Loading...
HomeMy WebLinkAboutB11-0280 comment letter Date:8/31/2011 Re: 610 W Lionshead Cr Unit 704 Dear Mr. Turner, RESPONSE INSTRUCTIONS ● Submit four complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Architectural Comments: Sheet A2.1 1. Plans to reflect building type, occupancy classification, and applicable codes. See Town of Vail submittal requirements. 2. Plans to be sealed by a licensed architect if penetrating fire assemblies with mechanical equipment. Please provide cross-sectional details for proposed installations. 3. Provide flame spreads classification for the proposed flooring showing compliance for the building type. Reference section 603 IBC 4. Obtain a DRB approval for the HVAC and decking materials prior to resubmittal. Sheet A2.4 1. Show on plans the ceiling height of all spaces. Reference Town of Vail submittal requirements. Structural Comments: Reviewed and accepted Plumbing Comments: Reviewed and accepted Mechanical Comments: Sheet M-1 1. Provide a minimum 20 x 30 access for each air handler. Reference section 306.3 IMC 2. Plans to do not reflect the required condensate drains per section 307 of the IMC. Revise plans. Electrical Comments: 1 Provide complete electrical plans for review. See Town of Vail submittal requirements. PLANNING COMMENTS DRB approval required prior to resubmittal FIRE COMMENTS Reviewed and accepted PUBLIC WORKS COMMENTS NA Sincerely, Martin A. Haeberle Chief Building Official