HomeMy WebLinkAboutB11-0017 CCD23 plans 11-23-11 Frontage Road Transit Building 01 June 2011 Page 1 A 23 November 2011 Mr. Martin Haeberle Mr. Tom Kassmel Chief Building Official Town Engineer Department of Community Development Town of Vail Public Works 5 South Frontage Road 1309 Elkhorn Drive Vail, Colorado 81657 Vail, CO 81657 Chief Mike McGee, Deputy Chief & Mr. Warren Campbell Chief Mike Vaughan, Fire Marshall Chief of Planning Town of Vail Fire Department Department of Community Development 42 W. Meadow Drive 5 South Frontage Road Vail, CO 81657 Vail, Colorado 81657 Lionshead Transit Welcome Center Permit Application # B11-0017 Dear Sirs Attached are revisions to the level 2 kitchen that incorporate a oven/range and a exhaust hood with fan. The cabinetry in the kitchen as been revised to accommodate the new equipment. Also included in this submittion are a few structural sketches generated due to field conditions. These sketches have been included on S621 (attached) Attached. A820, A822, M001, M102, M103, M201, M202, M400, M500, E102, E400, S621 Please contact me with any additional comments or questions. Best Regards, Tracy Hart LEED AP Senior Associate <cc: Tom Kassmel/Town of Vail E. Randal Johnson/4240 21064.20/3.2 Attachment TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ Martin 12/08/2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ AIR COOLED CONDENSING UNIT SCHEDULE EXHAUST FAN SCHEDULE BOILER SCHEDULE MISCELLANEOUS MECHANICAL EQUIPMENT SCHEDULE HEAT RECOVERY VENTILATOR FAN COIL SCHEDULE (HYDRONIC HEAT/DX COOLING) WATER HEATER SCHEDULE (ELECTRIC) COPYRIGHT 2010 BGANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 M001 MECHANICAL SCHEDULES 3 ADDENDUM 1 02.18.2011 4 ADDENDUM 2 03.02.2011 -CCD 11 07.08.2011 -CCD 23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ 1.2 1.3 2.2 2.3 2.4 2.5 2.6 2.9 2.11 1.1 2.1 2.8 2.10 AA BB A 2.12 2.13 B 2.7 1.4 SCALE: HVAC LEVEL 02 1/8" = 1'-0" FLAG NOTES: NOTES: COPYRIGHT 2010 B GANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 M102 HVAC LEVEL 02 PLAN 3 ADDENDUM 1 02.18.2011 4 ADDENDUM 2 03.02.2011 7 B.D. RESPONSES 04.11.2011 10 CCD 03 05.16.2011 -CCD 16 10.03.2011 -CCD 23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ 1.2 1.3 2.2 2.3 2.4 2.5 2.6 2.9 2.11 1.1 2.1 2.8 2.10 AA BB A 2.12 B 2.7 1.4 SCALE: HVAC LEVEL 03 1/8" = 1'-0" FLAG NOTES: NOTES: COPYRIGHT 2010 B GANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 M103 HVAC LEVEL 03 PLAN 3 ADDENDUM 1 02.18.2011 4 ADDENDUM 2 03.02.2011 7 B.D. RESPONSES 04.11.2011 8 CCD02 04.25.2011 10 CCD 03 05.16.2011 -CCD 23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ 1.2 1.3 2.2 2.3 2.4 2.5 2.6 2.9 2.11 1.1 2.1 2.8 2.10 AA BB A A.5 2.12 2.13 B 2.7 SCALE: 1 PLUMBING LEVEL 01 1/8" = 1'-0" FLAG NOTES: NOTES: SCALE: 2 WASTE/VENT ISOMETRIC NONE MAIN LEVEL PUBLIC RESTROOMS COPYRIGHT 2010 B GANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 M201 PLUMBING LEVEL 01 PLAN 3 ADDENDUM 1 02.18.2011 4 ADDENDUM 2 03.02.2011 7 B.D. RESPONSES 04.11.2011 -CCD 7 06.03.2011 -CCD 11 07.08.2011 -CCD 12 07.08.2011 20 CCD 17 09.30.2011 -CCD 23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ 1.2 1.3 2.2 2.3 2.4 2.5 2.6 2.9 2.11 1.1 2.1 2.8 2.10 AA BB A 2.12 2.13 B 2.7 1.4 SCALE: 1 PLUMBING LEVEL 02 1/8" = 1'-0" FLAG NOTES: NOTES: SCALE: 2 RESTROOMS WASTE/VENT ISOMETIC NONE SECOND LEVEL INDIVIDUAL COPYRIGHT 2010 B GANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 M202 PLUMBING LEVEL 02 PLAN 3 ADDENDUM 1 02.18.2011 7 B.D. RESPONSES 04.11.2011 -CCD 23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ CLEANOUT DIAGRAMS NO SCALE ISLAND VENT DIAGRAM NO SCALE DRAIN THRU WALL DIAGRAM SANITARY OR STORM BLDG. NO SCALE WALL CLEANOUT DIAGRAM NO SCALE PIPE THRU ROOF DIAGRAM NO SCALE DIAGRAM TRAP PRIMER CONNECTION NO SCALE F ZONE HEATING COIL ASS'Y DIAGRAM NO SCALE RADIANT/SNOWMELT MANIFOLD PIPING DIAGRAM NO SCALE HJ D C E B G DOMESTIC WATER ENTRANCE DIAGRAM NO SCALE A COIL ASS'Y DIAGRAM ZONE HEATING NO SCALE K GAS PIPING ONE-LINE NO SCALE L HEAT TAPE DIAGRAM NO SCALE M NO SCALE GREASE EXHAUST FAN AN DUCT DIAGRAM N COPYRIGHT 2010 BGANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 M400 MECHANICAL DIAGRAMS 4 ADDENDUM 2 03.02.2011 -CCD 23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ GENERAL CONTROLS NOTES: SCALE: 1 CONTROL SYSTEM ARCHITECTURE (BACNET) NONE SCALE: 3 CUH AND UH CONTROL SCHEMATIC NO SCALE SCALE: 2 DOMESTIC WATER HEATER PIPING DIAGRAM NONE SCALE: 7 VENTILATOR CONTROLS SCHEMATIC NO SCALE HEAT RECOVERY SCALE: 4 THERMOSTAT CONTROL SCHEMATIC NONE EXHAUST FAN SCALE: 5 OCCUPANCY SENSOR SCHEMATIC NO SCALE EXHAUST FAN SCALE: 6 WALL SWITCH CONTROL SCHEMATIC NO SCALE EXHAUST FAN SYSTEM POINTS LIST ANALOG BINARY SYSTEM FEATURE INPUT OUTPUT INPUT OUTPUT ALARMS PROGRAMS SYSTEM POINT DESCRIPTION GRAPHIC SCREEN ANIMATED POINT ON GRAPHIC TEMPERATURE PRESSURE RELATIVE HUMIDITY KW KWH BTU HR GPM PERCENT CFM DDC (4-20 ma, 0-10 vdc) STATUS STATUS ON/OFF FILTER STATUS STATUS OPEN/CLSD. TIMED OVERRIDE STOP/START OPEN/CLOSED LOCK OUT ENABLE/DISABLE HIGH/LOW SPEED FLOATING CONTROL HIGH OR LOW VALUE OUT OF RANGE STATUS DIFF. FROM CMD TREND VALUE TREND STATUS LEAD/LAG ROTATIONALLY SEQUNCE NOTES DHW CV x GENERAL NOTES: SCALE: 8 PUMP CONTROL SCHEMATIC NO SCALE ELEVATOR SHAFT SUMP x DHW AQUASTAT x x x x x DHW TEMP x x x x DHW RECIRC TEMP x x x x DHW RECIRC PUMP START/STOP x x DHW RECIRC PUMP STATUS x x x HRV DUCT COIL CONTROL VALVE x x HRV DUCT COIL DISCHARGE AIR TEMP x x x x HRV STATUS x x x HRV START/STOPx x HRV DUCT COIL PUMP STATUS x x HRV DUCT COIL PUMP START/STOPx x SCALE: 9 HEATER CONTROL SCHEMATIC NO SCALE ELEVATOR SHAFT SUMP SCALE: 10 HEATER CONTROL SCHEMATIC NO SCALE ELEVATOR SHAFT SUMP SCALE: 11CONTROLS SCHEMATIC NO SCALE GREASE EXHAUST FAN FAN STATUS x x x COPYRIGHT 2010 B GANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 M500 MECHANICAL CONTROLS 3 ADDENDUM 1 02.18.2011 7 B.D. RESPONSES 04.11.2011 -CCD 23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ SCALE: LEVEL 02 ELECTRICAL PLAN 1/8" = 1'-0" FLAG NOTES: 1.2 1.3 2.2 2.3 2.4 2.5 2.6 2.9 2.11 1.1 2.1 2.8 2.10 AA BB A 2.12 2.13 B 2.7 1.4 NOTES: COPYRIGHT 2010 B GANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 E102 POWER LEVEL 02 PLAN 3 ADDENDUM 1 02.18.2011 4 ADDENDUM 2 03.02.2011 7 B.D. RESPONSES 04.11.2011 -CCD 16 10.03.2011 CCD #23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ SCALE: 1 ELECTRICAL ONE-LINE DIAGRAM NONE 􀑐􀀃, SCALE: 2 PV ONE-LINE DIAGRAM (BID ALTERNATE) NONE WIRING SCHEDULE -COPPER AMPS (2WG) (3WG) (4WG) 1Ø, 2 WIRE, GROUND 1Ø, 3 WIRE, GROUND OR 3Ø, 3 WIRE, GROUND 3Ø, 4 WIRE, GROUND 20 (2#12 & 1#12 G) 3/4"C (3#12 & 1#12 G) 3/4"C (4#12 & 1#12 G) 3/4"C 30 (2#10 & 1#10 G) 3/4"C (3#10 & 1#10 G) 3/4"C (4#10 & 1#10 G) 3/4"C 40 (2#8 & 1#10 G) 3/4"C (3#8 & 1#10 G) 3/4"C (4#8 & 1#10 G) 1"C 50 (2#6 & 1#10 G) 3/4"C (3#6 & 1#10 G) 1"C (4#6 & 1#10 G) 1"C 60 (2#4 & 1#10 G) 1"C (3#4 & 1#10 G) 1"C (4#4 & 1#10 G) 1 1/4"C 70 (2#4 & 1#8 G) 1"C (3#4 & 1#8 G) 1 1/4"C (4#4 & 1#8 G) 1 1/4"C 80 (2#2 & 1#8 G) 1"C (3#2 & 1#8 G) 1 1/4"C (4#2 & 1#8 G) 1 1/2"C 90 (2#2 & 1#8 G) 1"C (3#2 & 1#8 G) 1 1/4"C (4#2 & 1#8 G) 1 1/2"C 100 (2#1 & 1#8 G) 1 1/4"C (3#1 & 1#8 G) 1 1/2"C (4#1 & 1#8 G) 1 1/2"C 110 (2#1 & 1#6 G) 1 1/4"C (3#1 & 1#6 G) 1 1/2"C (4#1 & 1#6 G) 1 1/2"C 125 (2#1 & 1#6 G) 1 1/4"C (3#1 & 1#6 G) 1 1/2"C (4#1 & 1#6 G) 1 1/2"C 150 (2#1/0 & 1#6 G) 1 1/4"C (3#1/0 & 1#6 G) 1 1/2"C (4#1/0 & 1#6 G) 2"C 175 (2#2/0 & 1#6 G) 1 1/2"C (3#2/0 & 1#6 G) 2"C (4#2/0 & 1#6 G) 2"C 200 (2#3/0 & 1#6 G) 1 1/2"C (3#3/0 & 1#6 G) 2"C (4#3/0 & 1#6 G) 2"C 225 (2#4/0 & 1#4 G) 2"C (3#4/0 & 1#4 G) 2"C (4#4/0 & 1#4 G) 2 1/2"C 250 (2-250 KCMIL & 1#4 G) 2"C (3-250 KCMIL & 1#4 G) 2 1/2"C (4-250 KCMIL & 1#4 G) 3"C 300 (2-350 KCMIL & 1#4 G) 2"C (3-350 KCMIL & 1#4 G) 3"C (4-350 KCMIL & 1#4 G) 3"C 380 (2-500 KCMIL & 1#3 G) 2 1/2"C (3-500 KCMIL & 1#3 G) 3"C (4-500 KCMIL & 1#3 G) 3 1/2"C 400 2[(2#3/0 & 1#3 G) 1 1/2"C] 2[(3#3/0 & 1#3 G) 2"C] 2[(4#3/0 & 1#3 G) 2 1/2"C] 450 2[(2#4/0 & 1#2 G) 2"C] 2[(3#4/0 & 1#2 G) 2"C] 2[(4#4/0 & 1#2 G) 2 1/2"C] 500 2[(2-250 KCMIL & 1#2 G) 2"C] 2[(3-250 KCMIL & 1#2 G) 2 1/2"C] 2[(4-250 KCMIL & 1#2 G) 3"C] 600 2[(2-350 KCMIL & 1#1 G) 2 1/2"C] 2[(3-350 KCMIL & 1#1 G) 3"C] 2[(4-350 KCMIL & 1#1 G) 3"C] 700 2[(2-500 KCMIL & 1#1/0 G) 2 1/2"C] 2[(3-500 KCMIL & 1#1/0 G) 3"C] 2[(4-500 KCMIL & 1#1/0 G) 3 1/2"C] 760 2[(2-500 KCMIL & 1#1/0 G) 2 1/2"C] 2[(3-500 KCMIL & 1#1/0 G) 3"C] 2[(4-500 KCMIL & 1#1/0 G) 3 1/2"2"C] 800 3[(2-300 KCMIL & 1#1/0 G) 2"C] 3[(3-300 KCMIL & 1#1/0 G) 2 1/2"C] 3[(4-300 KCMIL & 1#1/0 G) 3"C] CONDUCTOR SIZES ARE BASED ON 60°C TERMINATIONS LESS THAN 100A AND 75°C TERMINATIONS GREATER THAN 100A CONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION). DISTRIBUTION PANEL: VOLTAGE: 277/480V, 3PH, 4W MDP MINIMUM BUS: 600 LOCATION: MAIN: MLO MOUNTING: MINIMUM AIC: SURFACE 22,000 PANELS/RISERS MOTORS/EQUIPMENT PANEL MARK: HP1 XFMR SPACE ELEV-1 ELEV-2 SPACE SUBTOTAL DEMAND PANEL TOTAL OCPD: 125/3 CB 225/3 CB 60/3 CB 60/3 CB RESIDENTIAL 100% 0 LIGHTING 0 30740 30740 125% 38425 RECEPTACLES 0 6192 6192 NEC 220 6192 LARGEST MOTOR 33240 33240 25% 8310 MOTORS 0 45288 33240 33240 145008 100% 145008 EQUIPMENT 19000 38330 57330 100% 57330 APPLIANCES 0 7200 7200 0 7200 PANEL TOTAL (KVA): 262.5 PANEL TOTAL (A): 316 PANEL: HP1 VOLTAGE: 277/480V, 3PH, 4W MINIMUM BUS: 125 LOCATION: ROOM 311 MAIN: MLO MOUNTING: SURFACE MINIMUM AIC: 14,000 NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO. A B C POLE TRIP A B C TRIP POLE A B C 1 2400 E HEAT TRACE (1) 1 30 + SPACE 2 3 2100 E HEAT TRACE (1) 1 30 + SPACE 4 5 2400 E HEAT TRACE (1) 1 30 + SPACE 6 7 2100 E HEAT TRACE (1) 1 30 + SPACE 8 9 2100 E HEAT TRACE (1) 1 30 + SPACE 10 11 1200 E HEAT TRACE (1) 1 30 + SPACE 12 13 SPARE 1 30 + SPACE 14 15 2100 E HEAT TRACE (1) 1 30 + SPACE 16 17 3000 E HEAT TRACE (1) 1 30 + SPACE 18 19 1600 E HEAT TRACE (1) 1 30 + 21 SPACE 20 21 900 HEAT TRACE (1) 1 30 + SPACE 22 23 SPACE + SPACE 24 LOAD TYPE PANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES: A. (L) LIGHTING 0 0 125% 0 B. (R) RECEPTACLES 0 0 NEC 220 0 C. (LM) LARGEST MOTOR 0 0 25% 0 D. (M) MOTORS (ALL) 0 0 100% 0 E. (E) EQUIPMENT 19000 19000 100% 19000 SPECIFIC NOTES: (A) APPLIANCES 0 0 0 0 (1) PROVIDE 30MA TRIP GFE CIRCUIT BREAKER PANEL TOTAL (KVA): 19.0 (2) (3) PANEL TOTAL (A): 23 (4) (5) PANEL: LP1A VOLTAGE: 120/208V, 3PH, 4W MINIMUM BUS: 400 LOCATION: ELEC ROOM 111 MAIN: 400/3 CB MOUNTING: SURFACE MINIMUM AIC: 10,000 NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO. A B C POLE TRIP A B C TRIP POLE A B C 1 540 R RESTROOM RECEPT 1 20 + 20 1 E FACP 750 2 3 1500 E HAND DRYER 116 1 20 + 20 1 E FIREPLACE 100 4 5 1500 E HAND DRYER 115 1 20 + 20 1 E VENDING (1) 1200 6 7 1500 E HAND DRYER 117 1 20 + 20 1 E VENDING (1) 1200 8 9 300 E PLUMBING PWR 1 20 + 20 1 E MECH CONTROLS 250 10 11 1080 R CORR & WAITING 109 1 20 + 20 1 L 1ST FLR LIGHTING 881 12 13 1080 R WAITING 109 1 20 + 20 1 L 1ST FLR LIGHTING 676 14 15 1080 R 107,103 1 20 + 20 1 L 1ST FLR LIGHTING 776 16 17 1080 R LOBBY 1 20 + 20 1 L 1ST FLR LIGHTING 793 18 19 1080 R 105, 104 1 20 + 20 1 E IRRIGATION CONTROLS 250 20 21 500 R IT ROOM 129 1 20 + 20 1 L EAST STAIR LTG. 427 22 23 500 R IT ROOM 105 1 20 + 20 2 L EXTERIOR LIGHTING 626 24 25 500 M ADA DOOR OPERATOR 1 20 + L 626 26 27 360 R ELEV PIT 1 20 + 20 1 L EXTERIOR LIGHTING 1080 28 29 500 R ELEV CAB 1 20 + 20 1 L EXTERIOR LIGHTING 1120 30 31 360 R ATM, PARK-N-PAY 1 20 + + 20 1 L EXTERIOR LIGHTING 846 32 33 900 R STORAGE AREAS 1 20 + 20 1 L EXTERIOR LIGHTING 352 34 35 100 M FIRE SMOKE DAMPERS 1 20 + 20 1 L EXTERIOR LIGHTING 652 36 37 200 M DAMPERS 1 20 + 20 1 L EXTERIOR LIGHTING 1500 38 39 180 R ELEC ROOM 111 1 20 + 20 1 L EXTERIOR LIGHTING 672 40 41 720 R EXT RECEPT 1 20 + 20 1 L EXTERIOR LIGHTING 425 42 LOAD TYPE PANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES: A. PROVIDE 250 AMP SUB-FEED BREAKER TO LP2 (L) LIGHTING 11452 8444 19896 125% 24870 B. PROVIDE 150 AMP SUB-FEED BREAKER TO LP1B (R) RECEPTACLES 9960 20780 30740 NEC 220 20370 C. (LM) LARGEST MOTOR 0 6192 6192 25% 1548 D. (M) MOTORS (ALL) 800 44488 45288 100% 45288 E. (E) EQUIPMENT 8550 28780 37330 100% 37330 SPECIFIC NOTES: (A) APPLIANCES 0 7200 7200 0 7200 (1) PROVIDE 5MA TRIP GFCI CIRCUIT BREAKER PANEL TOTAL (KVA): 136.6 (2) (3) PANEL TOTAL (A): 379 (4) (5) PANEL: LP1B VOLTAGE: 120/208V, 3PH, 4W MINIMUM BUS: 225 LOCATION: ELECT. RM 111 MAIN: MLO MOUNTING: SURFACE MINIMUM AIC: 10,000 NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO. A B C POLE TRIP A B C TRIP POLE A B C 1 750 R SPECIAL EVENT RECEPT. 1 20 + 15 3 M FC-1 576 2 3 750 R SPECIAL EVENT RECEPT. 1 20 + M 576 4 5 750 R SPECIAL EVENT RECEPT. 1 20 + M 576 6 7 750 R SPECIAL EVENT RECEPT. 1 20 + 30 3 LM CU-1 2064 8 9 750 R SPECIAL EVENT RECEPT. 1 20 + LM 2064 10 11 750 R SPECIAL EVENT RECEPT. 1 20 + LM 2064 12 13 800 L HOLIDAY RECEPT. 1 20 + 30 1 M HRV-1 2300 14 15 1200 L HOLIDAY RECEPT. 1 20 + 15 1 E B-1 500 16 17 250 E UNIT HEATERS, UH-1 1 10 + 20 1 E INFO CENTER TELECOM 500 18 19 480 E CABINET UNIT HEATERS 1 15 + 20 2 E WH-2 1000 20 21 480 E CABINET UNIT HEATERS 1 15 + E 1000 22 23 1176 M P-9 1 20 + 20 1 M P-1 1176 24 25 720 EXT. RECEPTACLES 1 20 + 20 1 M P-1 1176 26 27 180 R RESTROOM 131 1 20 + 20 1 M P-1 1176 28 29 1600 HOLIDAY RECEPT. 1 20 + 15 3 M P-2 444 30 31 360 R HOST SKII STORAGE 1 20 + M 444 32 33 500 E ADA DOOR OPERATOR 2 20 + M 444 34 35 85 M P-8 1 10 + 15 3 M P-2 444 36 37 1176 M P-7 1 20 + M 444 38 39 1176 M P-4 1 20 + M 444 40 41 85 M P-3 1 10 + SPACE 42 LOAD TYPE PANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES: A. FEED THROUGH LUGS (L) LIGHTING 2000 0 2000 125% 2500 B. (R) RECEPTACLES 5040 0 5040 NEC 220 5040 C. (LM) LARGEST MOTOR 6192 0 6192 25% 1548 D. (M) MOTORS (ALL) 20110 0 20110 100% 20110 E. (E) EQUIPMENT 4710 1000 5710 100% 5710 SPECIFIC NOTES: (A) APPLIANCES 0 0 0 0 0 (1) PANEL TOTAL (KVA): 34.9 (2) (3) PANEL TOTAL (A): 97 (4) (5) PANEL: LP2 (SECTION 1) VOLTAGE: 120/208V, 3PH, 4W MINIMUM BUS: 250 LOCATION: IT/ELECT. RM. #210 MAIN: MLO MOUNTING: SURFACE MINIMUM AIC: 10,000 NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO. A B C POLE TRIP A B C TRIP POLE A B C 1 360 R IT 210 1 20 + 20 1 R 213 900 2 3 360 R IT 210 1 20 + 20 1 R 213,212 900 4 5 360 R KITCHEN 209, STORAGE 1 20 + 20 1 R 201 720 6 7 540 R MECH 211 1 20 + 20 1 R 201 720 8 9 200 M DAMPERS 1 20 + 20 1 R MECH 202 REC. UH-1 800 10 11 100 E PLUMBING CONTROLS 1 20 + 20 1 E MECH CONTROLS 250 12 13 1500 E HAND DRYER 207 1 20 + 20 1 L 2ND FLR. LIGHTING 793 14 15 1500 E HAND DRYER 208 1 20 + 20 1 L 2ND FLR. LIGHTING 707 16 17 250 M FIRE SMOKE DAMPER 1 20 + 20 1 L 2ND FLR. LIGHTING 1222 18 19 360 R COUNTER 209 1 20 + 15 3 M FC-2 828 20 21 360 R COUNTER 209 1 20 + M 828 22 23 1000 A DISPOSAL 209 1 20 + M 828 24 25 1200 A REFER 209 1 20 + 15 3 M FC-3 576 26 27 3840 E KILN 209 3 40 + M 576 28 29 3840 E + M 576 30 31 3840 E + 25 3 M CU-2 1718 32 33 900 R OFFICE 205 1 20 + M 1718 34 35 900 R OFFICE 204 1 20 + M 1718 36 37 1260 R OFFICE 203 1 20 + 30 3 LM CU-3 2064 38 39 900 R OFFICE 206 1 20 + LM 2064 40 41 SPARE 1 20 + LM 2064 42 LOAD TYPE PANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES: A. PROVIDE FEED-THRU LUGS. (L) LIGHTING 2722 3722 6444 125% 8055 B. 2-SECTION PANELBOARD. SECTION 2 SPACE ONLY. (R) RECEPTACLES 10340 5400 15740 NEC 220 12870 C. (LM) LARGEST MOTOR 6192 0 6192 25% 1548 D. (M) MOTORS (ALL) 16008 8370 24378 100% 24378 E. (E) EQUIPMENT 14870 9200 24070 100% 24070 SPECIFIC NOTES: (A) APPLIANCES 2200 5000 7200 0 7200 (1) PANEL TOTAL (KVA): 78.1 (2) (3) PANEL TOTAL (A): 217 (4) (5) PANEL: LP3 VOLTAGE: 120/208V, 3PH, 4W MINIMUM BUS: 250 LOCATION: STORAGE 311 MAIN: MLO MOUNTING: SURFACE MINIMUM AIC: 10,000 NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO. A B C POLE TRIP A B C TRIP POLE A B C 1 180 R STORAGE 311 1 20 + 20 1 R PANTRY 309 540 2 3 900 R WALL 308 1 20 + 20 1 R PANTRY 309 540 4 5 1260 R FLOOR 308 1 20 + 20 1 E ICE MACHING 309 1500 6 7 360 R IT 1 20 + 20 1 M FIRE SMOKE DAMPER 250 8 9 360 R IT 1 20 + 20 1 MECH CONTROLS 10 11 200 M DAMPERS 1 20 + 20 1 L EVENT RM LIGHTING 640 12 13 1500 E HAND DRYER 304 1 20 + 20 1 L EVENT RM LIGHTING 640 14 15 1500 E HAND DRYER 304 1 20 + 20 1 L EVENT RM LIGHTING 960 16 17 1500 E HAND DRYER 303 1 20 + 20 1 L EVENT RM LIGHTING 650 18 19 1500 E HAND DRYER 303 1 20 + 20 1 L CATEREING PANTRY LTG 293 20 21 200 E PLUMBING 1 20 + 20 1 L 3RD FLR. LIGHTING 539 22 23 180 R BATH 304 1 20 + 15 3 M FC-4 576 24 25 180 R BATH 303 1 20 + M 576 26 27 180 R JANITOR 305 1 20 + M 576 28 29 720 R VESTIBULE 301 1 20 + 15 3 M CU-4 2064 30 31 2500 A ROLL-IN 2 30 + M 2064 32 33 2500 A + M 2064 34 35 1000 E MOTORIZED SHADES 1 20 + 20 1 HRV-2 972 36 37 500 E AUTO DOOR OPERATOR 1 20 + 15 1 P-8, CUH, UH 615 38 39 SPARE 1 20 + SPARE 40 41 SPARE + SPARE 42 LOAD TYPE PANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES: A. PROVIDE FEED THROUGH LUGS (L) LIGHTING 3722 3722 125% 4653 B. (R) RECEPTACLES 5400 5400 NEC 220 5400 C. (LM) LARGEST MOTOR 0 0 25% 0 D. (M) MOTORS (ALL) 8370 8370 100% 8370 E. (E) EQUIPMENT 9200 9200 100% 9200 SPECIFIC NOTES: (A) APPLIANCES 5000 5000 0 5000 (1) PANEL TOTAL (KVA): 32.6 (2) (3) PANEL TOTAL (A): 91 (4) (5) PANEL: LP2 (SECTION 2) VOLTAGE: 120/208V, 3PH, 4W MINIMUM BUS: 250 LOCATION: IT/ELECT. RM. #210 MAIN: MLO MOUNTING: SURFACE MINIMUM AIC: 10,000 NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO. A B C POLE TRIP A B C TRIP POLE A B C 43 500 E AUTO DOOR OPERATOR 20 1 + SPACE 44 45 4000 RANGE 40 2 + SPACE 46 47 4000 + SPACE 48 49 500 ANSIL SYSTEM (1) 20 1 + SPACE 50 51 + SPACE 52 53 500 HOOD POWER 20 1 + SPACE 54 55 935 HOOD FAN 20 1 + SPACE 56 57 SPACE + SPACE 58 59 SPACE + SPACE 60 61 SPACE + SPACE 62 63 SPACE + SPACE 64 65 SPACE + SPACE 66 67 SPACE + SPACE 68 69 SPACE + SPACE 70 71 SPACE + SPACE 72 73 SPACE + SPACE 74 75 SPACE + SPACE 76 77 SPACE + SPACE 78 79 SPACE + SPACE 80 81 SPACE + SPACE 82 83 SPACE + SPACE 84 LOAD TYPE PANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES: A. (L) LIGHTING 0 0 125% 0 B. (R) RECEPTACLES 0 0 NEC 220 0 C. (LM) LARGEST MOTOR 0 0 25% 0 D. (M) MOTORS (ALL) 0 0 100% 0 E. (E) EQUIPMENT 500 500 100% 500 SPECIFIC NOTES: (A) APPLIANCES 0 0 0 0 (1) SHUNT TRIP BREAKER PANEL TOTAL (KVA): 0.5 (2) (3) PANEL TOTAL (A): 1 (4) (5) NOTES: PANEL: LP1C VOLTAGE: 120/208V, 3PH, 4W MINIMUM BUS: 225 LOCATION: ELECT. RM 111 MAIN: MLO MOUNTING: SURFACE MINIMUM AIC: 10,000 NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO. A B C POLE TRIP A B C TRIP POLE A B C 1 1000 E FIREPLACE VENT 1 20 + 2 3 500 L WAITING DISPLAY 1 20 + 4 5 SPARE 1 20 + 6 7 SPARE 1 20 + 8 9 SPARE 1 20 + 10 11 SPARE 1 20 + 12 13 SPARE 1 20 + 14 15 + 16 17 + 18 19 + 20 21 + 22 23 + 24 25 + 26 27 + 28 29 + 30 31 + 32 33 + 34 35 + 36 37 + 38 39 + 40 41 + 42 LOAD TYPE PANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES: A. (L) LIGHTING 500 500 125% 625 B. (R) RECEPTACLES 0 0 NEC 220 0 C. (LM) LARGEST MOTOR 0 0 25% 0 D. (M) MOTORS (ALL) 0 0 100% 0 E. (E) EQUIPMENT 1000 1000 100% 1000 SPECIFIC NOTES: (A) APPLIANCES 0 0 0 0 (1) PANEL TOTAL (KVA): 1.6 (2) (3) PANEL TOTAL (A): 5 (4) (5) FLAG NOTES: COPYRIGHT 2010 B GANZE EAUDIN (970) 949-6108 (530) 550-7334 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Lake Tahoe: Denver: Fort Collins: Albuquerque: www.bgce.com ISS. # ARCHITECT'S PROJECT NO. : KEY PLAN DESCRIPTION DATE 21064.04 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 copyright 2010 f: 303.292.3113 VAIL, COLORADO TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 ALPINE ENGINEERING INC. 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER PEAK LAND CONSULTING , INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR MARTIN/MARTIN, INC. 12499 WEST COLFAX AVE. LAKEWOOD, CO 80215 STRUCTURAL ENGINEER BEAUDIN GANZE CONSULTING ENGINEERS, INC. 222 CHAPEL PLACE UNIT AC-201 AVON, CO 81620 MEP ENGINEER t: 970.479.2158 t: 970.926.3373 f:970-926-3390 t: 970.476.8644 t: 303.431.6100 t: 970.949.6108 LIONSHEAD TRANSIT WELCOME CENTER MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 2 CONSTRUCTION 02.18.2011 E400 ELECTRICAL ONE-LINE DIAGRAM 3 ADDENDUM 1 02.18.2011 4 ADDENDUM 2 03.02.2011 7 B.D. RESPONSES 04.11.2011 CCD #23 11.16.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________ 4" LOCKDECK L4x4x1/4xCONT 2" Pd=70plf Ps=500plf 3/8"Øx0'-2 1/2 LAG SCREW AT EA PIECE OF DECKING EMBED PLATE BY PRECASTER (DFS) @24"OC 5" ±1" ROOF SHEATHING SST LS 90 @12"OC, TYP ENTIRE LENGTH OF 2x12, ES OF 2x12 BEYOND WALL 1/2"Øx0'-6 SCREW ANCHORS @16"OC (8"OC @SIM) CONT PT 2x12. SEE PLAN FOR EXTENTS. 1/4 4 1/4 4 BUILDING FELT Pw=160plf 8 VERT SLIP CONN BY WINDOW SUPPLIER (DFS) 600S162-54xCONT (2)600T150-54xCONT #10 SCREWS @8"OC S541 10 DOWNSPOUT, SEE ARCH. MAX Ø=6". CENTER ON T&G DECKING. DO NOT INSTALL IN ADJACENT PIECES OF T&G DECKING. L3x3x1/4x1'-0 ES OF DOWNSPOUT. NOTE: ANGLES ARE ABOVE T&G DECKING. 1/2"Øx0'-2 1/2 LAG SCREWS CENTERED ON EA PIECE OF DECKING 8 2.2 TSN VERTICLIP SLD362 @EA STUD W/(2)#8 SCREWS INTO CLIP AND (3)#12 WOOD SCREWS INTO T&G DECKING. DO NOT ATTACH TO TIMBER TRUSS FOR DETAILS NOT NOTED, SEE S600 10 PRECAST DT (DFS) SEE PLAN EMBED PL BY PRECASTER (DFS) TOPPING SLAB TOPC Pd = 4.1k Ps = 14.8k PRECAST IT (DFS) Pw = 1.2k FOR DETAILS NOT NOTED, SEE S600 10 PRECAST DT (DFS) SEE PLAN EMBED PL BY PRECASTER (DFS) TOPPING SLAB TOPC Pd = 5.4k Ps = 17.9k PRECAST IT (DFS) Pw = 2.2k 16d TOE-NAILS @6", TYP AT NON-SNOWGUARD LVL'S AND AT BLOCKING (1)2x LVL @16" WHERE OUTSIDE REGION OF SNOWGUARDS. RIP TO ACHIEVE RIDGE ELEVATION AT TOP OF ROOFING. SEE ARCH. 12 S620 (2)2x LVL'S CENTRED ABOUT SNOWGUARD. RIP TO ACHIEVE RIDGE ELEVATION AT TOP OF ROOFING. SEE ARCH. ROOF SHEATHING. FOR ATTACHMENT, SEE S620 2 S620 11 FOR INFO NOT SHOWN 16d TOE-NAILS @6", TYP TO BLOCKING 5/8" SHEATHING 10d NAILS @4" SOLID 2x BLOCKING BTWEN LVL'S @48" 4" 4" MIN 8" (6)5/8"Ø HILTI KWIK BOLT TZ EXP BOLTS (4" EMBED). GA=4". 6 S622 (9)5/8"Ø HILTI KWIK BOLT TZ EXP BOLTS (4" EMBED). GA=4". 2" 4" 4" PL 3/8x8x2'-6 MC10x22x1'-0 3/16 PL 1/2x8x1'-4, ES PL 3/8x3x2'-6 1/4 2-8 6" EA 1/4 2-8 END PL 1x6x0'-3 1/4 TYP ES FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION 1/4 2" 1/4 2" PL 7/8x4x0'-8 (MIN) L5x5x1/2 1/4 (2) 5/8"Ø THRU-BOLTS W/1/2x4x0'-4 WASHER PLS (6" GAGE) 3 1/2" FOR INFORMATION NOT SHOWN, SEE S611 8 OWNER 4240 ARCHITECTURE INC 3003 LARIMER STREET DENVER, CO 80205 ARCHITECT t: 303.292.3388 ISS. # 4240 Architecture Inc. copyright 2011 ARCHITECT'S PROJECT NO. : KEY PLAN f: 303.292.3113 DESCRIPTION DATE ALPINE ENGINEERING INC 34510 U.S. 6 UNIT A9 EDWARDS, CO 81632 CIVIL ENGINEER t: 970.926.3373 f: 970.926.3390 MM JOB #: PRINCIPAL: EOR: PROJECT MANAGER: DESIGNERS: DATE PRINTED: MARTIN /MARTIN 12499 W. COLFAX AVE LAKEWOOD, CO 80215 STRUCTURAL ENGINEER t: 303.431.6100 f: 303.431.6866 PEAK LAND CONSULTING, INC. 1000 LIONSRIDGE LOOP VAIL, CO 81675 SURVEYOR t: 970.476.8644 BEAUDIN GANZE CONSULTING ENGINEERS, INC. 110 E. BEAVER CREEK SUITE 202 AVON, CO 81620 MEP ENGINEER t: 970.949.6108 TOWN OF VAIL DEPARTMENT OF PUBLIC WORKS 1309 ELKHORN DRIVE VAIL, CO 81632 t: 970.479.2158 21064.04 MARY HART DESIGN POST OFFICE BOX 8528 BRECKENRIDGE, CO 80424 LANDSCAPE ARCHITECT t: 970.389.3583 11.18.2011 395 East Lionshead Circle VAIL, COLORADO 81657 11/18/2011 2:28:01 PM C:\Users\EricS\Desktop\ESobel documents\ERS Revit Models (local)\21615.S.05 AUX BUILDING-ers.rvt S621 TYP TIMBER DETAILS LIONSHEAD TRANSIT WELCOME CENTER ERIC SOBEL ERIC SOBEL MIKE McAFFREY 21615.S.05 MIKE McAFFREY 5 1 1/2" = 1'-0" WOOD DIAPHRAGM CONN AT ELEV 3 1 1/2" = 1'-0" NORTH WALL CLERESTORY 1 NO SCALE TYP FRAMING @DOWNSPOUT 3 2 1 1/2" = 1'-0" LT-GA FRAMING ON GRID 2.2 4 44 7 1 1/2" = 1'-0" TIMBER COL BASE CONNECTION -IT 7 8 1 1/2" = 1'-0" TIMBER COL BASE CONNECTION -LB 7 8 6 NO SCALE TYP OVER-BUILD @ELEVATOR BREEZEWAY RFI #079 9 1 1/2" = 1'-0" GLULAM BEAM TO PC WALL (RFI #104) RFI #104 4 NO SCALE EXT TRUSS -END CONN (RFI #114) RFI #114 2 CONSTRUCTION 02.04.2011 3 ADDENDUM #1 02.18.2011 4 ADDENDUM #2 03.02.2011 7 B.D. RESPONSES 04.11.2011 8 CCD02 04.25.2011 17 SKETCHES 11.18.2011 Martin 12/08/2011 TOWN OF VAIL REVIEWED FOR CODE COMPLIANCE Date ________