HomeMy WebLinkAboutB11-0255 comment letter
Date: August 18, 2011
Re: 2733 Kinnickinnick B11-0255
Dear Thom Conville,
RESPONSE INSTRUCTIONS
● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each comment.
BUILDING COMMENTS
Architectural Comments:
1. Please clarify if the proposed work is being done in a R-3 occupancy or R-2 .
2. Provide plans on the same sheet size as per Town of Vail submittal requirements.
3. Provide, on plans, the u value of the proposed skylights
Structural Comments:
Reviewed and accepted
Plumbing Comments:
1. Please clarify proposed plumbing to be done. It is not reflected on the plans
Mechanical Comments:
1. Fireplace must not release more than 7.5 grams of particulates per hour. Please annotate on the plans
Electrical Comments:
Reviewed and accepted
PLANNING COMMENTS
Reviewed and accepted
FIRE COMMENTS
Reviewed and accepted
PUBLIC WORKS COMMENTS
NA
Sincerely,
Martin A. Haeberle
Chief Building Official