Model F1 Res Sprinklers engineered for the lowest flows
to meet the minimum design density of .05 gpnVW
Types:
1. F1 Res 49 Pendent
2. F1 Res 49 Recessed Pendent /F1
3. F1 Res 49 Recessed Pendent /FP
4. F1 Res 49 CCP Pendent
5. F1 Res 58 Pendent
6. F1 Res 58 Recessed Pendent /F1
7. F1 Res 58 Recessed Pendent /FP
8. F1 Res 58 CCP Pendent
9. F1 Res 44 & 58 HSW
10. F1 Res 44 & 58 HSW Recessed HSW /F2
11. F1 Res 44 SWC
12. F1 Res 76 Pendent
13. F1 Res 76 Recessed Pendent /F1
14. F1 Res 76 Recessed Pendent /FP
15. F1 Res 76 CCP Pendent
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
2. NYC MEA 258 -93 -E
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the
Model F1 Res 49 & 58 Pendent Sprinklers
Product Description
Model F1Res Pendent sprinklers (Figs. 1, 2, 3 & 4)
combine excellent durability, high sensitivity glass -bulb
and low profile decorative design.
The 3mm glass -bulb pendent sprinklers permit the
efficient use of residential water supplies for sprinkler
coverage in residential fire protection design.
The low flow F1 Res sprinklers are specially
engineered for fast thermal response to meet the
sensitive fire protection application needs of the latest
residential market standards (UL 1626 Standard *).
Upon fire conditions, rising heat causes a sprinkler's
heat - sensitive glass -bulb to shatter, releasing the
waterway for water flow onto the deflector, evenly
distributing the discharged water to control a fire.
F1 Res 44 & 58
Recessed HSW/F2
F1 Res 44 SWC
Technical Data:
• Thermal Sensor: Nominal 3mm glass -bulb
• Sprinkler Frame: Brass Casting
• Sprinklers' Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size: 1 12 ' NPT 91/2)
• KT 4.9 (AcLo - F1 Res 49 Pendal Spnnkler
5.8 (Actual) - F1 Res 58 Pendant & HSW SpriW
7.6 (Actual) - F1 Res 76 Pendent Sprinkler
4.4 (Actual) - F1 Res 44 HSW Sprinkler
• Density: Minimum 0.10 gprr
Residential Sprinklers for
Design Density of .10 gpm/ft
Bulletin 176 Rev. A
F1 Res 49,58 & 76 F1 Res 49,58 & 76
Recessed Pendent/ F1 Recessed Pendent /FP
F1 Res 49, 58 & 76
CCP Pendent
* Effective date 7/12/02
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
Model F1 Res Sprinklers are used for Residential Fire
Protection according to UL 1626 Standard *. Be sure
that orifice size, temperature rating, deflector style and
sprinkler type are in accordance with the latest
published standards of The National Fire Protection
Association or the approving authority having
jurisdiction.
When using F1 Residential Sprinklers for systems
design to NFPA 13D or NFPA 13R, use listed area of
coverage and minimum flow and pressure requirements
shown in Bulletin 135.
For systems designed to NFPA 13, use information in
this bulletin. The number of design sprinklers shall be the
most hydraulically demanding sprinklers as required by
NFPA 13. Flows and pressures can not be below the
baseline flows and pressurers.
NFPA 13
For residential sprinkler systerris designed to NFPA 13,
a minimum density of 0.1 gpm /ft must be provided over
the "design area" that includes the four (4) hydraulically
most demanding sprinklers for the actual coverage
areas being protected by the 4 sprinklers. The minimum
required discharge from each of the four most
hydraulically demanding sprinklers shall be the greater
of the following:
1.The flow rates given in the Reliable Residential
Sprinkler Technical Bulletins referenced in Table A
for NFPA 13D and 13R as a function of temperature
rating and maximum allowable coverage area (for
actual coverage areas less than or between those
indicated in the respective technical bulletin, it is
required to use the minimum required flow for the
next largest coverage area); or
2.A minimum discharge density of 0.1 gpm/ft
2
applied over the "design area" consisting of the four
most hydraulically demanding sprinklers for the
actual coverage areas being protected by the four
sprinklers. The maximum dimension of the actual
coverage area cannot be any greater than the
maximum coverage area indicated in the technical
bulletins referenced in Table A.
Design Note: Using the A = S x L method to
determine the sprinkler protection area of coverag-9
in accordance with NFPA 13, apply the 0.1 gpm /ft
density to this area to determine the minimum
required flog. Compare this flow to the minimum
0.05 gpm /ft cULus Listed flow for the appropriate
coverage area in the technical bulletin for the
specific residential sprinkler. If the flow stated in the
techni al bulletin is less than the calculated 0.1
gpm /f' density flow required, the .1 density flow
must then be used in the equation Q =KVP, solving
for P, to establish the minimum required pressure
using the sprinkler K- factor. Note: In many cases
the listed flow of individual residential sprinkler
may exceed the required minimum 0.05 gpm /ft
density. Reliable has available residential sprinklers
with larger K- factors (K =5.8 and K =7.6) that wi
provide lower pressure demands for 0.1 gpm /ft
densities in NFPA 13 residential applications.
Example No. 1
Room Size= 12 ft x 20 ft (3.6 m x 6.1 m)
Coverage Area= 12 x 20 = 240 ft (22.3 m 2 )
Flow @ 0.10 gpm /ft density= 240 x 0.10 = 24 gpm
Using an F1 Res 49 Pendent Sprinkler, K =4.9
Pressure= (24/4.9) = 24 psi (1.65 bar)
The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m)
coverge area using the baseline density of 0.05
gpm /ft will be 20 gpm @ 16.7 psi (75.7 L/min @ 1.14
bar). Therefore, the minimum flow required is 24 gpm @
24 psi (90.8 L/min @ 1.65 bar).
Example No-2
Room Size= 8 ft x 20 ft (2.4 m x 6.1 m)
Coverage Area= 8 x 20 = 160 ft (14.9 m 2 )
Flow @ 0.10 gpm /ft density= 160 x 0.10 = 16 gpm
Using an F1 Res 49 Pendent Sprinkler, K =4.9
Pressure= (16/4.9) = 10.7 psi (0.74 bar)
The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m)
coverye area using the baseline density of 0.05
gpm /ft will be 20 gpm @ 16.7 psi (75.7 L/min @ 1.14
bar). Therefore, the minimum flow required is 20 gpm @
16.7 psi (75.7 L/min @ 1.14 bar).
Example No. 3
Room Size= 10 ft x 16 ft (3.0 m x 4.91 m)
Coverage Area= 10 x 16 = 160 ft (14.9 m 2 )
Flow @ 0.10 gpm /ft density= 160 x 0.10 = 16 gpm
Using an F1 Res 76 Pendent Sprinkler, K =7.6
The baseline flow for a 16 ft x 16 ft coverage area is 21
gpm @ 7.6 psi (79.5 L/min @ 0.52 bar). Therefore, the
minimum flow and pressure is 21 gpm @ 7.6 psi (79.5
Umin @ 0.52 bar).
Example No. 4
Room Size= 14ftx 18ft (4.3mx5.5m)
Coverage Area= 14 x 18 = 252 ft (23.6 m 2 )
Flow @ 0.10 gpm /ft density= 252 x 0.10 = 25.2 gpm
(94.6 L/min)
Using an F1 Res 76 Pendent Sprinkler, K =7.6
Pressure= (252/7.6) = 11 psi (0.76 bar)
The baseline flow and pressure of an 18 ft x 18 ft
coverage area is 21 gpm @ 7.6 psi (79.5 L/min @ 0.52
bar). Therefore, the minimum flow and pressure is 25.2
gpm @ 11 psi (94.6 L /min @ 0.76 bar).
In general residential sprinklers require
flows and pressures as listed for 0.05
densities to achieve the proper spray pattern
so the flows and pressures at 0.05 density are
the baseline flows and pressures. Flows and
pressures below the listed 0.05 density shall
not be used.
2.
Installation
Models F1 Res sprinklers are to be installed as
shown. Model F1, F2 and FP Escutcheons, illustrated
herewith, are the only recessed escutcheons to be used
with Model F1 Res sprinklers. Use of any other
recessed escutcheon will void all approvals and
warranties. For installing Model F1 Res Pendent
sprinklers use only the Model D sprinkler Wrench; for
installing Models F1 Res Recessed Pendent, CCP
sprinklers use only the Model GFR2 sprinkler wrench;
for installing Model F1 Res recessed HSW sprinklers
• Model F1 Res 49, 58 & 76 Pendent
use only the Model GFR2 Sprinkler wrench. Use of
wrenches other than those specified may damage
these sprinklers.
Note: A'leak tight" sprinkler joint can be obtained with
the following torque:
• 3 /4 " NPT (R3/4) - 14 -20 ft-Ibs (19 - 27.1 N -m)
• 1 /2 " NPT (R1/2) - 8 -18 ft -Ibs (10.8 - 24.4 N -m)
Do not tighten sprinklers over maximum
recommended torque. It may cause leakage or
impairment of the sprinklers.
• Model F1 Res 49, 58 & 76
Recessed Pendent/ F1 /1
n �
ol _
w�
F1 escutcheon, /" (19mm) adjustment
1.35FCO3
Fig, 1
Note: See escutcheon table for dimensions.
2 1 /.' IIOLC 04
(5 -1
1 15/16' Dw.
1 • X 1 12' RE fI
4.
RJRN C UMIL
)ACMI A 6O S, SPRMx([R
WRENCH @OSS.
1 I
EACE nmNC 10
_ cExn+C DMl[l/SIOM
J/16 -15/16 (F1 ESCUICIEON)
J fY / / // / evu�vv 3116 -11/16 (f2 CSCUICNEON)
4AN5l,1EN, 4NaYa
1/6
(,.2m
i
135FO02A 2 27132' DK
[72.2 -1
Fig. 2
3.
Technical Data: F1 Res 49 Pendent and Recessed Pendent
Nominal
Sprinkler
Max,
Max.
Inch (mm) Inch (mm)
Sprinkler
Thread Orifice
Temp.
Pressures
Ambient
Actual
ht
Len
S he Inch
Rati
17 64.3
Tem
Factor
Inch
16.7(l 14)
(mm)
OF
°C
l
°F
°C
'' /z" NPT
( R 1 /2)
(mm)
Y,11 � T
'' /'s (11)
151 7
69
175 (12)
150
1 66
4.9
2.25 (57)
Escutcheon *. F1 or F2. Data:
T yp e
Adjustment "A"
Face of fitting to
ceili
Sprinkler
Identification
Number (SIN
R3516
Inch (mm) Inch (mm)
Inch (mm
F1
%(19.0)
Min. =Y (19.1)
Max. =1' " (38.1)
/ _,/ (4.7 -24.0)
B
F2
% (12.7)
Min.= 1 %" (23.8)
Max. =1' " 38.1
' /,s _, (4.7 - 17.4)
" Note: Escutcheons F1 or F2 may be used with
Model F1 Res 49 & 58 Recessed Pendent Sprinkler
* *Baseline flows and pressures for 0.05 density
Deflector - to - ceiling
Maximum 1" (25mm) to 4" (100mm)
Max. Sprinkler
Spacing
ft m
Flow
m (Lm)
9Pp
Pressure
p sl (bar)
Sprinkler
Identification
Number (SIN
R3516
12 x 12 3.6x3.6
13 49
7.0 0.48
14 x 14 4.3x4.3
13 49
7.0 0.48
16 x 16 4.9x4.9
13 49
7.0 0.48
18 x 18 5.5x5.5
17 64.3
12.0 0.83
20 x 20 (6.14.1)
20 (75.7)
16.7(l 14)
*Deflector - to - ceiling
Maximum 4 00mm) to &' (203mm)
Max. Sprinkler
Spacing
ft m
Flow
9Pm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number SIN
R3516
12 x 12 (3.6x3.6)
15 57
9.4 0.65
14 x 14 4.3x4.3
16 60.5
10.6 0.73
16 x 16 4.9x4.9
17 64.3
12.0 0.83
18 x 18 5.5x5.5
19 72
15.0 1.0
20 x 20 6.1 x6.1
22 83.2
20.2(l.4
"Note: The F1 Res 49 pendent and recessed pendent
residential sprinklers can be installed per NFPA 13 in
beamed ceilings meeting the following criteria:
1. Maximum beam depth = 7" (178mm)
2. Beam spacing at or greater than 7.5 ft. (2.3m) on center.
Technical Data: F1 Res 58 Pendent and Recessed Pendent
* *Baseline flows and pressures for 0.05 density
Max. Sprinkler
Nominal
Sprinkler
Max.
Max.
Sprinkler
Thread
Orifice
Temp.
pressure
Ambient K
Length
Size
Inch
Rail no
psi
Tem P. Factor
Inch
OF
I °C
16 61
(mm)
(bar)
OF °C
(mm)
'' /z" NPT
( R 1 /2)
/. (13)
155
175
68
79
175 (12)
100
150
38 5.8
66
2.25 (57)
* *Baseline flows and pressures for 0.05 density
Max. Sprinkler
Flow
Pressure
Ceiling -to-
Sprinkler
Spacing
gp m ( L p m )
( ) r bar
Deflector
Identification
ft m
7.6 0.53
Inch mm
Number SIN
12 x 12 3.6x3.6
16 61
(25- 00)
R3513
14 x 14 43x4.3
16 61
7.6 0.53
16 x 16 4.9x4.9
16 61
7.6 0.53
18 x 18 5.5x5.5
19 72
10.8 0.75
20 x 20 (6.1 x6.1)
22 (83.3)
14.4 (1.0)
"Calculate for a .10 density but in no case
go below the baseline flows & pressures
4.
Technical Data: F1 Res 76 Pendent and Recessed Pendent
• Model F1 Res 49, 58 & 76
Pendent
D
2 518" [66.7mm] DIA.
2 5/16" DIA, HOLE IN CEILING
(58.7mm)
CUP 1- _ .
1 --- '�� - - - "' 1 ° x1/2" REDUCER
CUP \\ I
4
CEILING �— -
MAX. FACE OF FITTING
TO FACE OF CEILING
DIMENSION
COVER ADJUSTMENT I HEIGHT
3 5116" DIA.
7 35FG04C [84.1 mm)
F1 RES 49. 58 & 76 CCP PEND.
Fig. 3
NOTE: The F1 Res 76 will use a 1" x 3 /" reducer.
• Model F1 Res 49, 58 & 76
Recessed Pendent/ FP
u-
FP push -on /thread -off
escutcheon
2 518 Du. [66.7mm]
HOLE IN CEILING
AAmc
-- -
Sprinkler
(5 &7-1
CUP
Thread
Orifice
� Pressure
Ambiert
L ength
K
I I
- --1--- --
I X I / ?' REDUCER
Size
Inch
I
psi
T
Facbr
Inch
m NAx.
` - -- -
EACE or EImNc
0
r0 CE OE GELLING
(mm)
°F
°C
(bar)
°F
°C
- AQ/USrA1ENr
(mm)
%" NPT
(Rj
, Y32' (13 5)
155
175
68 1
79
100
150
38
66
7.6
2.25 (57)
T YPe
Adjustment
"
Face of fitting to
ceiling
-- , _
Inch (mm)
Inch (mm)
Inch (mm)
*
ase ine ows an ressures for 0.05 den
P
F1
3, ( 9 .0)
IMi�= 1 N (38.1)
%6 - ' %6 (4.7 - 24.0)
Max. Sprinkler
_
- - --
sprinkler SItY
F2
'/z (12.7)
Min.= l% (23.8)
Max. -1/" 38.1)
%6 -,, ,6 (4.7-17.4)
Spacing
Flo
°
Pressure
.. .
Identification
ft m
9Pm (Lpm)
psi (bar)
Number SIN
12x12 3.6x3.6
21
76(0.53)
14 x 14 4.3x4.3
21
7.653)
16 x 16 4.9x4.9
21
7.6 0.53
R7618
*Calculate for a .10 density
but in no case
18 x 18 5.5x5.5
21
7.6 (0.53)
go below
the baseline flows & pressures
20 x 20 (6.1x6.1)
23
9 2 (0.63)
• Model F1 Res 49, 58 & 76
Pendent
D
2 518" [66.7mm] DIA.
2 5/16" DIA, HOLE IN CEILING
(58.7mm)
CUP 1- _ .
1 --- '�� - - - "' 1 ° x1/2" REDUCER
CUP \\ I
4
CEILING �— -
MAX. FACE OF FITTING
TO FACE OF CEILING
DIMENSION
COVER ADJUSTMENT I HEIGHT
3 5116" DIA.
7 35FG04C [84.1 mm)
F1 RES 49. 58 & 76 CCP PEND.
Fig. 3
NOTE: The F1 Res 76 will use a 1" x 3 /" reducer.
• Model F1 Res 49, 58 & 76
Recessed Pendent/ FP
u-
FP push -on /thread -off
escutcheon
2 518 Du. [66.7mm]
HOLE IN CEILING
2 5116 ON.
(5 &7-1
CUP
I I
- --1--- --
I X I / ?' REDUCER
I
J
aN 1/JG
m NAx.
` - -- -
EACE or EImNc
0
r0 CE OE GELLING
\`
DIMENSION
112 [13-] -X.
- AQ/USrA1ENr
A
I
Fig. 4
5.
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent / FP
*Baseline flows and pressures for 0.05 density FP Data ..A,,:
Max. Sprinkler Flow
Spacing
ft W gpm (Lpm)
12 x 12 3.6x3.6 13 49
r- --
Sprinkler
Identification
Number (SI
7.0 0.48
R3516
14 x 14 4.3x4.3
CCP Options Dat
7.0 0.48
16 x 16 4.9x4.9
NorNnal
Sprinkler
OCP
A�tlbll/
NWC
Max
20x20 6.1x6.1
ni "A"
16.7 1.14
Inch
Thread
orifice
Temp.
T
�
Pressure
Ambient
K
��
Cover Adjustment
(bar)
H
CCP Height
She
InCh
R*rg
T�
F
hch
Inch mm
oC
Inch_ (mm)
of
(mm)
of
°C
,
,C
(bar)
of
°C
57
(m m)
/ 12.7
38
5 24
Y(RNPT
' % (11) 155
1 68 l
135
57
1 175 (12)
100
38
4.9 57
s 4.7
s 19
*Baseline flows and pressures for 0.05 density FP Data ..A,,:
Max. Sprinkler Flow
Spacing
ft W gpm (Lpm)
12 x 12 3.6x3.6 13 49
Pressure
psi (bar)
Sprinkler
Identification
Number (SI
7.0 0.48
R3516
14 x 14 4.3x4.3
13 49
7.0 0.48
16 x 16 4.9x4.9
14 53
8.2 0.56
18 x 18 5.54.5
18(68.1
13.5 0.93
20x20 6.1x6.1
20 75.7
16.7 1.14
FP Position
..A„
Inch mm
Max. Recessed
Y16 11
Min. Recessed
1 24
Note: Sprinklers shown in Fig. 3 and Fig. 4 are not
suitable for installation in ceilings which have
positive pressure in the space above.
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP
*Baseline flows and pressures for 0.05 de nsity
Max. Sprinkler Flow
Spacing gpm (Lpm)
Nominal
Sprinkler
ccP
AY
MML
I Max
R3513
SpMdw
Thread
Orifice
TUTP
T aT41
Pressure
Arnllient
K
Length
Size
Inch
RlAng
57
psi
Temp.
Factor
hd1
2.25
(57
(mm)
°F
(bar)
(MM)
of
°C
oC
of
IC
NPT R /z
'/i (13)
155
68
135
57
175 (12)
100
38
5.8
2.25 (57)
*Baseline flows and pressures for 0.05 de nsity
Max. Sprinkler Flow
Spacing gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Number N'
12 x 12 3.6x3.6
16 61
7.6 0.53
R3513
14 x 14 4.3x4.3
16 61
7.6 0.53
16 x 16 4.9x4.9
16 61
7.6 0.53
18 x 18 5.5x5.5
19 72)
10.8 0.75
1
20x 20(6.14.1)
22(833)
Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP
Nominal SpriidNa��
Max
Max
Spdrida
Thread Orifice TemR
Size Inch Railing
(mm) °F °C
T Pressure
yob psi
°F °C
Ambient
Teri¢
K
Fackm
Levillh
(rim)
°F
°C
3 /," NPT
(R3 /�
'%z
(13.5
155
175
68
79
135
57
1 17,5(12)
100
150 _
38
66
7 ' 6
2.25
(57
*Baseline f lows and
Max. Sprinkler Flow
Spacing
ft m gpm(Lprn)
12 x 12 (3.64.6 ) 21
14 x 14 4.3x4.3 21 _
16 x 16 4.9x4.9 21
18 x 18 5.5x5.5 22
20 x 20 (6.1 x6.1) 25
ressures for 0.05 density
Pressure Sprinkler
psi (bar) Identification
Number SIN
7.6 0.53
7.6 0.53
7.6 0.53 R7618
8.4 0.58
10.8 (0.74)
*Calculate for a .10 density but in no case
go below the baseline flows & pressures
A
• Model F1 Res 44 & 58 HSW
• Model F1 Res 44 & 58
Recessed HSW /F2
F2 escutcheon, y" (13mm)
adjustment
Technical Data: F1 Res 44 HSW & HSW /F2
Escutcheon, F2, Data:
Nominal ' Max. N1ax. Sprir�fder
Thread Orifloe T� Pressure A K
am Irtcht psi T Fkllor �
(mm)
OF c 1 (bar) cF °C (mm)
Type Adjustment
Face of�i ng
Inch (mm)
Inch mm
F2
13
3 /, - 4.7- 17.4),
1 /2" NPT y• (10) 175 68 1 75 (12) 150 66 4.4 2.45 (62)
*Baseline flows and pressures for 0.05 density
4 -6
(101 -152)
A
16x18 4.94.5
15
18 x 18 5.54.5
Max. Sprinkler
Ceiling -to-
Sprinkler Temp.
Flow
Pressure Sprinkler
Spacing
Deflector
Rating
j
gpm
Psi (bar) Identification
ft (m)
Inch mm
OF ( °C)
(fpm)
17 64.4
Number (SIN)
12 x 12 (3.6x3.6 )
20 75.7
155 68
175 79
12 45.4
-- 75(0.52 )
14 x 14 43x4.3
155 (68)
175 (791
14 53.0
102(0-71
16x16 4.9x4.9
4 -6
(101 -152)
155
16x18 4.94.5
15
18 x 18 5.54.5
155
16 x 20 4.9x6.1
155
12 x 12 3.6x3.6
6-12
(152 -305)
155
14 x 14 43x4.3
155
16 x 16 4.9x4.9
155
16 x 18 4.94.5
155
16 x 20 (4.9x6.1)
155
175 (79)
16 60.6
13.3 0.92
R3531
175 79
18 68.1
16.8 1.16
175 79
19 72.0
18.7(l.29
175 79
23 87.1
27.4(l.89)
175 79
14 53.0
10.2 0.71
175 79
16 60.6
13.3 0.92
175 79
17 64.4
15.0 1.04
175 79
20 75.7
20.7 1.43
175 (79)
23 (87.1)
27.4 (1.89)
'Calculate for a .10 density but in no case
go below the baseline flows & pressures
7.
Model F1 Res 44 SWC
N,
1
rMM a' to 12'
1101,60mm To
1 1 1e' (31.75mm] Maximum 30e.80mm]
Face Of Fitting TURN TO COVER THEN
,
To Wall Dimension TURN 0 ADJUST UNTIL
P� TIGHT AGAINST WALL.
1' X 1/2' Reducer
Recommended ,1 "
Wou H.I. 2 5116'
2 518' (58.7imm] - -- - - -�- 3 5116'
[66.58mm] DA.. '
Dio. [Be. A.,
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER `' 21 1 32'
WRENCH BOSS. /
(e2.07mm]
usrc6T 112' [12.70mm]
Adjustment
F1 RES 44 SWC
Fig, 5
Technical Data: F1 Res 44 SWC
Nominal Sprinlder CMWT Max, Max. Spri-ider
Thread Orifice Temp. Rah y RMSS.Lfe anjjmtTemp Factor hd
Sho Inch
(mm) F IC 9 C (bar) (mm)
Iz(R1)T %" (10) 155 68 135 57 175 (12) 100 38 4.4 2.45 (62)
*Baseline flows and pressures for 0.05 density
'Calculate for a .10 density but in no case
go below the baseline flows & pressures
i
Technical Data: F1 Res 58 HSW & HSW /F2
*Baseline flows and pressures for 0.05 density
Max. Sprinkler Sprinkler Temp.
Spacing Ceilin g -ton- Rating
ft (m) Inch mm) OF (°C)
Nominal
Sprinkler
Max.
Max.
(101-152)
155 68
Escutcheon, F2, Data:
Sprinkl
Ad'ustmtxK Face of Fitting
Thread
Orifice
Temp.
Pressure
Ambient
K
Length
Type Inch (mm) to wall
Sbae
Inch
Ra1i
psi
Tem •
Factor
Inch
Inch mm
16 x 20 4.9x6.1
(mm)
°F °C
(►ter)
OF °C
5.8
(mm)
2.45 (62)
F2 13 3 - 4.7 - 17.4
1 /2" NPT
R'/2
%" (
1 155
175
68
79
175 (12)
100
150
38
66
*Baseline flows and pressures for 0.05 density
Max. Sprinkler Sprinkler Temp.
Spacing Ceilin g -ton- Rating
ft (m) Inch mm) OF (°C)
ROW
gpm
(Lpm)
Pressure
psi (bar)
Sprinkler
ification
Number (SIN)
12 x 12 3.6x3.6
(101-152)
155 68
175 (79)
16 60.6
7.6 (0.53
R3533
14 x 14 4.3x4.3
155 68
175 79
18 68.2
9.7 0.67
16 x 16 4.9x4.9
155 68
175 79
21 79.5
13.2 0.91
16 x 18 4.9x5.5
155 68
175 79
25 94.7
18.6(l.28
16 x 20 4.9x6.1
155 68
175 79
29 109.8
25 1.73
12 x 12 3.6x3.6
6-12
(152 -305)
155 68
175 79
22 83.3
14.4 1.0
14 x 14 4.3x4.3
155 68
175 79
22 83.3
14.4 1.0
16 x 16 4.9x4.9
155 68
175 79
26 98.4
20.1 1.39
16 x 18 4.9x5.5
155 68
175 79
31 117.4
28.6(l.97
*Calculate for a .10 density but in no case
go below the baseline flows & pressures
Finishes
Standard Finishes
Sprinkler
F1 F2 FP Escutcheons
Bronze
Brass
Chrome Plated
Bright Chrome Plated
White Pol ester Coated
White Painted
Special Appil cation Finishes
Sprinkler
F1 F2 Escutcheons
Bright Brass
Bright Brass
Black Plated
Black Plated
Black Paint
Black Paint
Off White
Off White
Satin Chrome
Satin Chrome
Other finishes and colors are available on special order.
Consult factory for details.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Escutcheon Finish
0
Maintenance
Model F1 Res 49, F1 Res 58 & F1 Res 76 Sprinklers
should be inspected quarterly, and the sprinkler system
maintained in accordance with NFPA 25, 13, 13D, and
13R. Do not clean sprinkler with soap and water, Ammonia
or any other cleaning fluids. Remove dust by using a soft
brush or gentle vacuuming. Remove any sprinkler which
has been painted (other than factory applied) or damaged
in any way. A stock of spare sprinklers should be
maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers that
could cause improper operation or non - operation.
Model F1 RES 49 Residential
Sprinkler Specifications
Model F1 Res 49 & 58 Pendent
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258- 93 -E)] low flow residential pendent
sprinklers engineered to provide a minimum design
density of 0.10 gpm/ft over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch of up to [4/12]
[8/12], the sprinklers shall be listed for such use.
Deflector -to- ceiling distance listing shall be 1" to 8"
maximum. Sprinkler frame and deflector shall be of bronze
frame construction having a' /2' NPT thread. Water seal
assembly shall consist of a Teflon- coated Belleville spring
washer and top - loaded extruded cup with 3 mm glass bulb
containin no plastic parts, and having a temperature
rating of T155 °F (68 0 C)] [175 °F (79 0 C)]. Sprinklers shall
have a nominal K- factor of 4.9 & 5.8. Standard finish:
[Bronze] [Chrome - plated] [White Polyester] [Special finish -
specify]. Residential pendent sprinklers shall be Reliable
Model F1 Res 49 & 58, SIN R3516 & R3513 (Bulletin 135).
Model F1 Res 49 & 58 Recessed Pendent/F1,
Model F1 Res 49 & 58 Recessed Pendent/F2,
Model F1 Res 49 & 58 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258- 93 -E)] low flow residential recessed
pendent sprinklers engine red to provide a minimum
design density of 0.10 gpm /ft'over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's installation
guidelines and the applicable installation standard. Where
pendent residential sprinklers are installed under sloped
ceilings having a pitch of up to [4/12] [8/12], the sprinklers
shall be listed for such use. Deflector -to- ceiling distance
listing shall be 1" to 8" maximum. Sprinkler frame and
deflector shall be of bronze frame construction having a' /2
NPT thread. Water seal assembly shall consist of a
Teflon- coated Belleville spring washer and top - loaded
extruded cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155 °F (68 0 C)]
[175 °F (79 0 C)]. Sprinklers shall have a nominal K- factor of
4.9 (70). Standard finish: [Bronze] [Chrome - plated] [White
Polyester] [Special finish- specify]. Recessed escutcheon
assembly shall be a steel, two-piece escutcheon [with 1 /2"
adjustment (Model F2)] [with 3 /d' adjustment (Model F1)] [of
push -on and thread off design with 1 12 " adjustment (Model
FP)]. Standard finish shall be [brass][bright chrome] [white
painted]. Residential recessed pendent sprinklers shall be
Reliable [Model F1 Res 49 & 58 Recessed Pendent/Fl]
[Model F1 Res 49 & 58 Recessed Pendent/F2] [Model F1
Res 49 & 58 Recessed Pendent/FP] SIN R3516 & R3513
(Bulletin 135).
Model F1 Res 49 & 58 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258- 93 -E)] low flow residential concealed
sprinklers engineered to provide a minimum design
density of 0.10 gpm /ft over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch of up to
[4/12] [8/12], the sprinklers shall be listed for such use.
Sprinkler frame and deflector shall be of bronze frame
construction having a ' /z" NPT thread. Water seal
assembly shall consist of a Teflon- coated Belleville
spring washer and top - loaded extruded cup with 3 mm
glass bulb containing no plastic parts, and having a
temperature rating of 155 °F (68 0 C). Cover plate
assembly shall consist of a brass cover plate and copper
alloy retainer flange. Method of attaching the cover plate
to the sprinkler cup shall be a push -on and thread -off
design allowing a 1 /2 " cover plate adjustment. Cover
plate temperature rating shall be 135 °F (57 0 C). A plastic
protective cap shall be provided and factory installed
inside the sprinkler cup to protect the sprinkler from
damage, which could occur during construction before
the cover plate is installed. Standard cover plate finish:
[White] [Custom Color- specify]. ]. Concealed pendent
sprinklers shall be Reliable Model F1 Res 49 & 58 CCP,
SIN R3516 & R3513 (Bulletin 135).
10.
Model F1 Res 44 & 58 Horizontal Sidewall
Sprinkler
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258- 93 -E)] low flow residential horizontal
sidewall sprinklers engineered to provide a minimum
design density of 0.10 gpm /ft over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Where horizontal sidewall
residential sprinklers are installed under sloped ceilings
having a pitch of up to [4112] [8/12], the sprinklers shall
be listed for such use. Sprinkler frame and deflector shall
be of bronze frame construction having a 1 12" NPT thread.
Water seal assembly shall consist of a Teflon- coated
Belleville spring washer and top - loaded extruded cup
with 3 mm glass bulb containing no plastic parts, and
having a temperature rating of [155 °F (68 0 C)] [175 °F
(79 0 C)]. Sprinklers shall have a nominal K- factor of 5.8.
Standard finish: [Bronze] [Chrome - plated] [White
Polyester] [Special finish- specify]. Residential horizontal
sidewall sprinklers shall be Reliable Model F1 Res 58,
SIN R3513 (Bulletin 135).
Model F1 Res 44 & 58 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model F1 Res 58 horizontal
sidewall sprinkler with the following modifications:
Replace "horizontal sidewall sprinkler" with "recessed
horizontal sprinkler." Add: Recessed escutcheon
assembly shall be a steel, two -piece escutcheon with 1 12 "
adjustment (Model F2). Standard finish shall be
[ brass][bright chrome] [white painted] [Special finish -
specify]. Residential recessed horizontal sidewall
sprinklers shall be Reliable Model F1 Res 58/F2, SIN
R3513 (Bulletin 135).
Model F1 Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.10 gpm /e over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's installation
guidelines and the applicable installation standard.
Sprinkler frame and deflector shall be of bronze frame
construction having a 3 /4" NPT thread. Water seal assembly
shall consist of a Teflon- coated Belleville spring washer and
machined cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155 °F (68 0 C)]
[175 °F (79 0 C)]. Sprinklers shall have a nominal K- factor of
7.6. Standard finish: [Bronze] [Chrome - plated] [White
Polyester] [Special finish- specify]. Residential pendent
sprinklers shall be Reliable Model F1 Res 76, SIN R7618
(Bulletin 135).
Model F1 Res 76 Recessed Pendent/F1,
Model F1 Res 76 Recessed Pendent/F2,
Model F1 Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.10 gpm/ft over the listed
coverage area. Listed flows as specified by the
manufacturer's technical data sheets are to be used.
Residential sprinklers shall be installed in conformance
with the manufacturer's installation guidelines and the
applicable installation standard. Sprinkler frame and
deflector shall be of bronze frame construction having a
3 /4" NPT thread. Water seal assembly shall consist of a
Teflon- coated Belleville spring washer and machined
cup with 3 mm glass bulb containing no plastic parts, and
having a temperature rating of [155 °F (68 0 C)] [175 °F
(79 0 C)]. Sprinklers shall have a nominal K- factor of 7.6.
Standard finish: [Bronze] [Chrome - plated] [White
Polyester] [Special finish- specify]. Recessed
escutcheon assembly shall be a steel, two -piece
escutcheon [with 1 /2 " adjustment (Model F2)] [with 3 /4"
adjustment (Model F1)] [of push -on and thread off design
with 1 12 " adjustment (Model FP)]. Standard finish shall be
[brass][bright chrome] [white painted]. Residential
recessed pendent sprinklers shall be Reliable [Model F1
Res 76 Recessed Pendent/Fl] [Model F1 Res 76
Recessed Pendent /1 [Model F1 Res 76 Recessed
Pendent/FP] SIN R7618 (Bulletin 135).
Model F1 Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engin eyed to provide a minimum
design density of 0.10 gpm /Rover the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's installation
guidelines and the applicable installation standard.
Sprinkler frame and deflector shall be of bronze frame
construction having a 3 /4" NPT thread. Water seal assembly
shall consist of a Teflon- coated Belleville spring washer and
machined cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of 155 °F (68 0 C).
Cover plate assembly shall consist of a brass cover plate
and copper alloy retainer flange. Method of attaching the
cover plate to the sprinkler cup shall be a push -on and
thread -off design allowing a 1 /2 " cover plate adjustment.
Cover plate temperature rating shall be 135 °F (57 °C). A
plastic protective cap shall be provided and factory installed
inside the sprinkler cup to protect the sprinkler from
damage, which could occur during construction before the
cover plate is installed. Standard cover plate finish: [White]
[Custom Color- specify]. ]. Concealed pendent sprinklers
shall be Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin
135).
11.
Reliable ... For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision -made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances, whenever applicable.
Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable
sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
O The Reliable Automatic Sprinkler Co., Inc.
Relle ia bi (800) 431 -1588 Sales Offices Recycled
(800) 848 -6051 Sales Fax ®Paper
(914) 829 -2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 05/08 PM 9999970322
Ja 0
R I ble
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft with
low GPM requirements.
Features
1. Very low water flow requirements.
2. 'h" (13mm) Total adjustment.
3. Thread- On/Thread -Off or Push- On/Thread
Off cover attachment option.
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
2. NYC MEA 258 -93 -E
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ from
standard sprinklers primarily in their response time and
water distribution patterns.
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has dem-
onstrated, in fire testing, an ability for controlling residen-
tial fires, and thereby providing significant evacuation time
for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and Y2" (13mm) of cover adjustment for ease of
installation. The small diameter cover plate is easily and
positively attached and blends into the ceiling, concealing
Bulletin 006 Rev. F
Model RFC30 (SIN RA0611)
Model RFC43 (SIN RA0612)
Model RFC49 (SIN RA0616)
Residential Flat Concealed
Sprinklers
the most dependable fire protection available, an automat-
ic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residential
Sprinklers to be installed in the residential portions of any
occupancy in accordance with NFPA 13, 13R, & 13D.
The RFC30, RFC43 and RFC49 can reduce the need for
precise cutting of drop nipples. The threaded cover plate
assembly can be adjusted without tools to fit accurately
against the ceiling. The fire protection system need not be
shut down to adjust or remove the cover plate assembly.
Application and Installation
The RFC30, RFC43 and RFC49, for residential installa-
tions, use a 165 °F (74 °C) fusible solder link in a tuning fork
style sprinkler frame with a drop -down deflector. This as-
sembly is recessed into the ceiling and concealed by a flat
cover plate. The cover plate is attached to the skirt, using
135 °F (57 °C) ordinary temperature classification solder.
When the ceiling temperature rises, the solder holding
the cover plate releases the cover allowing the deflector
to drop into position and exposing the sprinkler inside to
0
0
0
M
T
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
ceiling temperature. The subsequent operation of the sol-
der link opens the waterway and causes the deflector to
drop into position to distribute the discharging water in a
hemispherical pattern below the sprinkler deflector. Any
adjustment of thread engagement between the cover
plate and cup will assure that the drop -down deflector is
properly located below the ceiling. The residential distri-
bution pattern contains a finer droplet size than a standard
sprinkler, and the pattern produces significantly higher
wall wetting.
After a 2 /s inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench.
When installing a sprinkler, the wrench is first positioned
into the sprinkler /cup assembly and around the hexagonal
body of the sprinkler frame. The Wrench must bottom out
against the cup in order to ensure proper, safe installation.
The sprinkler is then tightened into the pipe fitting. When
inserting or removing the wrench from the sprinkler /cup
assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART
Temperature Rating
OF THE SPRINKLER /CUP ASSEMBLY. MODEL RFC30,
RFC43 AND RFC49 CONCEALED SPRINKLERS MUST
BE INSTALLED ONLY WITH 135 °F RATED COVERS.
Note: A leak tight Y2" NPT (R1/2) sprinkler joint can be ob-
tained with a torque of 8 -18 ft -lbs (10,8 - 24,4 N -m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Cover assemblies provide up to 1 /2 " ( 13mm) of adjust-
ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push -on /thread -off option, the
cover assembly is pushed onto the cup and final adjust-
ment is made by turning the cover clockwise until the skirt
flange makes full contact with the ceiling. Cover removal
requires turning in the counter - clockwise direction.
In ceilings that have a plenum space above the sprinkler,
the plenum space may have neutral or negative pressur-
ization but must not be positively pressurized. Inspect all
sprinklers after installation to ensure that the gap between
the cover plate and ceiling and the 4 slots in the cup are
all open and free from any air flow impediment.
Sprinkler
Cover Plate
Max. Ambient Temp.
165 °F /74 °C
135 °F /57 °C
I 100 °F /38 °C
Installation Data: RFC30 (SIN RA0611)
Thread
K Factor
Sprinkler
Maximum
Minimum
Minimum Required
Size
K Factor
Spacing
Distance to
Distance between
Sprinkler Discharge
Flow
Press.
inch (mm)
'/2" (15mm)
ft. (m)
Wall
s p rinklers
8(2.43)
12 (45)
7.8 (0.54)
ft. (m)
ft. (m)
gpm (Lpm)
psi (bar)
'/2 (15mm)
3.0
12 x 12 (3.6x3.6)
6(1.83)
8(2.43)
9(34.1)
9.0 (0.62)
1 12" (15mm)
3.0
14 x 14 (4.3x4.3)
7(2.13)
8(2.43)
10 (37.8)
11 (0.76)
Note: 1 bar = 100 Kpa
Installation Data: RFC43 (SIN RA0612)
Thread
Size
Inch (mm)
K Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance to
Wall
Minimum
Distance between
sprinklers
Minimum Required
Sprinkler Discharge
Flow
Press.
ft (m)
ft. (m)
gpm (Lpm)
psi (bar)
'/2" (15mm)
4.3
12 x 12 (3.6x3.6)
6(1.83)
8(2.43)
12 (45)
7.8 (0.54)
Y2" (15mm)
4.3
14 x 14 (4.3x4.3)
7(2.13)
8(2.43)
13 (49)
9.1 (0.63)
/2" (15mm)
4.3
16 x 16 (4.9x4.9)
8(2.43)
8(2.43)
13 (49)
9.1 (0.63)
Y2" (15mm)
4.3
18 x 18 (5.5x5.5)
9(2.74)
8(2.43)
18 (68)
17.5(l.21)
'/2 (15mm)
4.3
20 x 20 (6.0x6.0)
10 (3.05)
8(2.43)
21 (79)
23.8(l.64)
Note: 1 bar = 100 Kpa
Installation Data: RFC49 (RA0616)
Thread
Size
inch (mm)
K Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance to
Wall
Minimum
Distance between
sprinklers
Minimum Required
Sprinkler Discharge
Flow
Press.
ft. (m)
ft. (m)
gpm (Lpm)
psi (bar)
1 12" (15mm)
4.9
12 x 12 (3.6x3.6)
6(1.83)
8(2.43)
13 (49)
7.0 (0.48)
h" (15mm)
4.9
14 x 14 (4.3x4.3)
7(2.13)
8(2.43)
13 (49)
7.0 (0.48)
12" (15mm)
4.9
16 x 16 (4.9x4.9)
8(2.43)
8(2.43)
13 (49)
7.0 (0.48)
'/2 (15mm)
4.9
18 x 18 (5.5x5.5)
9(2.74)
8(2.43)
17 (64.3)
12.0 (0.83)
12" (15mm)
4.9
20 x 20 (6.0x6.0)
10 (3.05)
8(2.43)
20 (75.7)
16.7(l.14)
Note: 1 bar = 100 Kpa
FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035.
2.
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler cover plate assem-
bly which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until
used to minimize the potential for damage to sprinklers
that would cause improper operation or non - operation.
Model RFC30, RFC43 and RFC49 Residential
Concealed Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop -down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm /ftz. Sprinkler frame and deflector
shall be of bronze frame construction having a' /2 NPT
thread. Thermal element shall consist of an approved
black - painted beryllium- nickel fusible solder link with
symmetric lever mechanism, maintaining a Teflon- coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler
K- factor shall be nominal 3.0 (44), 4.3 (62.4), and 4.91
(70) having a 5 /, ", 3 / 8 " and 7 /,6 " orifice. Temperature rating
shall be Ordinary 165 °F (74 0 C); cover plate temperature
rating to be 135 °F (57 0 C). Cover plate assembly shall
consist of a brass cover plate and copper alloy retainer
flange allowing a' /2" cover plate adjustment. Any secure
engagement between the cover plate and the cup will
assure that the drop -down deflector is properly located
below the ceiling. A plastic protective cap shall be
provided and factory installed inside the sprinkler cup
to protect the drop -down sprinkler deflector from dam-
age, which could occur during construction before the
cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty - specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA0611
(Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006)
or Model RFC49, SIN RA0616 (Bulletin 006).
Ordering Information Cover Plate Finishes M
Specify:
Standard Finishes
1. Sprinkler Model
2. Cover Plate Finish
Chrome
3. Thread -On or
White
Push -On Feature
Special Application
1" x 112" REDUCING
TEE OR ELBOW
L I r
92' [66.55mm)
2 " [58.42mm] DIA I HOLE IN CEILING
CUP
CEILING
" [ 12.70 —] MAX.
COVER ADJUSTMENr
CC P COVER PLA rE
ASSEMBLY
34" [84.21mml DIA.
2" [50.8-1 1 MAX.
FACE OF FITTING
rO FACE OF CEILING
DIMENSION
1 J" [4.96, m]
ooa rA
COVER PLATE: 1 /2 " L12.7mml ADJUSTMEN
Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other colors and finishes avail-
able. Consult factory for details.
Note: Paint or any other coatings
applied over the factory finish will
void all approvals and warran-
ties.
3.
Reliable... For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision -made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges Identification signs
• Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. ® Recycled
Re'; (800) 431 -1588 Sales Offices Paper
�� (800) 848 -6051 Sales Fax Revision lines indicate updated or new data.
' (914) 829 -2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A 02111 PM 9999970261