Loading...
HomeMy WebLinkAboutB11-0278 comment letter 2 Date: 9/20//2011 Re: 1406 Moraine Drive B11-0278 comment letter 2 Dear Mr. Plavec, RESPONSE INSTRUCTIONS ● Submit three complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Architectural Comments: Sheet A3 1. How is the boiler to be protected from damage in the garage per section 303.4 IMC 36” is inadequate for vehicle protection. Many private vehicles exceed 36” in height. Provide an approved barrier as specified by the code. Structural Comments: NA Plumbing Comments: Sheet A3 1. Provide gas piping isometrics for the proposed work showing compliance with section 402.3 of the IFGC. Gas piping isometrics is incomplete. Unable to determine required gas piping sizing from submitted drawing Electrical Comments: 1. Please provide electrical plans for the proposed electrical work. Only indication of electrical work is in the construction valuation. Additional circuits require a load calculations submittal. See Town of Vail submittal requirements PUBLIC WORKS COMMENTS Annotate on plans that the sidewalk shall not be heated Sincerely, Martin A. Haeberle Chief Building Official