Date:10/14/2011
Re: 186 East Gore Creek Drive B11-0404
Dear Mr. Cremonese,
RESPONSE INSTRUCTIONS
● Submit four complete sets of revised construction documents containing
the requested information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each
comment.
BUILDING COMMENTS
Architectural Comments:
Sheet A1.1
1. Provide proposed and existing occupancy classification and building type per section 107.2 IBC
2. Show how compliance
with section 2902, minimum plumbing fixtures is being achieved. Note: Include plans for travel distance location and fixture calculations. See sections 2902.1.1, 2902.3, 2902.3.1, and
2902.3.2 IBC. Not required if same occupancy classification and occupant load
3. How is the exit discharge to be illuminated. Reference section 1006 IBC
Sheet A2.1
1. Please clarify
the conflict of plans showing the storage space and office space in the same area.
Sheet A3.1
1. Provide the u value of proposed glazing and doors for the storefront showing compliance
with the IECC.
Sheet A4.1
1. Details do not reflect the required weather protection per section 1405.2 IBC
Structural Comments:
NA
Plumbing Comments:
See architectural comments
Mechanical Comments:
Reviewed and accepted
Electrical Comments:
See architectural comments
PLANNING COMMENTS
Reviewed and accepted
FIRE
COMMENTS
Reviewed and accepted
PUBLIC WORKS COMMENTS
Construction staging plan required if to be in right of way