOSED FLOOR LEVEL = 8081'
35/6,15/2 8080
WC =3.2
DD =112
-200=18
40/6,10/1 8075
50/5 8070
WC =4.0
LL
DD =128
- 200 =23
0
C5
a.>
w
50/3 8065
8060 6•uI I 50/5 50/12 8060
8055 1 35/6 ,20/2 8055
WC =5.9
DD =137
- 200 =24
8050 8050
Note: Explanation of symbols is shown on Figure 3.
H
110 364A C7Q LOGS OF EXPLORATORY BORINGS Figure 2
He worth — Powlok Geotechnical
BORING 2
ELEV.= 8084'
:IS
LEGEND:
TOPSOIL; organic sandy clayey silt, moist, dark brown.
SAND AND GRAVEL (SM -GM); silty, cobbles and possible boulder size rock fragments, medium dense,
slightly moist to moist, brown.
Relatively undisturbed drive sample; 2 -inch I.D. California liner sample.
50/12 Drive sample blow count; indicates that 50 blows of a 140 pound hammer falling 30 inches were
required to drive the California sampler 12 inches.
— 0 Depth at which boring had caved after drilling.
NOTES:
1. Exploratory borings were drilled on November 12, 2010 with 4 -inch diameter continuous flight power auger.
2. Locations of exploratory borings were measured approximately by pacing from features shown on the site plan
provided.
3. Elevations of exploratory borings were obtained by interpolation between contours shown on the site plan provided.
4. The exploratory boring locations and elevations should be considered accurate only to the degree implied by the
method used.
5. The lines between materials shown on the exploratory boring logs represent the approximate boundaries between
material types and transitions may be gradual.
6. No free water was encountered in the borings at the time of drilling. Fluctuation in water level may occur with time.
7. Laboratory Testing Results:
WC = Water Content ( %)
DD = Dry Density (pcf)
-200 = Percent passing No. 200 sieve
110364A I Ge0d>teCh I LEGEND AND NOTES I Figure 3
HonwnrAL_D..wL.L n__a__�_e__i
i
Moisture Content = 7.2 percent
Dry Density = 103 pcf
Sample of. Silty Sandy Clay and Gravel
From: Boring 1 at 4 Feet
0
1
Compression
upon
2 wetting
0
0
U)
2 3
a
E
0
U
4
5
0.1 1.0 10 100
APPLIED PRESSURE - ksf
H
110 364A -- [SWELL-CONSOLIDATION TEST RESULTS Figure 4
Hepworth— Pawlak Geotechnical
U
z
J
U
z
U
W
O
' w
V
g
Q
a
Ilz
2
O
a
w
2
Q
M
O
0
z
O
r-,
LO
J
D
W
w
L O
f -
N Q N
m
n
LL
O
}
Q
Z)
cn
w
J
m
LU
«i
«i
O
C d
�
Q
777�
o°
U V)
�
v1
LO
`0
r. M
M
cz
cn �U
V) C7 v) C7 rig C7 v� C7
w
° >_
LL V) (D
Z
LL
� �
Oaf
a
[-
N
::D U
U X
P W
Lo
z
w
m
w �F
Q a
...I J
o
z
ow
W N >
w ¢ O
z
N
N
C)
z
z �
O
a
0
< J
LU
u
Z)
O M
I"
00
C14
zoo r,
_ LU
�z
F -- o
N
00
Z
z =
O Cl.
0
�
O
J
W
a C7
g z
O
m
I
State of Colorado
Asbestos Testing & Abatement Requirements
Asbestos testing and abatement protects workers, homeowners, neighbors and emergency services responders from ex-
posure to harmful asbestos. It is your responsibility to be in compliance with the State. Please contact the State directly
for their requirements at the contact info listed below.
When is asbestos testing required?
ANY building projects disturbing more than these threshold levels of building materials require asbestos testing:
One- and Two - Family Dwellings: 32 square feet
All Others (commercial spaces, hotel rooms, etc): 160 square feet
Definition of a single - family dwelling: any dwelling unit that is used primarily for a single family, including
multi - family /condominium units, and fractional fee units.
Asbestos testing results must be provided with your application for a building permit.
Tests which identify POSITIVE results at more than 1% require abatement by a State - certified abatement contractor. The
air clearance letter or form must be submitted to the Town of Vail before the building permit will be issued.
Project Checklist
My proje falls into the category checked below:
Will not disturb more than the threshold limits identified above.
Tested negative, or at 1% or below (1 copies of test results included)
Tested positive at more than 1 %, requires abatement (1 copies of test results included)
Tips & Facts:
• Even recent construction projects may include asbestos - containing materials, so buildings of gny age require testing.
• The "1989 Ban" on asbestos - containing materials is commonly misunderstood. "In fact, in 1991 the U.S. Fifth Circuit
Court of Appeals vacated much of the so- called "Asbestos Ban and Phaseout" rule and remanded it to the EPA. Thus,
much of the original 1989 EPA ban on the U.S. manufacturing, importation, processing, or distribution in commerce
of many asbestos - containing product categories was set aside and did not take effect." - CDPHE
Asbestos test results should be submitted to: Town of Vail, Community Development, 75 S Frontage Rd, Vail, CO, 81657.
Town of Vail Contact:
Fire Prevention Bureau
Vail Fire Department
75 S Frontage Rd
Fire_ inspectors @vailgov.com
970 - 479 -2252
www.vailgov.com
State of Colorado Contact:
Colorado Department of Public Health
and Environment
Asbestos Compliance Assistance Group
303 - 692 -3158
asbestos@state.co.us
www.cdphe.state.co.us
01- Jan -II
05-31-2012 Inspection Request Reporting Page 1
4:54 pm Vail, CO - City Of
Requested Inspect Date: Friday,June 01, 2012
Site Address: 1456 WESTHAVEN CR VAIL
SECONDARY SIDE/SOUTH SIDE
A/P/D Information
Activity B11-0068 Type: COMBO Sub Type: ADUP Status: ISSUED
Const Type Occupancy: Use: R-3 Insp Area:
Owner 1456 VAIL LLC
Contractor: SUNDER INC Phone: (970)926-2777
Description: NEW SECONDARY SIDE/SOUTH SIDE
Requested Inspection(s)
Item 228 FIRE-Final Requested Time: 08:00 AM
Requestor Phone:
Comments 390-1885
Assigned To ** "*"'" Entered By: MHAEBERLE K
Action Time Exp:
Item 534 PLAN...gli TGO Requested Time: 08:00 AM
Requestor Phone:
Comments 390-1885
Assigned To BGIBSON Entered By: MHAEBERLE K
Action f? r6.,rt4 Time Exp: nr
s ll� (t3 /e45 .�jr /tt'r A c o1
Item 190 ELEC-Final Requested Time: 03:30 PM
Requestor Phone:
Comments 390-1885
Assigned To JMONDRAGON Entered By: MHAEBERLE K
Action Time Exp:
Comment GI-CI in all in mech room
missing recpt at west slider near kitchen
Item 290 PLMB-Final Requested Time: 03:00 PM
Requestor Phone:
Comments 390-1885
Assigned To JMONDRAGON Entered By: MHAEBERLE K
Action Time Exp:
Comment hammer arrestors at all quick closing vavles
vacuum breaker for house bib in mech room
hot and cold reversed at kitchen sink
Item 390 MECH-Final Requested Time: 02:30 PM
Requestor Phone:
Comments 390-1885
Assigned To JMONDRAGON Entered By: MHAEBERLE K
Action Time Exp:
Comment still need a tix for the dryer vents that do meet code
Item 530 BLDG-Temp. C/O Requested Time: 01:30 PM
Requestor Phone:
Comments 390-1885
Assigned To JMONDRAGON Entered By: MHAEBERLE K
Action Time Exp:
REPT131 Run Id: 14452
�
Community Development Department
75 South Frontage Road
Vail, Colorado LISA 81657
TEMPOI�►ARY
CERTIFICATE OF OCCUPANCY
This certificate is issued pursuant to the requirements of Title 10, Section 10-1-2, ADOPTED CODES of the Vail Town
Code certifying that, at the time of issuance, this structure was found to be substantially in compliance with the various
ordinances of the town regulating building construction or use for the following:
Name and description of project Duplex (South Side �
Address of project: 1456 Westhaven Circle
Owner name and address: 1456 Vail LLC PO Box 745 Vail Colorado 81658
IBC Edition: 2009 IBC Occupancy Group(s): R-3 Type(s) of Construction: VB
Permit Number(s) Bl1-0068 Occupant Load:
Expiration Date:_ 6/30/2012
,
1�Iartin aeberle, Building Official
SEE ATTACHED CONDITIONS.
Sprinkler System Y/N Type: 13R
_ 06/01/2012
Date
Project #: r'K.) 1 I"
BUILDING PERMIT APPLICATION
(Separate applications are required for alarm & sprinkler)
Project Street Address:
(Number) (Street) (Suite #)
Building /Complex Name:
Contractor Information
Business Name: �NL
Business Address: K \3
city GS State: CO zip:
Contact Name: Q�
Contact Phone: R �G l i Ee w
-
Contact E -Mail: J 1" 5UAt 0� 0— Ut'��L •
X
Owner /Owner's prp'senta &vo- signature (Required)
Project Information
Owner Name:
h a (Q ^ �
Parcel #: �-►d�� z_ -- Tu �C�Cp
(For Parcel #, contact Eagle County Assessors Office at (970- 328 -8640 or visit
www.eaglecounty.us/patie)
Detailed Scope and Location of Work:
DRB #: 1) I �-_) os 1> Q
Building Permit #: B I I — 0008,
Lot #: 3 Block # Subdivision:
Work Class: New ( Addition ( ) Alteration ( )
Type of Building:
Single - Family ( ) Duplex (Multi- Family ( )
Commercial( ) Other( )
Work Type: Interior ( ) Exterior( ) Both (✓r
Valuatioa-of
6
Work Included
Plans Included Work
Electrical �) es ( )No
(_fes
( )No
Sf 3
Mechanical ( )Yes ( )No
(L -)'?es
( )No
Plumbing &_) ( )No
(/f es
( )No
Building (�'es ( )No
( Yes
( )No E t I Do
(o Ord
Value of all work being performed:
$ `J
(value based on IBC Section 109.3 & IRC Section 108.3)
Electrical Square Footage
3
Department of Community Development
75 South Frontage Road
Vail,. Colorado .81657;
Tel:. 970= 479 - 2128,._
Web: www.vailgov.com
Development Review Coordinator
(use additional sheet if necessary)
For Offr Use Onl Ce � ��
Fee Paid:
Received From:
Cash Check #
CC: Visa / MC Last 4 CC # exp date:
Auth #
Date] D.) Tt�(5 CAJ(5—:
6W Ck FEE Po o�)
Fee Items- B11 -0068 16:21 04/20/2011
Item #
Descri Lion
Fee Amount
Pmt Amount
Balance
Account code
10
BUILDING PERMIT FEES
$5,281.00
$0.00
$5,281.00
BP 00100003111100
20
PLUMBING PERMIT FEES
$900.00
$0.00
$900.00
PP 00100003111100
30
MECHANICAL PERMIT
FEES
$1,120.00
$0.00
$1,120.00
MP
00100003111100
40
ELECTRICAL PERMIT
FEES
($122.00)
$0.00
($122.00)
EP 00100003111100
42
ELEC PERMIT FEES-
GFP012
$513.00
$0.00
$513.00
00100003111100,
GFP012
47
ELEC PLAN REVIEW
$254.15
$0.00
$254.15
PF 00100003112300
80
PLAN CHECK FEES
$3,937.65
$0.00
$3,937.65
PF 00100003112300
140
RECREATION FEES
$0.00
$0.00
$0.00
RF 11100003112700
150
WILL CALL INSPECTION
FEE
$20.00
$0.00
$20.00
WC
00100003112800
160
RESTAURANT PLAN
REVIEW
$0.00
$0.00
$0.00
FS 00100003112400
1205
USE TAX 4%
$18,412.00
$0.00
$18,412.0
0
UT 11000003106000
1210
INVESTIGATION FEE
BLDG
$0.00
$0.00
$0.00
PIN 00100003153000
Total Rows: 12
Page 1
07-24-2012 Inspection Request Reporting Page 3
4:28 pm Vail, CO - City Qf
Requested Inspect Date: Wednesday, July 25,2012
Site Address: 1456 WESTHAVEN CR VAIL
SECONDARY SIDE/SOUTH SIDE
A/P/D Information
Activity B11-0068 Type: COMBO Sub Type: ADUP Status: ISSUED
Const Type Occupancy: Use: R-3 Insp Area:
Owner 1456 VAIL LLC
Contractor: SUNDER INC Phone: (970)926-2777
Description: NEW SECONDARY SIDE/SOUTH SIDE
Requested Inspection(s)
Item: 534 PLAN- FINAL C/O Requested Time 08:15 AM
Requestor Phone
Assigned To BGIBSON Entered By MHAEBERLE K
Action Time Exp:
Comment A final do approval was granted to the secondary side.
gligersv 7/2-64
Inspection History
Item: 91 PW-Final driveway grade **Approved**
06/01/12 Inspector: Is Action: AP APPROVED
Comment:
Item: 532 PW-TEMP. 0/0 **Approved**
06/01/12 Inspector: Is Action: AP APPROVED
Comment:
Item: 539 PW-FINAL 0/0 **Approved**
06/22/12 Inspector: Is Action: AP APPROVED
Comment:
Item: 10 BLDG-FOOTING **Approved**
06/16/11 Inspector: JRM Action: AP APPROVED
Comment: SECONDARY SIDE FOOTERS COMPLETE
07/11/11 Inspector: sgremmer Action: PI PARTIAL INSPECTION
Comment: see highlighted plans for progress
05/31/12 Inspector: sgremmer Action: AP APPROVED
Comment:
Item: 20 BLDG-Foundation/Steel **Approved**
06/29/11 Inspector: sgremmer Action: AP APPROVED
Comment: see highlighted plans for progress
07/11/11 Inspector: sgremmer Action: PI PARTIAL INSPECTION
Comment: see highlighted plans for progress
05/31/12 Inspector: sgremmer Action: AP APPROVED
Comment:
Item: 110 ELEC-Service **Approved**
09/27/11 Inspector: sgremmer Action: AP APPROVED
Comment:
Item: 120 ELEC-Rough **Approved**
09/20/11 Inspector: sgremmer Action: PI PARTIAL INSPECTION
Comment: undergorund for service laterals
01/05/12 Inspector: sgremmer Action: AP APPROVED
Comment:
01/06/12 Inspector: Martin Action: DN DENIED
Comment: Move electrical panel and av panel in fire wall of carsge. Observed on mechanical rough
02/14/12 Inspector: sgremmer Action: AP APPROVED
Comment: panels were incased with 5/8 rock to maintain Martin's request.
Item: 200 MECH-Rough **Approved **
01/06/12- Inspector: Martin Action: DN DENIED
Comment: 1. Provide protective plates ay all flue and plumbing plate
REPT131 Run Id: 14657