Loading...
HomeMy WebLinkAboutB11-0134 comment letter 060711 Date June 7, 2011 Re: B11-0134/135 616 Forest Road Dear Scott Turnipseed, RESPONSE INSTRUCTIONS ● Submit four complete sets of revised construction documents containing the . requested information with all plan revision items clouded or otherwise identified ●Please respond in writing to each comment with a response letter addressing each comment . BUILDING COMMENTS Architectural Comments: General 1. All plans sheets to be signed and dated per the State of Colorado 2. Provide plans and specifications for the required radon system per Appendix F of the IRC. 3. Provide a window and door schedule on the plans showing the location and u value of glazing per the submitted Rescheck program. Sheet A1.1 1. Provide engineered design for boulder walls 4’ or taller per Town of Vail amended code section 1603.2 IBC 2. Provide engineer design for the proposed retaining walls exceeding four feet and or supporting a surcharge. Structural Comments: General 1. Provide structural design criteria or structural calculations identifying all design criteria in compliance with the building code. 2. Identify on plans all required special inspections per the IBC and include a special inspection agreement available on the Town of Vail web page. Plumbing Comments: Sheet A1.1 1. Revise plans to show building sewer being provided from the public utility on each individual property. Reference section 701.3 IPC Mechanical Comments: Sheet M1.3 Indicate on plans the proposed cfm for the kitchen hoods to identify the need for outside air. Reference section 505.2 IMC Electrical Comments: General 1. Identify on plans the locations of the required CO detectors per the IRC PLANNING COMMENTS 1. The area of the west garage was expanded in order to address building height issues, however the cover sheet still identifies the garage area as 600 square feet. I believe this garage may exceed 600 square feet resulting in the need for a new GRFA analysis to be performed. Please revise the cover sheet and provide a new GRFA analysis. From the cover sheet calculations the secondary unit is at the allowable maximum for GRFA. I will be looking to see how the expansion of garage square footage is accounted for and affects the allowable GRFA for the site and the secondary unit. 2. Please provide a cut sheet of the proposed light fixture in order for staff to determine that the light fixture will comply with the 14-10-7, Outdoor Lighting, Vail Town Code. 3. Please show the gutters and downspouts on the elevation plans. 4. Please show the snow guards on the elevations or roof plans. FIRE COMMENTS PUBLIC WORKS COMMENTS Sincerely, Martin A. Haeberle Chief Building Official Town of Vail Page2