HomeMy WebLinkAboutF08-0081TOWN OF VAIL F IRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRON'T'AGE ROAD
VAIL, CO 81657
970-479-2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
SPRINKLER PERMIT
10/09/2008
Job Address: 2211 N FRONTAGE RD VAIL
Location.....: 143 E MEADOW DRIVE
Parcel No...: 210108202001
Project No
OWNER SOLARIS PROPERTY OWNER LLC
2211 N FRONTATGE RD STE A
VAIL
CO 81657
APPLICANT FRONTIER FIRE PROTECTION
2617 WEST HOLDEN PLACE
DENVER
CO 80204
License: 446 -S
CONTRACTOR FRONTIER FIRE PROTECTION
2617 WEST HOLDEN PLACE
DENVER
CO 80204
License: 446 -S
Permit #: F08 -0081
Status ... .
Applied ..
Issued . . .
Expires. ..
ISSUED
10/09/2008
10/24/2008
10/09/2008 Phone: 303 - 629 -0221
10/09/2008 Phone: 303 - 629 -0221
Desciption: TEMPORARY STANDPIPE SYSTEM FOR NEW COMMERCIAL BUILDING
( SOLARIS)
Valuation: $55,000.00
**s*#s##s#}s+}+*}*****#*##s#+s }s + * +s * * * * * * # # # # } +s + } }s +s + * * * ** #sss } +} FEE SUMMARY s}+s++}+****# s + #s #ss +s } +s * * * * * * * #s + # } } + * * + *# *sss #s +s * * * } * * **
Mechanical - ->
$0.00 Restuarant Plan Review - ->
$0.00
Total Calculated Fees --- >
$2,687.50
Plan Check - ->
$350.00 DRB Fee----------- - - - - ->
$0.00
Additional Fees --- ------- >
$0.00
Investigation ->
$0.00 TOTAL FEES - --
$2,687.50
Total Permit Fee — -------- >
$2,687.50
Will Call --
$0.00
Payments--------- - - - - ->
$2,687.50
BALANCE DUE --------- >
$0.00
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE
DEPARTMENT
10/23/2008
McGee Action: AP
teve
42 West Meadow Drive
Vail, Colorado 81657
970 - 479 -2250
October 23, 2008
Steve Martin
Frontier Fire Protection
2617 West Holden Place
Denver, Colorado 80204
Re: Solaris Temp Standpipe
Permit F08 -0081
Dear Steve;
The plans for the temporary standpipe at the Solaris project are approved
1. Page 16 of 16 shows a 3 inch in -line Wilkins Z3004 PRV. The letter trom Fr(
Sept 15, 2008 indicates under item # 2, that PRV's will be eliminated from the sti
Either remove the PRV or provide an engineered explanation of why it is there. Thf
do not indicate the minimum and maximum flows and pressures. No material cut sheet
provided.
2. Material cuts sheets were provided but nothing on the plans or notes indicate
the location of heavy fittings, Schedule 10 or Schedule 40 pipe or other relevant
materials cut sheet for the Mega Flow does not indicate class or pressure ratings
3. Additional discussion is needed on the hydraulics for the fire pump. The cz
provided for the final design indicate 100 psi will be available at the top FHV. '.
appendices of NFPA 14, 2007 edition, Section A 7.8, discusses options fire departs
use for high rise fire hose configurations. Vail Fire Dept. does in fact use the .
example, 50 ft of 2 % inch, a wye and two 100 ft sections of 1 % in hose. Credit i
fire hose length at 200 ft. The length of the fire hose would be restricted to 151
the current scenario. Demand pressures are calculated to be 120 149 psi.
Nothing in the current plan for the temporary standpipe would need to be changed :
of the outcome of the pending discussion on the hydraulics. Please submit a schedi
indicating the schedule of pipe per location.
Sincerely,
Michael McGee
Deputy Chief, FSSI 006
Vail Fire Department
Response:
October 23, 2008
Mr. Mike McGee, Deputy Chief /Fire Marshal
Town of Vail, Fire and Emergency Services
42 West Meadow Drive
Vail, Colorado 81657
1- 970 - 479 -2135 (Office)
1- 970 - 376 -0738 (Cell)
mmcgee@vailgov.com
RE: FIRE SPRINKLER PLAN REVIEW DATED 10 -23 -08
Solaris Project at 141 East Meadow Drive
Vail, Colorado
Dear: Mike:
The following is our response to the plan review comments:
1.
The 3" pressure reducing valve should not be shown on the temporary standpipe draN
PRV is because the expansion tanks for the anti - treeze systems require the pressu:
reduced to 125 PSI.
2.
The schedule 40 pipe will be used on pipe sizes 1 thru 2 pipe and the schedule
be used on pipe sizes 2 thru 8 ". The mega tlow pipe will be used in 2 -1/2" thru
sizes only. The series S00 grooved fittings and couplings will be used on all pip(
1" thru 8 ". The lowest pressure rating on the grooved couplings is 300 PSI which I
exceed the system pressure. The threaded titting will be ductile iron tittings in
thru 2 -1/2" and are all rated at 300 PSI.
3.
I pertormed a source calculation which will show how must pressure we can provide
top fire hose valve and that is 119.83 PSI.
Sincerely Yours,
Frontier Fire Protection
Wm. Steve Martin
Vice President
CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE SEVENTY -TWO HOURS IN ADVANCE BY TELEPHONE AT 970 - 479 -2252
FROM 8:00 AM - 5 PM.
ATURE OF OWNEK-OR CONTRACTOR FOR HIMSELF AND OWNER
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
TOWN OF VAIL, COLORADO Statement
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Statement Number: R080002026 Amount: $2,687.50 10/24/200802:09 PM
Payment Method: Check Init: SAB
Notation: 010299 FRONTIER
FIRE PROTECTION
Permit No: F08 -0081 Type: SPRINKLER PERMIT
Parcel No: 2101 - 082 - 0200 -1
Site Address: 2211 N FRONTAGE RD VAIL
Location: 143 E MEADOW DRIVE
Total Fees: $2,687.50
This Payment: $2,687.50 Total ALL Pmts: $2,687.50
Balance: $0.00
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------- - - - - -- ------------------------ - - - - -- ------ - - - - --
BP 00100003111100 SPRINKLER PERMIT FEES 2,337.50
PF 00100003112300 PLAN CHECK FEES 350.00
TOWN OF VE
75 S. Frontage Rd.
Vail, Colorado 81657
T01 M OF VAIL FIRE SPRINKLER PERMIT APPLICATION
Fire Sprinkler shop drawings are required at time of permit submittal and
must include the following. Permit application will not be accepted
without this information:
• A Colorado Registered Engineer's stamp or N.I.C.E.T. Level III (min)
stamp.
• Equipment cut sheets of material
• Hydraulic calculations.
• A State of Colorado Plan Registration form.
• Plans must be submitted by a Registered Fire Protection Contractp!
CONTRACTOR INFORMATION
Fire Sprinkler Contractor: Town of Vail Reg. No.: Contact and Phone #s:
Frontfe_( Rf'e_ flrcte/_+ o f) 1 Vic. Steve_. M a vl 0 ( 3o 3) - ( - L 9 - 022
E-Mail Address: 1 5rn, - jr_hy1 0
Contractor Signature:
J�%
PLETE VALUATIONS FOR ALARM PERMIT (Labor & Materials)
7!
Fire Sprinkler: $
Contact Eagle Count y Office at 970-328-8640 or visit www. eagle us for Parcel #
Parcel# izl0lop,?n jy1&
Job Name: Job Address: 145 avid 14 E, Meadow Pr
Val CC) S1 (p5
Legal Description Lot: f Block: S - Filin Subdivision: a i 1 V F hn,3 I
wners,.Namq: Address: 221 Wci- , fi e- Rol Suite- A Phone:
�Do I a'" C511. prozet Ow 616,,51 970-q 11 -7
F �91 neer: 13CEK Inc, Address: 1542o war,) KA ) 3 422 - 7' Dt)
ArvaAi , CO 80'002- i
Detailed Location of work: (i.e., floor, unit #, bldg. #) 13u1 1,Affn
Detailed description of work: n 7P_
Work Class: New ()() Addition ) Remodel ) Repair ) Retro-fit ( ) Other ( )
[Type ofBIdg.: Single-family( ) Two-family( ) Multi-family( Commercial( ) Restaurant( ) Other (N) Pl
Use-1
No. of Existing Dwelling Units in this building: 0
Does a Fire Alarm Exist: Yes No
hr
11 No. of Accommodation Units in this building: j7
Does a Fire Sprinkler Svstem-ExLst-- Yes( ) f
F: \cd ev\FO RM S \Pe & es\Fi r7e6Vn nkf & perm =1U 19-06.
TOWN OF VAIL
10/19/2006 —
PHONE: (303) 629 -0221
FAX: (303) 623 -7830
517 West Holden Place, Denver, Colorado • 80204
INTIER F =RE PROTECTION xxc.
FIRE PROTECTION ENGINEERS AND CONTRACTORS
October 23, 2008
Mr. Mike McGee, Deputy Chief/Fire Marshal
Town of Vail, Fire and Emergency Services
42 West Meadow Drive
Vail, Colorado 81657
1- 970 - 479 -2135 (Office)
1- 970 - 376 -0738 (Cell)
mmcgeegvaiIgov.com
RE: FIRE SPRINKLER PLAN REVIEW DATED 10 -23 -08
Solaris Project at 141 East Meadow Drive
Vail, Colorado
Dear: Mike:
The following is our response to the plan review comments:
1. The 3" pressure reducing valve should not be shown on the temporary standpipe
drawing. The 3" PRV is because the expansion tanks for the anti - freeze systems
require the pressure to be reduced to 125 PSI.
2. The schedule 40 pipe will be used on pipe sizes 1" thru 2" pipe and the schedule
10 pipe will be used on pipe sizes 2" thru 8 ". The mega flow pipe will be used in
2 -1/2" thru 4" pipe sizes only. The series 500 grooved fittings and couplings will
be used on all pipe sizes from 1" thru 8 ". The lowest pressure rating on the
grooved couplings is 300 PSI which will not exceed the system pressure. The
threaded fitting will be ductile iron fittings in sizes 1" thru 2 -1/2" and are all rated
at 300 PSI.
3. I performed a source calculation which will show how must pressure we can ,
provide you at the top fire hose valve and that is 119.83 PSI.
Sincerely Yours, j
Frontier Fire Protection
s
Wm. Steve Martin
Vice President