HomeMy WebLinkAboutF11-0034TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970 - 479 -2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
SPRINKLER PERMIT
Permit #:
F11 -0034
Job Address: 100 E MEADOW DR VAIL
Status ...:
ISSUED
Location.....: VAIL VILLAGE INN PLAZA CONDOS UNIT 305
Applied..:
06/22/2011
Parcel No...: 210108261015
Issued . .:
07/06/2011
Project No
Expires. .:
$717.12
OWNER GABRIEL, PATRICIA ANN 06/22/2011
$0.00
1 E RIDGEWOOD AVE
$717.12
PARAMUS
BALANCE DUE --------- >
NJ 07653
**************************************************************************************************************
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
APPLICANT WESTERN STATES FIRE PROTECTI 06/22/2011 Phone:
303 - 792
-0022
7026 S TUCSON WAY
Item: 05600 FIRE
DEPARTMENT
CENTENNIAL
CO 80112
mvaughan Action: AP
Spacing of
License: 0000003191
shall be in com
with
CONTRACTOR WESTERN STATES FIRE PROTECTI 06/22/2011 Phone: 303 - 792 -0022
7026 S TUCSON WAY
CENTENNIAL
CO 80112
License: C000003191
Desciption: RELOCATE 16 HEADS, PLUG 2, ADD 2. NO CHANGE IN HEAD COUNT.
Valuation: $6,708.80
************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** FEE SUMMARY ************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Mechanical --- >
$0.00 Restuarant Plan Review - ->
$0.00
Total Calculated Fees --- >
$717.12
Plan Check --- >
$432.00 DRB Fee --------------------- >
$0.00
Additional Fees------ - - - - ->
$0.00
Investigation ->
$0.00 TOTAL FEES--------- - - - - ->
$717.12
Total Permit Fee ---------- >
$717.12
Will Call - - - - ->
$0.00
Payments ------------------- >
$717.12
BALANCE DUE --------- >
$0.00
**************************************************************************************************************
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE
DEPARTMENT
07/01/2011
mvaughan Action: AP
Spacing of
sprinkler heads
shall be in com
with
listing on cut sheets. Approval subject to field inspections.
CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 53
(FIRE 2007) Monitored fire sprinkler system required and shall comply with NFPA
13 (2007) and VFES Standards.
************************************************************************************************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970 - 479 -2252
FROM 8:00 AM - 5 PM.
SIGNATURE Of OWNER OR CONTRACTOR FOR HIMSELF AND OWNEF
Copy Reprinted on 01 -04 -2013 at 11:37:20
RECEIPT NUMBER: R110000738
SET ID: S000000364
SET RECEIPT
01/04/2013
SET NAME: Temporary Set
TRANSACTION DATE: 07/06/2011 TOTAL PAYMENT: 1,285.76
TOTAL PAID FROM TRUST: .00
TOTAL PAID FROM CURRENCY: 1,285.76
SET TRANSACTIONS:
Set Member Amount
---- - - - - -- ------ - - - - --
Fll -0034 717.12
Fll -0036 568.64
TOTAL: 717.12
TRANSACTION LIST:
Type Method Description Amount
---- - - - - -- -- - - - - -- --------------------- - - - - -- ------ - - - - --
Payment Check 120963 1,285.76
TOTAL: 1,285.76
ACCOUNT ITEM LIST:
Description Account Code Current Pmts
------------------------ - - - - -- ---------- - - - - -- ------ - - - - --
PLAN CHECK FEES PF 0010000311230 864.00
SPRINKLER PERMIT FEES BP 0010000311110 421.76
TOTAL: 1,285.76
RECEIPT ISSUED BY: LCAMPBELL INITIALS: LC
ENTERED DATE: 07/06/2011 TIME: 08:46 AM
FIRE SPRINKLER PERMIT
Commercial & Residential Fire Alarm shop drawings are required at the time of
application submittal and must include the following information:
1. A Colorado Registered Engineer's stamp or N.I.C.E.T level III (min) stamp
2. Equipment cut sheets of materials
3. Hydraulic calculations
4. A State of Colorado contractor registration number
5. Plans must be submitted by a Registered Fire Protection Contractor
Project Street Address: Office Use:
`bb C 1y\e6,kA, 5 Project #: C S I - ODq
(Number) (Street) (Suite #)
Building Permit #:
BuildinglComplex Name: `A Q Jv\A
Sprinkler Permit #:
Contractor Information: rt Lot M Block # Subdivision:
Company: JAk S �vut S F-1 Tvb}ec.�'1o�1
.
Company Address: 16x6 S,Tuc %y� t & Detailed Description of Work: tZe`D(Ak t�
City: ( idvll State: Zip: Q _ ilAo„ {��� — a . �o LEA
Contact Name: �oc��a t C� l� kewu bq,&k
(use additional sheet If necessary
Contact Phone: h7 O) ak 6 - 7 - 3 A r _ _
E -Mail ICo& C� wS'pp . US Detailed Location of Work: 1A\A �-
Town of Vail Contractor Registratlon No.:
Contractor Sign atur - eJr qutr y
Property Information _ i
Parcel M aw I OnV odd j
(For parcel #, contact Eagle County Assessors Office at 970 - 328 -8640 or
visit www.eaglecounty.us/patie) i
Tenant Name: 0_4.x\ �� Ul
c' �� t
i
Owner Name: s�sr�t — v.T7 J �a .�_+�c" . OT US 1�EA1I l
Complete Valuation for Fire Sprinkler Permit: Q CQAaY� .
Fire Sprinkler $: 0
Does a Monitored Fire Alarm Exist? Yes ( t'rNo ( )
Does a Sprinkler System Exist? Yes (� { )
Work Class:
New ( ) Addition ( ) Remodel ( -Repair ( )
Retro -Fit ( ) Other ( )
Type of Building:
Single - Family ( ) Duplex ( ) Multi - Family
Commercial ( ) Restaurant () Other ( )
Date Received:
JUN 2 0 2011
TOWN OF VAIL
01- Feb-10
el
Model F1 FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
- HSW 1 Deflector
Model F1 FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Listings & Approvals
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters' Laboratories of Canada (ULC)
3. Certified by FM Approvals
4. Loss Prevention Council (LPC, UK)
5. NYC BS&A No. 587 -75 -SA
6. Meets MIL- S -901C and MIL -STD 167 -1
7. Verband der Schadenversicherer (VdS, Germany)
8. NYC MEA 258 -93 -E
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number
VNIV
Patents: US Patent No. 6,374,920 Applies to
Model F1FR Vertical Sidewall Sprinklers.
Product Description
Reliable Models F1 FR and F1 FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a
standard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models F1 FR and F1 FR Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers. This
quick response enables the Model F1 FR and F1 FR Recessed
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response. The balance of
parts are made of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid ex-
Bulletin 136 Rev.O
Model F1 FR
Model F1 FR Recessed
Quick Response
Sprinklers
�f
O .
Upright
�ir i
i
Pendent
Vertical Sidewall Conventional
�- 11
Horizontal Sidewall Recessed Pendent
HSW 1 Deflector (Model FP Shown)
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13, FM Global Loss Prevention Data
Sheet 2 -8N or other applicable standards. Quick response
sprinklers and standard response sprinklers should not be
intermixed.
W
1
w
Lel
The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523
Model F1 FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
10mm Orifice XLH with W Thread 1 4.2 1 60 1 56mm 83674
1 15mm Standard Orifice with Y," NPT RY Thread 5.6 80 56mm 4,6,7 83675
20mm Lar a Orifice with 3 /4 ' NPT (R /,)Thread 8.0 115 58mm 4,7 83672
f) t Polyester coated upriqht UL and ULC listed corrosion resistant.
n
I
c�
Upright Pendent
Model F1 FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor
i
Sprinkler Identification
Sprinkler Type
Metric
y" (15mm)
Sprinkler
Approval
Number (SIN)
2.2" (56mm)
1,2,3,4,5,7,8
US Metric
_
Height
Organization
-
SSU __
Standard -U ri
ht (SSU
and Pendent (SSP) Deflectors
5.6 80
8.0 115
Marked to Indicate
2.2" 56mm
2.3" 58mm
Position
1,2,3,4,5,6,7
1,2,3,4,7,8
R3625
R3622
R3615
R3612
15mm Standard Orifice with " NPT (Ry ) Thread
20mm Large Orifice with 3 '" NPT R /A Thread
1,2,8
4.2
2.8
60
40
2.2 56mm
2.2" (56mm)
1,2,8
1,2,8
R3623t
R3621
R3613
R3611
"(17mm ) Smal I Orifice with "NPT Ry)Thread
(10mm ) Small Orifice with "NPT Ry)Thread
10mm Orifice XLH with R Thread
Rte
4.2
60
56mm
4,6,7
R3624
R3614
Conventional- Install in Upright or
Pendent Position
10mm Orifice XLH with W Thread 1 4.2 1 60 1 56mm 83674
1 15mm Standard Orifice with Y," NPT RY Thread 5.6 80 56mm 4,6,7 83675
20mm Lar a Orifice with 3 /4 ' NPT (R /,)Thread 8.0 115 58mm 4,7 83672
f) t Polyester coated upriqht UL and ULC listed corrosion resistant.
n
I
c�
Upright Pendent
Model F1 FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor
Sprinkler
Height
Approvalt' Sprinkler Identification
Organizations Number (SIN)
Us
Metric
y" (15mm)
Y NPT (R
5.6
80
2.2" (56mm)
1,2,3,4,5,7,8
R3615
'% " (20mm)
gY NPT (R
8.0
115
2.3" (58m
1,2,3,8
R3612
%B' (11 mm)
}z" NPT (RY2)
4.2
60
2.2" (56mm) —
1,2,8
R3613
Y'" (10mm)
}/ NPT (R' /2)
2.8
40
2.2" (56mm)
1,2,8
R3611
10mm
Rte
4.2
60
56mm t
4,7
83614
t' Refer to escutcheon data table for approvals and dimensions.
1 114' HOLE VIA.
(57.2mm]
1 15116" DA
(49.2 -1
1' X 111' REDVCER
lL'RN COLLAR
VNlIL FICHT
AGAINST SPRINKLER
NRENGI 8055
FACE OF
ADJUSTMENT (I) 00 VN 1 CEILI
fJ.1mm]
2 17132" VA.
[72.2mm] IJ6FG07_E
(1) REFER TO F1 h F2 ESCUTCHEON VAT, TABLE FOR APPROVALS AND DIMENSIONS.
"(
CEILING
f- 2 518 DIA. (66.7m 1
HOLE IN CEILING
2 5116" DIA. [58.7mm]
CUP
1 I
L J-
Convent
I X 112° REDUCER
VJDVC FACE OF FITTING
C - -- - TO FACE OF CEILING
\\ DIMENS/ON
(/}
11
A' (I)
4DJUSTM£NT -- --
--
(1) REFER FO FP ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
Model F1 FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal
Thread
K Factor
Sprinkler
Approval
Sprinkler
US
Metric
Orifice
Size
Height
Organizations
Identification
Number (SIN)
Y2" 1 /2" NPT (R /2)
5.6
80
2.2" (56mm)
1, 2, 3, 6, 8
[31.8mm)
2 114" HOLE DIA.
[57.2mmJ
R3685
15mm
Yi' NPT (R' /2)
5.6
80
2.2" (56mm)
4 (1)
DEFLECTOR
171 LPC Approval is for Pendent position only.
tis
d if
Vertical Sidewall
US Patent No. 6,374,920
Orientation Deflector to Ceiling
Dimension (Min. - M
Up right 4" - 12" 102mm - 305mm _
Pendent 6" - 12" 152mm - 305mm
Model F1 FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Approval Organizations
K Factor and Type of Approval
Nominal Thread Sprinkler Light Ordinary
Orifice Size US Metric Length Hazard Hazard
Y (15mm) I y" NPT(R'/2) 1 5.6 1 80 I 2.63" (67mm) I 1,2,3,5,8 1,2,5,8
NOTE: UL, ULC and MEA Listing permits use with F1 or F2 recessed escutcheon.
-1
Horizontal Sidewall
Sprinkler
Identification
Number (SIN)
R 3635
736FG04
(1) FACE
f!J
OF FITTING TO
WALL DIMENSION
1 1/4" MIN.
[31.8mm)
2 114" HOLE DIA.
[57.2mmJ
[3.2mm) [101.6mm- 152.4mm]
CEILING TO
1 " X 1/2" REDUCER
DEFLECTOR
1 15116" DIA. l inii
- --
49.2mm
[ )
2 27132" DIA.
liltl I
[72.2mm]
TURN COLLAR UNTIL
TIGHT SPRINKLER
`� t
WRENCH�BOSS.
`\
ADJUSTMENT
(1) REFER TO ESCUTHCEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
3.
Installation
Quick response sprinklers are intended for installation as
specified in NFPA 13, FM Global Loss Prevention Data Sheet
2 -8N or other applicable standards. Quick response sprin-
klers and standard response sprinklers should not be inter-
mixed.
The Model F1 FR Recessed Quick Response Sprinklers are to
be installed as shown. The Model F1 or F2 Escutcheons illus-
trated are the only recessed escutcheons to be used with the
Model F1 FR Sprinklers. The use of any other recessed escutch-
eon Will void all approvals and negate all warranties.
When installing Model F1 FR Sprinklers, use the Model D Sprin-
kler Wrench. When installing Model F1 FR Recessed Pendent or
Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any
other type of wrench may damage these sprinklers.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation. RE-
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Re-
moval of the protectors before this time may leave the bulb vul-
nerable to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PROTECTORS
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS
TO REMOVE THE PROTECTORS.
Temperature Ratin
Classification
Sprinkler
Tempe rature
Max. Ambient
Temp.
Bulb
Color
°C
"F
Ordinary
57
135
100
Orange
Ordinary
68
155
100 F(38°C)
Red
Intermediate
79
175
150-F (66-C)
Yellow
Intermediate
93
200
150-F (66-C)
Green
High (t)
141
286
225 °F(107 °C)
Blue
(t) Not available for recessed sprinklers.
Escutcheon Data
Esculdlieorti
S rinkler
Escutcheon
Bronze
Face of Filing
Model
Approtials
White Polyester Coated (4)
Dimension
to Ceiling or
Sprinkler
Escutcheon
Bright Brass
Bright Brass
Wall Dirttension
Black Plated
Black Paint
Black Paint
1 /
Off White
F1
1,2,4,8
Max Recess
(38.1 mm)
%6 " - %6
Min Recess
%"
(5mm -24mm)
19.1 mm
1y"
F2
1,2,3,4,5,7,8
Max Recess
(38.1 mm)
�/
716
Min Recess
6 ,6
(5mm -17mm)
24mm
FP
1,2
Max Recessed
�6
1y "(38.1mm)
11 mm
Push-on/
Thread -off
1,2
Min Recessed
/16
1" (25.4mm)
( 2 mm
No Dimensional Figure for FP
Maintenance
The Models F1FR and F1FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non - operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSW1
Finishes " 121
Standard Finishes
S rinkler
Escutcheon
Bronze
Brass
Chrome Plated
Chrome Plated (3)
White Polyester Coated (4)
White Painted (3)
Special Application Finishes
Sprinkler
Escutcheon
Bright Brass
Bright Brass
Black Plated
Black Plated
Black Paint
Black Paint
Off White
Off White
Satin Chrome
Satin Chrome
(t) Other finishes and colors are available on special order.
Consult the factory for details.
( FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
( FP Push- on/Thread -off escutcheon.
( UL and ULC listed corrosion resistance.
SIN numbers: R3621, R3622, R3623, R3625.
Note: For }2" orifice pendent FM approved white
polyester coated and UL approved white polyester
corrosion resistant sprinklers refer to Bulletin 014.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throuahout the United States. Canada and foreian countries.
Manufactured by
fleliabld
The Reliable Automatic Sprinkler Co., Inc.
(800)431 -1588 Sales Offices
(800)848 -6051 Sales Fax
(914)829 -2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Recycled
Paper
Revision lines indicate updated or new data
EG. Printed in U.S.A. 3/07 P/N9999970027
Wheatland's
Schedule 40
Sprinkler Pipe
Wheatland's Schedule 40 Sprinkler Pipe is a high quality sprinkler pipe offering you the full
range of assurances you require. Schedule 40 Sprinkler Pipe has passed some of the
toughest lab tests ever created for sprinkler pipe.
Made in the U.S.A. by Wheatland Tube
Company means made to the highest
standards for consistant quality.
Specifications and Approvals
Wheatland's schedule 40 Sprinkler Pipe is made
from the highest quality steel in one of the
nation's most modern and most complete pipe
manufacturing plants. Our proprietary mill coating
offers you a clean, corrosion and heat resistant
surface that outlasts and outperforms standard
lacquer coatings. Plus, this coating can be
quickly and easily painted without special
preparation. Or it may be hot - dipped galvanized
to meet FM requirements for dry systems in
accordance with the zinc coating specification of
ASTM A795. Schedule 40 is also available as
ASTM A 53 Type F, Grade A in NPS 1 - 6 and is
UL Listed and FM Approved.
Wheatland's Schedule 40 Standard
Wall Sprinkler Pipe meets or
exceeds the following:
• UL Listed
• FM Approved
• ASTM A795, Type E, Grade A
Please refer to appropriate documentation for
up -to -date listing and approval information.
Specifications and descriptions are accurate as
known at time of publication and are subject to
change without notice.
Specifications
NPS
Nominal O.D
Nominal I.D
Nominal Wall
Nominal Weight
UL CRR'
Pieces
Lift
in.
mm
in.
mm
in.
mm
lbs. /ft.
kg /m
1 "
1.315
33.4
1.049
26.6
.133
3.38
1.68
2.50
1.00
70
1 1/4"
1.660
42.2
1.380
35.1
.140
3.56
2.27
3.39
1.00
51
1 1/2"
1.900
48.3
1.610
40.9
.145
3.68
2.72
4.05
1.00
44
2"
1 2.375
1 60.3
1 2.067
1 52.5
.154
3.91
3.66
1 5.45
1.00
30
Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY
The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. Schedule 40 steel pipe is used as the
benchmark (value of 1.0).
Wheatland Tube Company
Council Avenue, P.O. Box 608 Wheatland, PA 16161 -0608
Ph 800.257.8182 Fax 724.346.7260
www.wheatiand.com 0207 1.Wrev01