HomeMy WebLinkAboutB11-0486 comment letter Date: November 22, 2011 Re: B11-0486 1422 Morraine Dear Mr. Riddle RESPONSE INSTRUCTIONS ● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Architectural Comments: NA Structural Comments: NA Plumbing Comments: 1. Please provide a complete gas piping plan per the Town of Vail submittal requirements showing compliance with section 402.1 IFGC. Mechanical Comments: 1. Show vent termination to be in compliance with the town code: Section 503.6.4 - Gas Vent Terminations: This section is hereby amended with the addition of the following language: Item 8. Gas appliance vent terminations located on the exterior of a building shall have the lowest side of such openings located not less than sixty (60) inches vertically from the adjoining ground or thirty-six (36) inches above the roof. Electrical Comments: 1. Provide carbon monoxide detectors in the home per the IRC. Annotate on the plans PLANNING COMMENTS Awaiting HOA and DRB approval FIRE COMMENTS PUBLIC WORKS COMMENTS Sincerely, Martin A. Haeberle Chief Building Official