HomeMy WebLinkAboutB11-0227NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL
TIMES
6
,.
mwN OFVAII
Town of Vail, Community Development, 75 South Frontage Road, Vail, Colorado 81657
p. 970.479.2139, f. 970.479.2452, inpsections 970.479.2149
COMBINATION BLDG PERMIT Permit #: 1311 -0227
Project #: PRJ11 -0373
Job Address: 4295 NUGGET LN VAIL Applied.....: 07/26/2011
Location......: Issued...: 07/26/2011
Parcel No....: 210112306001
OWNER ROBERT C. MAYNOR JR TRUST 07/26/2011
JEFFREY DALE MAYNOR TRUSTEE
1405 DARNELL ST
HUNSTVILLE
AL 35801
APPLICANT JOHNNY ELECTRIC 07/26/2011 Phone: 970 - 376 -1463 CELL #
P.O. BOX 3968
Avon
CO 81620
License: 137 -E
CONTRACTOR JOHNNY ELECTRIC 07/26/2011 Phone: 970 - 376 -1463 CELL #
P.O. BOX 3968
Avon
CO 81620
License: 137 -E
Description:
PULL NEW SERVICE TO REPLACE EXISTING
Occupancy: Type Construction: Valuation: $6,000.00
.................................................. ............................... FEE SUMMARY
Building Permit -- - - - - -> $125.25 Bldg Plan Check ----- - - - - -> $81.41 Use Tax Fee------------------ - - - - ->
$0.00
Electrical Permit --- - - - - -> $287.50 Elec Plan Check ------ - - - - -> $186.88 Restuarant Plan Review--- - - - - ->
$0.00
Mechanical Permit - - - - -> $0.00 Mech Plan Check ---- - - - - -> $0.00 Additional Fees ---------- – -------- >
($206.66)
Plumbing Permit - - ---> $0.00 Plmb Plan Check - - - - -> $0.00 Recreation Fee ----- ---- ------- >
$0.00
Investigation -------- ----- -------- >
$0.00
Will Call --------------- — ---- – ------ >
$5.00
TOTAL PERMIT FEES ------------ –>
$479.38
Payments ------------------------ -- ----- >
$479.38
BALANCE DUE --- – ------------ – ----- >
$0.00
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information
as required is correct. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure
according to the town's zoning and subdivision codes, design review approved, International Building and Residential Codes and other ordinances of the Town
applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TW NTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROM
8:00 AM - 4:00
_+ _u _-
Sr ature of Owner or Contractor Date
.SD tinn �, U"�SS
Print NIame
combination permit - 012811
CONDITIONS OF APPROVAL TO BE MET PRIOR TO FINAL SIGN OFF
Permit* B11 -0227 Address: 4295 NUGGET LN VAIL
Owner: ROBERT C. MAYNOR JR TRUST Location:
combination permit-012811
TOWN OF VAILh
REQUIRED INSPECTIONS AND STATUSES
Permit* B11 -0227 Address: 4295 NUGGET LN VAIL
Owner: ROBERT C. MAYNOR JR TRUST Location:
Item: 00120 ELEC -Rough
Item: 00190 ELEC -Final
Item: 00090 BLDG -Final
combination permit-012811
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
TOWN OF VAIL, COLORADO Statement
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Statement Number: R110000846 Amount: $479.38 07/26/201111:03 AM
Payment Method: Check Init: JRM
Notation:
-----------------------------------------------------------------------------
Permit No: Bll -0227 Type: COMBINATION BLDG PERMIT
Parcel No: 2101 - 123 - 0600 -1
Site Address: 4295 NUGGET LN VAIL
Location:
Total Fees: $479.38
This Payment: $479.38 Total ALL Pmts: $479.38
Balance: $0.00
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------- - - - - -- ------------------------ - - - - -- ------ - - - - --
EP 00100003111100 ELECTRICAL PERMIT FEES 287.50
PF 00100003112300 PLAN CHECK FEES 186.88
WC 00100003112800 WILL CALL INSPECTION FEE 5.00
t
TOWN OF VAIC' y
00 c.ci ! [e_'._h
Project #: V CL AS
BUILDING PERMIT APPLICATION
(Separate applications are required for alarm & sprinkler)
Project Street Address:
' 4 L.v
(aumber) (Street) (Suite #)
Building /Complex Name:
Contractor Information
{{
Business Name: 'Cl'eak "' /
Business Address: L2 ^ee ;Pt`
City State: CL') Zip: 91631
Contact Name:, �T'04^' L[ G/
Contact Phone: C70 _ 3 - 1'W 3
Contact E -Mail: Jbkhh aK'm LfGe - " �A-C_ •CoN1
X
Owner /Owrr Representative Signature (Required)
Applicant Information
DRB #: 1 -- k " t
Building Permit #: U k — u 2?_-
Lot #: Block # Subdivision:
Work Class: New ( ) Addition ( ) Alteration (
Type of Building:
Single - Family Z ) Duplex( ) Multi - Family ( )
Commercial( Other( )
Work Type: Interior ( ) Exterior Both ( )
ical
Department of Community Development
75 South Frontage Road
Vail, CO 81657
Tel: 970 - 479 -2128
www.vailgov.com
Development Review Coordinator
Valuation of
Work Included Plans Included Work
( Yes (
)No
()()Yes (
)No 6OA0.Oa
( )Yes (
)No
( )Yes (
)No
( )Yes (
)No
( )Yes (
)No
( )Yes (
)No
( )Yes (
)No
Applicant Name: 5 AX4, QC C, , Z6d%/.L_ f Plumbing
Applicant Phone:
Applicant E -Mail:
Project Information
Owner Name:
Parcel #: 2 10 t 1 06 00 1
(For Parcel #, contact Eagle County Assessors Office at (970- 328 -8640 or visit
www. ea g I ecou nty. us /patie)
Value of all work being performed: $
(value based on IBC Section 109.3 & IRC Section 108.3)
Electrical Square Footage
Detailed Scope and Location of Work: &1i Iv 5 e , 6 - ,, ty rPplots c)(i
(use additional sheet if necessary)
For Office Use OnC /.y -
Fee Paid:
T.
Received From:
Cash Check #
CC: Visa / MC Last 4 CC # exp date:
Auth # Ar _n G
Date Received:
(p�CECnIEOWIE(�
JUL 25 2011 IUI
TOWN OF VAIL
01 -Jan -I 1
Free NEC Electrical Load Calculation Software
ZenFixit!
Free NEC Electrical Load Calculator
Home >Site Map >Safety! >Contact Me! >
Page 1 of 4
Don't see What you were looking for? Search This
Site...
► Pirl_ search
Search
Is by G000le Load Calc Calculation HVAC Load Electrical Wiring Load Measurement
NEC Standard Method Single Family Residential - Electric Service
Entrance Load Calculator
Enter plain numbers in cells without text or labels. If you leave any cells empty they will be calculated as
zero.
Total Square feet of dwelling
2650
Total # of Small Appliance Branch circuits (must be at least 2). If you have gas appliances which require a
120v branch circuit include them here. i
2
Total # of Laundry Branch circuits (must be at least 1)
1
Fastened in place Electrical appliances - Do not include gas appliances in this
section. Use nameplate rating in volt -amps or watts - If appliance is rated in
amps then volt -amps = amps * volts. Voltage value is either 120 or 240.
So, for a 120 volt appliance which is rated at 15 amps, 120 volts * 15 amps
= 1800 volt -amps.
Total # of water heaters
1
Volt -amp rating of water heater
4500
Total # of trash compactors
Volt -amp rating of trash compactor
1500
Total # of dishwashers
Volt -amp rating of dishwasher
1200
Total # of disposals
1
Volt -amp rating of disposal
900
� JUL 2 2011
TOWN OF VAIL
Total # of microwave ovens
1
What's the Difference
between Watts and Volt
-Amps? Volt -amps as the
name implies = volts
amps, but watts also =
volts * amps, so what is
the difference? Volt -amp
ratings represent a
maximum value, whereas
Watt ratings are more like
an average value over
time. For some appliances
both ratings have the same
value, and for others there
is a large difference.
Imagine an oven that
draws lots of current while
it is preheating, but then
may use very little for
several minutes at a time
once it is heated up. When
there is a difference then
volt -amps will be the larger .
of the two, and the ratio of
watts /volt -amps is called
the power factor, and is
represented as either a
decimal (0.8) or a
percentage (80 %).
Confused? Don't sweat it,
just use which ever value
is on the appliance name
plate or the larger of the i
two in the rare case that
both might be listed.
http:// www. zenfixit .com/load_calculations.shtml 7/25/2011
Free NEC Electrical Load Calculation Software Page 2 of 4
Volt -amp rating of microwave oven
1500
Total # of range hoods
1
Volt -amp rating of range hood
600
Other fastened in place appliances - use this section to define things like spas which aren't specified
above.
Total # of other fastened in place appliance #1
0
Volt -amp rating of other fastened in place appliance #1
Total # of other fastened in place appliance #2
0
Volt -amp rating of other fastened in place appliance #2
Total # of other fastened in place appliance #3
0
Volt -amp rating of other fastened in place appliance #3
Total # of clothes dryers
1
V olt -amp rating of clothes dryer (must be at least 5000)
5000
Total # of Ranges
1
Volt -amp rating of Range
10000
Total # of Ovens - Note: If there is a range, and no additional oven then don't put anything here.
1
Volt -amp rating of Oven
3000
Total # of Cooktops - Note: If there is a range, and no additional cooktop then don't put anything here.
0
Volt -amp rating of Cooktop
6000
http: / /www.zenfixit.com/load calculations. shtml 7/25/2011
Free NEC Electrical Load Calculation Software Page 3 of 4
Total # of Other cooking appliance over 1750 volt -amps
Volt -amp rating of Other cooking appliance over 1750 volt -amps
12000
Volt -amp rating of Larger of Heating OR Air conditioning system - always include air handler. For heat pump
include compressor and the maximum amt of electrical heat that can be energized while compressor is
running.
10000
Voles rating of Largest Single Motor (usally the HVAC compressor or air handler motor)
800
Service voltage is assumed to be 240
Calculate Load
This is a simple free program for calculating electrical load for single family residential dwellings. This
calculation determines the size of your electric service entrance (and meter) and main electrical panel based
upon your potential load usage. If you are thinking about adding on or building a new house, then this
calculator will help you to determine if your existing entrance is big enough or if you will have to spend a
considerable amount to upgrade. Your local codes department will probably let you use a larger service
entrance than the minimum if you want (up to a point), but you can't (and don't want to) have one that is
even a little bit too small.
This program calculates total service load based upon the 2005 National Electrical Code Article 220. A
balanced load is assumed.
Note: This program makes quick work of a lengthy calculation. In many cases you can use the values for volt
-amp nameplate ratings that are provided and you will still get pretty good results (as an estimate only). Also
this program does not have any provisions for usage allocation in the case of multiple major appliances
circuits, so you will notice that if you input that the dwelling has more than one dryer circuit for example
(maybe one in the basement and another in a main floor utility area) then it will show that you need to have
a much bigger service entrance, but this isn't really correct in all cases because the code recognizes that you
probably don't usually have a dryer plugged into both of them at the same time. If however, you have a
second dryer outlet in an area of the house which might be used as a separate habitation the inspector will
probably count the extra appliance circuit against the total load, and make you get a bigger entrance,
because of the likely potential for simultaneous use - for example if the basement not only has a dryer plug,
but also it's own full bath and a kitchenete area, and an exterior entrance. When in doubt, contact your local
codes authority before you do anything expensive.
Table 310.15(6) Conductor Types and Sizes for
120 /240 -Volt, 3 wire, Single Phase Dwelling Services
and Feeders. Conductor Types RHH, RHW, RHW -2, THHN,
WHHW -2, SE, USE, USE -2
http:// www. zenfixit .com/load_calculations.shtml 7/25/2011
Service
Copper
Copperor
Copper
or
Feeder
clad
rating
Aluminum
in
Amperes
�n�n
100
�n�n
110
1/0
�
125
n
2/0
— �nr�
�
150
inn
http:// www. zenfixit .com/load_calculations.shtml 7/25/2011
Free NEC Electrical Load Calculation Software
uu�u
3/0 � 250 � 225
4/0 � 300 � 250
250 � 350 � 300
350 � 500 � 350
400 � 600 � 400
Site Map
http://www.zenfixit.com/load
Page 4 of 4
7/25/2011
Results for Load Calculations Page 1 of 1
Results for Load Calculation
/ 6-2,.2u P�
Minimum Service Entrance Size =
Round up to standard size for service entrance. Use your back button to try again.
np—
http:// www .zenfixit.com/load.php ?squareft= 2650 &smallapps =2 &laundrys = l &al =1 &al w... 7/25/2011
08 -01 -2011 Inspection Request Reporting Page 12
4:41 Dm Vail, CO - City Of
Requested Inspect Date: Tuesda , Auggust 02, 2011
Site Address: 4295 N�GGET LN VAIL
A/P /D Information
Activity: B11 -0227 Type: COMBO Sub Type: OTHER Status: ISSUED
Const Type: Occupancy: Use: Insp Area:
Owner: ROBERT C. MAYNOR JR TRUST
Contractor: JOHNNY ELECTRIC Phone: 970 - 376 -1463 CELL #
Description: PULL NEW SERVICE TO REPLACE EXISTING
Reauested Inspection(s
Item: 190 ELEC -Final
Requestor:
Comments: 376 -1463
Assigned To: S R
Action: Time Exp:
V'
Requested Time: 08:00 AM
Phone:
Entered By: MHAEBERLE K
Insaection Histo
Item: 120 ELEC -Rough ** Approved **
07/28/1 T Inspector: sgremmer Action: AP APPROVED
Comment: Service and underground
Item: 190 ELEC -Final
Item: 90 BLDG -Final
R£PT131 Run Id: 13372