HomeMy WebLinkAboutB11-0312 comment letter Date: 9/12/2011 Re: 5177 Black gore Drive/ B11-0312 Dear Mr. Blomquist, RESPONSE INSTRUCTIONS ● Submit three complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Architectural Comments: Reviewed and accepted Structural Comments: Sheet S1 1. How is frost protection to be achieved? Reference section 1809.5 IBC Plumbing Comments: NA Mechanical Comments: NA Electrical Comments: 1. Provide complete electrical plans to include load calculations showing compliance with the National Electric Code 2008 edition PLANNING COMMENTS 1. Provide a cut sheet for the exterior light fixture confirming compliance with Town of Vail Lighting regulations. FIRE COMMENTS Reviewed and Accepted PUBLIC WORKS COMMENTS Reviewed and Accepted Sincerely, Martin A. Haeberle Chief Building Official