Date: July 6, 2011
Re: B11-0185
Dear Steve,
RESPONSE INSTRUCTIONS
● Submit three complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each comment.
BUILDING COMMENTS
Architectural Comments:
Sheet A2.1
1 Annotate on plans the required smoke and CO detectors
Structural Comments:
General
1. Provide signed special inspection agreement for welding with resubmittal.
2. Show location and method for required snow retention per amended Town of Vail building code.
Plumbing Comments:
Sheet A2.1
1. Provide gas piping plan per Town of vail submittal requirements.
Mechanical Comments:
Reviewed and accepted
Electrical Comments:
General
1. Show location and size of service panel and sub panels per Town of vail submittal requirements.
2. Annotate on plans lighting to be 50% high efficacy per IECC.
3. Provide exterior lighting plan per Town of Vail submittal requirements.
PLANNING COMMENTS
Reviewed and accepted
FIRE COMMENTS
Reviewed and accepted
PUBLIC WORKS COMMENTS
NA
Sincerely,
Martin A. Haeberle
Chief Building Official