Loading...
HomeMy WebLinkAboutA11-0041 unit 110 WIRE AND CONDUIT CHARACTERISTICS Wire Schedule Cable /Wire Desigination Conductor size Insulation Number of Conductors Conductor Dia. (in) Conductor /Cable Area (sq-in) Conduit Size (in) Conduit ID (in) Area (sq-in) A (SLC) 16AWG CABLE 2 Con Cable 0.176 0.0243 1/2 0.622 0.304 B (Strobes) 14AWG THHN 2 0.111 0.0194 3/4 0.824 0.533 C (Speakers) 16AWG CABLE 2 Con Cable 0.178 0.0249 1 1.049 0.864 D (24VDC) 14AWG CABLE 2 0.111 0.0194 E (RS-485) 16AWG CABLE 2 Con Cable 0.178 0.0249 1-1/4 1.380 1.496 G (IDC) 16AWG THHN 2 0.096 0.0145 1-1/2 1.610 2.036 2 2.067 3.356 I (Sounder Base Interconnect) 16AWG THHN 1 0.096 0.0072 2-1/2 2.731 5.858 3 3.356 8.846 Fire alarm cable for Signaling Line Circuit (SLC) type "A" shown in wire schedule is : Non Plenum 16awg, non shielded, 2cond, solid, TYPE FPLR. OD = 0.176 Each B circuit consists of 2 #14 conductors Fire alarm cable for Speaker Circuit type "C" shown in wire schedule is : Non Plenum 16awg, OA shielded, 2cond, solid, TYPE FPLR. OD = 0.178 Each D circuit consists of 2 #14 conductors Fire alarm cable for RS-485 Circuit type "E" shown in wire schedule is : Non Plenum 16awg, OA shielded, 2cond, solid, TYPE FPLR. OD = 0.178 Each G circuit consists of 2 #16 conductors Each I circuit consists of 1 #16 conductor CONDUIT FILL CALCULATION TABLE CONDUIT SIZE CONDUCTORS IN CONDUIT SEGMENT 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 1A 8.0% 4.6% 2.8% 1.6% 1.2% 0.7% 0.4% 1A,1D 14.4% 8.2% 5.1% 2.9% 2.1% 1.3% 0.7% 2A,2D 28.8% 16.4% 10.1% 5.8% 4.3% 2.6% 1.5% 3A,2D 36.8% 20.9% 12.9% 7.5% 5.5% 3.3% 1.9% 1A,1D,1I 16.8% 9.5% 5.9% 3.4% 2.5% 1.5% 0.9% 2A,2D,2I 31.1% 17.7% 10.9% 6.3% 4.6% 2.8% 1.6% 1B,1C 14.6% 8.3% 5.1% 3.0% 2.2% 1.3% 0.8% 2B,2C 29.1% 16.6% 10.2% 5.9% 4.3% 2.6% 1.5% 3B,3C 43.7% 24.9% 15.4% 8.9% 6.5% 4.0% 2.3% 4B,4C 58.2% 33.2% 20.5% 11.8% 8.7% 5.3% 3.0% 1G 2.4% 1.4% 0.8% 0.5% 0.4% 0.2% 0.1% 2G 4.8% 2.7% 1.7% 1.0% 0.7% 0.4% 0.2% 3G 7.1% 4.1% 2.5% 1.5% 1.1% 0.6% 0.4% 4G 9.5% 5.4% 3.4% 1.9% 1.4% 0.9% 0.5% 5G 11.9% 6.8% 4.2% 2.4% 1.8% 1.1% 0.6% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 1D,1E 11.1% 6.3% 3.9% 2.3% 1.7% 1.0% 0.6% 1D,2E 15.9% 9.1% 5.6% 3.2% 2.4% 1.4% 0.8% 2D,1E 17.5% 10.0% 6.2% 3.6% 2.6% 1.6% 0.9% 2D,2D 22.3% 12.7% 7.8% 4.5% 3.3% 2.0% 1.2% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0% M.L. Vaughan, Fire Marshal Digitally signed by M.L. Vaughan, Fire Marshal DN: cn=M.L. Vaughan, Fire Marshal, o=Vail Fire & Emergency Services, ou=Prevention, email=mvaughan@vailgov .com, c=US Date: 2011.09.01 15:07:38 -06'00' Adjust strobe locations as discussed and noted on plan. move this strobe to cloud at top of sheet. A11-0041 Johnson Controls. IFC-320 FIRE ALARM CONTROL PANEL -FAP4 Calculation Column 1 Primary, Non-Fire Alarm Current (amps) Calculation Column 2 Primary, Fire Alarm Current (amps) DEVICE QTY. AMPS. TOTAL QTY. AMPS. TOTAL IFC-320 1 0.2500 0.2500 1 0.2300 0.2300 KDM-R2 DISPLAY 1 0.1000 0.1000 1 0.1000 0.1000 ACPS-2406 0 0.1287 0.0000 0 0.0000 0.0000 BACNet Gateway 0 0.3600 0.0000 0 0.3600 0.0000 LCD-80,LCD-80TM 0 0.1000 0.0000 0 0.1000 0.0000 JNCA 0 0.4000 0.0000 0 0.5000 0.0000 LDM-32 0 0.0400 0.0000 0 0.0000 UZC-256 0 0.0350 0.0000 0 0.0850 0.0000 AMG-1,AMG-E 0 0.0600 0.0000 0 0.0600 0.0000 FFT-7,FFT-7S 0 0.0600 0.0000 0 0.1200 0.0000 AA-30 0 0 AA-100,AA-120 0 0 M302MJ,M502MJ 0 0.0094 0.0000 0 0.0900 0.0000 XPIQ 0 0.0000 0 0.0000 RPT-W,RPT-WF,RPT-F,NCM-W 1 0.0170 0.0170 1 0.0170 0.0170 UDACT Communicator 0 0.0400 0.0000 0 0.1000 0.0000 Notification Appliance 1 1 3.3730 3.3730 SOUNDER BASES 0 0.0010 0.0000 0 0.0150 0.0000 Power Supervision Relays 0 0.0200 0.0000 0 0.0200 0.0000 DH500,DH502 Duct Detectors 0 0.0000 0 0.0000 CHG-120 Battery Charger 0 0 SLC #1 Totals 1 0.2000 0.2000 1 0.2000 0.2000 TOTAL 0.57 3.92 TOTAL CURRENT -STANDBY OPERATION 0.567 HOURS REQUIRED FOR OPERATION 24 BATTERY REQUIREMENTS FOR 4 HRS 13.61 TOTAL CURRENT -ALARM OPERATION 3.920 HOURS REQUIRED FOR OPERATION (15min) 0.25 BATTERY REQUIREMENTS FOR 15 MIN 0.98 TOTAL BATTERY REQUIREMENTS 14.59 BATTERY REQUIRED WITH 20% FACTOR 17.51 BATTERY TO BE INSTALLED 18 AMP-HR Project Name Solaris Date 11/17/2010 Circuit Number Remote Power Supply #5 /RPS5-3 Voltage Voltage Voltage Location First Level Retail 110 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.385 120 0.22 0.385 120 0.295 0.385 120 0.147 Minimum Device Voltage 16 End of Line Voltage 20.18 End of Line Voltage 20.11 End of Line Voltage 20.25 Total Circuit Current 0.385 Wire Ohm's Percent Drop 1.10% Percent Drop 1.44% Percent Drop 0.72% Gauge Per 1000 Distance from source to 1st device 70 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.220 70 20.23 0.172 0.84% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.165 50 20.18 0.225 1.10% END 20.18 0.225 1.10% Device Manufacturer Wheelock Device Manufacturer Wheelock END 20.18 0.225 1.10% END 20.18 0.225 1.10% Candela Candela END 20.18 0.225 1.10% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 20.18 0.225 1.10% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 20.18 0.225 1.10% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 20.18 0.225 1.10% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 20.18 0.225 1.10% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 20.18 0.225 1.10% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 20.18 0.225 1.10% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 20.18 0.225 1.10% END 20.18 0.225 1.10% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 20.18 0.225 1.10% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 20.18 0.225 1.10% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 20.18 0.225 1.10% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 20.18 0.225 1.10% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 20.18 0.225 1.10% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 20.18 0.225 1.10% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.385 120 End of Line Voltage 20.18 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.385 OUT SPARE CAPACITY = 74% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Totals Totals Totals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Current @Rated Voltage Current @Rated Voltage Model # Project Name Solaris Date 11/17/2010 Circuit Number Remote Power Supply #5 /RPS5-5 Voltage Voltage Voltage Location First Level Partial Area 4 Parking Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 1.642 670 4.13 1.642 670 7.019 1.642 670 3.509 Minimum Device Voltage 16 End of Line Voltage 16.27 End of Line Voltage 13.38 End of Line Voltage 16.89 Total Circuit Current 1.642 Wire Ohm's Percent Drop 20.24% Percent Drop 34.41% Percent Drop 17.20% Gauge Per 1000 Distance from source to 1st device 90 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.220 90 19.46 0.943 4.62% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.220 60 18.91 1.487 7.29% Device 3 0.060 70 18.38 2.024 9.92% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.060 60 17.94 2.461 12.06% Device 5 0.092 45 17.63 2.772 13.59% Candela Candela Device 6 0.165 45 17.34 3.056 14.98% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) Device 7 0.165 60 17.03 3.372 16.53% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 Device 8 0.220 120 16.52 3.877 19.01% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 Device 9 0.220 60 16.35 4.046 19.83% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 Device 10 0.220 60 16.27 4.130 20.24% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 16.27 4.130 20.24% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 16.27 4.130 20.24% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 16.27 4.130 20.24% END 16.27 4.130 20.24% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 16.27 4.130 20.24% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 16.27 4.130 20.24% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 16.27 4.130 20.24% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 16.27 4.130 20.24% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 16.27 4.130 20.24% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 16.27 4.130 20.24% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 1.642 670 End of Line Voltage 16.27 Setup Note: confgure this output so that it is not shared. This output AMPS will have the entire 3.0 amps available. OUT AVAILABLE CURRENT 3 OUT TOTAL CURRENT 1.642 OUT SPARE CAPACITY = 45% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method CIRCUIT IS WITHIN LIMITS Totals Totals Totals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Current @Rated Voltage Current @Rated Voltage Model # Project Name Solaris Date 11/17/2010 Circuit Number Remote Power Supply #5 /RPS5-6 Voltage Voltage Voltage Location First Level Partial Area 4 Skate Rental Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.165 250 0.26 0.165 250 0.263 0.165 250 0.132 Minimum Device Voltage 16 End of Line Voltage 20.14 End of Line Voltage 20.14 End of Line Voltage 20.27 Total Circuit Current 0.165 Wire Ohm's Percent Drop 1.29% Percent Drop 1.29% Percent Drop 0.65% Gauge Per 1000 Distance from source to 1st device 250 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.165 250 20.14 0.263 1.29% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). END 20.14 0.263 1.29% END 20.14 0.263 1.29% Device Manufacturer Wheelock Device Manufacturer Wheelock END 20.14 0.263 1.29% END 20.14 0.263 1.29% Candela Candela END 20.14 0.263 1.29% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 20.14 0.263 1.29% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 20.14 0.263 1.29% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 20.14 0.263 1.29% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 20.14 0.263 1.29% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 20.14 0.263 1.29% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 20.14 0.263 1.29% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 20.14 0.263 1.29% END 20.14 0.263 1.29% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 20.14 0.263 1.29% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 20.14 0.263 1.29% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 20.14 0.263 1.29% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 20.14 0.263 1.29% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 20.14 0.263 1.29% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 20.14 0.263 1.29% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.165 250 End of Line Voltage 20.14 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.165 OUT SPARE CAPACITY = 89% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method CIRCUIT IS WITHIN LIMITS Totals Totals Totals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Current @Rated Voltage Current @Rated Voltage Model # Project Name Solaris Date 11/17/2010 Circuit Number Remote Power Supply #5 /RPS5-7 Voltage Voltage Voltage Location First Level Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.000 0 0.00 0.000 0 0.000 0.000 0 0.000 Minimum Device Voltage 16 End of Line Voltage 20.40 End of Line Voltage 20.40 End of Line Voltage 20.40 Total Circuit Current 0.000 Wire Ohm's Percent Drop 0.00% Percent Drop 0.00% Percent Drop 0.00% Gauge Per 1000 Distance from source to 1st device 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0 20.40 0.000 0.00% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). END 20.40 0.000 0.00% END 20.40 0.000 0.00% Device Manufacturer Wheelock Device Manufacturer Wheelock END 20.40 0.000 0.00% END 20.40 0.000 0.00% Candela Candela END 20.40 0.000 0.00% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 20.40 0.000 0.00% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 20.40 0.000 0.00% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 20.40 0.000 0.00% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 20.40 0.000 0.00% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 20.40 0.000 0.00% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 20.40 0.000 0.00% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 20.40 0.000 0.00% END 20.40 0.000 0.00% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 20.40 0.000 0.00% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 20.40 0.000 0.00% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 20.40 0.000 0.00% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 20.40 0.000 0.00% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 20.40 0.000 0.00% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 20.40 0.000 0.00% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.000 0 End of Line Voltage 20.40 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.000 OUT SPARE CAPACITY = 100% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method CIRCUIT IS WITHIN LIMITS Totals Totals Totals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Current @Rated Voltage Current @Rated Voltage Model # Project Name Solaris Date 11/17/2010 Circuit Number Remote Power Supply #5 /RPS5-8 Voltage Voltage Voltage Location First Level Partial Area 1 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.000 0 0.00 0.000 0 0.000 0.000 0 0.000 Minimum Device Voltage 16 End of Line Voltage 20.40 End of Line Voltage 20.40 End of Line Voltage 20.40 Total Circuit Current 0.000 Wire Ohm's Percent Drop 0.00% Percent Drop 0.00% Percent Drop 0.00% Gauge Per 1000 Distance from source to 1st device 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0 20.40 0.000 0.00% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). END 20.40 0.000 0.00% END 20.40 0.000 0.00% Device Manufacturer Wheelock Wheelock Device Manufacturer Wheelock END 20.40 0.000 0.00% END 20.40 0.000 0.00% Candela Candela END 20.40 0.000 0.00% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 20.40 0.000 0.00% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 20.40 0.000 0.00% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 20.40 0.000 0.00% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 20.40 0.000 0.00% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 20.40 0.000 0.00% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 20.40 0.000 0.00% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 20.40 0.000 0.00% END 20.40 0.000 0.00% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 20.40 0.000 0.00% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 20.40 0.000 0.00% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 20.40 0.000 0.00% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 20.40 0.000 0.00% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 20.40 0.000 0.00% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 20.40 0.000 0.00% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.000 0 End of Line Voltage 20.40 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.000 OUT SPARE CAPACITY = 100% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method CIRCUIT IS WITHIN LIMITS Totals Totals Totals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Current @Rated Voltage Current @Rated Voltage Model # Project Name Solaris Date 11/23/2010 Circuit Number Remote Power Supply #5 /RPS5-1 Voltage Voltage Voltage Location First Level Retail 108 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.724 245 0.81 0.724 245 1.132 0.724 245 0.566 Minimum Device Voltage 16 End of Line Voltage 19.59 End of Line Voltage 19.27 End of Line Voltage 19.83 Total Circuit Current 0.724 Wire Ohm's Percent Drop 3.98% Percent Drop 5.55% Percent Drop 2.77% Gauge Per 1000 Distance from source to 1st device 110 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.220 110 19.89 0.508 2.49% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.060 40 19.76 0.637 3.12% Device 3 0.060 25 19.69 0.708 3.47% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.192 15 19.66 0.744 3.65% Device 5 0.192 55 19.59 0.812 3.98% Candela Candela END 19.59 0.812 3.98% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 19.59 0.812 3.98% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.59 0.812 3.98% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.59 0.812 3.98% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.59 0.812 3.98% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.59 0.812 3.98% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.59 0.812 3.98% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.59 0.812 3.98% END 19.59 0.812 3.98% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.59 0.812 3.98% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.59 0.812 3.98% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.59 0.812 3.98% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.59 0.812 3.98% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.59 0.812 3.98% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.59 0.812 3.98% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.724 245 End of Line Voltage 19.59 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.724 OUT SPARE CAPACITY = 52% Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 ma Voltage Current @Rated Voltage Current @Rated Voltage Model # CIRCUIT IS WITHIN LIMITS Totals Totals Totals This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Solaris Date 7/11/2011 Circuit Number Remote Power Supply #5 /RPS5-4 Voltage Voltage Voltage Location First Level Retail 112 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.300 360 0.42 0.300 360 0.689 0.300 360 0.345 Minimum Minimum Device Voltage 16 End of Line Voltage 19.98 End of Line Voltage 19.71 End of Line Voltage 20.06 Total Circuit Current 0.300 Wire Ohm's Percent Drop 2.06% Percent Drop 3.38% Percent Drop 1.69% Gauge Per 1000 Distance from source to 1st device 115 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.060 115 20.18 0.220 1.08% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.060 35 20.13 0.274 1.34% Device 3 0.060 55 20.06 0.337 1.65% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.060 65 20.01 0.387 1.90% Device 5 0.060 90 19.98 0.421 2.06% Candela Candela END 19.98 0.421 2.06% Speaker/Strobes (Wall Mount) Strobes (Wall Mount) END 19.98 0.421 2.06% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.98 0.421 2.06% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.98 0.421 2.06% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.98 0.421 2.06% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.98 0.421 2.06% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.98 0.421 2.06% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.98 0.421 2.06% END 19.98 0.421 2.06% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.98 0.421 2.06% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.98 0.421 2.06% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.98 0.421 2.06% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.98 0.421 2.06% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.98 0.421 2.06% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.98 0.421 2.06% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.300 360 End of Line Voltage 19.98 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.300 OUT SPARE CAPACITY = 80% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. End of Line and Load Centering Methods use only the wire guage for the first device to source .150 = 150 ma Voltage Totals Totals Totals CIRCUIT IS WITHIN LIMITS This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name Solaris Date 8/16/2011 Circuit Number Remote Power Supply #5 /RPS5-2 Voltage Voltage Voltage Location First Level Retail 110 Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.557 265 0.56 0.557 265 0.942 0.557 265 0.471 Minimum Device Voltage 16 End of Line Voltage 19.84 End of Line Voltage 19.46 End of Line Voltage 19.93 Total Circuit Current 0.557 Wire Ohm's Percent Drop 2.73% Percent Drop 4.62% Percent Drop 2.31% Gauge Per 1000 Distance from source to 1st device 70 14 3.19 Wire Gauge for balance of circuit 14 3.19 18=7.77 16=4.89 14=3.19 12=1.98 10=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.060 70 20.15 0.249 1.22% the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 2 0.060 25 20.07 0.328 1.61% Device 3 0.060 15 20.03 0.370 1.81% Device Manufacturer Wheelock Device Manufacturer Wheelock Device 4 0.060 15 19.99 0.406 1.99% Device 5 0.165 40 19.91 0.487 2.39% Candela Candela Device 6 0.092 55 19.86 0.540 2.65% Speaker/Strobes (Wall Wall Mount) Strobes (Wall Mount) Device 7 0.060 45 19.84 0.557 2.73% E70-24MCW-FW 15 0.060 RSS-24MCW-FW 15 0.060 END 19.84 0.557 2.73% E70-24MCW-FW 30 0.092 RSS-24MCW-FW 30 0.092 END 19.84 0.557 2.73% E70-24MCW-FW 75 0.165 RSS-24MCW-FW 75 0.165 END 19.84 0.557 2.73% E70-24MCW-FW 110 0.220 RSS-24MCW-FW 110 0.220 END 19.84 0.557 2.73% E70-24MCWH-FW 135 0.300 RSS-24MCWH-FW 135 0.300 END 19.84 0.557 2.73% E70-24MCWH-FW 185 0.420 RSS-24MCWH-FW 185 0.420 END 19.84 0.557 2.73% END 19.84 0.557 2.73% Speaker/Strobes (Ceiling Mount) Speaker/Strobes (Wall Mount) END 19.84 0.557 2.73% E90-24MCC-FW 15 0.065 RSS-24MCC-FW 15 0.065 END 19.84 0.557 2.73% E90-24MCC-FW 30 0.105 RSS-24MCC-FW 30 0.105 END 19.84 0.557 2.73% E90-24MCC-FW 75 0.189 RSS-24MCC-FW 75 0.189 END 19.84 0.557 2.73% E90-24MCC-FW 95 0.249 RSS-24MCC-FW 95 0.249 END 19.84 0.557 2.73% E90-24MCCH-FW 115 0.300 RSS-24MCCH-FW 115 0.300 END 19.84 0.557 2.73% E90-24MCCH-FW 177 0.420 RSS-24MCCH-FW 177 0.420 Totals 0.557 265 End of Line Voltage 19.84 AMPS OUT AVAILABLE CURRENT 1.5 OUT TOTAL CURRENT 0.557 OUT SPARE CAPACITY = 63% Current @Rated Voltage Current @Rated Voltage Model # Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. End of Line and Load Centering Methods use only the wire guage for the first device to source .150 = 150 ma Voltage Totals Totals Totals CIRCUIT IS WITHIN LIMITS This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method PS-8 BATTERY CAPACITY CALCULATION FOR RPS5 OPERATION ON BATTERY BACKUP POWER DEVICE TYPE QTY STAND-BY CURRENT QTY ALARM CURRENT EACH TOTAL EACH TOTAL RPS5-1 1 0.000 0.000 1 0.724 0.724 RPS5-2 1 0.000 0.000 1 0.557 0.557 RPS5-3 1 0.000 0.000 1 0.385 0.385 RPS5-4 1 0.000 0.000 1 0.300 0.300 RPS5-5 1 0.000 0.000 1 1.642 1.642 RPS5-6 1 0.000 0.000 1 0.165 0.165 RPS5-7 1 0.000 0.000 1 0.000 0.000 RPS5-8 1 0.000 0.000 1 0.000 0.000 MAIN PC BOARD 1 0.129 0.129 1 0.129 0.129 Number of Slave power Supplys 0 0.006 0.000 0 0.006 0.000 0 0.000 0.000 0 0.000 0.000 0 0.000 0.000 0 0.000 0.000 TOTAL CURRENT 0.129 3.902 TOTAL CURRENT -STANDBY OPERATION 0.129 HOURS REQUIRED FOR OPERATION 24.00 BATTERY STANDBY REQUIREMENTS 3.10 TOTAL CURRENT -ALARM OPERATION 3.902 HRS REQUIRED FOR OPERATION 0.250 (15 MIN) BATTERY ALARM REQUIREMENT 0.98 TOTAL BATTERY REQUIREMENTS 4.07 BATTERY REQUIRED WITH 20% FACTOR 4.89 7 AMP-HOUR BATTERIES INSTALLED AMPS AVAILABLE CURRENT 8 TOTAL CURRENT 3.902 SPARE CAPACITY 51.23%