Loading...
HomeMy WebLinkAboutB11-0274 comment letter Date: 8/29/2011 Re: Arthex Medical B11-0274 Dear Mr. Faulhaber, RESPONSE INSTRUCTIONS ● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Architectural Comments: Sheet A201 1. Show compliance for accessibility at toilet, drinking fountain, and locker room. Reference sections 3411.7, 3411.8.11, and 3411.8.12 of the IBC. 2. Provide the required maneuvering clearances at door 4 per section 404.2.3 A117.1 ANSI. Structural Comments: NA Plumbing Comments: Sheet P2.0 1. Clarify that the existing DWV system is adequate to support the additional loads proposed. Reference sections 710 and 916 of the IPC. 2. Clarify that the existing water supply is adequate for the additional water fixtures proposed. Reference section 604.3 IPC 3. Clarify back flow protection device(s) to be used for hose bib connections. Reference section 608 IPC Mechanical Comments: Sheet M2.0 1. Please clarify occupancy classifications used to determine required outside air requirements. Reference Table 403.3 IMC. Electrical Comments: Reviewed and accepted PLANNING COMMENTS NA FIRE COMMENTS Reviewed and accepted PUBLIC WORKS COMMENTS NA Sincerely, Martin A. Haeberle Chief Building Official