Hydraulic Calcs
LIONSHEAD WELCOME CENTER 395 EAST LIONSHEAD CIRCLE VAIL, CO HYDRAULIC CALCULATIONS AND PRODUCT SUBMITTALS THIS SET OF FIRE SPRINKLER SHOP SPECIFICATIONS AND HYDRAULIC CALCULATIONS HAVE BEEN REVIEWED AND FOUND TO BE ACCEPTABLE – N.I.C.E.T. IV #102055 SR. ENGINEERING TECHNICIAN – FIRE PROTECTION, NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNICIANS ________________________ _________________________ ________/________/__________ TIMOTHY N TROSTEL, JR – SET DATE PHOENIX AUTOMATIC SPRINKLER 7684 S. BRENTWOOD ST. LITTLETON, CO 80128 720.922.9231 PHONE Project Name : LIONSHEAD WELCOME CENTER Drawing No. : Project Location: 395 EAST LIONSHEAD CIRCLE City: VAIL, CO 81657 CALCULATION SUMMARY Design Areas Design Area Name Min. Density Area of Application Occupancy Calculated Heads Min. Pressure Hose Streams Total Water Pressure @Source Margin To Source (ft²) (gpm) (psi) (gpm/ft²) (psi) # (gpm) (psi) Min. Flow (gpm) Calc. Mode (Model) 1 Demand (HW) LIGHT 1400 483.9 78.9 0.1 16.1 22.5 16 100 40.9 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 1 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg DesignRemote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Pressure at Source (psi) Type of System Volume -Entire System (gal) 1 3RD FLOOR EAST SIDE LIGHT 0.1 1400 225 16 0 100 483.9 78.9 Wet 297.7 gal Water Supply Information Date Location Source HYDRAULIC CALCULATIONS for 5-23-11 HYD NEAR BLD W1 ENTIRE 3RD FLOOR EVENT RM Project Name : LIONSHEAD WELCOME CENTER Contract No. : Project Location: 395 EAST LIONSHEAD CIRCLE City: VAIL, CO 81657 Date: 5/24/2011 Name of Contractor: PHOENIX AUTOMATIC SPRINKLER Address: Phone Number: Name of Designer: DBA Authority Having Jurisdiction: VAIL FIRE DEPARTMENT City: LITTLETON, CO E-mail: Job Information Contractor Information Notes Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 2 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Diagram for Design Area : 1 (Optimized Hydraulic Simplified) Node Labels: Pipe Labels: Off Off Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 3 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Hydraulic Analysis for : 1 Water Supply Parameters Calculation Info Calculation Mode Hydraulic Model Fluid Name Fluid Weight, (lb/ft³) Fluid Dynamic Viscosity, (lb·s/ft²) Demand Hazen-Williams Water @60F (15.6C) N/A for Hazen-Williams calculation. N/A for Hazen-Williams calculation. Supply 1 : W1 Flow (gpm) Pressure (psi) 0 124 1350 81 Inside Hose Flow (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm) 100 100 HosesOvehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm) 383.9 0 0 383.9 Required Margin of Safety (psi) W1 -Pressure (psi) W1 -Flow (gpm) Demand w/o System Pump(s) 0 78.9 383.9 N/A Sprinklers Other Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 4 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Hydraulic Analysis for : 1 Supply System Demand Add. Out. Hose Flow, gpm Pressure, psi 150 140 130 120 110 100 90 80 70 60 50 40 30 20 100 S1 S2 71.746 D1 D2 D3 0 400500 600 700 800 900 1000 1100 1200 1300 1400 1500 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 5 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Hydraulic Analysis for : 1 Pressure (psi) Label Graph Labels Flow (gpm) Values Description S1 Supply point #1 -Static 0 124 S2 Supply point #2 -Residual 1350 81 D1 Elevation Pressure 0 11 D2 System Demand 383.9 78.9 D3 System Demand + Add.Out.Hose 483.9 78.9 Pressure (psi) Curve Name Curve Intersections & Safety Margins Flow (gpm) Intersection Safety Margin Pressure (psi) @Flow (gpm) Supply 117.4 489.5 38.7 483.9 Open Heads Head Ref. Density Density K-Factor Flow Pressure Pressure (gpm/psi½) (gpm/ft²) (gpm) (psi) (gpm/ft²) (psi) Flow (gpm) Coverage (ft²) Required Calculated Head Type 100 Overhead 225 5.6 0.1 22.5 16.1 0.105 23.7 17.9 Sprinkler 101 Overhead 225 5.6 0.1 22.5 16.1 0.108 24.2 18.7 Sprinkler 102 Overhead 225 5.6 0.1 22.5 16.1 0.106 23.9 18.3 Sprinkler 103 Overhead 225 5.6 0.1 22.5 16.1 0.101 22.6 16.4 Sprinkler 104 Overhead 225 5.6 0.1 22.5 16.1 0.106 23.8 18.1 Sprinkler 105 Overhead 225 5.6 0.1 22.5 16.1 0.1 22.5 16.1 Sprinkler 106 Overhead 225 5.6 0.1 22.5 16.1 0.102 22.9 16.7 Sprinkler 107 Overhead 225 5.6 0.1 22.5 16.1 0.107 24.1 18.5 Sprinkler 108 Overhead 225 5.6 0.1 22.5 16.1 0.101 22.8 16.5 Sprinkler 109 Overhead 225 5.6 0.1 22.5 16.1 0.104 23.5 17.6 Sprinkler 110 Overhead 225 5.6 0.1 22.5 16.1 0.11 24.7 19.4 Sprinkler 111 Overhead 225 5.6 0.1 22.5 16.1 0.104 23.3 17.3 Sprinkler 112 Overhead 225 5.6 0.1 22.5 16.1 0.108 24.4 19 Sprinkler Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 6 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg 113 Overhead 225 5.6 0.1 22.5 16.1 0.114 25.6 21 Sprinkler 114 Overhead 225 5.6 0.1 22.5 16.1 0.108 24.2 18.7 Sprinkler 115 Overhead 225 5.6 0.1 22.5 16.1 0.122 27.5 24.2 Sprinkler Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 7 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Node Data Hydraulic Calculations /Fluid Delivery Time Analysis Node# Elev ft Type Hgroup K-Fact. Open/Closed gpm/psi½ Discharge Overdischarge gpm gpm Coverage Density ft² gpm/ft² Tot. Pres. Elev. Pres. psi psi Req. Pres. Req. Discharge psi gpm 105 28.29 Overhead Sprinkler HEAD 5.6 Open 22.5 0 225 0.1 16.1 -11 16.1 22.5 103 28.29 Overhead Sprinkler HEAD 5.6 Open 22.6 0.1 225 0.101 16.4 -11 16.1 22.5 108 28.29 Overhead Sprinkler HEAD 5.6 Open 22.8 0.3 225 0.101 16.5 -11 16.1 22.5 106 28.29 Overhead Sprinkler HEAD 5.6 Open 22.9 0.4 225 0.102 16.7 -11 16.1 22.5 111 28.29 Overhead Sprinkler HEAD 5.6 Open 23.3 0.8 225 0.104 17.3 -11 16.1 22.5 109 28.29 Overhead Sprinkler HEAD 5.6 Open 23.5 1 225 0.104 17.6 -11 16.1 22.5 100 28.29 Overhead Sprinkler HEAD 5.6 Open 23.7 1.2 225 0.105 17.9 -11 16.1 22.5 104 28.29 Overhead Sprinkler HEAD 5.6 Open 23.8 1.3 225 0.106 18.1 -11 16.1 22.5 102 28.29 Overhead Sprinkler HEAD 5.6 Open 23.9 1.4 225 0.106 18.3 -11 16.1 22.5 107 28.29 Overhead Sprinkler HEAD 5.6 Open 24.1 1.6 225 0.107 18.5 -11 16.1 22.5 101 28.29 Overhead Sprinkler HEAD 5.6 Open 24.2 1.7 225 0.108 18.7 -11 16.1 22.5 114 28.29 Overhead Sprinkler HEAD 5.6 Open 24.2 1.7 225 0.108 18.7 -11 16.1 22.5 112 28.29 Overhead Sprinkler HEAD 5.6 Open 24.4 1.9 225 0.108 19 -11 16.1 22.5 110 28.29 Overhead Sprinkler HEAD 5.6 Open 24.7 2.2 225 0.11 19.4 -11 16.1 22.5 113 28.29 Overhead Sprinkler HEAD 5.6 Open 25.6 3.1 225 0.114 21 -11 16.1 22.5 115 28.29 Overhead Sprinkler HEAD 5.6 Open 27.5 5 225 0.122 24.2 -11 16.1 22.5 312 45.22 Node NODE 12.8 -18.3 323 45.22 Node NODE 13.3 -18.3 315 41.94 Node NODE 13.4 -16.9 326 41.94 Node NODE 13.9 -16.9 334 45.22 Node NODE 14.3 -18.3 281 45.22 Node NODE 14.8 -18.3 337 41.94 Node NODE 14.8 -16.9 284 42.7 Node NODE 15.7 -17.2 311 41.73 Node NODE 15.8 -16.8 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 8 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Node Data Hydraulic Calculations /Fluid Delivery Time Analysis Node# Elev ft Type Hgroup K-Fact. Open/Closed gpm/psi½ Discharge Overdischarge gpm gpm Coverage Density ft² gpm/ft² Tot. Pres. Elev. Pres. psi psi Req. Pres. Req. Discharge psi gpm 285 41.94 Node NODE 15.9 -16.9 345 45.22 Node NODE 16 -18.3 322 41.73 Node NODE 16.3 -16.8 280 41.73 Node NODE 16.5 -16.8 348 41.94 Node NODE 16.5 -16.9 278 41.29 Node NODE 17.2 -16.6 333 41.73 Node NODE 17.3 -16.8 276 41.29 Node NODE 17.4 -16.6 274 41.29 Node NODE 17.9 -16.6 272 41.29 Node NODE 19.1 -16.6 344 41.73 Node NODE 19.2 -16.8 270 41.29 Node NODE 21 -16.6 002 41.29 Node NODE 23.9 -16.6 013 38.29 Node NODE 47 -15.3 014-A 38.29 Node NODE 47 -15.3 014-B 38.29 Node NODE 48.2 -15.3 016-A 38.29 Node NODE 48.3 -15.3 016-B 38.29 Node NODE 50.7 -15.3 018-A 38.29 Node NODE 50.7 -15.3 018-B 38.29 Node NODE 51.3 -15.3 019 38.29 Node NODE 52.6 -15.3 026-A 6.5 Node NODE 71.2 -1.5 026-B 6 Node NODE 71.7 -1.3 028-A 3.17 Node NODE 73.1 -0.1 028-028-B 2.67 Node NODE 76.1 0.1 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 9 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Node Data Hydraulic Calculations /Fluid Delivery Time Analysis Node# Elev ft Type Hgroup K-Fact. Open/Closed gpm/psi½ Discharge Overdischarge gpm gpm Coverage Density ft² gpm/ft² Tot. Pres. Elev. Pres. psi psi Req. Pres. Req. Discharge psi gpm W1 3 Supply SUPPLY -383.9 78.9 0 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 10 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Hydraulic Calculations PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) LFT (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES Path No: 1 105 315 28.29 41.94 5.6 22.5 22.5 1 1.049 1x(us.Tee-Br)=5 14.815 19.81 120 0.1613 16.1 -5.9 3.2 315 312 41.94 45.22 0 22.5 1.25 1.38 2x(us.90)=6 13.26 19.2 120 0.0424 13.4 -1.4 0.8 312 311 45.22 41.73 22.6 45.1 1.25 1.38 9.220 9.22 120 0.154 12.8 1.5 1.4 311 276 41.73 41.29 23.8 69 1.5 1.61 1x(us.Tee-Br)=8 1.158 9.15 120 0.1593 15.8 0.2 1.5 276 274 41.29 41.29 71.9 140.8 2.5 2.635 9.840 9.84 120 0.0543 17.40 0.5 274 272 41.29 41.29 69.8 210.6 2.5 2.635 9.780 9.78 120 0.1144 17.90 1.1 272 270 41.29 41.29 71.4 282 2.5 2.635 10.030 10.03 120 0.1964 19.102 270 002 41.29 41.29 74.3 356.3 2.5 2.635 9.50 9.5 120 0.3029 210 2.9 002 013 41.29 38.29 27.5 383.9 2.5 2.635 3x(us.90)=24.71 37.85 24.71 62.56 120 0.3477 23.9 1.3 21.8 013 014-A 38.29 38.29 0 383.9 3 3.26 0.540 0.54 120 0.1233 470 0.1 014-A 014-B 38.29 38.29 0 383.9 30 101 0 1.2037 470 1.2 Riser Manifold 014-B 016-A 38.29 38.29 0 383.9 3 3.26 0.880 0.88 120 0.1233 48.20 0.1 016-A 016-B 38.29 38.29 0 383.9 30 101 0 2.339 48.30 2.3 VIC CHECK 016-B 018-A 38.29 38.29 0 383.9 3 3.26 0.490 0.49 120 0.1233 50.70 0.1 018-A 018-B 38.29 38.29 0 383.9 30 101 0 0.6164 50.70 0.6 Butterfly Valve 018-B 019 38.29 38.29 0 383.9 3 3.26 1x(us.90)=9.41 0.45 9.41 9.86 120 0.1233 51.30 1.2 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 11 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Hydraulic Calculations PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) LFT (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES Path No: 1 019 026-A 38.29 6.5 0 383.9 4 4.26 4x(us.90)=52.67 1x(us.Tee-Br)=26.33 65.53 79 144.53 120 0.0335 52.6 13.8 4.8 026-A 026-B 6.56 0 383.9 40 101 0 0.3329 71.2 0.2 0.3 Flow Switch 026-B 028-A 6 3.17 0 383.9 4 4.26 3.330 3.33 120 0.0335 71.7 1.2 0.1 028-A 028-B 3.17 2.67 0 383.9 40 101 0 2.7687 73.1 0.2 2.8 Febco850 028-B W1 2.673 0 383.9 4 4.3 3x(us.90)=54.98 67.9 54.98 122.88 140 0.0241 76.1 -0.13 W1 78.9 Path No: 2 103 312 28.29 45.22 5.6 22.6 22.6 1 1.049 1x(us.Tee-Br)=5 18.35 23.3 120 0.1632 16.4 -7.3 3.8 312 12.8 Path No: 3 108 326 28.29 41.94 5.6 22.8 22.8 1 1.049 1x(us.Tee-Br)=5 14.815 19.81 120 0.1648 16.5 -5.9 3.3 326 323 41.94 45.22 0 22.8 1.25 1.38 2x(us.90)=6 13.26 19.2 120 0.0433 13.9 -1.4 0.8 323 322 45.22 41.73 22.9 45.7 1.25 1.38 9.220 9.22 120 0.1574 13.3 1.5 1.5 322 274 41.73 41.29 24.1 69.8 1.5 1.61 1x(us.Tee-Br)=8 1.158 9.15 120 0.1628 16.3 0.2 1.5 274 17.9 Path No: 4 106 323 28.29 45.22 5.6 22.9 22.9 1 1.049 1x(us.Tee-Br)=5 18.35 23.3 120 0.1668 16.7 -7.3 3.9 323 13.3 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 12 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Hydraulic Calculations PIPE INFORMATION Path No: 5 111 337 28.29 41.94 5.6 23.3 23.3 1 1.049 1x(us.Tee-Br)=5 14.815 19.81 120 0.1722 17.3 -5.9 3.4 337 334 41.94 45.22 0 23.3 1.25 1.38 2x(us.90)=6 13.26 19.2 120 0.0453 14.8 -1.4 0.9 334 333 45.22 41.73 23.5 46.8 1.25 1.38 9.220 9.22 120 0.1645 14.3 1.5 1.5 333 272 41.73 41.29 24.7 71.4 1.5 1.61 1x(us.Tee-Br)=8 1.158 9.15 120 0.1701 17.3 0.2 1.6 272 19.1 Path No: 6 109 334 28.29 45.22 5.6 23.5 23.5 1 1.049 1x(us.Tee-Br)=5 18.35 23.3 120 0.1743 17.6 -7.3 4.1 334 14.3 Path No: 7 100 281 28.29 45.22 5.6 23.7 23.7 1 1.049 1x(us.Tee-Br)=5 18.35 23.3 120 0.1779 17.9 -7.3 4.1 281 280 45.22 41.73 23.9 47.7 2 2.067 9.220 9.22 120 0.0238 14.8 1.5 0.2 280 278 41.73 41.29 24.2 71.9 2 2.067 1x(us.Tee-Br)=10 1.15 10 11.15 120 0.051 16.5 0.2 0.6 278 276 41.29 41.29 0 71.9 2.5 2.635 9.90 9.9 120 0.0156 17.20 0.2 276 17.4 Path No: 8 104 311 28.29 41.73 5.6 23.8 23.8 1 1.049 1x(us.Tee-Br)=5 14.525 19.52 120 0.1791 18.1 -5.8 3.5 311 15.8 Path No: 9 102 285 28.29 41.94 5.6 23.9 23.9 1 1.049 1x(us.Tee-Br)=5 14.815 19.81 120 0.1809 18.3 -5.9 3.6 285 284 41.94 42.7 0 23.9 1.25 1.38 1.970 1.97 120 0.0476 15.9 -0.3 0.1 284 281 42.7 45.22 0 23.9 2 2.067 2x(us.90)=10 11.23 10 21.23 120 0.0066 15.7 -1.1 0.1 281 14.8 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 13 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Hydraulic Calculations PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) LFT (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES Path No: 10 107 322 28.29 41.73 5.6 24.1 24.1 1 1.049 1x(us.Tee-Br)=5 14.525 19.52 120 0.183 18.5 -5.8 3.6 322 16.3 Path No: 11 101 280 28.29 41.73 5.6 24.2 24.2 1 1.049 1x(us.Tee-Br)=5 14.525 19.52 120 0.1848 18.7 -5.8 3.6 280 16.5 Path No: 12 114 348 28.29 41.94 5.6 24.2 24.2 1 1.049 1x(us.Tee-Br)=5 14.815 19.81 120 0.1852 18.7 -5.9 3.7 348 345 41.94 45.22 0 24.2 1.25 1.38 2x(us.90)=6 13.26 19.2 120 0.0487 16.5 -1.4 0.9 345 344 45.22 41.73 24.4 48.6 1.25 1.38 9.220 9.22 120 0.1769 16 1.5 1.6 344 270 41.73 41.29 25.6 74.3 1.5 1.61 1x(us.Tee-Br)=8 1.158 9.15 120 0.1829 19.2 0.2 1.7 270 21 Path No: 13 112 345 28.29 45.22 5.6 24.4 24.4 1 1.049 1x(us.Tee-Br)=5 18.35 23.3 120 0.1874 19 -7.3 4.4 345 16 Path No: 14 110 333 28.29 41.73 5.6 24.7 24.7 1 1.049 1x(us.Tee-Br)=5 14.525 19.52 120 0.1912 19.4 -5.8 3.7 333 17.3 Path No: 15 113 344 28.29 41.73 5.6 25.6 25.6 1 1.049 1x(us.Tee-Br)=5 14.525 19.52 120 0.2055 21 -5.84 344 19.2 Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 14 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Hydraulic Calculations PIPE INFORMATION Path No: 16 115 002 28.29 41.29 5.6 27.5 27.5 1 1.049 1x(us.Tee-Br)=5 1x(us.90)=2 15.777 22.77 120 0.2346 24.2 -5.6 5.3 002 23.9 * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. * Maximum Velocity of 22.58 ft/s occurs in the following pipe(s): (013-002) Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 15 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Device Graphs Pressure vs. Flow Function Design Area: 1; Supply Ref.: W1; Supply Name:W1 Flow, gpm 0 200 300 400 500 600 700 800 900 1000 1350 Pressure, psi 140 130 120 110 100 90 80 70 60 50 40 30 20 100 Pressure Loss Function Design Area: 1; BFP Ref.: 441 (Febco850, Size = 4) Flow, gpm 50 200 400 600 Pressure, psi 4.5 3.5 2.5 1.5 0.5 2.8 psi @383.9 gpm Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 16 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Device Graphs Pressure Loss Function Design Area: 1; Valve Ref.: 437 (Riser Manifold, Size = 3) Flow, gpm 0 100 200 250 300 400 500 600 700 800 1000 Pressure, psi 6.953 5.953 4.953 3.953 2.953 1.953 0.953 1.2 psi @383.9 gpm Pressure Loss Function Design Area: 1; Valve Ref.: 438 (VIC CHECK, Size = 3) Flow, gpm 0 20 30 50 100 150 200 250 300 350 400 450 500 550 600 700 Pressure, psi 6.15 5.15 4.15 3.15 2.15 1.15 0.15 2.3 psi @383.9 gpm Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 17 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg Job : LIONSHEAD WELCOME CENTER Device Graphs Pressure Loss Function Design Area: 1; Valve Ref.: 439 (Butterfly Valve, Size = 3) Flow, gpm 0 50 100 200 250 300 400 500 600 700 750 800 900 1000 Pressure, psi 3.477 2.977 2.477 1.977 1.477 0.977 0.477 0.6 psi @383.9 gpm Pressure Loss Function Design Area: 1; Valve Ref.: 440 (Flow Switch, Size = 4) Flow, gpm 0 50 100 200 300 400 500 750 1000 1500 2000 Pressure, psi 6.788 5.788 4.788 3.788 2.788 1.788 0.788 0.3 psi @383.9 gpm Date 6/16/2011 Copyright © 2002-2011 Tyco Fire Protection Products Page 18 File: C:\dwg\Phoenix Fire\LionsHead\LH FS-1.dwg ES-F-850L S P E C I F I CAT I O N S H E E T FEBCO product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact FEBCO. FEBCO reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on FEBCO products previously or subsequently sold. Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––––––––––––––––––– Job Location ––––––––––––––––––––––––––––––––––––––––– Approval ––––––––––––––––––––––––––––––––––––––––––––– Engineer –––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. –––––––––––––––––––––––––––––––––– Approval –––––––––––––––––––––––––––––––––––––––––––– Representative –––––––––––––––––––––––––––––––––––––––– MasterSeries® 850 Double Check Valve Assemblies Size: 21⁄2" -10" (65mm -250mm) The FEBCO Master Series® 850 Double Check Valve Assemblies are designed for non-health hazard applications. End Connections – Flanged ANSI B16.1 Class 125 Pressure – Temperature Max. Working Pressure: 175psi (12.1 bar) Hydrostatic Test Press: 350psi (24.1 bar) Temperature Range: 32°F to 140°F (0°C to 60°C) Materials Main Valve Body: Ductile iron Grade 65-45-12 Coating: Fusion epoxy coated internal and external AWWA C550-90 Shutoff Valves: NRS resilient wedge gate valves AWWA C509 Trim: Bronze Elastomer Discs: EPDM Spring: Stainless steel Clamp: AWWA C606 Approvals – Standards • Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. -21⁄2" -8" (65 -80mm) (Horizontal & Vertical Up) • ANSI/AWWA (C510) -21⁄2" -8" (Horizontal & Vertical Up), 10" (Horizontal) * Less gates not FM approved. Less gates not UL Classified unless installed with UL listed gate valves. Model 850 Vertical Installation Flow 4" min (100mm) Refer to local codes Model 850 Double Check Assembly U.S. Patent No. 4,989,635 HEADLOSS Capacity 21⁄2" 3" 21⁄2" & 3" (65mm & 80mm) kPa psi 103 15 69 10 34 5 0 0 0 80 160 240 320 400 gpm 0 304 606 910 1210 1520 lpm 4" & 6" (100mm & 150mm) kPa psi 103 15 69 10 34 5 0 0 0 400 800 1200 1600 2000 gpm 0 1520 3040 4540 6060 7600 lpm 8" & 10" (200mm & 250mm) kPa psi 103 15 69 10 34 5 0 0 0 1000 2000 3000 4000 5000 gpm 0 3800 7600 11400 15140 19000 lpm HEADLOSS HEADLOSS Models • UL/FM OS&Y RW Gate Valves • Wye-Strainer 1015 B64.5 6" Min. (150mm) Refer to local codes 21⁄2" -8" (65 -200mm) (Horizontal & Vertical up) 10" (250mm) (Horizontal) 21⁄2" -8" (65 -200mm) (Horizontal & Vertical up) SIZE (DN) DIMENSIONS A B C* D G H NRS OS&Y in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. lbs. kgs. 21⁄2 65 403⁄4 1035 251⁄2 648 125⁄8 321 10 254 41⁄2 114 71⁄8 181 199 90 203 92 3 80 417⁄8 1064 255⁄8 651 127⁄8 327 10 254 41⁄2 114 73⁄8 187 211 96 213 97 4 100 461⁄4 1175 28 711 143⁄8 365 101⁄8 257 51⁄2 140 81⁄8 206 288 131 312 142 6 150 56 1422 343⁄4 883 187⁄8 479 123⁄4 324 61⁄2 165 97⁄8 251 450 204 494 224 8 200 65 1651 413⁄4 1061 231⁄2 597 155⁄8 397 7 178 111⁄8 283 711 323 773 351 10 250 725⁄8 1845 463⁄8 1178 271⁄2 699 155⁄8 397 9 229 123⁄8 314 980 445 1080 490 Dimensions and Weights Size: 21⁄2" -10" (65 -250mm) ITEM DESCRIPTION MATERIAL 1 Body A536 GR 65-45-12 1.1 Pipe Plug Galv. Steel 1.2 Bushing (21/2 -4 only) Brass 2 Cover A536 GR 65-45-12 2.1 O-Ring EPDM ASTM D2000 2.2 Cap Screw Plated Steel 2.3 Hex Nut Plated Steel 3 Seat Ring B584 Alloy C83600 3.1 Gasket EPDM ASTM D2000 4 Arm B584 Alloy C83600 4.1 Bushing-Swing Pin Acetal Resin 4.2 Swing Pin 304 SS 5 Retaining Clip 302 SS 5.1 Retaining Clip 302 SS 6 Check Disk Assy EPDM Coated GR, 45 Ductile Iron with type 304 SS stem 7 Load Pin 304 SS 8 Lwr Spring Retnr B584 Alloy C83600 9 Spring Stem 304 SS 9.1 Elastic Stop Jam Nut 18-8 SS 10 Spring A313 Type 631 SS 11 Spring Guide B130 Alloy C22000 12 Upr Spring Retnr B584 Alloy C83600 12.1 Bushing-Spr. Stem Acetal Resin 13 Pivot Bearing B585 Alloy C83600 14 Flange Gasket Rubber/Fabric 15 Bearing Socket Acetal Resin 16 Hex Jam Nut 18-8 SS 17 Washer 302 SS 18 Flange Nut Plated Steel 18.1 Flange Nut Plated Steel 19 Cover A36 Stl Epoxy Coated 24 Bolt Plated Steel 24.1 Washer Plated Steel 25 Nut Plated Steel 26 Gasket EPDM ASTM D2000 35 O-Ring EPDM ASTM D2000 35.1 Back-Up Ring Acetal Resin 36 Cover B584 Alloy C83600 40 Ball Valve B584 Alloy C84400 41 Nipple Brass 41.1 Nipple Brass 41.2 Nipple Brass 42 Gate Valve AWWA C509 60 Id Plate B36 Alloy C26000 62 Drive Screw SS 70 Clamp AWWA 606 (10" Only, Not Shown Above) Model 850 /Materials of Construction Top View * With NRS Gate Valves Note: Dimensions shown are nominal. Allowances must be made for normal manufacturing tolerances. USA: 4381 N. Brawley • Ste. 102 • Fresno, CA • 93722 • Tel. (559) 441-5300 • Fax: (559) 441-5301 • www.FEBCOonline.com Canada: 5435 North Service Rd. • Burlington, ONT. • L7L 5H7 • Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.FEBCOonline.ca ES-F-850L 0651 © 2009 FEBCO A Watts Water Technologies Company B A D CHG General Description The Series TY-FRB, 2.8, 4.2, 5.6, and 8.0 K-factor, Upright and Pendent Sprinklers described in this data sheet are quick response -standard coverage, decorative 3 mm glass bulb type spray sprinklers designed for use in light or ordinary hazard, commercial occupancies such as banks, hotels, shopping malls, etc. The recessed version of the Series TY-FRB Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. It uses either a two-piece Style 10 (1/2 inch NPT) or Style 40 (3/4 inch NPT) Recessed Escutcheon with 1/2 inch (12,7 mm) of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment from the flush pendent position, or a two-piece Style 20 (1/2 inch NPT) or Style 30 (3/4 inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush pendent position.The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. An intermediate level versions of the Series TY-FRB Pendent Sprinklers are detailed in Technical Data Sheet TFP356, and Sprinkler Guards are detailed in Technical Data Sheet TFP780 WARNINGS The Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Model/Sprinkler Identification Numbers TY1131 -Upright 2.8K, 1/2"NPT TY1231 -Pendent 2.8K, 1/2"NPT TY2131 -Upright 4.2K, 1/2"NPT TY2231 -Pendent 4.2K, 1/2"NPT TY3131 -Upright 5.6K, 1/2"NPT TY3231 -Pendent 5.6K, 1/2"NPT TY4131 -Upright 8.0K, 3/4"NPT TY4231 -Pendent 8.0K, 3/4"NPT Technical Data Approvals UL and C-UL Listed. FM, LPCB, and NYC Approved. (Refer to Table A for complete approval information including corrosion resistant status.) Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K = 2.8 GPM/psi1/2 (40,3 LPM/bar1/2) K = 4.2 GPM/psi1/2 (60,5 LPM/bar1/2) K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2) K = 8.0GPM/psi1/2 (115,2 LPM/bar1/2) Temperature Ratings Refer to Table A and B Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage Page 1 of 8 JULY, 2004 TFP171 Technical Services: Tel: (800) 381-9312 /Fax: (800) 791-5500 IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Customer Service/Sales: Tel: (414) 570-5000 /(800) 558-5236 Fax: (414) 570-5010 /(800) 877-1295 Finishes Sprinkler: Refer to Table A and B Recessed Escutcheon: White Coated, Chrome Plated, or Brass Plated Physical Characteristics Frame . . . . . . . . . . . . . Bronze Button . . . . . . . . . Brass/Copper Sealing Assembly . . . . . . . . . . . . . . . Beryllium Nickel w/Teflon† Bulb . . . . . . . . . . . . . . Glass Compression Screw . . . . . Bronze Deflector . . . . . . . Copper/Bronze Bushing (K=2.8) . . . . . . . Bronze Operation The glass Bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, allowing the sprinkler to activate and water to flow. Page 2 of 8 TFP171245673 (57,2 mm) 2-1/4"(39,7 mm) 1-9/16" 1 PENDENT CROSS SECTION PLATE SEATING ESCUTCHEON 7/16" (11,1 mm) NOMINAL MAKE-IN FLATS WRENCH SURFACE NPT 1/2" RECESSED PENDENT UPRIGHT 2-7/8" (73,0 mm) DIA. (11,1 mm) NOMINAL MAKE-IN 7/16" RECESSED STYLE 10 or 20 ESCUTCHEON (55,6 mm) 2-3/16" 1/2" NPT DEFLECTOR SSU SSP DEFLECTOR ** ** * * FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT 1 -Frame 2 -Button 3 -Sealing Assembly 4 -Bulb 5 -Compression Screw 6 -Deflector 7 -Bushing * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. **Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K-FACTOR, 1/2 INCH NPT 1 -Frame 2 -Button 3 -Sealing Assembly 4 -Bulb 5 -Compression Screw 6 -Deflector * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. **Pipe thread connections per ISO 7/1 can be provided on special request. 2456 PENDENT CROSS SECTION (55,6 mm) 2-3/16"(38,1 mm) 1-1/2" PLATE SEATING ESCUTCHEON 7/16" (11,1 mm) NOMINAL MAKE-IN FLATS WRENCH SURFACE 13 NPT 1/2" RECESSED PENDENT UPRIGHT 2-7/8" (73,0 mm) DIA. (11,1 mm) NOMINAL MAKE-IN 7/16" RECESSED STYLE 10 or 20 ESCUTCHEON (55,6 mm) 2-3/16" 1/2" NPT DEFLECTOR SSU SSP DEFLECTOR ** ** * * * † DuPont Registered Trademark Design Criteria The Series TY-FRB Pendent and Upright Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Prevention Data Sheets ). Only the Style 10, 20, 30, or 40 Recessed Escutcheon, as applicable, is to be used for recessed pendent installations. Installation The Series TY-FRB Sprinklers must be installed in accordance with the following instructions:NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler TFP171 Page 3 of 8 2456 PENDENT CROSS SECTION (58,7 mm) 2-5/16"(39,7 mm) 1-9/16" PLATE SEATING ESCUTCHEON 1/2" (12,7 mm) NOMINAL MAKE-IN FLATS WRENCH SURFACE 13 NPT 3/4" RECESSED PENDENT UPRIGHT 2-7/8" (73,0 mm) DIA. (12,7 mm) NOMINAL MAKE-IN 1/2" RECESSED STYLE 30 or 40 ESCUTCHEON (57,2 mm) 2-1/4" 3/3/4" NPT DEFLECTOR SSU SSP DEFLECTOR ** ** * * * FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K-FACTOR, 3/4 INCH NPT 1 -Frame 2 -Button 3 -Sealing Assembly 4 -Bulb 5 -Compression Screw 6 -Deflector * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. **Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT 1 -Frame 2 -Button 3 -Sealing Assembly 4 -Bulb 5 -Compression Screw 6 -Deflector * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. **Pipe thread connections per ISO 7/1 can be provided on special request. 2456 PENDENT CROSS SECTION (55,6 mm) 2-3/16"(38,1 mm) 1-1/2" PLATE SEATING ESCUTCHEON 7/16" (11,1 mm) NOMINAL MAKE-IN FLATS WRENCH SURFACE 13 NPT 1/2" RECESSED PENDENT UPRIGHT 2-7/8" (73,0 mm) DIA. (11,1 mm) NOMINAL MAKE-IN 7/16" RECESSED STYLE 10 or 20 ESCUTCHEON ((55,6 mm) 2-3/16" 1/2" NPT DEFLECTOR SSU SSP DEFLECTOR ** ** * * * held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F/57°C to 3/32 inch (2,4 mm) for the 286°F/141°C temperature ratings. A leak tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A maximum of 21 ft. lbs. (28,5 Nm) of torque may be used to install sprinklers with 1/2 NPT connections. A leak tight 3/4 inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). A maximum of 30 ft.lbs. (40,7 Nm) of torque is to be used to install sprinklers with 3/4 NPT connections. Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to make-up for insufficient adjustment in the escutcheon plate by under-or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit. The Series TY-FRB Pendent and Upright Sprinklers must be installed in accordance with the following instructions. Step 1. Pendent sprinklers are to be installed in the pendent position, and upright sprinklers are to be installed in the upright position. Step 2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 13). With reference to Figures 1, 2, 3, and 4, the W-Type 6 Sprinkler Wrench is to be applied to the sprinkler wrench flats. The Series TY-FRB Recessed Pendent Sprinklers must be installed in accordance with the following instructions. Step A. After installing the Style 10. 20, 30, or 40 Mounting Plate, as applicable, over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step B. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 14).With reference to Figure 1, 2, 3, and 4, the W-Type 7 7 Recessed Sprinkler Wrench is to be applied to the sprinkler wrench flats. Step C. After the ceiling has been installed or the finish coat has been applied, slide on the Style 10, 20, 30, or 40 Closure over the Series TY-FRB Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. Page 4 of 8 TFP171 TYPE TEMP. BULB LIQUID NATURAL BRASS CHROME PLATED WHITE*** POLYESTER 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C 286°F/141°C PENDENT (TY1231) and UPRIGHT (TY1131) SPRINKLER FINISH (See Note 7) 1, 2, 3, 5 Orange Red Yellow Green Blue RECESSED PENDENT (TY2231)* Figure 7 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C Orange Red Yellow Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. *** Frame and Deflector only. Listings and approvals apply to color (Special Order). N/A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 2.8 AND 4.2 K-FACTOR SPRINKLERS K 4.2 1/2" NPT PENDENT (TY2231) and UPRIGHT (TY2131) 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue 1, 2 2.8 1/2" NPT 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C RECESSED PENDENT (TY2231)** Figure 8 Orange Red Yellow Green RECESSED PENDENT (TY1231)* Figure 5 RECESSED PENDENT (TY1231)** Figure 6 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C Orange Red Yellow Green Orange Red Yellow Green 1, 2, 5 TFP171 Page 5 of 8 TYPE TEMP. BULB LIQUID NATURAL BRASS CHROME PLATED WHITE*** POLYESTER 155°F/68°C 175°F/79°C 200°F/93°C SPRINKLER FINISH (See Note 8) RECESSED PENDENT (TY3231)* Figure 9 135°F/57°C Orange Red Yellow Green 1, 2, 4, 5 NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. *** Frame and Deflector only. Listings and approvals apply to color (Special Order). N/A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K-FACTOR SPRINKLERS LEAD COATED N/A 1, 2, 3, 5 K 5.6 1/2" NPT PENDENT (TY3231) and UPRIGHT (TY3131) 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue 1, 2, 3, 4, 5, 6, 7 RECESSED PENDENT (TY4231)* Figure 11 135°F/57°C 1, 2, 4, 5 155°F/68°C Orange 175°F/79°C Red 200°F/93°C Yellow N/A 8.0 3/4" NPT PENDENT (TY4231) and UPRIGHT (TY4131) 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C 286°F/141°C Blue Green Yellow Red Orange 1, 2, 3, 4, 5, 6, 7 1, 2, 5 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C Green RECESSED PENDENT (TY3231)** Figure 10 Orange Red Yellow Green 1, 2, 3, 4, 5 N/A Orange Red Yellow Green 1, 2, 3, 4, 5 N/A RECESSED PENDENT (TY4231)** Figure 12 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C 1, 2, 4, 5 Care and Maintenance The Series TY-FRB Sprinklers must be maintained and serviced in accordance with the following instructions: NOTES Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers -before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). Frequent visual inspections are recommended to be initially performed for corrosion resistant coated sprinklers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condi-Page 6 of 8 TFP171 FIGURE 6 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT FIGURE 5 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT (57,2 mm) 2-1/4" DIA. (73,0 mm) 2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SERIES SURFACE FACE OF FITTING (15,9±6,4 mm) 5/8±1/4" (3,2 mm) 13/16" (20,6 mm) 1-5/16" (33,3 mm) PLATE MOUNTING 1/8" 1/4" (6,4 mm) 3/4" (19,1 mm) TY-FRB (12,7±3,2 mm) 1/2±1/8" 2-1/4" DIA. (57,2 mm) (73,0 mm) 2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SURFACE FACE OF FITTING (3,2 mm) 1-1/16" (27,0 mm) 1-5/16" (33,3 mm) PLATE MOUNTING 1/8" 1/4" (6,4 mm) 1/2" (12,7 mm) TY-FRB SERIES FIGURE 7 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT FIGURE 8 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT (57,2 mm) 2-1/4" DIA. (73,0 mm) 2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SERIES SURFACE FACE OF FITTING (15,9±6,4 mm) 5/8±1/4" (3,2 mm) 3/4" (19,1 mm) 1-1/4" (31,8 mm) PLATE MOUNTING 1/8" 1/4" (6,4 mm) 3/4" (19,1 mm) TY-FRB (12,7±3,2 mm) 1/2±1/8" 2-1/4" DIA. (57,2 mm) (73,0 mm) 2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SURFACE FACE OF FITTING (3,2 mm) 1" (25,4 mm) 1-1/4" (31,8 mm) PLATE MOUNTING 1/8" 1/4" (6,4 mm) 1/2" (12,7 mm) TY-FRB SERIES tion and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The installing contractor or sprinkler manufacturer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. TFP171 Page 7 of 8 FIGURE 13 W-TYPE 6 SPRINKLER WRENCH FIGURE 14 W-TYPE 7 RECESSED SPRINKLER WRENCH WRENCH RECESS (END "A" USED FOR 1/2" NPT MODELS) WRENCH RECESS (END "B" USED FOR 3/4" NPT MODELS) RECESS WRENCH WITH SPRINKLER ENGAGEMENT IN TO ENSURE WRENCHING AREA PUSH WRENCH FIGURE 9 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT FIGURE 10 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT (57,2 mm) 2-1/4" DIA. (73,0 mm) 2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SERIES SURFACE FACE OF FITTING (15,9±6,4 mm) 5/8±1/4" (3,2 mm) 3/4" (19,1 mm) 1-1/4" (31,8 mm) PLATE MOUNTING 1/8" 1/4" (6,4 mm) 3/4" (19,1 mm) TY-FRB (12,7±3,2 mm) 1/2±1/8" 2-1/4" DIA. (57,2 mm) (73,0 mm) 2-7/8" DIA. SPRINKLER MOUNTING CLOSURE SURFACE FACE OF FITTING (3,2 mm) 1" (25,4 mm) 1-1/4" (31,8 mm) PLATE MOUNTING 1/8" 1/4" (6,4 mm) 1/2" (12,7 mm) TY-FRB SERIES FIGURE 11 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 INCH NPT FIGURE 12 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 INCH NPT 2-7/8" DIA. (73,0 mm) 2-1/4" DIA. (57,2 57,2 mm) MOUNTING SPRINKLER CLOSURE SURFACE FITTING FACE OF (15,9±6,4 mm) 5/8±1/4" MOUNTING PLATE 1-5/16" (33,3 mm) 13/16" (20,6 mm) (3,2 mm) 1/8" 3/4" (19,1 mm) 1/4" (6,4 mm) SERIES TY-FRB 2-7/8" DIA. (73,0 mm) 2-1/4" DIA. (57,2 mm) MOUNTING SPRINKLER CLOSURE SURFACE FITTING FACE OF (12,7±3,2 mm) 1/2±1/8" 1-5/16" (33,3 mm) 1-1/16" (27,0 mm) MOUNTING PLATE (3,2 mm) 1/8" 1/2" (12,7 mm) 1/4" (6,4 mm) SERIES TY-FRB Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products’ sole option. Tyco Fire Products neither assumes, nor authorizes any person to assume for it, any other obligation in connection connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR CHARGES, REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHERWARRANTIES EXPRESS OR IMPLIED, INCLUDINGWARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Ordering Procedure When placing an order, indicate the full product name. Refer to the Price List for complete listing of Part Numbers. Contact your local distributor for availability. Sprinkler Assemblies with NPT Thread Connections: Specify: (Specify Model/SIN), Quick Response, (specify K-factor), (specify temperature rating), Series TY-FRB (specify Pendent or Upright) Sprinkler with (specify type of finish or coating), P/N (specify from Table C). Recessed Escutcheon: Specify: Style (specify) Recessed Escutcheon with (specify finish), P/N (specify). 1/2" (15 mm) Style 10 Chrome Plated . . . . . . . . . . . . P/N 56-701-9-010 White Coated . . . . . . . . . . . . . P/N 56-701-4-010 White RAL9010* . . . . . . . . . . . P/N 56-701-3-010 Brass Plated . . . . . . . . . . . . . . P/N 56-701-2-010 1/2" (15 mm) Style 20 Chrome Plated . . . . . . . . . . . . P/N 56-705-9-010 White Coated . . . . . . . . . . . . . P/N 56-705-4-010 White RAL9010* . . . . . . . . . . . P/N 56-705-3-010 Brass Plated . . . . . . . . . . . . . . P/N 56-705-2-010 3/4" (20 mm) Style 30 Chrome Plated . . . . . . . . . . . . P/N 56-705-9-011 White Coated . . . . . . . . . . . . . P/N 56-705-4-011 White RAL9010* . . . . . . . . . . . P/N 56-705-3-011 Brass Plated . . . . . . . . . . . . . . P/N 56-705-2-011 3/4" (20 mm) Style 40 Chrome Plated . . . . . . . . . . . . P/N 56-700-9-010 White Coated . . . . . . . . . . . . . P/N 56-700-4-010 White RAL9010* . . . . . . . . . . . P/N 56-700-3-010 Brass Plated . . . . . . . . . . . . . . P/N 56-700-2-010 * Eastern Hemisphere sales only. Sprinkler Wrench: Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. Page 8 of 8 TFP171 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 P/N 57 — XXX—X — XXX 155 155°F/68°C TEMPERATURE RATING 135 135°F/57°C 1 SPRINKLER TABLE C PART NUMBER SELECTION SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS 175°F/79°C 286 200 200°F/93°C 286°F/141°C WHITE POLYESTER 175 NATURAL BRASS 94 MODEL/SIN CHROME PLATED 7 LEAD COATED 390 8.0K UPRIGHT (3/4"NPT) 391 8.0K PENDENT (3/4"NPT) 330 2.8K UPRIGHT (1/2"NPT) 331 2.8K PENDENT (1/2"NPT) 370 5.6K UPRIGHT (1/2"NPT) 371 5.6K PENDENT (1/2"NPT) TY1131 TY1231 TY3131 TY3231 TY4131 TY4231 340 341 4.2K UPRIGHT (1/2"NPT) 4.2K PENDENT (1/2"NPT) TY2131 TY2231 3 WHITE (RAL9010)* * Eastern Hemisphere sales only. General Description The Series DS-1, 5.6 K-factor, Quick Response (3 mm Bulb) and Standard Response (5 mm Bulb), Extended Coverage Horizontal Sidewall, Dry Type Sprinklers are decorative glass bulb automatic sprinklers. They are intended for use in applications where the sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures (e.g., horizontal piping extensions through a wall to protect an unheated area of a building). The Series DS-1 Extended Coverage Horizontal Sidewall Sprinklers are designed for extended coverage use in light hazard occupancies (ECLH). WARNINGS The Series DS-1 Dry Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the integrity of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted relative to any questions. The Series DS-1 Dry Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Model/Sprinkler Identification Numbers TY3338 -(3 mm Bulb Type) TY3358 -(5 mm Bulb Type) Technical Data Approvals UL and C-UL Listed. NYC Approved. (Refer to Table A) Maximum Working Pressure 175 psi (12,1 bar) Inlet Thread Connection 1 inch NPT Discharge Coefficient K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2) Temperature Ratings Refer to Table A Finishes Sprinkler: Natural Brass, Chrome Plated, White Polyester Escutcheon: White Coated or Chrome Plated Physical Characteristics Inlet . . . . . . . . . . . . . Copper Plug . . . . . . . . . . . . . Copper Yoke . . . . . . . . . Stainless Steel Casing . . . Galvanized Carbon Steel Insert . . . . . . . . . . . . . Bronze Bulb Seat . . . . . . Stainless Steel Bulb . . . . . . . . . . . . . . Glass Compression Screw . . . . . Bronze Deflector . . . . . . . . . . . . Bronze Frame . . . . . . . . . . . . . Bronze Guide Tube . . . . . Stainless Steel Water Tube . . . . . Stainless Steel Spring . . . . . . . . Stainless Steel Sealing Assembly . . . . . . . . . . . . . . . . Beryllium Nickel w/Teflon* Escutcheon . . . . . . Carbon Steel Patents U.S.A. Patent Number 5,188,185 may be applicable to the Series DS-1, 5.6 K-factor, Quick and Standard Response, Extended Coverage Horizontal Sidewall, Dry Type Sprinklers Operation When the Series DS-1 is in service, water is prevented from entering the assembly by the Plug & Belleville Sealing Assembly (Ref. Figure 1) in the Inlet of the Sprinkler. The glass Bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, and the Bulb Seat is released. The compressed Spring is then able to expand and push the Water Tube as well as the Guide Tube outward.This action simultaneously pulls inward on the Yoke, withdrawing the Plug & Belleville Seal from the Inlet allowing the sprinkler to activate and flow water. Page 1 of 6 JANUARY, 2003 TFP520 Series DS-1 — 5.6 K-factor Dry Type Sprinklers Quick and Standard Response, Extended Coverage * Registered Trademark of DuPont Technical Services: Tel: (800) 381-9312 /Fax: (800) 791-5500 Customer Service/Sales: Tel: (215) 362-0700 /(800) 523-6512 Fax: (215) 362-5385 Design Criteria The Series DS-1 Sprinklers are intended for use in fire sprinkler systems designed in accordance with the extended coverage installation guidelines provided by NFPA 13 and the installation criteria provide by Table B. The Series DS-1 Dry Type Sprinkler is to be installed in the 1 inch NPT outlet or run of malleable or ductile iron threaded tee fittings that meet the dimensional requirements of ANSI B16.3 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 with the end sprinkler fitting on a branch line to be plugged as shown in Figure 1. For wet pipe sprinkler systems, the Series DS-1 Dry Type Sprinklers may also be installed in the 1 inch NPT Page 2 of 6 TFP520 SPRINKLER FINISH Temperature Rating Bulb Color Code Natural Brass Chrome Plated 135°F/57°C 155°F/68°C Red Orange TY3338 HSW (3 mm Bulb Type) w/Standard Escutcheon (Ref. Fig. 2) TY3358 HSW (5 mm Bulb Type) w/Standard Escutcheon (Ref. Fig. 2) Notes: 1. Listed by Underwriters Laboratories, Inc. (Maximum order length of 48 inches). 2. Listed by Underwriters Laboratories for use in Canada (Maximum order length of 48 inches). 3. Approved by the City of New York under MEA 352-01-E. TABLE A SERIES DS-1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS White Polyester 1, 2, 3 1, 2, 3 Temperature Rating °F Coverage (1) W x L FT x FT (m x m) Min Flow GPM (LPM) 16 x 20 (4,9 x 6,1) 18 x 16 (5,5 x 4,9) 16 x 18 (4,9 x 5,5) TY3338 HSW 16 x 16 (4,9 x 4,9) (3 mm Bulb Type) For Quick Response Light Hazard Extended Coverage Per NFPA 13 Notes: 1. The minimum allowable spacing between sprinklers to prevent cold soldering is 14 feet (4,3 m). 2. To meet the deflector-to-ceiling distance of 4 to 12 inches (100 to 300 mm), the centerline of the sprinkler waterway must be 4-7/16 to 12-7/16 inches below the ceiling. TABLE B SERIES DS-1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS UL AND C-UL INSTALLATION CRITERIA Top Of Deflector To Ceiling Distance (2) Inches (mm) 29 (110) 135 & 155 4 to 12 (100 to 300) Min Pressure PSI (BAR) 32 (121) 29 (110) 21.6 (1,49) 26.8 (1,85) 32.7 (2,25) 26.8 (1,85) 26 (98) APPLICATION APPLICATION Coverage (1) W x L FT x FT (m x m) Min Flow GPM (LPM) Min Pressure PSI (BAR) Temperature Rating °F Top Of Deflector To Ceiling Distance (2) Inches (mm) TY3358 HSW (5 mm Bulb Type) For Standard Response Light Hazard Extended Coverage Per NFPA 13 16 x 16 (4,9 x 4,9) 16 x 18 (4,9 x 5,5) 16 x 20 (4,9 x 6,1) 18 x 16 (5,5 x 4,9) 26 (98) 29 (110) 32 (121) 29 (110) 21.6 (1,49) 26.8 (1,85) 32.7 (2,25) 26.8 (1,85) 135 & 155 4 to 12 (100 to 300) outlet of a Central Figure 730 Mechanical Tee Adapter Tee. NOTE Do not install the Series DS-1 into any other type fitting without first consulting the Technical Services Department. Failure to use the appropriate fitting may result in: failure of the sprinkler to properly operate due to formation of ice over the inlet Plug or binding of the inlet Plug; or, insufficient engagement of the inlet pipe threads with consequent leakage. Branch, cross, and feedmain piping connected to Dry Sprinklers and subject to freezing temperatures must be pitched for drainage in accordance with the minimum requirements of the National Fire Protection Association for dry pipe sprinkler systems. When Dry Sprinklers are to be used in wet pipe sprinkler systems protecting areas subject to freezing temperatures (e.g., horizontal extensions into freezers), consideration must be given to the appropriate length of the sprinkler that will prevent freezing of the water in the connecting pipes due to conduction. When the temperature surrounding the wet pipe sprinkler system is maintained at a minimum temperature of 40°F/4°C, the following are the minimum recommended lengths between the face of the sprinkler fitting and the outside surface of the protected area (i.e., length exposed to minimum ambient of 40°F/4°C): • 12 inches (300 mm) when the temperature within the protected area is -20°F/-29°C • 18 inches (450 mm) when the temperature within the protected area is -40°F/-40°C • 24 inches (600 mm) when the temperature within the protected area is -60°F/-51°C For protected area temperatures between those given above, theminimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values. NOTE When Dry Sprinklers penetrate a wall into an area subject to freezing, the clearance space around the Sprinkler Casing must be completely sealed in order to prevent the leakage of moist air into the freezing area which might result in the formation of condensate around the Frame, Deflector, Bulb Seat, or Bulb. Failure to prevent the formation of condensate could result in the build-up of ice around the releasing components. This could result in an inadvertent operation of the sprinkler or impaired operation due to reduced thermal sensitivity. TFP520 Page 3 of 6 WATER TUBE GUIDE INLET TUBE HOLE INSERT 3 or 5 mm DEFLECTOR SCREW COMPRESSION GASKETED SPRING PLUG WITH BULB SEAT YOKE 1" NPT CASING SPRING VENT FRAME BULB PLATE SEAL FIGURE 1 TY3338 (3 mm BULB) AND TY3358 (5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL ASSEMBLY FIGURE 2 TY3338 (3 mm BULB) AND TY3358 (5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL w/STANDARD ESCUTCHEON SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) MOUNTING FACE OF 4" ± 1/8" (101,6 ± 3,2 mm) SURFACE 7/16" (11,1 mm) CENTERLINE OF WATERWAY (76,2 mm) 3" DIA. ORDER LENGTHS: (63,5 to 1219,2 mm) 2-1/2" to 48" IN 1/4" (6,4 mm) INCREMENTS 1-3/4" DIA. (44,5 mm) FACE OF SPRINKLER FITTING FIGURE 3 W-TYPE 7 SPRINKLER WRENCH ENGAGEMENT IN TO ENSURE WITH SPRINKLER FLAT WRENCH PUSH WRENCH WRENCH FLATS RECESS WRENCH Installation The Series DS-1 Dry Type Sprinklers must be installed in accordance with the following instructions: NOTES The Series DS-1must only be installed in fittings that meet the requirements of the Design Criteria section. Refer to the Design Criteria section for other important requirements regarding piping design and sealing of the clearance space around the Sprinkler Casing. Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). A leak tight 1 inch NPT sprinkler joint should be obtained with a torque of 20 to 30 ft.lbs. (26,8 to 40,2 Nm). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutcheon Plate by under-or over-tightening the Sprinkler. Readjust the position of the sprinkler sprinkler fitting to suit. Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of waterway perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling. Step 2. With pipe thread sealant applied to the inlet threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Wrench tighten the sprinkler by wrenching on the Casing with a pipe wrench whenever the casing is readily accessible. Otherwise, use a W-Type 7 Sprinkler Wrench (Ref. Figure 3). The wrench recess of the W-Type 7 is to be applied to the sprinkler wrench flats (Ref. Figure 3). Step 4. After the wall has been installed/finished, slide on the outer piece of the Escutcheon until it comes in contact with the ceiling/wall. Care and Maintenance The Series DS-1 Dry Type Sprinklers must be maintained and serviced in accordance with the following instructions: NOTES Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must be obtained from the proper authorities and all personnel who may be affected by this actionmust be notified. A Vent Hole is provided in the Bulb Seat (Ref. Figure 1) to indicate if the Dry Sprinkler is remaining dry. Evidence of leakage from the Vent Hole is an indication that there may be weepage past the Inlet seal and that the sprinkler needs to be removed for determining the cause of leakage (e.g. an improper installation or an ice plug). The fire protection system control valve must be closed and the system drained before removing the sprinkler. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage -before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb (Ref. Installation Section). The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The installing contractor or sprinkler manufacturer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service. Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products’ sole option. Tyco Fire Products neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR CHARGES, REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHERWARRANTIES EXPRESSOR IMPLIED, INCLUDINGWARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Page 4 of 6 TFP520 Ordering Procedure Contact your local distributor for availability, and please specify the following: 1. Sprinkler. • Model/SIN. • Bulb Size (3 or 5 mm) • Extended Coverage Horizontal Sidewall Dry Type Sprinkler. • 5.6 K-factor. • Order Length. Dry Type Sprinklers are furnished based upon Order Length as measured from the face of the wall to the face of the sprinkler fitting (Ref. Figure 2). After the measurement is taken, round it to the nearest 1/4 inch increment. • 1 Inch NPT Inlet Connection. • Temperature Rating. • Sprinkler Finish. • Standard Escutcheon and Finish. • Part Number fro Table C. 2. W-Type 7 Sprinkler Wrench. Refer to the Price List for complete listing of Part Numbers. TFP520 Page 5 of 6 P/N 60 — XXX — X — XXX 48.00" 8.25" 480 082 ORDER LENGTH (1) (EXAMPLES) 055 5.50" 1 SPRINKLER FINISH TABLE C PART NUMBER SELECTION SERIES DS-1 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS 18.00" 372 187 18.75" 37.25" 180 WHITE POLYESTER NATURAL BRASS 94 MODEL/SIN CHROME PLATED 0 CHROME PLATED PLATED 350 EC Sidewall 3 mm Bulb (1"NPT), 135F/57C TY3338 EC Sidewall, 5 mm Bulb (1" NPT), 135F/57C WHITE WHITE CHROME PLATED WHITE ESCUTCHEON FINISH 950 TY3358 NOTES (1). Dry Type Sprinklers are furnished based upon “Order Length” as measured per Figure 2. After the measurement is taken, round it to the nearest 1/4 inch increment. 351 EC Sidewall 3 mm Bulb (1"NPT), 155F/68C TY3338 951 EC Sidewall, 5 mm Bulb (1" NPT), 155F/68C TY3358 Page 6 of 6 TFP520 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 S5 -3 Galvanized Pipe Superior Coating Specifications & Approvals American Made Schedule-10/Schedule-40 product can be “hot-dip” galvanized to meet FM requirements for dry systems in accordance with the zinc coating specifications of ASTM A-123. Our advanced formula mill coating offers a clean, durable surface. It is also paint-ready for custom color applications without special preparation. The internal surface of all black Allied Tube & Conduit Fire Sprinkler pipe products up to 4.5000” in diameter is coated with our new Antibacterial Formula, “ABF”. In scientific laboratory test, ABS proved to have superior resistance to microbial colonization of pipe walls, thereby delaying or possibly preventing the onset of Microbiologically Influenced corrosion (MIC) when the First Sprinkler System is first installed. When you specify Schedule-10/Schedule-40 sprinkler pipe you get a UL listed and FM approved product. Although these products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality assurance you demand. Our Sch-10 (11⁄4"– 8") pipe and Sch-40 (1"– 21⁄2") pipe have passed the same thorough lab testing as our other listed pipe products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality. Fully Listed and FM Approved Sprinkler Pipe Schedule-10®/Schedule-40® Meets “Buy American” requirement and is available through distributors in the USA, Canada and Mexico. Schedule-10/Schedule-40 pipe are in compliance with the following: ASTM A-135, and NFPA 13. Both pipe products have a working pressure rating of 300 psi maximum and also meet the stringent requirement for the following tests: • Welded Outlets • Hydrostatic Pressure • Side Wall Rupture • Vibration Test Sch-40 Specifications NPS Nominal I.D. Wt. Wt. (H2O Filled) Pcs/Wt/Lift (21') Wt/Lift (24') Wt/Lift (25') In; mm In; mm Lbs/Ft; Kg/m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg 1" 1.049 1.680 2.05 70 2,470 2,822 2,940 25 26.6 2.5 3.05 70 1,120 1,280 1,334 11⁄4" 1.380 2.270 2.93 51 2,431 2,778 2,894 32 35.1 4.36 4.36 51 1,103 1,260 1,313 11⁄2" 1.610 2.720 3.61 44 2,513 2,872 2,992 40 40.9 4.0 5.37 44 1,140 1,303 1,357 2" 2.067 3.650 5.13 30 2,300 2,628 2,738 50 52.5 5.4 7.63 30 1,043 1,192 1,242 21⁄2" 2.469 5.790 7.86 19 2,310 2,640 2,750 65 62.7 8.6 11.73 19 1,048 1,197 1,247 Sch-10 Specifications NPS Nominal I.D. Wt. Wt. (H2O Filled) Pcs/Wt/Lift (21') Wt/Lift (24') Wt/Lift (25') In; mm In; mm Lbs/Ft; Kg/m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg 1" 1.097 1.400 1.81 91 2,675 3,053 3,185 25 27.9 2.1 2.70 91 1,213 1,385 1,445 11⁄4" 1.442 1.810 2.52 61 2,319 2,664 2,760 32 36.6 2.7 3.75 61 1,052 1,208 1,252 11⁄2" 1.682 2.080 3.04 61 2,664 3,045 3,172 40 42.7 3.1 4.52 61 1,208 1,381 1,439 2" 2.157 2.640 4.22 37 2,051 2,344 2,442 50 54.8 3.9 6.28 37 930 1,063 1,108 21⁄2" 2.635 3.530 5.89 30 2,224 2,542 2,648 65 66.9 5.3 8.77 30 1,009 1,153 1,201 3" 3.260 4.330 7.94 19 1,728 1,975 2,057 80 82.8 6.4 11.82 19 784 896 933 4" 4.260 5.610 11.78 19 2,238 2,558 2,665 90 108.2 8.3 17.53 19 1,015 1,160 1,209 5" 5.295 7.77 17.33 10 1,632 1,865 1,943 125 134.5 11.56 25.80 10 740 846 881 6" 6.357 9.290 23.03 10 1,951 2,230 2,322 150 161.5 13.8 34.27 10 885 1,012 1,053 8" 8.249 16.490 40.15 7 2,424 2,770 2,885 200 209.5 24.5 59.75 7 1,100 1,256 1,309 FM Listed Approved Listed 16100 S. Lathrop • Harvey, IL 60426 11350 Norcom Rd. • Philadelphia, PA 19154 2525 N. 27 th Ave. • Phoenix, AZ 85009 Customer Service: (800) 882-5543 Fax 708-339-1806 Page 19 C.I. THREADED FITTINGS For fire protection services request submittal GRS 1.3 Cast iron threaded fittings are UL, ULC listed and factory mutual approved for 300 psi service. Gray iron per ASTM A126 class B. Dimensions conform to ANSI B16.4 class 125 except plugs conform to ASME B16.14. Threads are NPT per ANSI/ASME B1.20.1. CAST IRON 90 DEGREE ELBOW NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1 CB90033 300 1.50 1.50 0.95 1 1/4 CB90044 300 1.75 1.75 1.34 1 1/2 CB90055 300 1.94 1.94 1.80 2 CB90066 300 2.25 2.25 2.90 2 1/2 DIMENSIONS CAST IRON STRAIGHT TEE NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1 CT333 300 1.50 1.50 1.21 1 1/4 CT444 300 1.75 1.75 1.87 1 1/2 CT555 300 1.94 1.94 2.51 2 CT666 300 2.25 2.25 3.96 DIMENSIONS CAST IRON RED. COUPLING NOMINAL ITEM MAX. DIMENSION WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A PIECE 1X1/2 CRC031 300 1.70 0.62 1X3/4 CRC032 300 1.70 0.80 CAST IRON 45 DEGREE ELBOW NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1 CB45033 300 1.12 1.12 0.84 1 1/4 CB45044 300 1.29 1.29 1.40 1 1/2 CB45055 300 1.43 1.43 1.80 2 CB45066 300 1.68 1.68 2.79 DIMENSIONS CAST IRON RED. 90 DEG. ELBOW NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1X1/2 CB90031 300 1.26 1.36 0.64 1X3/4 CB90032 300 1.37 1.45 0.87 1 1/4X1/2 CB90041 300 1.34 1.53 0.96 1 1/4X3/4 CB90042 300 1.45 1.62 1.13 1 1/4X1 CB90043 300 1.58 1.67 1.16 1 1/2X1 CB90053 300 1.65 1.80 1.51 DIMENSIONS 1 1/2X1 1/4 CB90054 300 1.82 1.88 1.62 2X1/2 CB90061 300 1.49 1.88 2.00 2X3/4 CB90062 300 1.60 1.97 2.05 2X1 CB90063 300 1.73 2.02 2.10 2X1 1/4 CB90064 300 1.90 2.10 2.30 2X1 1/2 CB90065 300 2.02 2.16 2.60 CAST IRON PLUGS NOMINAL ITEM MAX. DIMENSION WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A PIECE 1/2 CPL001 300 0.94 0.10 3/4 CPL002 300 1.07 0.17 1 CPL003 300 1.25 0.28 1 1/4 CPL004 300 1.36 0.44 1 1/2 CPL005 300 1.45 0.62 2 CPL006 300 1.56 0.91 CB90077 300 2.70 2.70 4.75 2 1/2 CT777 300 2.70 2.70 6.45 1 1/2x1 1/2 CB90051 300 1.41 1.66 1.17 1 1/2x3/4 CB90052 300 1.52 1.75 1.28 Page 20 C.I. THREADED FITTINGS For fire protection services request submittal GRS 1.3 CAST IRON CROSS NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1 CX033 300 1.50 1.50 1.54 1 1/4 CX044 300 1.75 1.75 2.40 1 1/2 CX055 300 1.94 1.94 3.10 2 CX066 300 2.25 2.25 4.00 1 1/4X1 CX043 300 1.58 1.67 2.05 1 1/2X1 CX053 300 1.65 1.80 2.40 2X1 CX063 300 1.73 2.02 2.75 DIMENSIONS CAST IRON REDUCING TEE NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B C PIECE 1X1X1/2 CT331 300 1.26 1.26 1.36 0.95 1X1X3/4 CT332 300 1.37 1.37 1.45 1.10 1X1/2X1 CT313 300 1.50 1.36 1.50 1.08 1X3/4X1 CT323 300 1.50 1.45 1.50 1.18 1X1X1 1/4 CT334 300 1.67 1.67 1.58 1.52 1X1X1 1/2 CT335 300 1.80 1.80 1.65 1.73 1 1/4X1X1/2 CT431 300 1.34 1.26 1.53 1.17 1 1/4X1X3/4 CT432 300 1.45 1.37 1.62 1.38 1 1/4X1X1 CT433 300 1.58 1.50 1.57 1.47 1 1/4X1X1 1/4 CT434 300 1.75 1.67 1.75 1.80 1 1/4X1X1 1/2 CT435 300 1.88 1.80 1.82 2.05 1 1/4X1 1/4X1/2 CT441 300 1.34 1.34 1.53 1.37 1 1/4X1 1/4X3/4 CT442 300 1.45 1.45 1.45 1.62 1.54 1 1/4X1 1/4X1 CT443 300 1.58 1.58 1.67 1.65 1 1/4X1 1/4X1 1/2 CT445 300 1.88 1.88 1.82 2.21 1 1/4X1 1/4X2 CT446 300 2.10 2.10 1.90 2.55 1 1/2X1X1/2 CT531 300 1.41 1.34 1.66 1.41 1 1/2X1X3/4 CT532 300 1.52 1.37 1.75 1.65 1 1/2X1X1 CT533 300 1.65 1.50 1.80 1.65 1 1/2X1X1 1/4 CT534 300 1.82 1.67 1.88 2.00 1 1/2X1X1 1/2 CT535 300 1.94 1.80 1.94 2.30 1 1/2X1 1/4X1/2 CT541 300 1.41 1.34 1.66 1.58 1 1/2X1 1/4X3/4 CT542 300 1.52 1.45 1.75 1.72 1 1/2X1 1/4X1 CT543 300 1.65 1.58 1.80 1.85 1 1/2X1 1/4X2 CT546 300 2.16 2.10 2.02 2.80 1 1/2X1 1/2X1/2 CT551 300 1.41 1.41 1.66 1.76 1 1/2X1 1/2X3/4 CT552 300 1.52 1.52 1.75 1.87 1 1/2X1 1/2X1 CT553 300 1.65 1.65 1.80 1.94 1 1/2X1 1/2X1 1/4 CT554 300 1.82 1.82 1.88 2.29 1 1/2X1 1/2X2 CT556 300 2.16 2.16 2.02 3.28 2X1X2 CT636 300 2.25 2.02 2.25 3.40 2X1 1/4X2 CT646 300 2.25 2.10 2.25 2.80 2X1 1/2X1/2 CT651 300 1.49 1.41 1.88 2.09 2X1 1/2X3/4 CT652 300 1.60 1.52 1.97 2.40 2X1 1/2X1 CT653 300 1.73 1.65 2.02 2.54 2X1 1/2X1 1/4 CT654 300 1.90 1.82 2.10 2.85 2X1 1/2X1 1/2 CT655 300 1.49 1.41 1.88 2.24 2X1 1/2X2 CT656 300 2.25 2.16 2.25 3.75 2X2X1/2 CT661 300 1.49 1.49 1.88 2.60 2X2X3/4 CT662 300 1.60 1.60 1.97 2.71 2X2X1 CT663 300 1.73 1.73 2.02 2.97 2X2X1 1/4 CT664 300 1.90 1.90 2.10 3.32 2X2X1 1/2 CT665 300 2.02 2.02 2.16 3.72 DIMENSIONS 2x2x2 1/2 CT667 300 2.60 2.60 2.39 5.10 1 1/2x1 1/4x1 1/4 CT544 300 1.82 1.75 1.88 2.22 1 1/2x1 1/4x1 1/2 CT545 300 1.94 1.88 1.94 2.45 Page 8 GROOVED FITTINGS For fire protection services request submittal GRS 1.3 "S" Series products are specifically designed for use in fire protection applications where economy is a factor. All products are UL & ULC listed as well as factory mutual approved. Maximum working pressure for these products is 300psi. Fittings are cast steel per ASTM A 958 or ductile iron per ASTM A536. NOMINAL CENT E R AP P R OX. CENT E R AP P R OX. CENT E R AP P R OX. S IZ E t o WE IGH T t o WE IGH T t o WE IGH T IN. E ND E ACH E ND E ACH E ND E ACH (mm) IN.(mm) Lbs.(Kg) IN.(mm) Lbs.(Kg) IN. (mm) Lbs.(Kg) 2 2.75 1.50 2.00 1.29 2.75 2.27 50 70 0.68 51 0.59 70 1.03 2 1/2 3.00 2.14 2.25 2.00 3.00 3.30 65 76 0.97 57 0.91 76 1.50 3 3.38 3.60 2.50 3.06 3.38 5.04 80 86 1.63 64 1.39 86 2.29 4 4.00 5.78 3.00 4.89 4.00 7.86 100 102 2.62 76 2.22 102 3.57 6 5.50 11.78 3.50 9.95 5.50 19.05 150 140 5.34 89 4.51 140 8.64 8 6.81 21.10 4.25 15.40 6.94 33.30 200 173 9.57 108 6.99 176 15.10 SE-2 45° ELBOW ST-1 TEE FIRE PROTECTION FITTINGS SE-1 90° ELBOW NOMINAL E ND AP P R OX. S IZ E to WE IGHT IN. E ND E ACH (mm) IN.(mm) Lbs.(Kg) 2 1.00 0.54 50 25 0.3 2 1/2 1.00 0.75 65 25 0.4 3 1.00 1.23 80 25 0.6 4 1.06 1.95 100 27 1.1 6 1.06 4.58 150 27 2.1 8 1.19 8.98 200 30 3.5 1 1/4 0.87 0.32 200 30 3.5 1 1/2 0.87 0.39 200 30 3.5 SK-1 GROOVED CAP 0.2 0.2 0.2 0.3 0.9 4.1 32 40 NOMINAL IN. SE-5 GROOVE X THREAD REDUCING 90 ELBOW SE-9 DRAIN ELBOW DIMENSION -WEIGHTS NOMINAL Size IN. O.D. (IN) Thread (NPT) Approx. Weight (lbs.) C-E (IN) 2 2.5 346 2.375 2.875 3.500 4.500 6.625 1 -11.5 1 -11.5 1 -11.5 1 -11.5 1 -11.5 A (IN) 2.16 2.16 2.16 2.25 2.25 1.70 2.45 3.50 5.25 14.00 2.75 3.00 3.38 4.00 5.50 Page 9 GROOVED FITTINGS For fire protection services request submittal GRS 1.3 SW = Segmentaly Welded Steel * Forge Steel Drain elbow has a standard 1" Female NPT outlet Drain elbow is SCH 10 steel pipe NOMINAL CENT E R AP P R OX. CENT E R AP P R OX. CENT E R AP P R OX. CENT E R AP P R OX. CENT E R AP P R OX. S IZ E t o WE IGH T t o WE IGH T t o WE IGH T t o WE IGH T t o WE IGH T IN. E ND E ACH E ND E ACH E ND E ACH E ND E ACH E ND E ACH (mm) IN.(mm) Lbs.(Kg) IN.(mm) Lbs.(Kg) IN. (mm) Lbs.(Kg) IN. (mm) Lbs.(Kg) IN.(mm) Lbs.(Kg) 1 1/4 2.75 1.1 1.75 0.8 1.75 0.8 1.37 0.5 2.75 1.2 32 70 0.5 44 0.4 44 0.4 35 0.2 1.2 0.5 1 1/2 2.75 1.2 1.75 0.9 1.75 1.0 1.37 0.7 2.75 1.8 40 70 0.5 44 0.4 44 0.5 35 0.3 1.2 0.8 2 3.25 2.0 2.00 1.5 2.00 1.6 1.37 0.9 3.25 2.3 50 83 0.9 51 0.7 51 0.7 35 0.4 83 1.0 2 1/2 3.75 2.9 2.25 2.2 2.00 2.1 1.50 1.5 3.75 3.0 65 95 1.3 57 1.0 51 1.0 38 0.7 95 1.4 3 O.D. 3.75 3.1 2.25 1.9 65 95 1.4 57 0.9 3 4.25 4.3 2.50 3.2 2.25 3.1 1.50 2.0 4.25 3.6 80 108 2.0 64 1.5 57 1.4 38 0.9 108 1.6 4 5.00 8.7 3.00 5.7 2.87 5.4 1.75 3.3 5.00 3.7 100 127 3.9 76 2.6 73 2.4 44 1.5 127 1.7 5 5.50 11.9 3.25 8.2 2.88 7.8 2.00 5.0 5.50 4.3 125 140 5.4 83 3.7 73 3.5 51 2.3 140 2.0 6 6.50 18.2 3.50 11.0 3.12 8.3 2.00 6.5 6.50 10.7 150 165 8.3 89 5.0 79 3.8 51 2.9 165 4.9 6.5 O.D. 6.50 15.0 3.50 11.2 150 165 6.8 89 5.1 8 7.75 32.2 4.25 20.4 3.87 17.9 2.00 10.0 7.75 20.8 200 197 14.6 108 9.3 98 8.1 51 4.5 197 9.4 10 9.00 49.0 4.75 31.5 4.75 30.0 2.12 14.5 9.00 29.0 250 229 22.2 121 14.3 121 13.6 54 6.6 229 13.2 12 10.00 70.0 5.25 44.1 4.87 40.4 2.25 18.7 10.00 33.0 300 254 31.8 133 20.0 124 18.3 57 8.5 254 15.0 E-9 DRAIN ELBOW (SW) E-1 90° ELBOW E-2 45° ELBOW E-3 22 1/2° ELBOW (SW) E-4 11 1/4° ELBOW (SW) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 76, 1 165, 1 NOMINAL CE NT E R AP P R OX. S IZ E to WE IGHT IN. E ND E ACH (mm) IN.(mm) Lbs.(Kg) 1 1/4 2.75 1.7 32 70 0.8 1 1/2 2.75 1.8 40 70 0.8 2 3.25 2.9 50 83 1.3 2 1/2 3.75 4.6 65 95 2.1 3 O.D. 3.75 4.3 65 95 2.0 3 4.25 6.9 80 108 3.1 4 5.00 10.9 100 127 4.9 5 5.50 17.8 125 140 8.1 6 6.50 25.0 150 165 11.3 6.5 O.D. 6.50 24.5 150 165 11.1 8 7.75 42.1 200 197 19.1 10 9.00 69.0 250 229 31.3 12 10.00 91.0 300 254 41.3 T-1 TEE 76, 1 165, 1 * 150 lb. steel flanged NOMINAL E ND AP P R OX. S IZ E to WE IGHT IN. E ND E ACH (mm) IN.(mm) Lbs.(Kg) 1 1/4 4.00 2.8 32 102 1.3 1 1/2 4.00 3.2 40 102 1.5 2 4.00 5.2 50 102 2.4 2 1/2 4.00 8.0 65 102 3.6 3 4.00 10.2 80 102 4.6 4 6.00 17.2 100 152 7.8 5 6.00 21.4 125 152 9.7 6 6.00 26.0 150 152 11.8 8 6.00 38.4 200 152 17.4 10 8.00 65.0 250 203 29.5 12 8.00 91.0 300 203 41.3 F-2 FLANGE NIPPLE(SW) 1 1/4" -12" 14" -24" SW = Segmentaly welded steel * Forged steel NOMINAL ACT UAL E ND AP P R OX. S IZ E P IP E to WE IGHT IN. S IZ E E ND E ACH (mm) IN. (mm) IN. (mm) Lbs.(Kg) 1 1/4 1.660 1.00 0.40 32 42.2 25 0.2 1 1/2 1.900 1.00 0.51 40 48.3 25 0.2 2 2.375 1.00 0.68 50 60.3 25 0.3 2 1/2 2.875 1.00 0.99 65 73.0 25 0.4 3 O.D. 3.000 1.00 0.94 65 76.2 25 0.4 3 3.500 1.00 1.54 80 88.9 25 0.7 4 4.500 1.06 2.72 100 114.3 27 1.2 5 5.563 1.06 4.43 125 141.3 27 2.0 6 6.625 1.06 6.64 150 168.3 27 3.0 6.5 O.D. 6.500 1.00 5.50 150 165.1 25 2.5 8 8.625 1.19 11.28 200 219.1 30 5.1 10 10.750 1.25 21.00 250 273.1 32 9.5 12 12.750 1.25 35.50 300 323.9 32 16.1 K-1 GROOVED CAP 76, 1 165, 1 Page 10 GROOVED FITTINGS For fire protection services request submittal GRS 1.3 SW = Segmentaly welded steel (d) = Ductile iron SW = Segmentaly welded steel (d) = Ductile iron Page 11 GROOVED FITTINGS For fire protection services request submittal GRS 1.3 SW = Segmentaly welded steel (d) = Ductile iron SW = Segmentaly welded steel (d) = Ductile iron NOMINAL E ND AP P R OX. NOMINAL E ND AP P R OX. S IZ E to WE IGHT S IZ E to WE IGHT IN. E ND E ACH IN. E ND E ACH (mm) IN.(mm) Lbs.(Kg) (mm) IN.(mm) Lbs.(Kg) 1 1/2x1 3.31 0.73 3x2 1/2 3.31 1.2 40x25 84 0.41 80X65 84 0.5 2x1 3.31 0.61 4x1 3.38 2.2 50x25 84 0.37 100x25 86 1.0 2x1 1/4 3.31 0.81 4x1 1/2 3.38 2.3 50x32 84 0.37 100x40 86 1.0 2x1 1/2 3.31 0.81 4x2 3.38 2.3 50x40 84 0.37 100x50 86 1.0 2 1/2x1 3.31 0.81 4x2 1/2 3.38 2.3 65X25 84 0.37 100x65 86 1.0 2 1/2x1 1/4 3.31 0.92 4x3 3.38 2.6 65X32 84 0.42 100x80 86 1.2 2 1/2x1 1/2 3.31 0.92 5x4 3.50 4.5 65X40 84 0.42 125x100 89 2.0 2 1/2x2 3.31 0.92 6x1 3.50 5.9 65X50 84 0.42 150x25 89 2.7 3x1 3.31 1.2 6x2 3.50 6.0 80X25 84 0.55 150x50 89 2.7 3x1 1/2 3.31 1.2 6x3 3.50 6.0 80X40 84 0.55 150x80 89 2.7 3x2 3.31 1.4 6x4 3.50 5.9 80X50 84 0.55 150x100 89 2.7 R-3 CONCENTRIC REDUCER/THD(SW) (d) (d) 0.28 0.6 0.5 0.5 Page 12 GROOVED FITTINGS/MECHANICAL TEES For fire protection services request submittal GRS 1.3 N -1 G x MPT N -2 G x B N -3 G x G SW = Segmentaly welded steel (d) = Ductile iron NOMINAL E ND AP P R OX. S IZ E to WE IGHT IN. E ND E ACH (mm) IN.(mm) Lbs.(Kg) 1 3.00 0.40 25 76 0.18 1 1/4 4.00 0.80 32 102 0.36 1 1/2 4.00 0.90 40 102 0.41 2 4.00 1.20 50 102 0.54 2 1/2 4.00 1.90 65 102 0.86 3 4.00 2.50 80 102 1.13 4 6.00 5.50 100 152 2.49 5 6.00 7.40 125 152 3.36 6 6.00 9.50 150 152 4.31 8 6.00 14.20 200 152 6.44 10 8.00 27.00 250 203 12.25 12 8.00 33.00 300 203 14.97 ADAPTER NIPPLES N-1 N-2 N-3 NOMINAL E ND AP P R OX. S IZ E to WE IGHT IN. E ND E ACH (mm) IN.(mm) Lbs.(Kg) 1 1/4 3.75 2.0 32 95 0.9 1 1/2 3.75 2.2 40 95 1.0 2 3.75 3.0 50 95 1.4 2 1/2 3.75 5.0 65 95 2.3 3 4.25 7.1 80 108 3.2 4 5.00 11.9 100 127 5.4 5 5.25 17.1 125 133 7.8 6 6.50 27.5 150 165 12.5 8 7.75 47.0 200 197 21.3 10 9.00 68.0 250 229 30.8 12 10.00 107.0 300 254 48.5 CROSS(SW) X-1 N -4 G x H NOMINAL E ND E ND AP P R OX. S IZ E t o WE IGH T IN. E ACH (mm) IN.(mm) Lbs.(Kg) 1 3.25 0.40 1 1/4 3.62 0.70 1 1/4 4.00 0.80 2 4.62 1.3 2 1/2 5.50 2.1 3 6.00 3.3 4 7.25 5.5 5 9.75 8.1 6 11.00 13.2 8 12.50 24.0 10 14.00 29.00 12 16.00 46.00 HOSE NIPPLE N-425 32 40 50 65 80 100 125 150 200 250 300 83 92 102 117 140 152 184 248 279 318 356 406 0.18 0.32 0.36 0.59 0.95 1.50 2.49 3.67 5.99 10.88 13.15 20.86 Model MT-3 & MT-9 Mechanical tee serves the same function as MT-1 & MT-8 but uses a steel electro plated u-bolt to save space and for easier installation in tight places. It is ideal for direct connections with sprinkler heads and drop nipples. HOUSING: Ductile iron ASTM A536 grade 65-45-12. COATING: Zinc electroplated U -BOLT: Carbon steel SAE grade 2, zinc plated. NUT: Carbon steel ASTM A194, zinc plated. GASKET: EPDM (-30…F to + 230…F) THREADS: MT-3 NPT per ANSI/ASME B1.20.1 MT-9 British standard parallel (BSP) per BS21 MT-3 & MT-9 MECANICAL TEES NOMINAL MAX. HOL E AP P R OX. S IZ E WOR K ING S IZ E WE IGH T IN. P .S .I./IN. A B C D E E ACH (mm) (kP a) (mm) Lbs.(Kg) 1 1/4 x 1/2 300 1.19 2.14 1.64 3.50 1.21 2.25 0.83 32 x 12 2065 30 54 42 89 30.7 57.2 0.4 1 1/4 x 3/4 300 1.19 2.14 1.64 3.50 1.21 2.25 0.87 32 x 19 2065 30 54 42 89 30.7 57.2 0.4 1 1/4 x 1 300 1.19 2.27 1.61 3.50 1.21 2.25 1.06 32 x 25 2065 30 58 41 89 30.7 57.2 0.5 1 1/2 x 1/2 300 1.19 2.26 1.76 3.50 1.33 2.25 0.83 40 x 12 2065 30 57 48 89 33.8 57.2 0.4 1 1/2 x 3/4 300 1.19 2.26 1.76 3.50 1.33 2.25 0.87 40 x 19 2065 30 57 48 89 33.8 57.2 0.4 1 1/2 x 1 300 1.19 2.39 1.73 3.50 1.33 2.25 1.06 40 x 25 2065 30 61 44 89 33.8 57.2 0.5 2 x 1/2 300 1.19 2.51 2.01 2.01 3.75 1.56 2.25 0.87 50 x 12 2065 30 64 51 95 39.6 57.2 0.4 2 x 3/4 300 1.19 2.51 3.75 1.56 2.25 0.94 50 x 19 2065 30 64 51 95 39.6 57.2 0.4 2 x 1 300 1.19 2.64 1.98 3.75 1.56 2.25 1.09 50 x 25 2065 30 67 50 95 39.6 57.2 0.5 2 1/2 x 1/2 300 1.19 2.76 2.26 4.25 1.81 2.25 0.89 65 x 12 2065 30 70 57 108 46.0 57.2 0.4 2 1/2 x 3/4 300 1.19 2.76 2.26 4.25 1.81 2.25 0.98 65 x 19 2065 30 70 57 108 46.0 57.2 0.4 2 1/2 x 1 300 1.19 2.88 2.22 4.25 1.81 1.81 2.25 1.14 65 x 25 2065 30 73 56 108 46.0 57.2 0.5 DIME NS IONS -Inch/mm 3 O.D.x1/2 76, 1x12 300 2065 1.19 30 2.82 72 2.32 59 4.25 108 1.88 47.8 2.25 57.2 3 O.D.x3/4 76, 1x19 300 2065 1.19 30 2.82 72 2.32 59 4.25 108 1.88 47.8 2.25 57.2 3 O.D.x1 76, 1x25 300 2065 1.19 30 2.95 75 2.29 58 4.25 108 1.88 47.8 2.25 57.2 0.89 0.4 0.98 0.4 1.14 0.5 Page 5 GROOVED COUPLINGS For fire protection services request submittal GRS 1.3 The C-4 rigid coupling is designed for rigid piping applications. Cast in place teeth bite into the pipe/fitting shoulder to firmly restrict movement. * Contact Star Pipe Products for actual listings on specific pipes 1. Working pressure and/or end load are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. C-4 RIGID COUPLING NOMINAL ACT UAL MAX. MAX. AL LOW. AP P R OX. S IZ E P IP E WOR KING END P IP E END WE IGH T IN. S IZ E P .S .I./LOAD S E P . QT Y. S IZ E A B C E ACH (mm) IN. (mm) (kP a) Lbs.(N) IN.(mm) Lbs.(Kg) 1 1/4 1.660 300 1623 0 -0.06 2 3/8x2 4.20 2.55 1.70 1.48 32 42.2 5175 7219 0 -1.5 107 65 43 0.7 1 1/2 1.900 300 2126 0 -0.06 2 3/8x2 4.44 2.81 1.70 1.66 40 48.3 5175 9456 0 -1.5 113 71 43 0.8 2 2.375 300 3323 0 -0.06 2 3/8x2 1/4 4.88 3.28 1.76 1.85 50 60.3 5175 14781 0 -1.5 124 83 45 0.8 2 1/2 2.875 300 4869 0 -0.06 2 3/8x2 1/2 5.53 3.78 1.76 2.11 65 73.0 5175 21657 0 -1.5 140 96 45 1.0 3 O.D. 3.000 300 5301 0 -0.06 2 3/8x2 1/2 5.93 4.00 1.76 2.21 65 76.1 5175 23579 0 -1.5 151 102 45 1.0 3 3.500 300 7216 0 -0.12 2 3/8x2 1/2 6.38 4.40 1.76 2.41 80 88.9 5175 32097 0 -3.2 162 112 45 1.1 4 4.500 300 11928 0 -0.12 2 3/8x2 1/2 7.68 5.59 1.98 3.17 100 114.3 5175 53056 0 -3.2 195 142 50 1.4 5 5.563 300 17014 0 -0.12 2 1/2x3 9.06 6.93 2.06 4.50 125 141.3 4825 75678 0 -3.2 230 176 52 2.0 6 6.625 300 24130 0 -0.12 2 1/2x3 10.75 7.87 1.98 5.84 150 168.3 4825 107330 0 -3.2 273 200 50 2.6 6.5 O.D. 6.500 300 23228 0 -0.12 2 1/2x3 10.25 7.99 2.06 5.82 150 165.1 4825 103318 0 -3.2 260 203 52 2.6 8 8.625 300 35056 0 -0.12 2 5/8x3 1/2 13.44 10.21 2.22 10.82 200 219.1 4100 155929 0 -3.2 341 13 56 4.9 10 10.750 300 45381 0 -0.12 2 7/8x5 16.70 12.88 2.62 21.50 250 273.1 3450 201855 0 -3.2 424 327 67 9.8 12 12.750 300 51071 0 -0.12 2 7/8x5 1/2 18.50 14.89 2.62 27.36 300 323.9 2750 227164 0 -3.2 470 378 67 12.4 NUT S /B OL T S DIME NS IONS -Inch/mm (INCH ) UL or FM MAX. * 76, 1 165, 1 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 The C-3 coupling is a flexible light weight style which is ideal for fire protection services and other services where low pressure and ambient temperature conditions are expected. C-3 LW FLEXIBLE COUPLING NOMINAL ACT UAL MAX. MAX. AL LOW. AP P R OX. S IZ E P IP E WOR KING END P IP E END DEG. P E R P IP E WE IGHT IN. S IZ E P .S .I./LOAD S E P . QT Y. S IZ E COUP L ING IN./F T . A B C E ACH (mm) IN.(mm) (kP a) Lbs.(N) IN.(mm) (mm/m) Lbs.(Kg) 1 1/4 1.660 300 649 0 -0.13 2 3/8x2 4° -19' 0.90 3.82 2.53 1.65 1.16 32 42.2 2065 2887 0 -3.2 75 97 64 42 0.5 1 1/2 1.900 300 851 0 -0.13 2 3/8x2 3° -46' 0.79 4.06 2.78 1.65 1.16 40 48.3 2065 3785 0 -3.2 66 103 71 42 0.5 2 2.375 300 1329 0 -0.13 2 3/8x2 1/4 3° -01' 0.63 4.78 3.25 1.71 1.59 50 60.3 2065 5911 0 -3.2 53 121 83 43 0.7 2 1/2 2.875 300 1948 0 -0.13 2 3/8x2 1/4 2° -29' 0.52 5.29 3.75 1.71 1.82 65 73.0 2065 8665 0 -3.2 43 134 95 43 0.8 3 3.500 300 2886 0 -0.13 2 3/8x2 1/2 2° -03' 0.43 5.94 4.39 1.71 2.23 80 88.9 2065 12837 0 -3.2 36 151 112 43 1.0 4 4.500 300 4771 0 -0.25 2 1/2x2 3/4 3° -11' 0.67 7.68 5.81 2.06 4.42 100 114.3 2065 21221 0 -6.4 56 195 148 52 2.0 6 6.625 300 10342 0 -0.25 2 5/8x3 1/4 2° -10' 0.45 10.75 8.09 2.06 7.00 150 168.3 2065 46001 0 -6.4 38 273 205 52 3.2 8 8.625 300 17528 0 -0.25 2 0.35 13.44 10.43 2.06 13.00 200 219.1 2065 77965 0 -6.4 29 341 265 52 5.9 (INCH ) NUT S /B OL T S DE F L ECT ION DIMENS IONS -Inch/mm 3/4x4 1/4 1° -40' UL or FM MAX. * * Contact Star Pipe Products for actual listings on specific pipes Page 6 GROOVED COUPLINGS For fire protection services request submittal GRS 1.3 The model C-1 is our standard coupling designed for a broad range of piping applications. It is a flexible style which provides allowance for controlled pipe movement caused by thermal changes, settling or seismic action as well as dampen noise and vibration. C-1 FLEXIBLE COUPLING NOMINAL ACT UAL MAX. MAX. AL LOW. AP P R OX. S IZ E P IP E WOR KING END P IP E END DEG. P E R P IP E WE IGHT IN. S IZ E P .S .I./LOAD S E P . QT Y. S IZ E COUP L ING IN./F T . A B C E ACH (mm) IN.(mm) (kP a) Lbs.(N) IN.(mm) (mm/m) Lbs.(Kg) 1 1/4 1.660 300 300 300 300 300 300 300 300 300 300 300 300 300 2164 0 -0.13 2 3/8x2 4ß -19’ 0.90 4.20 2.75 1.78 1.40 32 42.2 6900 9625 0 -3.2 75 107 70 45 0.6 1 1/2 1.900 2835 0 -0.13 2 3/8x2 3ß -46’ 0.79 4.44 3.03 1.78 1.48 40 48.3 6900 12610 0 -3.2 66 113 77 45 0.7 2 2.375 4430 0 -0.13 2 3/8x2 3ß -01’ 0.63 4.88 3.46 1.84 2.00 50 60.3 6900 19705 0 -3.2 53 124 88 47 0.9 2 1/2 2.875 6492 0 -0.13 2 3/8x2 2ß -29’ 0.52 5.53 4.12 1.85 2.25 65 73.0 6900 28876 0 -3.2 43 140 105 47 1.0 3 O.D. 3.000 7069 0 -0.13 2 3/8x2 2ß -29’ 0.50 5.50 4.00 1.84 2.25 65 76.1 6900 31443 0 -3.2 52 140 102 47 1.0 3 3.500 9621 0 -0.13 2 1/2x2 3/4 2ß -03’ 0.43 6.38 4.62 1.84 2.70 80 88.9 6900 42794 0 -3.2 36 162 117 47 1.2 4 4.500 11928 0 -0.25 2 1/2x2 3/4 3ß -11’ 0.67 7.68 5.81 2.06 4.42 100 114.3 5175 53056 0 -6.4 56 195 148 52 2.0 5 5.563 17014 0 -0.25 2 5/8x3 1/4 2ß -35’ 0.54 9.68 7.12 2.06 6.26 125 141.3 4825 75678 0 -6.4 45 246 181 52 2.8 6 6.625 24130 0 -0.25 2 0.45 10.75 8.09 2.06 7.00 150 168.3 4825 107330 0 -6.4 38 273 205 52 3.2 6.5 O.D. 6.500 23228 0 -0.25 2 5/8x3 1/4 2ß -10’ 0.46 10.50 8.00 2.06 7.00 150 165.1 4825 103318 0 -6.4 38 267 203 52 3.2 8 8.625 35056 0 -0.25 2 3/4x4 1/4 1ß -40’ 0.35 13.44 10.43 2.38 13.00 200 219.1 4100 155929 0 -6.4 29 341 265 60 5.9 10 10.750 45381 0 -0.25 2 7/8x5 1/2 1ß -20’ 0.28 250 273.1 3450 201855 0 -6.4 23 12 12.750 51071 0 -0.25 2 7/8x5 1/2 1ß -07’ 0.23 300 323.9 2750 227164 0 -6.4 19 NUT S /B OL T S (INCH ) DE F L ECT ION D IME NS IONS -Inch/mm 5/8x3 1/4 2ß -10’ 28.39 23.00 10.4 12.9 2.59 2.59 66 66 15.38 13.25 337 391 18.50 16.00 406 470 76, 1 165, 1 UL or FM MAX. * 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 1. Working pressure and/or end load are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. Model C-7 couplings are available in sizes 3/4 -24 and are ideal for applications within industrial and commercial construction, power plants, mining, process piping and hydraulic elevator piping. It is a flexible style which provides allowance for controlled pipe movement caused by thermal changes, settling or seismic action as well as dampen noise and vibration. * Contact Star Pipe Products for actual listings on specific pipes C-7 FLEXIBLE COUPLING NOMINAL ACT UAL MAX. MAX. AL LOW. AP P R OX. S IZ E P IP IP E WOR KING END P IP E END DEG. P E R P IP E WE IGHT IN. S IZ E P .S .I./LOAD S E P . QT Y. S IZ E COUP L ING IN./F T . A B C E ACH (mm) IN.(mm) (kP a) Lbs.(N) IN.(mm) (mm/m) Lbs.(Kg) 3/4 1 1 1/4 1 1/2 2 2 1/2 34568 10 12 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.500 5.563 6.625 8.625 10.750 12.750 500 500 500 500 500 500 500 500 500 500 500 500 500 865 1358 2164 2835 4430 6492 9621 15904 24305 34471 46741 72610 102141 0 -0.13 0 -0.13 0 -0.13 0 -0.13 0 -0.13 0 -0.13 0 -0.13 0 -0.25 0 -0.25 0 -0.25 0 -0.25 0 -0.25 0 -0.25 2222222222222 3/8x2 3/8x2 1/2x2 1/2 1/2x2 1/2 1/2x2 1/2 1/2x2 3/4 1/2x2 3/4 5/8x3 1/4 3/4x4 1/4 3/4x4 1/4 7/8x5 1x6 1x6 1/2 6ß -46’ 5ß -26’ 4ß -19’ 3ß -46’ 3ß -01’ 2ß -29’ 2ß -03’ 3ß -11’ 2ß -35’ 2ß -10’ 1ß -40’ 1ß -20’ 1ß -07’ 1.42 1.14 0.90 0.79 0.63 0.52 0.43 0.67 0.54 0.45 0.35 0.28 0.23 3.63 3.88 4.63 5.00 5.63 6.25 7.00 8.50 10.25 11.50 14.50 16.75 19.00 2.13 2.38 2.63 3.00 3.63 4.25 5.00 6.38 7.63 9.00 11.38 13.50 15.50 1.75 1.75 1.75 1.75 1.75 1.75 1.75 2.00 2.00 2.00 2.38 2.50 2.50 1.3 1.4 2.1 2.3 2.7 3.8 4.2 7.0 11.5 13.5 23.0 31.0 35.0 20 25 32 40 50 65 80 100 125 150 200 250 300 26.7 33.4 42.2 48.3 60.3 73.0 88.9 114.3 141.3 168.3 219.1 273.1 323.9 6900 6900 6900 6900 6900 6900 6900 6900 6900 6900 5520 5520 5520 3847 6040 9625 12610 19705 28876 42794 70740 108108 153327 207903 322968 454322 0 -3.2 0 -3.2 0 -3.2 0 -3.2 0 -3.2 0 -3.2 0 -3.2 0 -6.4 0 -6.4 0 -6.4 0 -6.4 0 -6.4 0 -6.4 118 95 75 66 53 43 36 56 45 38 29 23 19 92 99 118 127 143 159 178 216 260 292 368 425 483 54 60 67 76 92 108 127 162 194 229 289 343 394 44 44 44 44 44 44 44 51 51 51 60 64 64 0.6 0.6 0.9 1.0 1.2 1.7 1.9 3.2 5.2 6.1 10.4 14.1 15.9 NUT S /B OL T S DE F L ECT ION DIMENS IONS -Inch/mm (INCH ) UL or FM MAX. * 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 1. Working pressure and/or end load are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe pipe schedules may be found on page 54. * Contact Star Pipe Products for actual listings on specific pipes Page 7 1. Working pressure and/or end load are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. The RC-1 reducing coupling allows connecting two different pipe sizes on the same run. This coupling replaces a reducer and two couplings. RC-1 REDUCING COUPLING NOMINAL ACT UAL MAX. MAX. AL LOW. AP P R OX. S IZ E P IP E WOR KING END P IP E END DEG. P E R P IP E WE IGHT IN. S IZ E P .S .I./LOAD S E P . QT Y. S IZ E COUP L ING IN./F T . A B C E ACH (mm) IN.(mm) (kP a) Lbs.(N) IN.(mm) (mm/m) Lbs.(Kg) 2x1 1/2 2.38/1.66 300 1551 0 -0.14 2 3/8x2 1¡ -53’ 0.40 4.88 3.30 1.85 2.05 50x40 60.3/48.3 2400 6899 0 -3.2 33 124 84 47 2.8 2 1/2x2 2.88/2.38 300 2272 0 -0.14 2 3/8x2 1¡ -33’ 0.32 5.75 4.04 1.85 2.84 65x50 70.3/60.3 2400 10106 0 -3.2 27 146 103 47 1.3 3x2 3.50/2.38 300 3367 0 -0.14 2 1/2x2 3/4 1¡ -17’ 0.26 6.42 4.54 1.85 3.65 80x50 88.9/88.9/60.3 2400 14976 0 -3.2 22 163 115 47 1.7 3x2 1/2 3.50/2.88 300 3367 0 -0.14 2 1/2x2 3/4 1¡ -17’ 0.26 6.42 4.54 1.85 4.26 80x65 88.9/73.0 2400 14976 0 -3.2 22 163 115 47 1.9 4x2 4.50/2.38 300 5567 0 -0.25 2 1/2x2 3/4 2¡ -38’ 0.55 7.82 5.75 2.00 5.36 100x50 144.3/60.3 2400 24762 0 -6.4 46 199 146 51 2.4 4x2 1/2 4.50/2.88 300 5567 0 -0.25 0.55 7.82 5.75 2.00 5.42 100x65 114.3/73.3 2400 24762 0 -6.4 46 199 146 51 2.5 4x3 4.50/3.50 300 5567 0 -0.25 2 1/2x2 3/4 2¡ -38’ 0.55 7.82 5.75 2.00 5.62 100x80 114.3/88.9 2400 24762 0 -6.4 46 199 146 51 2.5 5x4 5.56/4.50 300 8498 0 -0.25 2 5/8x3 1/4 2¡ -05’ 0.44 9.56 6.80 2.14 6.50 125x100 141.2/114.3 2400 37799 0 -6.4 37 243 173 54 2.9 6x4 6.63/4.50 300 12065 0 -0.25 2 5/8x3 1/4 1¡ -44’ 0.36 10.88 8.00 2.06 6.94 150x100 168.3/114.3 2400 53665 0 -6.4 30 276 203 52 3.1 8x6 8.63/6.63 300 20449 0 -0.25 2 7/8x5 1¡ -15’ 0.26 13.51 10.31 2.37 19.54 200x150 219.1/168.3 2400 90957 0 -6.4 22 343 262 60 8.9 (INCH ) NUT S /B OL T S DE F L ECT ION DIMENS IONS -Inch/mm 2 1/2x2 3/4 2¡ -38’ UL or FM MAX. * 2065 2065 2065 2065 2065 2065 2065 2065 2065 2065 Note: The effective sealing area of the mating flange must be free from gouges or deformities of any type to ensure proper sealing of the gasket. 1. Working pressure and/or end load are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. 4. Required flange bolts to be supplied by installer. 5. See F-1, page 9, for additional technical information. SF-1 GROOVED FLANGE ADAPTER NOMINAL ACT UAL MAX. MAX. AP P R OX. S IZ E P IP E WOR KING END MAX MIN WE IGHT IN. S IZ E P .S .I./LOAD QT Y. S IZ E A B C B OR E S U R F ACE E ACH (mm) IN.(mm) (kP a) Lbs.(N) D E Lbs.(Kg) 2 2.375 300 1329 4 5/8x2 3/4 6.00 4.75 0.75 2.375 3.270 3.20 50 60.3 2065 5911 152 121 19 60.3 83.1 1.5 2 1/2 2.875 300 1948 4 5/8x3 7.00 5.50 0.88 2.875 3.770 4.60 65 73.0 2065 8665 178 140 22 73.0 95.8 2.1 3 3.500 300 2886 4 5/8x3 7.50 6.00 0.94 3.500 4.395 5.70 80 88.9 2065 12837 191 152 24 88.9 111.6 2.6 4 4.500 300 4771 8 5/8x3 9.00 7.50 0.95 4.500 5.395 7.90 100 114.3 2065 21221 229 191 24 114.3 137.0 3.6 6 6.625 300 10342 8 3/4x3 1/2 11.00 9.50 1.00 6.625 7.520 10.00 150 76.1 2065 46001 279 241 25 168.3 191.0 4.5 8 8.625 300 17528 8 3/4x3 1/2 13.50 11.75 1.13 8.625 9.875 15.70 200 219.1 2065 77965 343 298 29 219.1 250.8 7.1 F LANGE NUT S /DIME NS IONS -Inch/mm B OL T S (INCH) ULOR FM MAX * GROOVED COUPLINGS For fire protection services request submittal GRS 1.3 * Contact Star Pipe Products for actual listings on specific pipes The SF-1 Flange enables class 125/150 flange end components to be connected directly into a grooved end piping system. A special gasket provides a permanent seal between the pipe and the mating flange. Integral closing tabs on the O.D. of the flange facilitate assembly. * Contact Star Pipe Products for actual listings on specific pipes 38 A H E A D O F T H E F L O W™ www.nibco.com Revised 08/01/03 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com MATERIAL LIST PART SPECIFICATION 1. Upper Stem Stainless Steel ASTM A 582 Type 416 2. Upper Bushing PTFE Bronze Sintered on Steel 3. "O" Ring Buna-N 4. Body Ductile Iron ASTM A 395 with Polymide Coating 5. Disc Ductile Iron ASTM A 395 with EPDM Encapsulation 6. Lower Bushing PTFE Bronze Sintered on Steel 7. Lower Stem Stainless Steel ASTM A 582 Type 416 8. Dust Plug PVC 9. Nameplate Aluminum 10. Gear Operator Cast Iron and Steel 11. Indicator Flag Cast Iron 12. Handwheel Cast Iron *-8N version has two factory mounted internal supervisory switches. -4N version is gear operated only Uses NIBCO model #TS-4 Switch Kit. Polymide coating has NSF certification. Dimensions Size J K L M N P Q R Weight In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. Lbs. Kg. 2¹⁄2 65 3.54 90 2.13 54 5.82 148 5.67 144 4.19 106 3.25 83 5.9 150 3.46 88 22 10.0 3 O.D. 76.1 3.54 90 2.13 54 5.82 148 5.67 144 4.19 106 3.25 83 5.9 150 3.46 88 22 10.4 3 80 3.54 90 2.13 54 5.82 148 5.94 151 4.44 113 3.54 90 5.9 150 3.97 101 23 10.4 4 100 3.54 90 2.13 54 7.64 194 6.31 173 5.33 135 4.35 110 5.9 150 5.03 128 28 12.7 5 125 3.54 90 2.13 54 7.64 194 7.32 186 5.83 148 4.84 123 5.9 150 6.27 159 31 14.1 6 150 3.54 90 2.13 54 7.64 194 8.62 219 7.11 181 5.93 151 5.9 150 7.25 184 41 18.6 6 O.D. 165.1 3.54 90 2.13 54 7.64 194 8.62 219 7.11 181 5.93 151 5.9 150 7.25 184 41 18.6 8 200 3.54 90 2.13 54 7.91 201 9.80 249 8.05 204 6.87 174 9.8 250 9.25 235 53 24.1 10 250 3.98 101 3.03 77 9.49 241 11.61 295 9.86 250 9.17 233 11.8 300 11.25 286 88 40.0 300 PSI/20.7 Bar Non-Shock Cold Water 2¹⁄2" -8" 175 PSI/12.1 Bar Non-Shock Cold Water 10" UL/ULC LISTED • FMRC APPROVED • 2¹⁄2" -10" UL LISTED FOR INDOOR AND OUTDOOR SERVICE • CALIFORNIA STATE FIRE MARSHALL APPROVAL NO. 7770-1243:101 • APPROVED BY THE NEW YORK CITY MEA 9-97-E 300 lb. WWP UL/FM Butterfly Valves Fire Protection Valve • Grooved Mechanical Style • Nylon Coated Ductile Iron • Extended Neck • Elastomer Encapsulated Disc • Accepts Internal and External Supervisory Switches DIMENSIONS—WEIGHTS—QUANTITIES Dimensions Size A B C D E F G H In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. 2¹⁄2 65 2.88 73 2.72 69 0.31 8 0.63 16 3.85 98 2.42 61 11.94 303 2.91 74 3 O.D. 76.1 3.00 76 2.84 72 0.31 8 0.63 16 3.85 98 2.42 61 11.94 303 2.91 74 3 80 3.50 89 3.34 85 0.31 8 0.63 16 3.85 98 2.86 73 12.48 317 2.91 74 4 100 4.50 114 4.33 110 0.38 10 0.63 16 4.56 116 3.84 98 14.18 360 2.91 74 5 125 5.56 141 5.39 137 0.38 10 0.63 16 5.86 149 4.79 122 15.17 385 2.91 74 6 150 6.63 168 6.45 164 0.38 10 0.63 16 5.86 149 5.73 146 17.54 446 2.91 74 6 O.D. 165.1 6.51 165 6.32 161 0.38 10 0.63 16 5.86 149 5.73 146 17.54 446 2.91 74 8 200 8.63 219 8.44 214 0.44 11 0.75 19 5.26 134 7.71 196 19.42 493 2.91 74 10 250 10.75 273 10.56 268 0.50 13 0.75 19 6.29 160 9.56 243 24.03 610 3.90 99 GD-4765-8N* Grooved 2¹⁄2" thru 8" GD-1765-8N 10" (not shown) IPS CARBON STEEL PIPE – GROOVED VALVES VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY ® REGISTERED TRADEMARK OF VICTAULIC – © COPYRIGHT 2005 VICTAULIC – PRINTED IN U.S.A. – SKU #WCAS-6AYRNC 1473 REV D 08.08 United States • Phone: 1-800-PICK-VIC (1-800-742-5842) • Fax: 610-250-8817 • e-mail: pickvic@victaulic.com Canada • Phone: 905-884-7444 • Fax: 905-884-9774 • e-mail: viccanada@victaulic.com Europe • Phone: 32-9-381-1500 • Fax: 32-9-380-4438 • e-mail: viceuro@victaulic.be UK • Phone: 44(0)1438741100 • Fax: 44(0)1438313883 • e-mail: viceuro@victaulic.be Central and South America • Phone: 610-559-3300 • Fax: 610-559-3608 • e-mail: vical@victaulic.com Australasia • Phone: 86-21-54253300 • Fax: 86-21-54253671 • e-mail: vicap@victaulic.com Series 716 Vic-Check® Valves PRODUCT DESCRIPTION The Series 716 check valve is a product of computer-assisted innovative engineering with quality features including a new hydrodynamically efficient profile. Available in sizes 21/2 -12"/65 -300 mm, the Vic-Check® valve utilizes a spring-assisted, single-disc design that achieves a leak-free seal with as little as 5 ft./1.5 m of head. The valve can be installed in both horizontal and vertical positions. Series 716 check valves are engineered for long life and seize-free sealing. In sizes 21/2 and 3"/65 and 80 mm, the elastomeric seal, mounted on the aluminum bronze disc, seats against the machined area of the body, which is completely coated with polyphenylene sulphide (PPS). Sizes 4 -12"/100 -300 mm feature an elastomer-encapsulated disc and a welded-in nickel seat. Every valve is factory tested to its working pressure of 300 psi/2065 kPa. Drains are provided both upstream and downstream of the disc. Grooved ends allow fast, easy installation with just two Victaulic couplings. The valve may also be connected to flanged (ANSI Class 150) components using Style 741 Vic-Flange adapters on either end. DIMENSIONS Sizes 21/2 & 3" Sizes 4 -12" Nom. Size In./mm Actual Outside Dia. In./mm Dimensions-Inches/millimeters Approx. Wgt. Ea. Lbs./kg E -E A Overall Width B C D E J K P R 21/2 2.875 3.88 4.25 3.60 – – – – – – 3.6 65 73.0 99 108 91 – – – – – – 1.6 76,1 mm 3.000 3.88 4.25 3.60 – – – – – – 3.6 76.1 99 108 91 – – – – – – 1.6 3 3.500 4.25 5.06 4.19 – – – – – – 4.5 80 88.9 108 129 106 – – – – – – 2.0 4 4.500 9.63 6.00 3.90 2.75 3.50 2.00 4.50 3.50 3.35 16.0 100 114.3 245 152 99 70 89 51 114 89 85 7.3 5 5.563 10.50 6.80 4.50 4.17 4.17 2.15 5.88 4.08 4.02 20.0 125 141.3 267 173 114 106 106 55 149 104 102 9.1 139,7 mm 5.500 10.50 6.80 4.50 4.17 4.17 2.15 5.88 4.08 4.02 27.0 139.7 267 173 114 106 106 55 149 104 102 12.3 6 6.625 11.50 8.00 5.00 4.50 4.50 2.38 6.67 4.73 3.89 28.0 150 168.3 292 203 127 114 114 61 169 120 99 12.7 165,1 mm 6.500 11.50 8.00 5.00 4.50 4.50 238 6.67 4.73 3.89 28.0 165.1 292 203 127 114 114 61 169 120 99 12.7 8 8.625 14.00 9.88 6.10 5.05 5.65 2.15 8.75 5.70 5.75 40.0 200 219.1 356 251 155 128 144 55 222 145 146 18.1 10 10.750 17.00 12.00 7.10 5.96 6.69 2.15 10.92 6.93 – 100.0 250 273.0 432 305 180 151 170 55 277 176 – 45.4 45.4 12 12.750 19.50 14.00 8.10 6.91 7.64 2.51 12.81 7.93 – 140.0 300 323.9 495 356 206 176 194 64 325 201 – 63.5 Typical 4 -8" Typical 10 -12" BK ¹⁄2" NPT Upstream Drain (Optional) ¹⁄2" NPT Downstream Drain (Optional) J 2 1 C D E A P R CE B D J K A P 2 1 3 ¹⁄2" NPT Upstream Drain (Optional) ¹⁄2" NPT Downstream Drain (Optional) 2" NPT (Drain Optional) Typical 21/2 -3" C A B 2 Series 716 Vic-Check® Valves 08.08 PERFORMANCE Formulas for C V Vic-Check valves combine Values: high pressure capabilities with low pressure drop performance. The grooved end design permits fast, easy installation. The seat provides leak-free sealing under conditions as low as five feet of head. CV values for flow of water at +60°F/+16°C with a fully open valve are shown in the table at right. Nom. Size In./mm Actual Outside Dia. In./mm C V (Full Open) Nom. Size In./mm Actual Outside Dia. In./mm C V (Full Open) Nom. Size In./mm Actual Outside Dia. In./mm C V (Full Open) 21/2 2.875 140 139.7 mm 5.500 700 8 § 8.625 1800 65 73.0 139.7 200 219.1 76,1 mm 3.000 140 5 5.563 700 10 § 10.750 3000 76.1 125 141.3 250 273.0 3 3.500 250 165.1 mm 6.500 1000 12 § 12.750 4200 80 88.9 165.1 300 323.9 4 4.500 390 6 6.625 1000 100 114.3 150 168.3 P Q2 CV2 = ---------Q CV = × P Where: Q = Flow (GPM) CV = Flow Coefficient P = Pressure Drop (psi) NOTE: Placement of check valves too close to sources of unstable flow will shorten the life of the valve and potentially may damage the system. To extend valve life, valves should be installed a reasonable distance downstream from pumps, elbows, expanders, reducers or other similar devices. Sound piping practices dictate a minimum of five (5) times the pipe diameter for general use. Distances between three (3) and five (5) diameters are allowable provided the flow velocity is less than eight (8) feet per second (2.4 mps). Distances less than three (3) diameters are not recommended and will violate the Victaulic product warranty. 800 3,000 8,000 6.0 5.0 4.0 3.0 2.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 PRESSURE DROP – P.S.I. 10 20 30 40 60 80 100 200 300 400 600 1,000 2,000 4,000 6,000 10,000 FLOW RATE – G.P.M. SERIES 716 FLOW OF WATER AT 60F (16C) THROUGH VALVE 2¹⁄2" & 76 mm5" & 139 mm 3" 4" 8" 6" & 165 mm10" 12" 08.08 Series 716 Vic-Check® Valves 3 MATERIAL SPECIFICATIONS Body: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. 21/2 -3"/65 -80 mm sizes PPS coated, UL classified in accordance with ANSI/NSF 61 for potable water service. 4 -12"/100 -300 mm sizes painted black enamel. Body Seat: Sizes 21/2 -3"/65 -80 mm machined surfaces PPS coated. 4 -12"/100 -300 mm integrally welded-on nickel alloy. Disc Seal or Coating: (Specify Choice) • Grade “E” EPDM EPDM (Green color code). Temperature range –30°F to +230°F/–34°C to +110°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for for cold +86°F/+30°C and hot +180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade “T” nitrile Nitrile (Orange color code). Temperature range –20°F to +180°F/–29°C to +82°C. Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range; except hot, dry air over +140°F/+60°C and water over +150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. • Grade “O” fluoroelastomer Fluoroelastomer (Blue color code). Temperature range +20°F to +300°F/–7°C to +149°C. Recommended for many oxidizing acids, petroleum oils, halogenated hydrocarbons, lubricants, hydraulic fluids, organic liquids and air with hydrocarbons to +300°F/+149°C. *Services listed are General Service Recommendations only. It should be noted that there are services for which these disc liners are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific liner service recommendations and for a listing of services which are not recommended. Discs: 21/2 -3"/65 -80 mm Aluminum bronze conforming to ASTM B-148. 4 -12"/100 -300 mm ductile iron conforming to ASTM A-536 Grade 65-45-12, fully encapsulated in Grade “E”, “T”, or ““O” elastomer. (See Disk Seal) Shaft: 21/2 -3"/65 -80 mm Type 416 stainless steel. 4 -12"/100 -300 mm Type 316 stainless steel. Spring: All sizes Type 302/304 stainless steel. Shaft Plug: 21/2 -3"/65 -80 mm only; SAE Hex Socket Type conforming to ASTM A-576, cadmium plated to military specifications QQ-P-416A, class 3 type 2. Pipe Plug: 4 -12"/100 -300 mm only; carbon steel zinc plated to ASTM B-633. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266 www.tolco.com 61 www.tolco.com Revision 5/24/2001 ™® a brand of Fig. 65 and Fig. 66 Reversible C-Type Beam Clamps 3/4" and 11/4" Throat Openings Size Range — (Fig. 65 and Fig. 66) 3/8", 1/2" and 5/8" rod Material — Carbon Steel with hardened cup point set screw and jam nut Function — Recommended for hanging from steel beam where flange thickness does not exceed 3/4" (Fig. 65) or 11/4" (Fig. 66). Features — All steel construction eliminates structural deficiencies associated with casting type beam clamps. May be used on top or bottom flange of the beam. (Beveled lip allows hanging from top flange where clearance is limited.) May be installed with set screw in up or down position. Offset design permits unlimited rod adjustment by allowing the rod to be threaded completely through the clamp. Open design permits inspection of thread engagement. Approvals — Underwriters’ Laboratories Listed in the USA (UL) and Canada (cUL). Factory Mutual Engineering approved. Conforms to Federal Specification WW-H-171E, Type 23 and Manufacturers Standardization Society SP-69, Type 19. Exceeds requirements of the National Fire Protection Association (NFPA), Pamphlet 13, 3/8" rod will support 1/2" thru 4" pipe, 1/2" rod will support 1/2" thru 8" pipe. Finish — Plain Note — Available in Electro-Galvanized and HDG finish. Order By — Figure number, rod size and finish Fig. 65 Patent #4,570,885 Dimensions • Weights Rod Size Max. Rec. Approx. A B C D E F Load Lbs.* Wt./100 3/8 13/16 3/4 1 7/16 1 610 28 1/2 11/2 3/4 1 9/16 11/4 1130 55 5/8 11/2 3/4 1 9/16 11/4 1130 55 * Max. loads for clamp with set screw in up or down position. Fig. 65 Dimensions • Weights Rod Size Max. Rec. Approx. A B C D E F Load Lbs.* Wt./100 3/8 13/16 11/4 1 7/16 1 610 28 1/2 11/2 11/4 1 9/16 11/4 1130 55 5/8 11/2 11/4 1 9/16 11/4 1130 55 * Max. loads for clamp with set screw in up or down position. Fig. 66 134 Hilti Product Technical Guide 2001 • Hilti U.S.: 1-800-879-8000 /www.us.hilti.com • Hilti Canada: 1-800-363-4458 /www.ca.hilti.com Anchor Size in. 1/4 3/8 1/2 5/8 3/4 Details (mm) (6.4) (9.5) (12.7) (15.9) (19.1) dbit: bit diameter1 in. 3/8 1/2 5/8 27/32 1 hnom: std. depth of embed. in. 1 19/16 2 29/16 33/16 : anchor length (mm) (25) (40) (51) (65) (81) h1: hole depth th: useable thread in. 7/16 5/8 11/16 7/8 13/8 length (mm) (11) (15) (17) (22) (34) Threads per in. 20 16 13 11 10 h: min. base material in. 3 31/8 4 51/8 63/8 thickness (mm) (76) (79) (102) (130) (162) Tinst: max. tightening ft lb 4 11 22 37 80 torque (Nm) (5.4) (14.9) (29.8) (50.2) (108.5) 4.3.5.3 TECHNICAL DATA HDI/HDI-L Specification Table Combined Shear and Tension Loading (Ref. Section 4.1.3) 10 HDI/HDI-L HDI/HDI-L HDI/HDI-L HDI HDI 1. For Hilti matched tolerance carbide tipped drill bits, see section 10.4.1. Hilti Product Technical Guide 2001 • Hilti U.S.: 1-800-879-8000 /www.us.hilti.com • Hilti Canada: 1-800-363-4458 /www.ca.hilti.com 135 Anchoring Systems 4.3.5 HDI /HDI-L Drop-In Anchor Carbon Steel HDI Ultimate Loads in Concrete Carbon Steel HDI Allowable Loads in Concrete Note: The ultimate shear and allowable shear values are based on the use of SAE Grade 5 bolts, (fy = 85 ksi, Fult = 120 ksi) with the exception of the 1/4" HDI/HDI-L in f’c = 6000 psi concrete which is based upon the use of a SAE Grade 8 bolt (fy = 120 ksi, Fult = 150 ksi). Note: The ultimate and allowable shear values are based on the use of Type 18-8 bolts. 1. The tabulated shear and tensile values are for anchors installed in structural lightweight concrete having the designated ultimate compressive strength at the time of installlation. The concrete must comply with ASTM C 330-77. 2. The tabulated shear and tensile values are for anchors installed through 20 gauge intermediate decking into structural lightweight concrete having the designated ultimate strength at the time of installation. The concrete must comply with ASTM C 330-77. Anchors were located in the valley of the fluted deck. 3. The allowable values are based on the use of SAE Grade 2 bolts installed in the anchors. 4. Based on using a safety factor of 4 Stainless Steel HDI Ultimate Loads in Concrete SS HDI – 1/4 ( 6.4) 1930 ( 8.6) 2400 (10.7) 2950 (13.1) 2400 (10.7) SS HDI – 3/8 ( 9.5) 4170 (18.5) 4920 (21.9) 5850 (26.0) 4920 (21.9) SS HDI – 1/2 (12.7) 7350 (32.7) 11040 (49.1) 9630 (42.8) 11040 (49.1) SS HDI – 5/8 (15.9) 10540 (46.9) 18040 (80.2) 15100 (67.2) 18040 (80.2) SS HDI – 3/4 (19.1) 15340 (68.2) 22320 (99.3) 20130 (89.5) 22320 (99.3) Anchor size 4000 psi (27.6 MPa) in. (mm) Tension lb (kN) Shear lb (kN) 6000 psi (41.4 MPa) Tension lb (kN) Shear lb (kN) Carbon Steel HDI Allowable Load in Lightweight Concrete3, 4 HDI – 1/4 ( 6.4) 480 ( 2.1) 600 ( 2.7) 740 ( 3.3) 600 ( 2.7) HDI – 3/8 ( 9.5) 1040 ( 4.6) 1230 ( 5.5) 1460 ( 6.5) 1230 ( 5.5) HDI – 1/2 (12.7) 1840 ( 8.2) 2760 (12.4) 2410 (10.7) 2760 (12.3) HDI – 5/8 (15.9) 2630 (11.7) 4510 (20.1) 3770 (16.8) 4510 (20.1) HDI – 3/4 (19.1) 3830 (17.0) 5580 (24.8) 5030 (22.4) 5580 (24.8) Anchor installed in 3000 psi (20.7 MPa) Anchor size Lt. Wt. Concrete 1 in. (mm) Tension lb (kN) Shear lb (kN) Anchor Installed Through Steel Decking into 3000 psi (20.7 MPa) Lt. Wt. Concrete2 Tension lb (kN) Shear lb (kN) Stainless Steel HDI Allowable Loads in Concrete HDI – 1/4 ( 6.4) 465 (2.1) 340 ( 1.5) 530 (2.4) 335 (1.5) HDI – 3/8 ( 9.5) 755 (3.4) 940 ( 4.2) 880 (3.9) 1010 (4.5) HDI – 1/2 (12.7) 1135 (5.0) 1700 ( 7.6) 1105 (4.9) 1755 (7.8) HDI – 5/8 (15.9) 1465 (6.5) 2835 (12.6) — — HDI – 3/4 (19.1) 2075 (9.2) 3680 (16.4) — — Anchor size 4000 psi (27.6 MPa) in. (mm) Tension lb (kN) Shear lb (kN) 6000 psi (41.4 MPa) Tension lb (kN) Shear lb (kN) 2000 psi (13.8 MPa) 4000 psi (27.6 MPa) 6000 psi (41.4 MPa) Tension lb(kN) Shear lb (kN) Tension lb(kN) Shear lb (kN) Tension lb (kN) Shear lb (kN) HDI HDI-L HDI HDI-L HDI HDI-L HDI HDI-L HDI HDI-L HDI HDI-L 1/4 ( 6.4) 1995 ( 8.9) 1995 ( 8.9) 1800 ( 8.0) 1800 ( 8.0) 2270 (10.1) 2270 (10.1) 2500 (11.1) 2500 (11.1) 3150 (14.0) 3150 (14.0) 2800 (12.5) 2800 (12.5) 3/8 ( 9.5) 3555 ( 15.8) 3555 (15.8) 3850 (17.1) 3850 (17.1) 4460 (19.8) 4460 (19.8) 5000 (22.2) 5000 (22.2) 5430 (24.2) 5430 (24.2) 6000 (26.7) 6000 (26.7) 1/2 (12.7) 4470 ( 19.9) 4470 (19.9) 6000 (26.7) 6000 (26.7) 7140 (31.8) 7140 (31.8) 8500 (37.8) 7750 (34.4) 9375 (41.7) 9375 (41.7) 10000 (44.5) 10000 (44.5) 5/8 (15.9) 7500 ( 33.4) -10000 (44.5) -11685 (52.0) -13000 (57.8) -14865 (66.1) -15000 (66.7) -3/4 (19.1) 10000 ( 44.5) -15500 (69.0) -16260 (72.3) -20000 (89.0) -22250 (99.0) -22000 (97.9) -Anchor size in. (mm) 2000 psi (13.8 MPa) 4000 psi (27.6 MPa) 6000 psi (41.4 MPa) Tension lb(kN) Shear lb (kN) Tension lb(kN) Shear lb (kN) Tension lb (kN) Shear lb (kN) HDI HDI-L HDI HDI-L HDI HDI-L HDI HDI-L HDI HDI-L HDI HDI-L 1/4 ( 6.4) 500 ( 2.2) 500 (2.2) 450 ( 8.0) 450 (8.0) 570 ( 2.5) 570 (2.5) 625 ( 2.8) 625 (2.8) 790 ( 3.5) 790 ( 3.5) 700 ( 3.1) 700 ( 3.1) 3/8 ( 9.5) 890 ( 4.0) 890 (4.0) 965 ( 4.3) 965 (4.3) 1115 ( 5.0) 1115 (5.0) 1250 ( 5.6) 1250 (5.6) 1360 ( 6.0) 1360 ( 6.0) 1500 ( 6.7) 1500 ( 6.7) 1/2 (12.7) 1120 ( 5.0) 1120 (5.0) 1500 ( 6.7) 1500 (6.7) 1785 ( 7.9) 1785 (7.9) 2125 ( 9.5) 1940 (8.6) 2345 (10.4) 2345 (10.4) 2500 (11.1) 2500 (11.1) 5/8 (15.9) 1875 ( 8.3) -2500 (11.1) -2920 (13.0) -3250 (14.5) -3715 (16.5) -3750 (16.7) -3/4 (19.1) 2500 (11.1) -3875 (17.2) -4065 (18.1) -5000 (22.2) -5565 (24.8) -5500 (24.5) -Anchor size in. (mm) 136 Anchoring Systems Hilti Product Technical Guide 2001 • Hilti U.S.: 1-800-879-8000 /www.us.hilti.com • Hilti Canada: 1-800-363-4458 /www.ca.hilti.com HDI /HDI-L Drop-In Anchor 4.3.5 1.0 0 0 .2 .4 .6 .8 1.0 scrsmin s hnom Anchor Spacing Adjustment Factor (fA) 2.0 3.0 Shear & Tension cmin = 2.0 hnom, ccr = 3.0 hnom fRN = 0.2 + 0.4 for ccr > c > cmin cmin = 2.0 hnom, ccr = 3.0 hnom fRV = 0.35 – 0.05 for ccr > c > cmin Anchor Spacing and Edge Distance Guidelines (See Anchoring Technology Section 4.1.3) Influence of Anchor Spacing and Edge Distance fA, fR Anchor Spacing Adjustment Factors Edge Distance Adjustment Factors hnom = standard embedment depth 1.0 0 0 .2 .4 .6 .8 1.0 ccr Edge Distance Adjustment Factor (fRV, fRN) c hnom2.0 3.0 Shear c Tension min s = Actual spacing smin = 2.0 hnom scr = 3.5 hnom c = Actual edge distance cmin = 2.0 hnom ccr = 3.0 hnom Load Adjustment Factors (Anchor Spacing) fA Tension/Shear Loads Load Adjustment Factors (Edge Distance) fR Spacing s in. (mm) Edge Distance c in. (mm) Anchor Diameter 1/4 3/8 1/2 5/8 3/4 Anchor Diameter 1/4 3/8 1/2 5/8 3/4 Anchor Diameter 1/4 3/8 1/2 5/8 3/4 Tension, fRN Shear, fRV smin = 2.0 hnom, scr = 3.5 hnom fA = 0.33 – 0.17 for scr > s > smin s hnom c hnom c hnom Anchor in. 1/4 3/8 1/2 5/8 3/4 Size (mm) (6.4) (9.5) (12.7) (15.8) (19.1) in. 1 19/16 2 29/16 33/16 (mm) (25) (40) (51) (65) (81) hnom N s c h V 2 ( 51) .50 2 ( 51) .80 .65 21/2 ( 64) .67 21/2 ( 64) .90 .83 3 ( 76) .83 .50 3 ( 76) 1.0 .80 1.0 .65 31/2 ( 89) 1.0 .58 31/2 ( 89) .85 .73 4 (102) .69 .50 4 (102) .91 .80 .85 .65 41/2 (114) .79 .58 41/2 (114) .98 .85 .96 .74 5 (127) .90 .67 .50 5 (127) 1.0 .90 .80 1.0 .83 .65 51/2 (140) 1.0 .75 .55 51/2 (140) .95 .83 .91 .70 6 (152) .83 .61 .50 6 (152) 1.0 .87 1.0 .77 7 (178) 1.0 .74 .57 61/2 (165) .91 .80 .84 .65 8 (203) .87 .67 7 (178) .95 .84 .91 .72 9 (229) 1.0 .77 8 (203) 1.0 .90 1.0 .83 10 (254) .88 9 (229) .96 .94 11 (279) .98 10 (254) 1.0 1.0 12 (305) 1.0 Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph: 909.737.5599 • Fax: 909.737.0330 Customer Service • 800.786.5266 www.tolco.com 86 www.tolco.com Revision 5/24/2001 ™® a brand of Fig. 200 -“Trimline” Adjustable Band Hanger Size Range — 1/2" thru 8" pipe Material — Carbon Steel, Mil. Galvanized to G90 specifications Function — For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features — • (1/2" thru 2") Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily installed around pipe. • (21/2" thru 8" Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. Approvals — Underwriters’ Laboratories listed (1/2" thru 8") in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4" thru 8"). Conforms to Federal Specifications WW-H-171E, Type 10 and Manufacturers Standardization Society SP-69, Type 10. Maximum Temperature — 650°F Finish — Mil. Galvanized. For Stainless Steel materials, order TOLCO™ Fig. 200WON. Order By — Figure number and pipe size Dimensions • Weights Pipe Rod Size Max. Rec. Approx. Size Inch Metric A B Load Lbs. Length 1/2 3/8 8mm or 10mm 31/8 25/8 400 11 3/4 3/8 8mm or 10mm 31/8 21/2 400 11 1 3/8 8mm or 10mm 33/8 25/8 400 12 11/4 3/8 8mm or 10mm 33/4 27/8 400 13 11/2 3/8 8mm or 10mm 37/8 27/8 400 14 2 3/8 8mm or 10mm 41/2 3 400 15 21/2 3/8 10mm 55/8 41/8 600 27 3 3/8 10mm 57/8 4 600 29 31/2 3/8 10mm 73/8 51/4 600 34 4 3/8 10mm 73/8 5 1000 35 5 1/2 12mm 91/8 61/4 1250 66 6 1/2 12mm 101/8 63/4 1250 73 8 1/2 12mm 131/8 83/4 1250 136 FIRE DEPT. INLET CONN. EXPOSED TYPE 6405-6425 SERIES Page 6-15 SINGLE CLAPPER TWO-WAY INLETS An exposed auxiliary inlet connection with 500 G.P.M. inlet capacity to supplement fire protection water supply. Exposed design provides an economical method of satisfying Fire Dept. inlet requirements. STANDARD EQUIPMENT: Cast brass two-way inlet body only with single swing clapper and pin lug swivel back or angle outlet connection as selected by figure number. SPECIFY THREAD. BRANDING: "Auto Spkr." FINISH: Cast Brass OPTIONAL FINISHES: PB -Polished Brass RC -Rough Chrome Plated PC -Polished Chrome Plated *U/L LISTED AND FM APPROVED ___________________________________________________ Model C 6 1/2 Outlet Dimensions Style A B 6405 Back 5 1/4 8 5/64 6407 Angle 6 5/16 7 11/16 4 3/4 DOUBLE CLAPPER TWO-WAY INLETS An exposed auxiliary inlet connection with 500 G.P.M. Inlet capacity to supplement fire protection water supply. Exposed design provides an economical method of satisfying Fire Department Inlet requirements. STANDARD EQUIPMENT: Cast brass two-way inlet body only with double drop clappers and pin lug swivels; back or angle outlet connection as selected by figure number. Branding as selected. SPECIFY THREAD AND BRANDING. BRANDING: "Standpipe", "Auto Spkr.", "Standpipe-Sprinkler" FINISH: Cast Brass OPTIONAL FINISHES: PB -Polished Brass RC -Rough Chrome Plated PC -Polished Chrome Plated *U/L LISTED AND FM APPROVED NY BSA-MEA APPROVED 6407 Angle Outlet 6420 Angle Outlet Outlet Style Dimensions Back Angle Size A B C D E *6410 4 X 2 1/2 X 2 1/2 9 5/8 12 1/4 6420 4 X 2 1/2 X 2 1/2 11 3/4 9 5/8 7 1/4 *6412 6 X 2 1/2 X 2 1/2 10 1/4 11 3/4 6422 6 X 2 1/2 X 2 1/2 12 1/2 10 1/8 7 1/2 6413 4 X 3 X 3 10 12 1/2 6423 4 X 3 X 3 12 1/2 10 1/8 7 1/2 6414 5 X 3 X 3 10 1/8 12 1/2 6424 5 X 3 X 3 12 1/4 10 1/2 7 1/2 6415 6 X 3 X 3 10 3/8 12 1/2 6425 6 X 3 X 3 12 1/4 10 7/8 7 1/4 Figure No. 6410-6415 Figure No. 6420-6425 6410 Back Outlet Figure No. 6405 Figure No. 6407 6405 Back Outlet