HomeMy WebLinkAboutF11-0028 TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
SPRINKLER PERMIT Permit #: F11-0028
Job Address: 600 VAIL VALLEY DR VAIL Status . . . : ISSUED
Location.....: NORTHWOODS, UNIT F8 Applied . . : 05/25/2011
Parcel No...: 210108119008 Issued . . : 06/07/2011
Project No : Expires . .:
OWNER SCHUTZ, STEPHEN & SUSAN TRUS 05/25/2011
P O BOX 1046
LA JOLLA
CA 92038-1046
APPLICANT NEDBO CONSTRUCTION 05/25/2011 Phone: 970-845-1001
P.O. BOX 3419
VAIL
CO 81658
License: 251-A
CONTR.ACTOR WESTERN STATES FIRE PROTECTI 06/07/2011 Phone: 303-792-0022
7026 S TUCSON WAY
ENGLEWOOD
CO 80112
License: 338-S
Desciption:
Valuation: $7,280.00
•i};tf#i#}#ff#t}►�t##t#t4t**t►###ff#fi#####t**t►tt##t4#*4#i*}#*###}# FEE SUMMA RY ******s***********as�*s+sat*f►**r*s*s**►*re******»*+►*sa*
Mechanical---> $o.00 Restuarant Plan Review--> $0.00 Total Calculated Fees--->
$741.40
Plan Check---> $432.00 DRB Fee---------------------> $o.oo Additional Fees-----------> $o.o0
Investigation-> $0.00 TOTAL FEES--------------> $741.40 Total Permit Fee----------> $741.40 `
Will Call-----> $0.00 Payments-------------------> $741.40
BALANCE DUE---------> $0.00 ;
sa»s#sa*�sa�*f�s►+**�*s*******sa*s**s::t��**est*****a*****aaasss*s��sss**sfss***�►**t****s*****sa�ss***s:sss��st�t**t*t**s**t****aaa**sss*fs�
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE DEPARTMENT
05/31/2011 mvaughan Action: AP
CONDITION OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 53
(FIRE 2007) Monitored fire sprinkler system required and shall comply with NFPA
13 (2007) and VFES Standards.
####i####f#�R*tt###t4#tt#*#f##}##i#t####t*##FM**###t*####*#*#########*###########*##tR****�+k►t#R###########fft###########R4##tR*tt#*M***i�###�F■
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with al)
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved,International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEPHONE AT 970-479-2252
FROM 8:00 AM-5 PM.
frL (/�^-�'
SIGN TURE OF ER OR CONTRACTOR FOR HIMSELF AND OWNEF
�
********�*�********************�********�***************************************************
TOWN OF VAIL, COLORADO Statement
**«****************�**************r******************�******�+*****�***********«************
Statement Number: R110000599 Amount: $741.40 06/07/201108:59 AM
Payment Method: Check Init: SAB
Notation: 120956 WESTERN
STATES FIRE
Permit No: F11-0028 Type: SPRINKLER PERMIT
Parcel No: 2101-081-1900-8
Site Address: 600 VAIL VALLEY DR VAIL
Location: NORTHWOODS, UNIT F8
Total Fees: $741.40
This Payment: $741.40 Total ALL Pmts: $741.40
Balance: $0.00
*******************+***********a***s********************************************************
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
BP 00100003111100 SPRINKLER PERMIT FEES 309.40
PF 00100003112300 PLAN CHECK FEES 432.00
-----------------------------------------------------------------------------
�
�
�'
e
� t� "��k` � Department of Community Development
� ....; ;y, .
� .,
r
, - '�' ���� � , 75 South Frontage Road
�
, �. � �
° : `� '`. •� 6�r . �,�,"�a '`� Vail, Colorado 81657'`
�'u:w�. ._,. �f, Y� 4�� .J�t �`',.'..£��,...�..
" {: :; y � �� � ����-:� � Tel: 970-479-2128;''
; ,, x .
M „ �, ,
N . .
� ^�,.. ���w �` .��} . � e �, 7 } . . Fax: 970-479-2452
, �
„ , `�.,.�~�° �'°�;�-�� �. vr r� . Web: www.vailgov.com ,
` , .
y� -�� ' ' DeKelo ment Review�Coordinator
! r> ��� " '"
i � ��w�c "� ` .L.t `."W'�r�ii�wy..,.�:.� .�" g ~ s
��L:��S�� � � .. �� p �
-
�. .,„
, ;�s � ,�,. ,,
� � ._...._ ..:,a..u.�°:�.:_ .,{ �#.� � ii�ili i3 ' .+.w_ - ..uu�".�'si��p�,.�_.JUi.ar��
FIRE SPRINKLER PERMIT
Commercial &Residential Fire Alarm shop drawings are required at the time of
application submittal and must include the following information:
1. A Colorado Registered Engineer's stamp or N.I.C.E.T level III (min) stamp
2. Equipment cut sheets of materials
3. Hydraulic calculations
4. A State of Colorado contractor registration number
5. Plans must be submitted by a Registered Fire Protection Contractor
Project Street Address: O�ce Use:
600 Vail Valley Drive Bldg. F #8 Project#: �S��- a Sy a
(Number) (Street) (Suite#)
Building Permit#: ���-0 3aS
Building/Complex Name: Northwoods Condominiums
Sprinkler Permit#: �� �^ o���
Contractor Information: Lot#:_Block# Subdivision:
Company: Western States Fire Protection
Company Address: 7026 South Tucson Way Detailed Description of Work: Relocate existing
City: Centennial State: CO Z;p:80112 heads and add 3 heads.
Contact Name: Kody Karch
Contact Phone:
720-219-0732 (use additional sheet if necessary)
E-Mail kody.karch@wsfp.us Detailed Location of Work: 5th floor of building.
Town of Vail Contractor Registration No.: 338-S
X C`_���'^�-� ��f'�`^'�• Does a Monitored Fire Alarm Exist? Yes(�) No( )
Contractor Signature(required) Does a Sprinkler System Exist? Yes(�) No( )
Property Information Work Class:
Parcel#: al O L O��900 S New( ) Addition(�) Remodel (�) Repair( )
(For parcel#,contact Eagle County Assessors Office at 970-328-8640 or
visit www.eaglecounty.us/patie) Retro-Fit( ) Other( )
Tenant Name: Type of Building:
Single-Family( ) Duplex( ) Multi-Family(�)
Owner Name: �6Pt�kE�l � SLl3Pk�L SC1�LLT Z
Commercial( ) Restaurant( ) Other( )
Complete Valuation for Fire Sprinkler Permit:
Fire Sprinkler$: $7280.00 Date Received• � � �o�f7 �
� v
MAY 2 4 2011
TOWN QF VAIL
01-Feb-10
DENVER BRANCH Fire Protectlon Syatams
� Western States 7026 S.TUCSON WAY pesian.FaWication.lnstallation
Fire Protection Co. CENTENNIAL�CO 80112 Commercia�.Industnal.Residen6a�.�nset�tionat
Special Hazards.High Tech.Defense.Hangars
����j���� a�d•������ 303-792•0022 PH 303-792-9049 FAX Reuor�t.service•Inspec6on.���amtenence
May 19, 2010 ,
i
Mr. Mike McGee
Project: Schutz Residence , 600 Vail Valley Dr., VaiI,CO ,
Re: Sprinkler System Modification
Mr. McGee,
Western States will be retrofitting the fire sprinkler systm at the aforementioned
address relocating and adding sprinkler heads. Completion of this project will require the
following:
► Piping 3 new sprinkler heads to an addition to the 5'h floor.
► Draining and recharging the anti-freeze system.
► All of the above work will be installed to NFPA and Vail Fire Department specs,
If any further information is required, please contact me at 303-792-0022 or cell phone
at 720-219-0732.
No work in addition to the above scope will be preformed by Western States Fire
Protection without receiving permission from Vail Fire Dept..
Sincerely, _
--�_ —'� `��_�� _��.
)
� `'�
`
Kody Karch
Project Manager
- Bulletin 176 Re�.A
�
� o Model F1 �
Residential Sprinklers for 2 �
Design Density of .10 gpm/ft �
D
Model F1 Res Sprinklers engineered for the lowest flows
to meet the minimum design density of.05 gpm/ft�
Types: �"""� �
1. F1 Res 49 Pendent `' � -' � � �� ��' t
2. F1 Res 49 Recessed Pendent/F 1 ����"`� !���
3. F1 Res 49 Recessed Pendent/FP :-- :-.. _: = :,
4. F1 Res 49 CCP Pendent �
5. F1 Res 58 Pendent F1 Res49,58&76 F1 Res49,58&76
6. F1 Res 58 Recessed Pendent/F1 RecessedPendent/F1 RecessedPendent/FP
7. F1 Res 58 Recessed Pendent/FP
8. F1 Res 58 CCP Pendent .��r�����+ � ,
9. F1 Res 44 & 58 HSW
10. F1 Res 44 & 58 HSW Recessed HSW/F2 '���
11. F1 Res 76 Pendent �,,�= -�:`'
12. F1 Res 76 Recessed Pendent/F1 ,�� ' �-'
13. F1 Res 76 Recessed Pendent/FP
14. F1 Res 76 CCP Pendent
F1 Res 49,58&76 F1 Res 44&58 '
CCP Pendent Recessed HSW/F2 '
Listings&Approvals '
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus) Technical Data:
• Thermal Sensor: Nominal 3mm glass-bulb
UL Listing Category • Sprinkler Frame : Brass Casting
Residential Automatic Sprinkler • Sprinklers' Pressure Rating : 175 psi
UL Guide Number Factory Hydrostatically Tested to 500 psi
VKKW • Thread Size: '/z" NPT(R1/2)
Patents • K-Factor:4.9(Actual)-F1 Res 49 Pendent Sprinkler
US Patent No. 6,516,893 applies to the 5.8 (Actual) -F1 Res58Pendent&HSWSprinkler
7.6(Actual)-F1 Res 76 Pendent Sprinkler
Model F1 Res 49 &58 Pendent Sprinklers 4.4(Actual)-F1 Res 44 HSW Sprinkler
• Density: Minimum 0.10 gprrVf[2
Product Description AppliCation
Model F1 Res Pendent sprinklers (Figs. 1, 2, 3 & 4) Model F1 Res Sprinklers are used for Residential Fire
combine excellent durability, high sensitivity glass-bulb Protection according to UL 1626 Standard". Be sure
and low profile decorative design. that orifice size, temperature rating, deflector style and
The 3mm glass-bulb pendent sprinklers permit the sprinkler type are in accordance with the latest
efficient use of residential water supplies for sprinkler published standards of The National Fire Protection
coverage in residential fire protection design. Association or the approving authority having
The low flow F1 Res sprinklers are specially jurisdiction.
engineered for fast thermal response to meet the When using F1 Residential Sprinklers for systems
sensitive fire protection application needs of the latest design to NFPA 13D or NFPA 13R, use listed area of
residential market standards (UL 1626 Standard '). coverage and minimum flow and pressure requirements
Upon fire conditions, rising heat causes a sprinkler's shown in Bulletin 135.
heat-sensitive glass-bulb to shatter, releasing the For systems designed to NFPA 13, use information in
waterway for water flow onto the deflector, evenly this bulletin.The number of design sprinklers shall be the
distributing the discharged water to control a fire. most hydraulically demanding sprinklers as required by
NFPA 13. Flows and pressures can not be below the
baseline flows and pressurers.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
NFPA 13
For residential sprinkler systerr�s designed to NFPA 13, Exam I .P�2. No. ?
a minimum density of 0.1 gpm/ft must be provided over Room Size= 8 ft x 20 ft (2.4 m x 6.1 m)
the"design area"that includes the four(4)hydraulically Coverage Area= 8 x 20 = 160 ft2(14.9 m2)
most demanding sprinklers for the actual coverage Flow Q 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm
areas being protected by the 4 sprinklers. The minimum Using an F1 Res 49 Pendent Sprinkler, K-4.9
required discharge from each of the four most Pressure- (16/4.9)2 = 10.7 psi (0.74 bar)
hydraulically demanding sprinklers shall be the gC�[ The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m)
of the following: covera e area using the baseline density of 0.05
1.The flow rates given in the Fieliable Residential gpm/ft�will be 20 gpm C� 16.7 psi (75.7 Umin Q 1.14
Sprinkler Technical Bulletins referenced in Table A bar). Therefore,the minimum flow required is 20 gpm C�3
for NFPA 13D and 13R as a function of temperature 16.7 psi (75.7 L/min Q 1.14 bar).
rating and maximum allowable coverage area (for
actual coverage areas less than or between those xa I No
indicated in the respective technical bulletin, it is p e . 3
required to use the minimum required flow for the Room Size= 10 ft x 16 ft (3.0 m x 4.91 m)
next largest coverage area); or Coverage Area= 10 x 16 = 160 ft2(14.9 m2) ;
2.A minimum discharge density of 0.1 gpm/ft2 Flow Q 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm
applied over the"design area"consisting of the four Using an F1 Res 76 Pendent Sprinkler, K=7.6
most hydraulically demanding sprinklers for the The baseline flow for a 16 ft x 16 ft coverage area is 21
actual coverage areas being protected by the four gpm @ 7.6 psi (79.5 Umin C� 0.52 bar). Therefore, the
sprinklers. The maximum dimension of the actual minimum flow and pressure is 21 gpm C�? 7.6 psi (79.5
coverage area cannot be any greater than the L/min Q 0.52 bar).
maximum coverage area indicated in the technical
bulletins referenced in Table A. �xamr�le No. 4
Design Note: Using the AS = S x L method to Room Size- 14 ft x 18 ft (4.3 m x 5.5 m)
determine the sprinkler protection area of coverag� Coverage Area- 14 x 18 - 252 ft2(23.6 m2)
in accordance with NFPA 13, apply the 0.1 gpm/ft Flow C� 0.10 gpm/ft2 density= 252 x 0.10 = 25.2 gpm
density to this area to determine the minimum �g4.6 L/min)
required f�o . Compare this flow to the minimum
� Using an F1 Res 76 Pendent Sprinkler, K=7.6
0.05 gpm/ft cULus Listed flow for the appropriate Pressure- (252/7.6)2 = 11 psi (0.76 bar)
coverage area in the technical bulletin for the The baseline flow and ressure of an 18 ft x 18 ft
specific residential sprinkler. if the flow stated in the p
techni�al bulletin is less than the calculated 0.1 coverage area is 21 gpm @ 7.6 psi (79.5 Llmin Q 0.52
gpm/ft density flow required, the .1 de,nsity flow bar). Therefore, the minimum flow and pressure is 25.2
must then be used in the equation Q=K,IP, solving 9pm @ 11 psi (94.6 L/min @ 0.76 bar).
for P, to establish the minimum required pressure
using the sprinkler K-factor. Note: In many cases In general residential sprinklers req uire
the listed flow of individual residential sprinkler� flows and pressures as listed for D.05 '�
may exceed the required minimum 0.05 gpm/ft densities to achieve the proper spray pattern �
density.Reliable has available residential sprinklers so the flows and pressures at 0.05 dens�ty are I,
with larger K-factors (K=5.8 and K=7.6) that wi� the baseline flows and pressures. Flows and
provide lower pressure demands for 0.1 gpm/ft pressureS below the listed 0.05 density shall
densities in NFPA 13 residential applications. nOt be used.
xample No. 1
Room Size= 12 ft x 20 ft(3.6 m x 6.1 m)
Coverage Area= 12 x 20 = 240 ft2(22.3 m2)
Flow Q 0.10 gpm/ft2 density= 240 x 0.10 = 24 gpm
Using an F1 Res 49 Pendent Sprinkler, K=4.9
Pressure= (24/4.9)2 = 24 psi (1.65 bar)
The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m)
covera2qe area using the baseline density of 0.05
gpm/ft will be 20 gpm Q 16.7 psi (75.7 Umin Q 1.14
bar). Therefore,the minimum flow required is 24 gpm Q
24 psi (90.8 Umin Q 1.65 bar).
2.
for installing Model F1 Res recessed HSW sprinklers
Installation use only the Model GFR2 Sprinkler wrench. Use of
Models F1 Res sprinklers are to be installed as wrenches other than those specified may damage
shown. Model F1, F2 and FP Escutcheons, illustrated these sprinklers.
herewith,are the only recessed escutcheons to be used Note:A'leak tight"sprinkler joint can be obtained with
with Model F1 Res sprinklers. Use of any other the following torque:
recessed escutcheon will void all approvals and . 3/,�° NPT(R3/4)- 14-20 ft-Ibs (19-27.1 N-m)
warranties. For installing Model F1 Res Pendent . �/2�� NPT(R1/2)-8-18 ft-Ibs (10.8-24.4 N-m)
sprinklers use only the Model D sprinkler Wrench; for po not tighten sprinklers over maximum
installing Models F1 Res Recessed Pendent, CCP recommended torque. It may cause leakage or
sprinklers use only the Model GFR2 sprinkler wrench; impairment of the sprinklers.
• Model F1 Res 49, 58 & 76
• Model F1 Res 49, 58 & 76 Pendent Recessed Pendent/ F1/F2
� -�.!�
�"r ° '_�•++�, .-�..r�
� _ .
a .._ ...
„�'�� �..,� �,
� , �� �,. ����'��.-'"" �
�'
� �� �'�.
� _ � � � �. :
.��,�5: �, .�.::� ,,,� ` -
. �
�
- .- �... w .. �
�-_�.y .. ♦. .
y � .�y�� �
:� �• �',.+ _" `�
._—. .��:'1 �-a��.s... � °`.
�
F1 escutcheon, /" (19mm) adjustment
Note: See escutcheon table for dimensions.
z,is•�,o�.�„ ,
-- �..�mm; ,a _
� � � 5/�E'O/a II
_ —I— — '(19.2mmJ
_ � �— �—��_.—�I
� rt — _ _I=_ i
I r
I i — —t— — , ,�/r RrcuccA
i
� �.v�o«na uNric ( � �
��rvsr< r�FF�
u�„u+eoss.
fl—` I --�
—._....'.._ r cc ov vi�r�HC�o
CE2/NL pM[NS�ON�
C....-_.=-�?-- !/�E-/5,/ib(��CSCUICl/EO f
����... � � —_:�_: r�
- �/�E-rr/rc;rz rscu�cr�reN�
�.�
_............
_ „
�ICJUSTMENI
�SSV� I
r: .
I
� -� -- --- I I
� � �, ,�e-
�,:mmi .,
� �_
i
I
� .
�JSFG03 '�,
I35FCO2A ____' 2 1'/J1'Ora. � ��
('12,.,,�j . ..
Fig. 1 Fig. 2
3.
Technical Data: F1 Res 49 Pendent and Recessed Pendent
_ __ Escutcheon*, F1 or F2, Data:
S rink�ler I-- -_
_ _ ..__
�
, p Max. i , Face of fitting to
TSized Tem I Max � Ambient Actual Sprinkler Ty� Adjustment "A �lin
! i Ratin PsiSbare'-_ Tem Factor I ch gmm I4..._..__--_ Inch(mm) Min'n/�(m g)1� I 3 nch mm
. °F _C p �� ) oF pC � ) � I5� �-�
/(R/)T '-- F1 /<�190) � %„�23.8) i / / �
-
-- , ,� � : e s 4 7 24 0)
" 155 68 175(12) 100 ' 38 4 9 2.25(57) __I Max.-1 2 38.1
175 79 150 66 F 2 %(1 2.7) !M�n-75 „ %s '%6(4.7 1 7 4) I�
------ --_ _ i M ax.=1� 38.1�.._1 .---
`Note: Escutcheons F1 or F2 may be used with ,
Model F1 Res 49&58 Recessed Pendent Sprinkler
' **Baseline flows and ressures for 0.05 densit I
p Y
Deflector-to-ceiling *Deflector-to-ceiling
Maximum 1"(25mm)to 4"(100mm) Maximum 4"(100mm)to 8"(203mm)
� SftaOm g gpm�(Lpm)f ps(ba) NumberaSlN ', ' MaSpacing ler�gPml(Lpm) ps(ba) Identificat on 'I
_ __---- P I P ,
,, �
ax. �� er f__ S rink{r � I, ...._._ft_�m? _ - Numbe�SlN
�----- - -- _ ; ---___ _........._-
----
12 x 12(3.6x3.6� _ 13_(49) 7.�0.48� F 12 x 12(3.6x3.6� __ 15(57� _ _ 9.4 �0.65
-- __
14 x 14 4 3x4.3 13 49 7.0�0 48� 14 x 14�4 3x4.� 16�0 5) 10.6�0.73
- - --- --
18 x 18 5.5x5.5 13 49 �.o(o a8� R3516 ' 16 x 16(4 9x4.� _17_64 3 12A(0.83 R3516
---
20 x 20 6.1 x6.1 ' 17 64�_ 12 0�0_83) _18_x 18�5:5x5.5 19 72 15_0�1_0
�._�- ___..Z!_ 20�75.7��1_6 7_(1 14)_,_ --- _ _ _-, 20 x 20�6.1 x6:1) _22 583.2) 20.2�1,4�
--- - __ __ _..-------
*Note: The F1 Res 49 pendent and recessed pendent
residential sprinklers can be installed per NFPA 13 in
beamed ceilings meeting the following criteria:
1. Maximum beam depth = 7"(178mm)
2.Beam spacing at or greater than 7.5 ft.(2.3m)on center.
Technical Data: F1 Res 58 Pendent and Recessed Pendent
_ ' Sprinlde� ; Max. � I
Thread Temp. M� : Ambient K SprinMer
Size ,----Ratin� P i'�bar��- -Temp. Factor Length ,
�F �C (u � � �F C_ ; , Inch(mm) ;
F
___ _- --- �_.
- ( ) _... - --- -�
Yz' NPT 155 68 100 38
RYz) 175 79 175 12 150 66 5.8 i 2.25(57)
� **Baseline flows and pressures for 0.05 density
--
I Max Sprinkler � ? Ceiling-to- , Sprinkler
' Spacing Flow Pressure p��. ; Identification
� gpm(Lpm) psi(bar)
._ _ ft{n!� _ - -__ _ - Inch(mmL� Number�SIN�_
! 12 x 12 3.6x3.6 16(61�---- 7 6(0.53�_ _ �
----- - --- �25-00)
14 x 14�4.3x4.3 16�61�_____ 7.6(0.5�
16 x 16 4.9x4.9 __16(6�_ 7.6 0.53� ___ R3513 II
_._
18 x 18 5.5x5.5 19�7� __ 10.8�0 75 I
-..
--
20 x 2�_1x6.1 22_(83 3) -- 14.4 1�-___..... ___._------- '
'� "Calculate for a.10 density but in no case
', go below the baseline flows&pressures
4.
Technical Data: F1 Res 76 Pendent and Recessed Pendent
_ � �
p
Thread Temp.� �i M� Amb nt K � S rinMer ,
P ,
Size ',_____Rating_..._; Pressure Temp._ Factor �
ngt �
�F , � ; psi(bar) oF o� i Inch(mm)
- — --
:-- --_ _ �__ ---- -i I Face of fitting to
%"NPT 155' 68 �I 175(12) 100 38 7 6 2 25(57) T � Adjustment "A„ �
��R/,� �1 7 5 _ 7 9 1 5 0 6 6 Y I� � ceilin g
� L___ _ _.... ____ ___ Inch(mm) Inch(mm) Inch(mm�
_____ __._.. ---
-
* F1 %(19.0) Min % (19.1) 3/s- /6(4.7 240)
Baseline flows and pressures for 0.05 density Max�z (38.1) _ 5
f i ; F2 %(12.7) Min '%s"(23.8) ../6-itifi�4.7-17.4) ;
Max.Sprinkler Spnnlder ___ Max_i/°(38 i) _ _____ ;
Flow Pressure
Spacing I Identification
ft m�- .--9Pm��Pm) I����r) { Number(SIN) j
_ __ _
12 x 12 3.6x3.6 21 7.6(0 53�_ �
-----.._ ----. . _._
_ 14 x 14�4.3x4.3 � 21 i 7.6(0.53)
16 x 16 4.9x4.9) � 21 7.6 0.53 R7618 "'Calculate for a .10 density but in no case
18 x 18�5.5x5.5) � 21 ; 7.6�0_53Z__ go below the baseline flows& pressures
-- -...._.._.
— ---- t---- �
20 x 20(6 1 x6.1) '_ 23 9.2(0.63�
• Model F1 Res 49, 58 & 76 • Model F1 Res 49, 58 & 76
CCP Pendent Recessed Pendent/FP
�; ,W�rr �
,.. � �� . .r�
� w:�';� � �
� �� �
�, =�,-�
FP push-on/thread-off
escutcheon
__________ _�� 1 S%d"'[Eo`.7mm�D1A. 7 5/6'ON.(66Jmm)
HOLE IN Cf/LINL
2 5j76"Dla. HOLf IN CEILING
�$8.?mm� 7 5/�6'Ott
CUP �._'_y_.__. 15 cuvml
:-..-.:z�1::�-:;:_::,.; /
_�—} .: I �_ �
.... I . .._ �.,..1/�.,pfDUCE� �.r=_——_-J
� r�_�-�
CJP " I . � I I r'x r/7'�r[auCea
; '� ---_I_---_
,�_. .___:._.y �-
_.. ;
CEIUNG ..:_:-_�=` _=
_... 1 I
- - 1 1/4"(3LSmm] \ /
..-,I � I MAX. FALE OF FITTING � � /
+ I 1"0 FACE OF CEIUNG � �
f ' ..-� I -v�/�plh�fENSlON
�
� � � L J
•,,�" Cfl[iNG
COl'ER ACJUSTMENT B^
� HElGH7 � � r i/7'(J8.rm..�/u,u�.
fACE OF il)/!NG
i 1` - " '- - !0 FACf 0(CCiunG
(\\ INMENSIQY
�\l� �
''t 3/'S/]6"'DIA. _�I
��JFCt/4�. lf'4.imm1
l/$"(IJmm]NAx. �
F 1_..._._R E S 4 9, 5 8 & 7 6 C C P P E N D, '°"°"'S'"E^" +-
Fig. 3 Fig. 4
NOT'E: The F1 Res 76 will use a 1"x 3/�"reducer.
5.
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/ FP
� CCP Options Data:
' __ - __ _ __
S nnMer' CCP .,A„ - .,B„
�! p Assembly Max. M�. I Sprinlder
'�Thread Temp. Ambient �( ; Cover Adjustment CCP Height
' Size Ratmg � Temp. Pressure Temp. �Factor! �n�h Inch(mm�_ _ Inch�mm�
_...__ ,
__ Rating psi(bar) .._..._ ...--- �Inch(mm) — ��i 2 7)__- '---- S 24)
R/z 155 68 135 57 --175(12) 100 38 I 4 9 ± '
_C __o_ �----1�_�47�.....-----�- 3^�19�------�
F F C _ F C
Yz"NPT -- �
� ' ) � 2 25(57)
__ ---- --____ _ _� i
*Baseline flows and pressures for 0.05 density FP Data "A":
--- __ - _._ ..
_ __ _ . _
Max.Sprinkler Sprinkler FP Position A'
Spacing _ Identfication __ _. _ _ Inch�m�
_..
ft m 9pm(Lpm) ps�(��) I Number SIN � Max Recessed �/ 11
u
--- __ { -- -.. _.
- - - - + --- -
-- ----- �Llfi
12 x 12 3.6x3 6�__ 13(49� _ 7 0(0_4� � ,--_ Min_Recessed _.__ _ '/�_�?�- —_
14 x 14(4_3x4.3 i3�as �o(o.aa� Note: Sprinklers shown in Fg. 3 and Fg. 4 are not
-- -- -- -—
I 16 x 16�4.9x4 9 ia�5� a 2(o.5s� i RsSis ' suitable for installation in ceilings which have
--- —
_ i s X 1 s 5.5X5.5� i a(s�_ 1 s.5�o.ss1_ , !i positive pressure in the space above.
_ 20 x 20_�6,1x6.1_) 20(75.7) 16 7(1.14) , '
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP
� p T CCP I
;Thread Temper�Assembly Mau. Ambient K Sprinkler
'i Size Rating Temp. Pressure Temp. Factor I Length
Rating ; psi(bar) ,______�____ Inch(mm)
F oC_ F oC °F °C
_ _— ---.._._ __ _ . _.... . .__-----
���RN�T 155 68 135 57 175(12) 100 38 5 8 �I 225(57)
*Baseline flows and pressures for 0.05 density
� ---.._ __._. _ _ __ _ __
Max.Sprinkler Flow I! p�u� Sprinlder
Spa�i jg m L � �i�p�r� Ident'rfication
_ ft m gp � �� Number(SINZ
-- - - - - - —---
__12 x 12_�3,6x3 6)____... . 16_�61� 7 6��53� _
I_....
14 x 14(4.3x4_3) , 16 i6�_ __ 7_6_(0_53�__
16 x 16 4.9x4.9 16 61 _ ___7:6(0 53) R3513
18 x 18(5.5x5_5��-9(72�--__ 10.8(0 7�---
20 x 20(6.1 x6.1) ! 22(83.3) 14.4(1.0)
Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP
' ccP 1 ___ i_ ____i
�Sprinlder Assembly Max. Max. I S rinlder
,,Thread L Temp—-- Ra�� ���ur� Amb�ent K ' �ngth
Size ( Rating Temp. Factor�I Inch(mm)
+_°F I °C °F °C � °F C
_. t
- - -
'/a"NPT I 155 68 100 38 !
(R314) j 175 79 , 135 i 57 I 175(12) 7 6 i 2.25(57)
150 66
--- � --- -_....__ .._..__.... ._ _i......_ ._----
�i *Baseline flows and�ressures for 0.05 density
— m L m ---._ ,
Flow � Sprinlder ;
Max.Sprinkler I
Spacing P��� Ident'rfication '
ft_�n?� ---9P � P ) I psi(bar) Number(SIN)- ,
_ --- ,...._._ ___ _ -
12 x 12�3.6x3 6)_� 21 � 7.6�0.53
14 x 14 4.3x4.3�_ 21 7 6{0_53�
__
16 x 16(4.9x4.9 ��_ 21 7 6�0.53�� R7618 *Calculate for a .10 density but in no case :
— ) ' -....----..__.._..._�-__---
18 x�5.5x5.5 22 8.4�0.58�� go below the baseline flows&pressures j
20 x 20_(6 1x6.1) � 25 ; 10.8(0 74) _ '
6.
• Model F1 Res 44 & 58 HSW • Model F1 Res 44 & 58
Recessed HSW/F2
_. �,
���; F ,
� � ,,,� _ . .�,�y ,r� �
Y��� � � 'P� � (r { � - ���,.
�'
�3,: �a,. i t ,�.
° , �
�:,,�� , <., , .: ,`. _� �
_ �� ,� •�
�
F2 escutcheon, y" (13mm)
adjustment
'� Technical Data: F1 Res 44 HSW & HSW/F2
;
i
i ' Escutcheon, F2, Data.
• RaUn Tem . ---� -- I _. _ ...._.._.
� SpnnMer I Max. ! Face of Fitting
Tem � P�U� Ambient �I p�n h i T Adjustment , to wall
0 0 lu� ) ' o o I � ) Inch(mm) � Inch mm
Thread p• Max. K nnkler Y�
� Si�e _� i bar -- P _ _ Factor Inch mm _ � ._..
..___ ___.
F C � F C I F2 � %(73) �/s-�%6(a.�-i�.a�
- --- -T-- - _ _ .....
_._..
Yz"NPT 155 68 I 100 38
(R'/z) 175 79 175(12�0 66 4.4 2 45(62)J
i *Baseline flows and pressures for 0.05 density
� � _
I' Max.S rinlder I g_ S rinkler Tem Flow r P��� i Sprinkler
p Ceilin to- p p' I
Spacing Rating gpm i Ident'rfication
ft(m)----� in�ch mm �F��C�. . ....�Lpm�. ; �i(bar) Number(SIN)
12 x 12 3.6x3.6 155 68 175 79 12 45.4 7.5 0.52 T
--�- � �-L �-�--�---�- -�--� -
�---- � � � _�':-. _� _
14 x 14 4.3x4.3 155 68 175 79 14 53.0 10.2�0.71�_
__.._... __.._.
16 x 16(4 9x4.9�_ 4_6 155_�68Z_ 175�) ;' 16 60.6 13.�2)_
----
16 x 18 i4 9x5.5�_ (101-152) ',, 155�68� 175_(79� ' 18{68.1) 16_8 1.16)
18 x 18�5_5x5.� 155(68) 175(79)_-- 19�72.0 _ 18.7(1.29�_�
16 x 20 4.9x6.� _- --I 155�68� 175_(79)- 23{87_1�_ 27 4�_89) R3531
12 x 12 3.6x3.6 ' 155 68� 175�79��14(53.0� 10.2(0.711 �
_14 x 14 4.3x4.3) 155�68� 175(7�, 16(60.6 13.�92��
16 x 1�4 9x4_9� 6��2 155(68) 175(7�'�17(64.4� 15.0�4��
(152-305) ,�
16 x 18 4.9x5.5 � 155�68 175�79) ; 20�7� 20J�4�
16 x 20(4 9x6.1) _I 155(68) 175(79) '� 23(87.1) 27.4(1.89)
*Calculate for a .10 density but in no case
go below the baseline flows& pressures
7.
Technical Data: F1 Res 58 HSW & HSW/F2
'i 2, Data:
_
scutc eon,
- _ _ _ _.._.
p Max. � Face of Fitting �I
S rinlder �
Thread Temp. M�• �, Ambient K Sprin{der Ty� Adjustment to wall
P�u�i Tem Lenyth Inch(mm) �
Siae _ Rating-- P•--- Factor -- --------Inch�mm�_ �I
–
�F �C - ��(bar) i oF- �C- - Inch(mm)_ F2 --� 13)_ �%6-"/,s(4.7-17.4 �
/2"` N jT- 155 , 69 175(12) � 160 66 5.8 2.45(62) I
�
� R/z 175 �---— -—- ---- ....___I
i
*Baseline flows and pressures for 0.05 density
, Max.Sprinlder A Sprinfder Temp. Flow � Sprinkler
, i Ceiling-to- Pressure
Spacing Rating gpm I �I Ident'rfication
I n�m� I Deflector oF�°C) , ��) psi(bar) Number(SIN) ;
} Inch(mm� ___ i
- - �-- —
--- -
12 x 12(3 6x3,6) � 155(68) , 175(7�� 16(60 6) 7.6(0.53) �
14 x 14 4.3x4.3� 155(68�_+175(79) 18(68.�__ 9.7(0.67)_ '
---- --
16 x 16 4.9x4.9 ��01- 52) 155(68� 1��79 21_�79.5 13.2 0.91�
16 x 18 4 9x5.5 155�68 ' 175�79 25�94JL 18_6�1.28) �
16 x 20�4 9x6 1) ___ _ 155 i68 175 S79 29 109.8 25�73 R3533
--------
12 x 12�3:6x3 6) _155(68)_�_175_�7� 22�83.3 14.4 1 A�-
----
14 x 14�.3x4_3� g_ �2 155�68) +175(79) 22(83 3�_ 14.4(1.0)
16 x 16�4 9x4.9 (152-305) 155�68� �r 175�7� 26�98.4 20.1 1.39�_
16 x 18(4 9x5_5)_ --------_ _155(68)� 175(79) 31 (117.4) 28.6(1.97)
' 'Calculate for a .10 density but in no case
, go below the baseline flows& pressures
8.
Finishes�'�
Standard Finishes Ordering Information
_._...-------- _... _. r __ __-- ---__ __— Specify:
_Sp�inkler__________ '_ F1,_F2,_FP_Escutcheons 1. Sprinkler Model
eronze � Brass
Chrome Plated Bright Chrome Plated 2. Sprinkler Type
wnite Poyester coated � wnice Painted ___ ____ 3. Temperature Rating
__. _�._ _....
p pp cation Finishes 4. Sprinkler Finish
--- _...... _ ---- --
S�rinkler __ F1,F2z Escutcheons
Bright Brass �', Bnght Brass
— - ---- 5. Escutcheon Finish
Black Plated Black Plated
Black Paint I Black Paint
Off White Off White
Satin Chrome Satin Chrome
"'Other finishes and colors are available on special order.
Consult factory for details.
Maintenance
Model F1 Res 49, F1 Res 58 & F1 Res 76 Sprinklers Model F1 Res 49 & 58 Recessed PendenUF1,
should be inspected quarterly, and the sprinkler system Model F1 Res 49 & 58 Recessed PendenUF2,
maintained in accordance with NFPA 25, 13, 13D, and Model F1 Res 49 & 58 Recessed Pendent/FP
13R. Do not clean sprinkler with soap and water,Ammonia Sprinklers shall be [cULus Listed] [New York City MEA
or any other cleaning fluids. Remove dust by using a soft Approved (258-93-E)] low flow residential recessed ,
brush or gentle vacuuming. Remove any sprinkler which pendent sprinklers engine red to provide a minimum I
has been painted(other than factory applied)or damaged design densiry of 0.10 gpm/�over the listed coverage area.
in any way. A stock of spare sprinklers should be Listed flows as specified by the manufacturer's technical
maintained to allow quick replacement of damaged or data sheets are to be used. Residential sprinklers shall be
operated sprinklers. Prior to installation, sprinklers should installed in conformance with the manufacturer's installation
remain in the original cartons and packaging until used. guidelines and the applicable installation standard. Where
This will minimize the potential for damage to sprinklers that pendent residential sprinklers are installed under sloped
could cause improper operation or non-operation. ceilings having a pitch of up to [4/12] [8/12], the sprinklers
shall be listed for such use. Deflector-to-ceiling distance
listing shall be 1" to 8" maximum. Sprinkler frame and
Model F1 RES 49 Residential deflector shall be of bronze frame construction having a Yz'
Sprinkler Specifications NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer and top-loaded
extruded cup with 3 mm glass bulb containing no plastic
Model F1 Res 49 & 58 Pendent parts, and having a temperature rating of [155°F (68°C)]
Sprinklers shall be [cULus Listed] [New York Ciry MEA [175°F(79°C)]. Sprinklers shall have a nominal K-factor of
Approved (258-93-E)] low flow residential pendent 4.9(70). Standard finish: [Bronze] [Chrome-plated] [White
sprinklers engineered to provide a minimum design Polyester� [Special finish—speciiy]. Recessed escutcheon
I density of 0.10 gpm/ft2 over the listed coverage area. assembly shall be a steel, two-piece escutcheon [with 'h"
Listed flows as specified by the manufacturer's technical adjustment(Model F2)] [with 3/a"adjustment(Model F1)] [of
data sheets are to be used. Residential sprinklers shall be push-on and thread off design with Yz" adjustment (Model
installed in conformance with the manufacturer's FP)]. Standard finish shall be [brass][bright chrome] [white
installation guidelines and the applicable installation painted]. Residential recessed pendent sprinklers shall be
standard. Where pendent residential sprinklers are Reliable [Model F1 Res 49 & 58 Recessed Pendent/F1]
installed under sloped ceilings having a pitch of up to[4/12] [Model F1 Res 49&58 Recessed Pendent/F2] [Model F1
[8/12], the sprinklers shall be listed for such use. Res 49 & 58 Recessed Pendent/FP] SIN R3516 & R3513
Deflector-to-ceiling distance listing shall be 1" to 8" (Bulletin 135).
maximum.Sprinkler frame and deflector shall be of bronze
frame construction having a '/z" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville spring
washer and top-loaded extruded cup with 3 mm glass bulb
containing no plastic parts, and having a temperature
rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall
have a nominal K-factor of 4.9 & 5.8. Standard finish:
[Bronze][Chrome-plated][White Polyester][Special finish—
specify]. Residential pendent sprinklers shall be Reliable
Model F1 Res 49&58,SIN R3516&R3513(Bulletin 135).
9.
Model F1 Res 49&58 CCP Pendent(Concealed) Belleville spring washer and top-loaded extruded cup
Sprinklers shall be[cULus Listed] [New York City MEA With 3 mm glass bulb containing no plastic parts, and
Approved (258-93-E)] low flow residential concealed having a temperature rating of [155°F (68°C)] [175°F
sprinklers engineered to provide a minimum design (79°C)]. Sprinklers shall have a nominal K-factor of 5.8.
!; densiry of 0.10 gpm/ft2 over the listed coverage area. Standard finish: [Bronze] [Chrome-plated] [White
Listed flows as specified by the manufacturer's technical Polyester][Special finish-specify].Residential horizontal
data sheets are to be used. Residential sprinklers shall sidewall sprinklers shall be Reliable Model F1 Res 58,
be installed in conformance with the manufacturer's SIN R3513 (Bulletin 135).
installation guidelines and the applicable installation ',
standard. Where pendent residential sprinklers are Model F1 Res 44 & 58 Recessed I
installed under sloped ceilings having a pitch of up to Horizontal Sidewall Sprinkler � �
[4/12J [8/12], the sprinklers shall be listed for such use. � '
Sprinkler frame and deflector shall be of bronze frame Use description for the Model F1 Fies 58 horizontal
construction having a '/z" NPT thread. Water seal sidewall sprinkler with the following modifications:
assembly shall consist of a Teflon-coated Belleville Replace "horizontal sidewall sprinkler" with "recessed
spring washer and top-loaded extruded cup with 3 mm horizontal sprinkler." Add: Recessed escutcheon
glass bulb containing no plastic parts, and having a assembly shall be a steel,two-piece escutcheon with'/z"
temperature rating of 155°F (68°C). Cover plate adjustment (Model F2). Standard finish shall be
assembly shall consist of a brass cover plate and copper [brass][bright chrome] [white painted] [Special finish-
alloy retainer flange. Method of attaching the cover plate specify]. Residential recessed horizontal sidewall
to the sprinkler cup shall be a push-on and thread-off sprinklers shall be Reliable Model F1 Res 58/F2, SIN
design allowing a Yz" cover plate adjustment. Cover R3513 (Bulletin 135).
plate temperature rating shall be 135°F(57°C). A plastic
protective cap shall be provided and factory installed Model F1 Res 76 Pendent
inside the sprinkler cup to protect the sprinkler from Sprinklers shall be [cULus Listed] low flow residential
damage, which could occur during construction before pendent sprinklers engine red to provide a minimum
the cover plate is installed. Standard cover plate finish: design density of 0.10 gpm/ft�over the listed coverage area. �
[White] [Custom Color- specify]. ]. Concealed pendent Listed flows as specified by the manufacturer's technical
sprinklers shall be Reliable Model F1 Res 49&58 CCP, data sheets are to be used. Residential sprinklers shall be
SIN R3516& R3513 (Bulletin 135). installed in conformance with the manufacturer's installation
guidelines and the applicable installation standard.
' Model F1 Res 44 & 58 Horizontal Sidewall Sprinkler frame and deflector shall be of bronze frame
I Sp1'Inkler' construction having a 3/a"NPT thread. Water seal assembly
Sprinklers shall be [cULus Listed] [New York City MEA shall consist of a Teflon-coated Belleville spring washer and
Approved (258-93-E)] low flow residential horizontal machined cup with 3 mm glass bulb containing no plastic
sidewall sprinklers engineered to provide a minimum Part o, andohaving a temperature rating of [155°F (68°C)]
', design density of 0.10 gpm/ft2 over the listed coverage �175 F(79 C)]. Sprinklers shall have a nommal K-factor of
area. Listed flows as specified by the manufacturer's ��6. Standard finish: [Bronze] [Chrome-plated] [White
technical data sheets are to be used. Residential Polyester] [Special finish- specify]. Residential pendent
sprinklers shall be installed in conformance with the sprinklers shall be Reliable Model F1 Res 76, SIN R7618
manufacturer's installation guidelines and the applicable �Bulletin 135).
installation standard. Where horizontal sidewall
residential sprinklers are installed under sloped ceilings
having a pitch of up to [4/12] [8/12], the sprinklers shall
be listed for such use.Sprinkler frame and deflector shall
be of bronze frame construction having a'/z"NPT thread.
Water seal assembly shall consist of a Teflon-coated
10.
Model F1 Res 76 Recessed PendenUF1, Model F1 Res 76 CCP Pendent (Concealed)
Model F1 Res 76 Recessed Pendent/F2, Sprinklers shall be [cULus Listed] low flow residential
Model F1 Res 76 Recessed Pendent/FP concealed sprinklers engin ered to provide a minimum
Sprinklers shall be [cULus Listed] low flow residential designdensiryof0.10gpm/�overthelistedcoveragearea. �
recessed pendent sprinklers engineere�d to provide a Listed flows as specified by the manufacturer's technical
� minimum design density of 0.10 gpm/ft over the listed data sheets are to be used. Residential sprinklers shall be
coverage area. Listed flows as specified by the installed in conformance with the manufacturer's installation
manufacturer's technical data sheets are to be used. guidelines and the applicable installation standard.
Residential sprinklers shall be installed in conformance Sprinkler frame and deflector shall be of bronze frame
with the manufacturer's installation guidelines and the construction having a 3/n"NPTthread. Water seal assembly
applicable installation standard. Sprinkler frame and shall consist of a Teflon-coated Belleville spring washer and
deflector shall be of bronze frame construction having a machined cup with 3 mm glass bulb containing no plastic
3/n" NPT thread. Water seal assembly shall consist of a parts, and having a temperature rating of 155°F (68°C).
Teflon-coated Belleville spring washer and machined Cover plate assembly shall consist of a brass cover plate
cup with 3 mm glass bulb containing no plastic parts,and and copper alloy retainer flange. Method of attaching the
having a temperature rating of [155°F (68°C)] [175°F cover plate to the sprinkler cup shall be a push-on and
(79°C)]. Sprinklers shall have a nominal K-factor of 7.6. thread-off design allowing a '/z" cover plate adjustment.
Standard finish: [Bronze] [Chrome-plated] [White Cover plate temperature rating shall be 135°F (57°C). A
Polyester] [Special finish- specify]. Recessed plasticprotectivecapshalibeprovidedandfactoryinstalled
escutcheon assembly shall be a steel, two-piece inside the sprinkler cup to protect the sprinkler from
escutcheon [with Yz" adjustment (Model F2)] [with 3/4" damage,which could occur during construction before the
adjustment(Model F1)][of push-on and thread off design cover plate is installed. Standard cover plate finish: [White]
with '/z"adjustment(Model FP)]. Standard finish shall be [Custom Color- specify]. ]. Concealed pendent sprinklers
[brass][bright chrome] [white painted]. Residential shall be Reliable Model F1 Res 76 CCP,SIN R7618(Bulletin
recessed pendent sprinklers shall be Reliable [Model F1 135).
Res 76 Recessed Pendent/F1] [Model F1 Res 76
Recessed Pendent/F2] [Model F1 Res 76 Recessed
Pendent/FP] SIN R7618 (Bulletin 135).
11.
Rel iable . . . For Com plete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers � Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented in[his bulletin is to be installed in accortlance with Ihe latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research
Corporation,or other similar organizations and also with the provisions of govemmental codes or ordinances,whenever applicable.
Products manufactured and distributetl by RELIABLE have been protecting lite and property tor over 80 years,and are installed and serviced by the most highly qualified and reputable
sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
� � The Reliable Automatic Sprinkler Co., Inc.
� (800)431-1588 Sales Offices Recycled
'� � (S00)848-6051 Sales Fax �Paper
(914)829-2042 Corporate Offices Revision lines indicate updated or new data.
www.re�iab�esprink�er.com Intefnet Addr@5S EG.Printed in U.S.A.10/07 P/N 9999970322