HomeMy WebLinkAbout10-039 Fireproofing 11-30-10 FIREPROOFII`IG 8494 WHEATGRASS CIRCLE.
- � PARKER,CO 80134
INSPEGTION REPORT 303-957-8436
WESTERN STATES
INSPECTION
Pa�E 1 0�2
CLIENT KOECHLI�IV COI�ISULT1NCa ENGINEERS
PROJECT/JOB# KCE# 'I 0-0�9 CLIE,NT PO# LIONSHEAD TRANS[T CENTER
DATE 1 1-30-'1 O CODE IIVTERNATtONAL BU[LD[NG CODE
HOURS OF SHIFT 6:00 AM TO 1 2:00 PM SPECIFICATION PROJECT SPECS.
M[LEAGE TO �OO MILEAC,E FROM 1 OO C�AY OF WEEK TUESDAY
INSPECTOR ROBERT H. POLLOCK TOTAL HOURS TODAY (6)
ASSISTANT NfA TOTAL MILEAGE 2OO
PER DIEM YES NO X CLIENT REP. SCOTT MEYER (KCE)
REPORT# LTC-04
REMARKS:
L[ONSHEAD TRANSIT CENTER
350 S. FROrvTaGE RD.
VA1L, CO.
1) TRAVEL TO PROJECT SITE, AS REQUESTED.
2) CONDUCT V[SUAL II�ISPEC710N AhiD REQUIR6D THICKNESS TESTWG OF"SPRAY APPLIED F[RE
RES[STNE MATER[AL" ON BUILDING STRUCTURAL MEMBERS.
3) THE FOLLOV�lING TYPES OF TESTING WILL BE CONDUCTED:
[,A,] V[SUAL[NSPECTION 8c THICKNESS TES7ING (ASTM SPEC. E6O'rJ &lBC)
[B] DRY DENSITY T�STING OF IN—PLAC�SFRM (ASTM SPEC.. E605&[BC)
[C] ADHESION I COHESION 7ESTING OF IN—PL.ACE SFRM (ASTM SPEC. E736 &IBC)
4) S�E ATTACHED R�PORT FOR DETAILS.
L�. �NG
E� �R� ` 186
Ppp �oa
S GG G
� ICG SPECIAL.INSPECTOR �SPRAY APPLIED FIREPROOFING� C�RT. #08752]-86 �
SIGNATURE ROBERT H. POLLOCK R • ��^'�"�
(INSPECTOR) ,
� F I R E P 1R00 F I 1`I C 8494 WHEATGRASS CIRCLE.
� y_�_ PARKER,CO SO 13�4
� �� Il`ISPECTION REPORT 303-957-8436
WESTERN STATES
INSPECTION
Pa�E 2 oF 2
CLIENT KOECHLIEN CONSULTII�IG �NGINEERS
PROJECT/,10B# KCE# �0-039 CL[ENT PO# LIOI�ISHEAD TRANS[7 CENT�R
DATE j 1-30-�O CODE INTERNAT[ONAL BUILDfIVCs CODE
HOURS OF SHIFT PG. 1 PM TO PG. 'l PM SPEGIFICATIOIV PROJEC7 SPECS.
M[LEAGE TO PG. 1 MILEAGE FROM PG. 1 DAY OF WEEK TUESDAY
INSPECTOR ROBERT H. POLLOCK TOTAL HOURS TODAY PG. '1
ASS1S?ANT NIA TOTAL MILEAGE PC. l
PER DIEM YES NO X CLIENT REP. SCOTT MEYER (KGE)
R�PORT# LTC-04
REMARKS:
� S/W STAIRS�
'I) COI�IDUCT V[SUAL I[�ISPECT[ON AND THICKNESS TESTING OF INTUMESCENT PAINT(ALBI CLAD 8OO)
APPLIED 70 (2) 6'�DIA.PIPE COLUMNS.THE FOLLOV�lING SHALL BE NOTED:
� ALBI COTE 49OW PRIMER WAS APPL[ED, PRIOR TO FINAL COATS �AGCEPTED�
IBI ALBI CLAD 8OO HAS BEEN APPLIED TO EXCEED THE MINIMUM [ACCEPTED]
THICKNESS REQUIREMENT (.B�J")
[Cl FINAL ACCEPTANCE OF APPLICAT[ON AT TH[S AREA WILL BE DELAYED UIVT[L IINFO]
PRODUCT HAS FULLY CURED
[D] AREA HAS BEEN HEATED TO ALLOW PROPER CURING OF PRODUCT.
�!�
�C p Roo
pL\E ��5�,1'
SP GEP� '
~ ICC SPECIAL INSPEC'TOR �SPRAY APPLIED FIREPROOF[NG� CERT. #08752 i-86 �
SIGNA7URE ROBERT H. POLLOCK R � ��(��
([NSPECTOR) .