HomeMy WebLinkAboutHadley Residence Material Submittal 1 of 2 MATERIAL SUBMITTAL FOR HADLEY RESIDENCE 1127 Vail Valley Drive Vail, Colorado 81657-5141 Platte Valley Fire Protection, Inc. State Lic. #11-501 P.O. Box #809 Wellington, CO 80549 (970)568-3178 platteva@frii.com TABLE OF CONTENTS Material Submittal 1. Sprinkler Heads A. Reliable Model F1 Residential Sprinklers B. Reliable Model rfc-49 Residential Pendant Sprinklers C. Reliable Guide for Residential Sprinklers in Sloped Ceilings 2. CPVC Pipe & Fittings A. Spears Pipe B. Spears Fittings 3. Copper Pipe & Fittings A. Copper Pipe B. Copper Fittings 4. Valves A. Wilkins Model 975XL Reduced Pressure Backflow B. Ball Valve C. Check Valve D. Reliable Residential Riser Assembly 5. Electrical A. Flow Switch B. Horn & Stobe C. Ball Valve Tamper Switch 6. Hangers A. Two Hole Strap B. Side Mount Strap C. No Block Hanger D. All Thread Rod E. Ring Hangers F. Sammie Screws for Wood G. Surge Restrainer 7. Miscellaneous A. 2 ½” F.D.C. B. 300 P.S.I. Pressure Gauge Kit C. Sprinkler Cabinet D. Escutcheons Note: Materials may be exchanged with other materials that have equal or excessive listings and specifications. SPRINKLER HEADS 1. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 135 Rev.G Bulletin 135 Rev.G Model F1Res Sprinklers engineered for the lowest flows to meet the minimum design density of .05 gpm/ft2 Types: 1. F1 Res 30 Pendent 2. F1 Res 30 Recessed Pendent/F2 3. F1 Res 30 Recessed Pendent/FP 4. F1 Res 49 Pendent 5. F1 Res 49 Recessed Pendent/F1 6. F1 Res 49 Recessed Pendent/FP 7. F1 Res 58 Pendent 8. F1 Res 58 Recessed Pendent/F1 9. F1 Res 58 Recessed Pendent/FP 10. F1 Res 76 Pendent 11. F1 Res 76 Recessed Pendent/F1 12. F1 Res 76 Recessed Pendent/FP 13. F1 Res 30 CCP Pendent 14. F1 Res 49 CCP Pendent 15. F1 Res 58 CCP Pendent 16. F1 Res 76 CCP Pendent 17. F1 Res 44 HSW 18. F1 Res 44 Recessed HSW/F2 19. F1 Res 58 HSW 20. F1 Res 58 HSW Recessed HSW/F2 21. F1 Res 44 SWC 22. F1 Res 40 HSW 23. F1 Res 40 Recessed HSW/F2 Listings & Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) 2. NYC MEA 258-93-E Slope Ceiling Approvals: Sprinklers for .10 Density: Product Description Model F1Res Pendent sprinklers (Figs. 1, 2, 3,&4) are fast response sprinklers combining excellent durability, high sensitivity glass-bulb and low profile decorative design. The F1 Res Horizontal Sidewall sprinklers (Figs. 5, 6&7) are equally attractivewhen above ceiling piping cannot be used. The 3mm glass-bulb pendent sprinklers permit the efficient use of residential water supplies for sprinkler coverage in residential fire protection design. Application Model F1 Res Sprinklers are used for Residential Fire Protection according to UL 1626 Standard*. Be sure that orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of The National Fire Protection Association or the approving authority having jurisdiction.F1Res30, 49, 58&76 RecessedPendent /F1 F1Res30, 49, 58&76 RecessedPendent /FP F1 Res 30, 49, 58 & 76 CCP Pendent F1 Res 40 Recessed HSW/F2 UL Listing Category Residential Automatic Sprinkler UL Guide Number VKKW Patents US Patent No. 6,516,893 applies to the Model F1 Res 49 & 58 Pendent Sprinklers The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the sensitive fire protection application needs of the latest residential market standards (UL 1626 Standard). Upon fire conditions, rising heat causes a sprinkler’s heat-sensitive glass-bulb to shatter, releasing the waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire. Technical Data: • Thermal Sensor: Nominal 3mm glass-bulb • Sprinkler Frame : Brass Casting • Sprinklers’ Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi • Thread Size: ½” NPT (R½) • K-Factor: 3.0 (Actual) -F1 Res 30 Pendent Sprinkler 4.9 (Actual) -F1 Res 49 Pendent Sprinkler 5.8 (Actual) -F1Res58Pendent&HSWSprinkler 7.6 (Actual) -F1 Res 76 Pendent Sprinkler 4.4 (Actual) -F1 Res 44 HSW Sprinkler 4.0 (Actual) -F1 Res 40 HSW Sprinkler • Density: Minimum 0.05 gpm/ft2 F1 Res 44 & 58 Recessed HSW/F2 F1 Res 44 SWC Model F1 Residential Sprinklers for Design Density of .05 gpm/ft2 Model F1 Res 30, 49, 58 & 76 Pendent Model F1 Res 30 Recessed Pendent /F2 Model F1 Res 49, 58 & 76 Recessed Pendent /F1 Fig. 1 Fig. 2 F1 escutcheon, 3 4(19mm) adjustment 2. Installation Models F1 Res sprinklers are to be installed as shown. Model F1, F2 and FP Escutcheons, illustrated herewith, are the only recessed escutcheons to be used with Model F1 Res sprinklers. Use of any other recessed escutcheon will void all approvals and warranties. For installing Model F1 Res Pendent sprinklers use only the Model D sprinkler Wrench; for installing Models F1 Res Recessed Pendent, CCP & SWC sprinklers use only the Model GFR2 sprinkler wrench; for installing Model F1 Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench. Use of wrenches other than those specified may damage these sprinklers. Install F1 Res 44 and 40 HSW with a ceiling to deflector distance of 4-12. Flow arrow on deflector must point away from near wall and “Top” marking must face ceiling. Type Adjustment Inch (mm) “A” Inch (mm) Face of fitting to ceiling Inch (mm) F1 3 4 (19.0) Min.= 3 4(19.1) Max.=112(38.1) 316 -1516 (4.7 -24.0) F2 12 (12.7) Min.= 1516(23.8) Max.=112(38.1) 316 -1116 (4.7 -17.4) Escutcheon*, F1 or F2, Data: * Note: Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. Actual K Factor Sprinkler Length Inch (mm) F C F C 12NPT (R12) 716" (11) 155 175 68 79 175 (12) 100 150 38 66 4.9 2.25 (57) Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48) R3516 14 x 14 (4.3x4.3) 13 (49) 7.0 (0.48) 16 x 16 (4.9x4.9) 13 (49) 7.0 (0.48) 18 x 18 (5.5x5.5) 17 (64.3) 12.0 (0.83) 20 x 20 (6.1x6.1) 20 (75.7) 16.7 (1.14) Deflector -to -ceiling Maximum 1(25mm) to 4(100mm) 3. Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 15 (57) 9.4 (0.65) R3516 14 x 14 (4.3x4.3) 16 (60.5) 10.6 (0.73) 16 x 16 (4.9x4.9) 17 (64.3) 12.0 (0.83) 18 x 18 (5.5x5.5) 19 (72) 15.0 (1.0) 20 x 20 (6.1x6.1) 22 (83.2) 20.2 (1.4) *Deflector -to -ceiling Maximum 4(100mm) to 8(203mm) *Note: The F1 Res 49 pendent and recessed pendent residential sprinklers can be installed per NFPA 13 in beamed ceilings meeting the following criteria: 1. Maximum beam depth = 7(178mm) 2. Beam spacing at or greater than 7.5 ft. (2.3m) on center. Technical Data: F1 Res 49 Pendent and Recessed Pendent Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) F C F C ½NPT (R½) 12" (13) 155 175 68 79 175 (12) 100 150 38 66 5.8 2.25 (57) Max. Sprinkler Spacing ft (m) Flow gpm(Lpm) Pressure psi (bar) Ceiling -to-Deflector Inch (mm) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 16 (61) 7.6 (0.53) 1-4 (25-100) R3513 14 x 14 (4.3x4.3) 16 (61) 7.6 (0.53) 16 x 16 (4.9x4.9) 16 (61) 7.6 (0.53) 18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75) 20 x 20 (6.1x6.1) 22 (83.3) 14.4 (1.0) Technical Data: F1 Res 58 Pendent and Recessed Pendent Technical Data: F1 Res 30 Pendent and Recessed Pendent Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. Actual K Factor Sprinkler Length Inch (mm) F C F C 12NPT (R12) 2164" (8.2) 155 175 68 79 175 (12) 100 38 3.0 2.25 (57) Max. Sprinkler Spacing ft (m) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 8 (30.3) 7.0 (0.48) R3511 14 x 14 (4.3x4.3) 10 (37.8) 11 (0.76) Deflector -to -ceiling Maximum 1(25mm) to 4(100mm) 4. Technical Data: F1 Res 76 Pendent and Recessed Pendent Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) F C F C 3 4NPT (R3 4) 1732" (13.5) 155 175 68 79 175 (12) 100 150 38 66 7.6 2.25 (57) Max. Sprinkler Spacing ft (m) Flow gpm(Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 21 7.6 (0.53) R7618 14 x 14 (4.3x4.3) 21 7.6 (0.53) 16 x 16 (4.9x4.9) 21 7.6 (0.53) 18 x 18 (5.5x5.5) 21 7.6 (0.53) 20 x 20 (6.1x6.1) 23 9.2 (0.63) Model F1 Res 30, 49, 58 & 76 CCP Pendent Model F1 Res 30, 49, 58 & 76 Recessed Pendent /FP FP push-on/thread-off escutcheon Fig. 3 Fig. 4 NOTE: The F1 Res 76 will use a 1" x ¾" reducer. Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pressure psi(bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) F C F °C F C ½NPT (R½) 2164" (8.2) 155 68 135 57 175 (12) 100 38 3.0 2.25 (57) Max. Sprinkler Spacing ft (m) Flow gpm(Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 8 (30.3) 7.0 (0.48) R3511 14 x 14 (4.3x4.3) 11 (41.6) 13.4 (0.92) Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent /FP Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) F C F °C F C ½NPT (R½) 12" (13) 155 68 135 57 175 (12) 100 38 5.8 2.25 (57) Max. Sprinkler Spacing ft (m) Flow gpm(Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 16 (61) 7.6 (0.53) R3513 14 x 14 (4.3x4.3) 16 (61) 7.6 (0.53) 16 x 16 (4.9x4.9) 16 (61) 7.6 (0.53) 18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75) 20 x 20 (6.1x6.1) 22 (83.3) 14.4 14.4 (1.0) Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP 5. Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch(mm) F C F °C F C ¾NPT (R3/4) 1732" (13.5) 155 175 68 79 135 57 175 (12) 100 150 38 66 7.6 2.25 (57) Max. Sprinkler Spacing ft (m) Flow gpm(Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 21 7.6 (0.53) R7618 14 x 14 (4.3x4.3) 21 7.6 (0.53) 16 x 16 (4.9x4.9) 21 7.6 (0.53) 18 x 18 (5.5x5.5) 22 8.4 (0.58) 20 x 20 (6.1x6.1) 25 10.8 (0.74) Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CCP Assembly Temp. Rating Max. Pressure psi(bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) F C F °C F C ½NPT (R½) 716" (11) 155 68 135 57 175 (12) 100 38 4.9 2.25 (57) Max. Sprinkler Spacing ft (m) Flow gpm(Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48) R3516 14 x 14 (4.3x4.3) 13 (49) 7.0 (0.48) 16 x 16 (4.9x4.9) 14 (53) 8.2 (0.56) 18 x 18 (5.5x5.5) 18 (68.1) 13.5 (0.93) 20 x 20 (6.1x6.1) 20 (75.7) 16.7 (1.14) “A” Cover Adjustment Inch (mm) “B” CCP Height Inch (mm) 12 (12.7) 1516 (24) 516 (7.9) 3 4 (19) CCP Options Data: FP Position “A” Inch (mm) Max. Recessed 716 (11) Min. Recessed 1516 (24) FP Data “A”: Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in the space above. Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent /FP 6. Model F1 Res 44 & 58 HSW Model F1 Res 44 & 58 Recessed HSW/F2 F2 escutcheon, 12(13mm) adjustment Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) F C F C ½NPT (R½) 3 8" (10) 155 175 68 79 175 (12) 100 150 38 66 4.4 2.45 (62) Type Adjustment Inch (mm) Face of Fitting to wall Inch (mm) F2 12 (13) 316 -1116 (4.7 -17.4) Escutcheon, F2, Data: Technical Data: F1 Res 44 HSW & HSW/F2 Max. Sprinkler Spacing ft (m) “A” Ceiling -to-Deflector Inch (mm) Sprinkler Temp. Rating F (C) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 4 -6 (101-152) 155 (68) 175 (79) 12 (45.4) 7.5 (0.52) R3531 14 x 14 (4.3x4.3) 155 (68) 175 (79) 14 (53.0) 10.2 (0.71) 16 x 16 (4.9x4.9) 155 (68) 175 (79) 16 (60.6) 13.3 (0.92) 16 x 18 (4.9x5.5) 155 (68) 175 (79) 18 (68.1) 16.8 (1.16) 18 x 18 (5.5x5.5) 155 (68) 175 (79) 19 (72.0) 18.7 (1.29) 16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.1) 27.4 (1.89) 12 x 12 (3.6x3.6) 6 -12 (152-305) 155 (68) 175 (79) 14 (53.0) 10.2 (0.71) 14 x 14 (4.3x4.3) 155 (68) 175 (79) 16 (60.6) 13.3 (0.92) 16 x 16 (4.9x4.9) 155 (68) 175 (79) 17 (64.4) 15.0 (1.04) 16 x 18 (4.9x5.5) 155 (68) 175 (79) 20 (75.7) 20.7 (1.43) 16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.1) 27.4 (1.89) Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) F C F C ½NPT (R½) 12" (13) 155 175 68 79 175 (12) 100 150 38 66 5.8 2.45 (62) Type Adjustment Inch (mm) Face of Fitting to wall Inch (mm) F2 12 (13) 316 -1116 (4.7 -17.4) Escutcheon, F2, Data: Technical Data: F1 Res 58 HSW & HSW/F2 Max. Sprinkler Spacing ft (m) “A” Ceiling -to-Deflector Inch (mm) Sprinkler Temp. Rating F (C) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 4 -6 (101-152) 155 (68) 175 (79) 16 (60.6) 7.6 (0.53) R3533 14 x 14 (4.3x4.3) 155 (68) 175 (79) 18 (68.2) 9.7 (0.67) 16 x 16 (4.9x4.9) 155 (68) 175 (79) 21 (79.5) 13.2 (0.91) 16 x 18 (4.9x5.5) 155 (68) 175 (79) 25 (94.7) 18.6 (1.28) 16 x 20 (4.9x6.1) 155 (68) 175 (79) 29 (109.8) 25 (1.73) 12 x 12 (3.6x3.6) 6 -12 (152-305) 155 (68) 175 (79) 22 (83.3) 14.4 (1.0) 14 x 14 (4.3x4.3) 155 (68) 175 (79) 22 (83.3) 14.4 (1.0) 16 x 16 (4.9x4.9) 155 (68) 175 (79) 26 (98.4) 98.4) 20.1 (1.39) 16 x 18 (4.9x5.5) 155 (68) 175 (79) 31 (117.4) 28.6 (1.97) 7. 8. Model F1 Res 44 SWC Fig. 5 Max. Sprinkler Spacing ft (m) “A” Ceiling -to-Deflector Inch (mm) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 4 -6 (101-152) 13 (49.2) 8.7 (0.60) R3531 14 x 14 (4.3x4.3) 14 (53.0) 10.2 (0.71) 16 x 16 (4.9x4.9) 17 (64.3) 15.0 (1.1) 16 x 18 (4.9x5.5) 19 (71.8) 18.7 (1.13) 16 x 20 (4.9x6.1) 23 (87.1) 27.4 (1.89) 12 x 12 (3.6x3.6) 6 -12 (152-305) 14 (52.9) 10.2 (0.71) 14 x 14 (4.3x4.3) 15 (56.7) 11.7 (0.81) 16 x 16 (4.9x4.9) 18 (68.1) 16.8 (1.16) 16 x 18 (4.9x5.5) 20 (75.6) 20.7 (1.43) Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating CoverTemp. Rating Max. Pressure psi (bar) Max. AmbientTemp. K Factor Sprinkler Length Inch (mm) F C F °C F C ½NPT (R½) 3 8" (10) 155 68 135 57 175 (12) 100 38 4.4 2.45 (62) Technical Data: F1 Res 44 SWC 2. 9. Model F1 Res 40 HSW Model F1 Res 40 Recessed HSW/F2 F2 escutcheon, 12(13mm) adjustment Fig. 6 Fig. 7 Max. Sprinkler Spacing ft (m) “A” Ceiling -to-Deflector Inch (mm) Sprinkler Temp. Rating F (C) Flow gpm (Lpm) Pressure psi (bar) Sprinkler Identification Number (SIN) 12 x 12 (3.6x3.6) 4 -6 (101-152) 155 (68) 175 (79) 13 (49.0) 10.6 (0.73) R3538 14 x 14 (4.3x4.3) 155 (68) 175 (79) 16 (60.5) 16.0 (1.10) 16 x 16 (4.9x4.9) 155 (68) 17 (64.3) 18.1 (1.24) 16 x 16 (4.9x4.9) 175 (79) 18 (68.1) 20.2 (1.39) 16 x 18 (4.9x5.5) 155 (68) 175 (79) 20 (75.7) 25.0 (1.72) 18 x 18 (5.5x5.5) 155 (68) 175 (79) 22 (83.3) 30.2 (2.08) 16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.0) 33.1 (2.28) 12 x 12 (3.6x3.6) 6 -12 (152-305) 155 (68) 175 (79) 13 (49.0) 10.6 (0.73) 14 x 14 (4.3x4.3) 155 (68) 175 (79) 17 (64.3) 18.1 (1.24) 16 x 16 (4.9x4.9) 155 (68) 175 (79) 20 (75.7) 25.0 (1.72) Thread Size Nominal Orifice Inch (mm) Sprinkler Temp. Rating Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) F C F C ½NPT (R½) 3 8" (10) 155 175 68 79 175 (12) 100 150 38 66 4.0 2.45 (62) Type Adjustment Inch (mm) Face of Fitting to wall Inch (mm) F2 12 (13) 316 -1116 (4.7 -17.4) Escutcheon, F2, Data: Technical Data: F1 Res 40 HSW & HSW/F2 Ordering Information Specify: 1. Sprinkler Model 2. Sprinkler Type 3. Temperature Rating 4. Sprinkler Finish 5. Escutcheon Finish 6. Cover Plate Finish Maintenance Model F1 Res 30, 49, F1 Res 58, F1 Res 76, F1 Res 44 and F1 Res 40 Sprinklers should be inspected quarterly, and the sprinkler system maintained in accordance with NFPA 25, 13, 13D, and 13R. Do not clean sprinkler with soap and water, Ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should remain in the original cartons and packaging until used. This will minimize the potential for damage to sprinklers that could cause improper operation or non-operation. Standard Finishes Sprinkler F1, F2, FP Escutcheons Cover Plates Bronze Chrome Plated White Polyester Coated Brass Brass Bright Chrome Plated White Painted White Painted Chrome Special Application Finishes Sprinkler F1, F2, Escutcheons Cover Plates Bright Brass Black Plated Black Paint Off White Satin Chrome Bright Brass Black Plated Black Paint Off White Satin Chrome Bright Brass Black Plated Black Paint Off White Satin Chrome Finishes(1) (1) Other finishes and colors are available on special order. Consult factory for details. Paint or any other coating applied over the factory finish will void all approvals and warranties. 10. Model F1 Res 30, 49 & 58 Pendent Sprinkler Specifications Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential pendent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Deflector-to-ceiling distance listing shall be 1” to 8” maximum. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155F (68C)] [175F (79C)]. Sprinklers shall have a nominal K-factor of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Residential pendent sprinklers shall be ReliableModel F1 Res 30, 49 & 58, SIN R3511, R3516 & R3513 (Bulletin 135). Model F1 Res 49 & 58 Recessed Pendent/F1, ModelF1Res30, 49&58RecessedPendent/F2, ModelF1Res30, 49&58RecessedPendent/FP Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with themanufacturer’s installation guidelines and the applicable installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Deflector-to-ceiling distance listing shall be 1” to 8” maximum. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with top-loaded extruded or cold head cup with 3mmglass bulb containing no plastic parts, and having a temperature rating of [155F (68C)] [175F (79C)]. Sprinklers shall have a nominal K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with ½” adjustment (Model F2)] [with ¾” adjustment (Model F1)] [of push-on and thread off design with ½” adjustment (Model FP)]. Standard finish shall be [brass][bright chrome] [white painted]. Residential recessed pendent sprinklers shall be Reliable [Model F1 Res 3.0, 49 & 58 Recessed Pendent/F1] [Model F1 Res 30, 49 & 58 Recessed Pendent/F2] [Model F1 Res 30, 49 & 58 Recessed Pendent/FP] SIN R3511, R3516 & R3513 (Bulletin 135). ModelF1Res30,49&58CCPPendent(Concealed) Sprinklers shall be [cULus Listed] [New York CityMEA Approved (258-93-E)] low flow residential concealed sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by themanufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with top-loaded extruded or cold head cup with 3mmglass bulb containing no plastic parts, and having a temperature rating of 155F (68C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a ½” cover plate adjustment. Cover plate temperature rating shall be 135F (57C). A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color– specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 30, 49 & 58 CCP, SIN R3511, R3516 & R3513 (Bulletin 135). ModelF1RES40andF1Res44Horizontal Sidewall Residential Sprinkler Specifications Model F1 Res 40 Horizontal Sidewall Sprinkler Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential horizontal sidewall sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Where horizontal sidewall residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155F (68C)] [175F (79C)]. Sprinklers shall have a nominal K-factor of 4.0 (57.1). Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Residential horizontal sidewall sprinklers shall be Reliable Model F1 Res 40, SIN R3538 (Bulletin 135). Model F1 Res 40 Recessed Horizontal Sidewall Sprinkler Use description for the Model F1 Res 40 horizontal sidewall sprinklerwith the following modifications: Replace “horizontal sidewall sprinkler” with “recessed horizontal sprinkler.” Add: Recessed escutcheon assembly shall be a steel, two-piece escutcheon with ½” adjustment (Model F2). Standard finish shall be [brass][bright chrome] [white painted] [Special finish– specify]. Residential recessed horizontal sidewall sprinklers shall be Reliable Model F1 Res 40/F2, SIN R3538 (Bulletin 135). Model F1 Res 44Horizontal SidewallSprinkler Sprinklers shall be [cULus Listed] [NewYorkCityMEA Approved (258-93-E)] low flow residential horizontal sidewall sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Where horizontal sidewall residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155F (68C)] [175F (79C)]. Sprinklers shall have a nominal K-factor of 4.4 (62.8). Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Residential horizontal sidewall sprinklers shall be ReliableModel F1 Res 44, SIN R3531 (Bulletin 135). Model F1 Res 44 Recessed Horizontal Sidewall Sprinkler Use description for the Model F1 Res 44 horizontal sidewall sprinkler with the following modifications: Replace “horizontal sidewall sprinkler” with “recessed horizontal sprinkler.” Add: Recessed escutcheon assembly shall be a steel, two-piece escutcheon with ½” adjustment (Model F2). Standard finish shall be [brass][bright chrome] [white painted] [[Special finish– specify]. Residential recessed horizontal sidewall sprinklers shall be Reliable Model F1 Res 44/F2, SIN R3531 (Bulletin 135). 11. The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances, whenever applicable. Productsmanufactured and distributed byRELIABLE have been protecting life and property for over 80 years, and are installed and serviced by themost highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 06/08 P/N 9999970235 Model F1 Res 76 Pendent Sprinklers shall be [cULus Listed] low flow residential pendent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155F (68C)] [175F (79C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Residential pendent sprinklers shall be Reliable Model F1 Res 76, SIN R7618 (Bulletin 135). Model F1 Res 76 Recessed Pendent/F1, Model F1 Res 76 Recessed Pendent/F2, Model F1 Res 76 Recessed Pendent/FP Sprinklers shall be [cULus Listed] low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155F (68C)] [175F (79C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with ½” adjustment (Model F2)] [with ¾” adjustment (Model F1)] [of push-on and thread off design with ½” adjustment (Model FP)]. Standard finish shall be [brass][bright chrome] [white painted]. Residential recessed pendent sprinklers shall be Reliable [Model F1 Res 76 Recessed Pendent/F1] [Model F1 Res 76Recessed Pendent/F2] [Model F1 Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135). Model F1 Res 76 CCP Pendent (Concealed) Sprinklers shall be [cULus Listed] low flow residential concealed sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used.Residential sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Water seal assembly shall consist of a Teflon-coated Belleville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of 155F (68C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a ½” cover plate adjustment. Cover plate temperature rating shall be 135F (57C). A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color– specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135). The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 006 Rev. E Bulletin 006 Rev. E Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features Very low water flow requirements. ½” (13mm) Total adjustment. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. Smooth aesthetic ceiling profile. Available in brass, chrome and black plated or painted finishes. Listings & Approval Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) NYC MEA 258-93-E UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC43 and RFC49 Concealed Residential Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler deflector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprinkler patterns. The combination of speed of operation and high discharge pattern required for residential sprinklers has demonstrated, in fire testing, an ability for controlling residential fires, and thereby providing significant evacuation time for occupants. The RFC43 and RFC49 Sprinklers provide the best form of fire protection by combining an attractive appearance and ½” (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily and posi-1. 2. 3. 4. 5. 1. 2. tively attached and blends into the ceiling, concealing the most dependable fire protection available, an automatic sprinkler system. The RFC43 and RFC49 are UL Listed Residential Sprinklers to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC43 and RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit accurately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. Application and Installation The RFC43 and RFC49, for residential installations, use a 165°F (74°C) fusible solder link in a tuning fork style sprinkler frame with a drop-down deflector. This assembly is recessed into the ceiling and concealed by a flat cover plate. The cover plate is attached to the skirt, using 135°F (57°C) ordinary temperature classification solder. When the ceil 2. ing temperature rises, the solder holding the cover plate releases the cover allowing the deflector to drop into position and exposing the sprinkler inside to ceiling temperature. The subsequent operation of the solder link opens the waterway and causes the deflector to drop into position to distribute the discharging water in a hemispherical pattern below the sprinkler deflector. Any adjustment of thread engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling. The residential distribution pattern contains a finer droplet size than a standard sprinkler, and the pattern produces significantly higher wall wetting. After a 25/8 inch diameter hole is cut in the ceiling, the sprinkler is to be installed with the Model FC Wrench. When installing a sprinkler, the wrench is first positioned into the sprinkler/cup assembly and around the hexagonal body of the sprinkler frame. The Wrench must bottom out against the cup in order to ensure proper, safe installation. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprinkler/cup assembly, care should be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC43 AND RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F RATED COVERS. Note: A leak tight ½” NPT (R1/2) sprinkler joint can be obtained with a torque of 8-18 ft-lbs (10,8 -24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. Cover assemblies provide up to 1/2” (13mm) of adjustment. Turn the cover clockwise until the flange is in contact with the ceiling. For the push-on/thread-off option, the cover assembly is pushed onto the cup and final adjustment is made by turning the cover clockwise until the skirt flange makes full contact with the ceiling. Cover removal requires turning in the counter-clockwise direction. In ceilings that have a plenum space above the sprinkler, the plenum space may have neutral or negative pressurization but must not be positively pressurized. Inspect all sprinklers after installation to ensure that the gap between the cover plate and ceiling and the 4 slots in the cup are all open and free from any air flow impediment. Temperature Rating Sprinkler Cover Plate Max. Ambient Temp. 165°F/74°C 135°F/57°C 100°F/38°C Installation Data: RFC43 (SIN RA0612) Thread Size inch (mm) K Factor Sprinkler Spacing ft. (m) Maximum Distance to Wall ft. (m) Minimum Distance between sprinklers ft. (m) Minimum Required Sprinkler Discharge Flow gpm (Lpm) Press. psi (bar) ½” (15mm) ½” (15mm) ½” (15mm) ½” (15mm) ½” (15mm) 4.3 4.3 4.3 4.3 4.3 12 x 12 (3.6x3.6) 14 x 14 (4.3x4.3) 16 x 16 (4.9x4.9) 18 x 18 (5.5x5.5) 20 x 20 (6.0x6.0) 6 (1.83) 7 (2.13) 8 (2.43) 9 (2.74) 10 (3.05) 8 (2.43) 8 (2.43) 8 (2.43) 8 (2.43) 8 (2.43) 12 (45) 13 (49) 13 (49) 18 (68) 21 (79) 7.8 (0.54) 9.1 (0.63) 9.1 (0.63) 17.5 (1.21) 23.8 (1.64) Note: 1 bar = 100 Kpa Installation Data: RFC49 (RA0616) Thread Size inch (mm) K Factor Sprinkler Spacing ft. (m) Maximum Distance to Wall ft. (m) Minimum Distance between sprinklers ft. (m) Minimum Required Sprinkler Discharge Flow gpm (Lpm) Press. psi (bar) ½” (15mm) ½” (15mm) ½” (15mm) ½” (15mm) ½” (15mm) 4.9 4.9 4.9 4.9 4.9 12 x 12 (3.6x3.6) 14 x 14 (4.3x4.3) 16 x 16 (4.9x4.9) 18 x 18 (5.5x5.5) 20 x 20 (6.0x6.0) 6 (1.83) 7 (2.13) 8 (2.43) 9 (2.74) 10 (3.05) 8 (2.43) 8 (2.43) 8 (2.43) 8 (2.43) 8 (2.43) 13 (49) 13 (49) 13 (49) 17 (64.3) 20 (75.7) 7.0 (0.48) 7.0 (0.48) 7.0 (0.48) 12.0 (0.83) 16.7 (1.14) Note: 1 bar = 100 Kpa FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035. 3. Maintenance Model RFC43 and RFC49 Concealed Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover plate assembly which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. Model RFC43 and RFC49 Residential Concealed Sprinkler Specifi cation Sprinklers shall be cULus Listed low flow residential concealed sprinklers with drop-down deflector and adjustable flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Thermal element shall consist of an approved black-painted beryllium-nickel fusible solder link with symmetric lever mechanism, maintaining a Teflon-coated Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler K-factor shall be nominal 4.3 (62.4), having a 7/16” orifice. Temperature rating shall be Ordinary 165°F (74°C); cover plate temperature rating to be 135°F (57°C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange allowing a ½” cover plate adjustment. Any secure engagement between the cover plate and the cup will assure that the drop-down deflector is properly located below the ceiling. A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the drop-down sprinkler deflector from damage, which could occur during construction before the cover plate is installed. Standard cover finish: [Chrome] [White] [Specialty – specify]. Residential concealed sprinklers shall be Reliable Model RFC43, SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 (Bulletin 006). Ordering Information Specify: Sprinkler Model Cover Plate Finish Thread-On or Push-On Feature 1. 2. 3. Cover Plate Finishes (1) Standard Finishes Chrome White Special Application Finishes Bright Brass Black Plating Black Paint Off White Satin Chrome (1) Other colors and finishes available. Consult factory for details. Note: Paint or any other coatings applied over the factory finish will void all approvals and warranties. The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A 04/10 P/N 9999970261 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrical sprinkler alarm switches Water flow detectors •••••••••••••••• Deluge valves Detector check valves Check valves Electrical system Sprinkler emergency cabinets Sprinkler wrenches Sprinkler escutcheons and guards Inspectors test connections Sight drains Ball drips and drum drips Control valve seals Air maintenance devices Air compressors Pressure gaugesIdentification signs Fire department connection ••••••••••••••• Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. Reliable...For Complete Protection The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 035 Rev. H Bulletin 035 Rev. H Guidelines for Listed Residential Sprinkler installations below Sloped Ceilings Residential Sprinkler For Sloped Ceilings The installation guidelines cover Residential Sprinkler Models: F1 Res 49 Pendent F1 Res 49 Recessed Pendent/F2 F1 Res 58 Pendent F1 Res 58 Recessed Pendent/F2 F1 Res 44 HSW F1 Res 44 Recessed HSW/F2 F1 Res 49 CCP F1 Res 58 CCP RFC 43 Flat Concealed RFC 49 Flat Concealed Listings & Approvals Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) NYC MEA 258-93-E UL Listing Category Residential Automatic Sprinkler UL Guide Number VKKW Patents: US Patent number 6,516,893 Model F1 Res 49 Product Description for F1 Res Sprinklers Model F1 Res Pendent sprinklers are fast response sprinklers combining excellent durability, high sensitivity glass-bulb and low profile decorative design. The F1 Res Horizontal Sidewall sprinklers are equally attractive when above ceiling piping cannot be used. The 3mm glass-bulb pendent sprinklers, with a K Factor of 4.9 & 5.8 for pendent and 4.4 for horizontal sidewall, permit the efficient use of residential water supplies for sprinkler coverage in residential fire protection design. The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the sensitive fire protection application needs of the latest residential market standards (UL 1626 Standard *). Upon fire conditions, rising heat causes a sprinkler’s heat-sensitive glass-bulb to shatter, releasing the waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire. 1. 2. * Effective date July 12, 2002 F1 Res 49 & 58 Pendent F1 Res 49 & 58 Recessed Pendent /F2 F1 Res 44 Recessed HSW/F2 F1 Res 44 HSW F1 Res 49 & 58 CCP Pendent RFC 43 & RFC 49 RFC 43 & RFC 49 2. Product Description for RFC 43 & RFC 49 Model RFC43 & RFC49 Concealed Residential Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC43 & RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler deflector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprinkler patterns. The combination of speed of operation and high discharge pattern required for residential sprinklers has demonstrated, in fire testing, an ability for controlling residential fires, and thereby providing significant evacuation time for occupants. The RFC43 & RFC49 Sprinkler provides the best form of fire protection by combining an attractive appearance and ½” (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily and positively attached and blends into the ceiling, concealing the most dependable fire protection available, an automatic sprinkler system. The RFC43 & RFC49 are UL Listed Residential Sprinkler to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC43 & RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit accurately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. Technical Data (F1 Res Sprinklers): Thermal Sensor : Nominal 3mm glass-bulb Sprinkler Frame : Brass Casting Sprinkler Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi Thread Size : ½” NPT (R½) K Factor : 4.9 (Actual) -F1 Res 49 Pendent Sprinkler 4.4 (Actual) -F1 Res 44 HSW Sprinkler 5.8 (Actual) -F1 Res 58 Pendent Sprinkler Density : Minimum .05 gpm/ft2 Technical Data (RFC 43 & RFC 49): Thermal Sensor : 165°F Fusible Link Sprinkler Frame : Brass Machined Sprinkler Pressure Rating Rating : 175 psi Factory Hydrostatically Tested to 500 psi Thread Size : ½” NPT (R½) K Factor : 4.3 (Actual) RFC43; 4.9 (Actual) RFC49 Density : Minimum .05 gpm/ft2 Application Model F1 Res and RFC 43 & RFC 49 Sprinklers are used for Residential Fire Protection according to UL 1626 Standard*. Be sure that orifice size, temperature rating, deflector style, cover plate and sprinkler type are in accordance with the latest published standards of The National Fire Protection Association or the approving Authority Having Jurisdiction. ••••••••••••* Effective date July 12, 2002 3. Model F1 Res 49 Pendent & F1 Res 49 Recessed Pendent/F2 & F1 Res 49 CCP Pendent, Model F1 Res 58 Pendent & F1 Res 58 Recessed Pendent/F2 & F1 Res 58 CCP Pendent, RFC 43 & RFC 49 Pendent Flat Concealed Sprinklers installed below Sloped Ceilings. Note: F1 Res 49 CCP Pendent, RFC 43 and RFC 49 sprinklers are not suitable for installation in ceilings which have positive pressure in the space above. F1 Res 49 & 58 Pendent F1 Res 49 & 58 Recessed Pendent /F2 F1 Res 49 & 58 CCP Pendent RFC 43 & RFC 49 RFC 43 & RFC 49 4. 5. Sprinkler spacing below multiple sloped ceilings with a maximum slope of 8/12 (33.7°) pitch. 6. Model F1Res 49 Pendent & F1 Res 49 Recessed Pendent/F2 installed below Sloped Ceiling. Technical Data Thread Size Max. Pressure psi (bar) Max. Ambient Temp. °F (°C) Actual K Factor (metric) Sprinkler Length Escutcheon Sprinkler Identifi cation Number (SIN) ½” NPT (R½) 175 (12) 100 (38) 4.9 (69,94) 2.25” (57mm) F2 (1/2“ Adjustment) R3516 Table 1 -Application Max. Sprinkler Spacing Along Slope (W) Width x ( L) Length ft (m) Max. Slope of 8/12 (33.7°) Pitch Max. Slope of 4/12 (18.4°) Pitch Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) Sprinkler Temp. Rating °F (°C) 155 (68) & 175 (79) 155°F (68°C) 175°F (79°C) 155°F (68°C) 175°F (79°C) Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) 12 x 12 (3,6 x 3,6) 13 (49) 13 (49) 7.0 (0,48) 7.0 (0,48) 13 (49) 7.0 (0,48) 14 x 14 (4,3 x 4,3) 13 (49) 13 (49) 7.0 (0,48) 7.0 (0,48) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 13 (49) 13 (49) 7.0 (0,48) 7.0 (0,48) 13 (49) 7.0 (0,48) 18 x 18 (5,5 x 5,5) 17 (64,3) 18 (68,2) 12.0 (0,83) 13.5 (0,93) 18 (68,3) 13.5 (0,93) 20 x 20 (6,1 x 6,1) 20 (75,7) 21 (79,5) 16.7.(1,15) 18.4 (1,28) 20 (75,7) 16.7 (1,15) Model F1Res 49 CCP Pendent installed below Sloped Ceiling. Technical Data Thread Size Sprinkler Temp. Rating °F (°C) CCP Assy. Temp. Rating °F (°C) Max. Pressure psi (bar) Max. Ambient Temp. °F (°C) Actual K Factor (metric) Sprinkler Length Sprinkler Identifi cation Number (SIN) ½” NPT (R½) 155 (68) 135 (57) 175 (12) 100 (38) 4.9 (69,94) 2.25” (57mm) R3516 Table 2 -Application Max. Sprinkler Spacing Along Slope (W) Width x ( L) Length ft (m) Max. Slope of 8/12 (33.7°) Pitch Max. Slope of 4/12 (18.4°) Pitch Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) 12 x 12 (3,6 x 3,6) 14 (53) 8.2 (0,57) 13 (49) 7.0 (0,48) 14 x 14 (4,3 x 4,3) 14 (53) 8.2 (0,57) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 14 (53) 8.2 (0,57) 14 (53) 8.2 (0,56) 18 x 18 (5,5 x 5,5) 23 (87) 22 (1,52) 20 (75,7) 17 (1,17) 20 x 20 (6,1 x 6,1) 23 (87) 22 (1,52) 21 (75,7) 17 (1,17) Model F1Res 58 Pendent & F1 Res 58 Recessed Pendent/F2 installed below Sloped Ceiling. Technical Data Thread Size Max. Pressure psi (bar) Max. Ambient Temp. °F (°C) Actual K Factor (metric) Sprinkler Length Escutcheon Sprinkler Identifi cation Number (SIN) ½” NPT (R½) 175 (12) 100 (38) 5.8 (83,38) 2.25” (57mm) F2 (1/2“ Adjustment) R3513 Table 3 -Application Max. Sprinkler Spacing Along Slope (W) Width x ( L) Length ft (m) Max. Slope of 8/12 (33.7°) Pitch Max. Slope of 4/12 (18.4°) Pitch Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) 155°F (68°C) 175°F (79°C) 155°F (68°C) 175°F (79°C) 155°F (68°C) 155°F (68°C) 12 x 12 (3,6 x 3,6) 21 (79.5) 23 (87) 13.1 (0,9) 15.7 (1,1) 14 x 14 (4,3 x 4,3) 21 (79.5) 23 (87) 13.1 (0,9) 15.7 (1,1) 16 x 16 (4,9 x 4,9) 21 (79.5) 23 (87) 13.1 (0,9) 15.7 (1,1) 18 x 18 (5,5 x 5,5) 23 (87) 15.7 (1,1) 20 (75,7) 12 (0,83) 20 x 20 (6,1 x 6,1) 23 (87) 15.7 (1,1) 20 (75,7) 12 (0,83) 7. Model F1Res 58 CCP Pendent Installed below sloped Ceiling. Technical Data Thread Size Sprinkler Temp. Rating °F (°C) CCP Assy. Temp. Rating °F (°C) Max. Pressure psi (bar) Max. Ambient Temp. °F (°C) Actual K Factor (metric) Sprinkler Length Sprinkler Identifi cation Number (SIN) ½” NPT (R½) 155 (68) 135 (57) 175 (12) 100 (38) 5.8 (83,38) 2.25” (57mm) R3513 Table 4 -Application Max. Sprinkler Spacing Along Slope (W) Width x ( L) Length ft (m) Max. Slope of 4/12 (18.4°) Pitch Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) 18 x 18 (5,5 x 5,5) 20 (75.7) 12 (0,83) 20 x 20 (6,1 x 6,1) 20 (75.7) 12 (0,83) Model RFC43 Pendent Flat Concealed installed below Sloped Ceiling. Technical Data Thread Size Sprinkler Temp. Rating °F (°C) Coverplate Temp. Rating °F (°C) Max. Pressure psi (bar) Max. Ambient Temp. °F (°C) Actual K Factor (metric) Max. Adjustment Sprinkler Identifi cation Number (SIN) ½” NPT (R½) 165 (74) 135 (57) 175 (12) 100 (38) 4.3 (61,4) ½” (13mm) RA0612 Table 5 -Application Max. Sprinkler Spacing Along Slope (W) Width x ( L) Length ft (m) Max. Slope of 8/12 (33.7°) Pitch Max. Slope of 4/12 (18.4°) Pitch Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) 12 x 12 (3,6 x 3,6) 18 (68) 17.5 (1,21) 13 (49) 9.1 (0,63) 14 x 14 (4,3 x 4,3) 18 (68) 17.5 (1,21) 13 (49) 9.1 (0,63) 16 x 16 (4,9 x 4,9) 18 (68) 17.5 (1,21) 13 (49) 9.1 (0,63) 18 x 18 (5,5 x 5,5) 24 (91) 31 (2,14) 18 (68) 17.5 (1,21) 20 x 20 (6,1 x 6,1) 24 (91) 31 (2,14) 21 (79) 23.8 (1,64) Model RFC 49 Pendent Flat Concealed installed below Sloped Ceiling. Technical Data Thread Size Sprinkler Temp. Rating °F (°C) Coverplate Temp. Rating °F (°C) Max. Pressure psi (bar) Max. Ambient Temp. °F (°C) Actual K Factor (metric) Max. Adjustment Sprinkler Identifi cation Number (SIN) ½” NPT (R½) 165 (74) 135 (57) 175 (12) 100 (38) 4.9 (69,94) ½” (13mm) RA0616 Table 6 -Application Max. Sprinkler Spacing Along Slope (W) Width x ( L) Length ft (m) Max. Slope of 8/12 (33.7°) Pitch Max. Slope of 4/12 (18.4°) Pitch Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) Min. Flow Per Sprinkler Head gpm (Lpm) Pressure psi (bar) 16 x 16 (4,9 x 4,9) 28 (106) 23 (19,3) 18 x 18 (5,5 x 5,5) 29 (109.8) 29 (20,0) 18 (68) 13.5 (0,93) 20 x 20 (6,1 x 6,1) 30 (113.6) 30 (30,0) 23 (87) 22 (1,52) Installation Guidelines For systems designed in accordance with NFPA 13, 13D and 13R, where specific UL Listed flows are not required, consult with the local Authority Having Jurisdiction regarding the number of design sprinklers for sloped ceilings having a pitch greater than (9.4°). Installation of UL Listed residential sprinklers under sloped ceilings shall be limited to a type of unobstructed construction consisting of smooth ceilings, as defined by NFPA 13, having a maximum pitch of 4/12 (18.4°) or 8/12 (33.7°). Spacing of residential sprinklers under sloped ceilings is measured along the slope when determining the distance off of walls and between sprinklers. Measure listed areas of coverage along the sloped ceiling. The actual floor coverage area will be less than the listed area. For coverage areas less than the listed coverage area shown in Tables 1 through 5, use the minimum flow requirement for the next largest listed coverage area. 1. 2. 3. 4. 5. Minimum spacing between pendent type sprinklers is 8 ft. (2.4 m). Minimum distance from a pendent type sprinkler and an adjacent wall is 4” (102 mm). Residential sprinklers located closest to the peak of the ceiling shall have the deflectors located not more than 3 ft (1m) vertically down from the peak. Align deflectors parallel with the ceiling slope 1” to 4” (25mm to 102mm) below the sloped ceiling. Hydraulic Requirements: For NFPA 13D Systems, the number of design sprinklers shall include all sprinklers within a compartment, up to a maximum of two sprinklers (where specific UL Listed flows are required) that requires the greatest hydraulic demand. For NFPA 13R Systems, the number of design sprinklers shall include all sprinklers within a compartment, up to a maximum of four (4) sprinklers (where specific UL Listed flows are required), that requires the greatest hydraulic demand. 6. 7. 8. a. b. 8. 9. Model F1Res 44 and F1 Res 44 HSW/F2 installed below Sloped Ceiling. F1 Res 44 HSW F1 Res 44 Recessed HSW/F2Horizontal Sidewall Sprinkler (with discharge directed down the slope) Horizontal Sidewall Sprinkler (with discharge directed across the slope) For NFPA 13 systems, the design area shall be the area that includes the four (4) hydraulically most demanding sprinklers. The minimum required discharge from each of the four hydraulically demanding sprinklers shall be the greater of the following: (1) In accordance with the minimum flow rates indicated by the individual listings (that already will provide a minimum density of 0.1 gpm/ft2); or (2) A calculated value based on delivering a minimum of 0.1 gpm/ft2 over the design area. Because of the varied nature of residential construction features, there will be some compartment designs which cannot be fully sprinklered in accordance with c. 9. NFPA 13, 13D, or 13R. In these instances, consult the Authority Having Jurisdiction (AHJ) for guidance and approval. This includes sloped ceilings having a pitch greater than 8/12 (33.7°). Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACE IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. 10. HSW Sprinkler spacing below multiple sloped ceilings with a maximum slope of 8/12 (33.7°) pitch. 10. HSW sprinkler spacing below single sloped ceilings with a maximum slope of 8/12 (33.7°) pitch. Table 8 -Application Max. Sprinkler Spacing Along Slope (W) Width x ( L) Length ft (m) Max. Slope of 8/12 (33.7°) Pitch Discharge Directed Down the Slope 4” to 6” Defl ector to Ceiling Discharge Directed Down the Slope 6” to 12” Defl ector to Ceiling (2)(3)Discharge Directed Across the Slope 4” to 12” Defl ector to Ceiling (1) Min. Flow gpm (Lpm) Pressure psi (bar) (1) Min. Flow gpm (Lpm) Pressure psi (bar) (1) Min. Flow gpm (Lpm) Pressure psi (bar) 12 x 12 (3,6 x 3,6) 12 (45,4) 7.5 (0,52) 14 (53,0) 10.2 (0,71) 16 (60,6) 13.3 (0,92) 14 x 14 (4,3 x 4,3) 14 (53,0) 10.2 (0,71) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92) 16 x 16 (4,9 x 4,9) 16 (60,6) 13.3 (0,92) 17 (64,4) 15 (1,04) 16 (60,6) 13.3 (0,92) 18 x 18 (4,9 x 5,5) 18 (68,1) 16.8 (1,16) 20 (75,6) 20.7 (1,43) 20 x 20 (4,6 x 6,1) 23 (72,0) 27.4 (1,89) 23 (87,1) 27,4 (1,89) (1) Minimum flow per sprinkler gpm (Lpm). (2) Minimum 3 head design in a compartment. (3) 155°F only. 11. Model F1RES 44 HSW & F1RES 44 HSW Recessed HSW/F2 installed below Sloped Ceiling. Technical Data Thread Size Sprinkler Temp. Rating °F (°C) Max. Pressure psi (bar) Max. Ambient Temp. °F (°C) Actual K Factor (metric) Sprinkler Lenght Escutcheon Sprinkler Identifi cation Number (SIN) ½” NPT (R½) 155 (68) 175 (79) 175 (12) 100 (38) 4.4 (62,8) 2.45” (62mm) F2 (½” Adjustment) R3531 Table 7 -Application Max. Sprinkler Spacing Along Slope (W) Width x ( L) Length ft (m) Max. Slope of 4/12 (18.4°) Pitch Discharge Directed Across the Slope 4” to 6” Defl ector to Ceiling Discharge Directed Across the Slope 6” to 12” Defl ector to Ceiling Min. Flow gpm (Lpm) Pressure psi (bar) Min. Flow gpm (Lpm) Pressure psi (bar) 12 x 12 (3,6 x 3,6) 16 (60,5) 13.3 (0,92) 17 (64,3) 15 (1,04) 14 x 14 (4,3 x 4,3) 16 (60,5) 13.3 (0,92) 17 (64,3) 15 (1,04) 16 x 16 (4,9 x 4,9) 16 (60,5) 13.3 (0,92) 17 (64,3) 15 (1,04) 18 x 18 (4,9 x 5,5) 18 (68,1) 16.8 (1,16) 20 (75,6) 20.7 (1,43) 20 x 20 (4,6 x 6,1) 23 (68,1) 27.4 (1,89) 23 (68,1) 27,4 (1,89) Installation Guidelines For systems designed in accordance with NFPA 13, 13D and 13R, where specific UL Listed flows are not required, consult with the local Authority Having Jurisdiction regarding the number of design sprinklers for sloped ceilings having pitch greater than (9.4°). Installation of UL Listed residential sprinklers under sloped ceilings shall be limited to a type of unobstructed construction consisting of flat, smooth ceilings, as defined by NFPA 13, having a maximum pitch of 4/12 (18.4°) or 8/12 (33.7°). Where listed, install horizontal sidewall sprinklers along the wall below the sloped ceiling when discharge is directed across the slope, and install at the peak below the sloped ceiling when discharge is directed down the slope. Always align the sprinkler deflector parallel with the direction of the sloped ceiling. Residential HSW sprinklers located closed to the peak of the ceiling shall have the deflectors located not more than 3 ft. (1m) vertically down from the peak. Spacing of residential HSW sprinklers under sloped ceilings is measured along the slope when determining the distance off of walls and between sprinklers. 1. 2. 3. 4. 5. Measure listed areas of coverage along the sloped ceiling. The actual floor coverage area will be less than the listed area. For coverage areas less than the listed coverage area shown in Tables 1 through 6, use the minimum flow requirement for next largest listed coverage area. Minimum spacing between horizontal sidewall sprinklers is 8 ft. (2.4 m). Minimum distance from a horizontal sidewall sprinkler and an adjacent wall is 4” (102 mm). Hydraulic Requirements: For NFPA 13D Systems, the number of design sprinklers shall include all sprinklers within a compartment, up to a maximum of two sprinklers (where specific UL Listed flows are required) that requires the greatest hydraulic demand. For NFPA 13R Systems, the number of design sprinklers shall include all sprinklers within a compartment, up to a maximum of four (4) sprinklers (where specific UL Listed flows are required), that requires the greatest hydraulic demand. 6. 7. 8. 9. a. b. For NFPA 13 systems, the design area shall be the area that includes the four (4) hydraulically most demanding sprinklers. The minimum required discharge from each of the four hydraulically demanding sprinklers shall be the greater of the following: (1) In accordance with the minimum flow rates indicated by the individual listings (that already will provide a minimum density of 0.1 gpm/ft2); or (2) A calculated value based on delivering a minimum of 0.1 gpm/ft2 over the design area. Because of the varied nature of residential construction features, there will be some compartment designs which cannot be fully sprinklered in accordance with c. 10. Fig. 7 12. NFPA 13, 13D, or 13R. In these instances, consult the Authority Having Jurisdiction (AHJ) for guidance and approval. This includes sloped ceilings having a pitch greater than 8/12 (33.7°). Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACE IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. 11. Model F1 res 49 Pendent, F1 Recessed Pendent/F2, F1Res 49 Concealed (CCP), RFC 49 and RFC 43 installed below sloped ceiling with a maximun slope of 8/12 (33.7°) pitch. Table 9 -Application Model K -Factor (metric) Max. Spacing Ft. x Ft (m x m) Min. Flow/Pressure gpm (lpm) /psi (bar) Sprinkler Temperature Rating °F (°C) Coverplate Temperature Rated°F (°C) F1 Res 49Pendent 4.9 (69,94) 10 x 10 (3 x 3) 13(49) /7.0(0,48) 155 (68) --F1 Res 49 Reccesed Pendent/F2 4.9 (69,94) 10 x 10 (3 x 3) 13(49) /7.0(0,48) 155 (68) --F1 Res 49CCP Pendent 4.9 (69,94) 10 x 10 (3 x 3) 13(49) /7.0(0,48) 155 (68) 135 (57) RFC49Pendent 4.9 (69,94) 10 x 10 (3 x 3) 14(53) /8.2(0,57) 165 (74) 135 (57) RFC43Pendent 4.3 (61,4) 10 x 10 (3 x 3) 18(68) /17.5(1,21) 165 (74) 135 (57) 13.   Fig. 8 Hydraulic Requirements: For UL1626A, the number of design sprinklers shall include up to a maximum of two sprinklers that requires the greatest hydraulic demand. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACE IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. A maximum distance from the floor to the ceiling peak of 24 ft. A maximum of two sprinklers installed within 3 ft. vertically of the peak. Installation is for smooth, flat ceilings only that do not extend into or serve as a ceiling for an upper level floor in the structure. 8. a. 9. 10. 11. 12. Installation Guidelines per UL1626A For systems designed in accordance with NFPA 13, 13D and 13R, where specific UL Listed flows are not required, consult with the local Authority Having Jurisdiction regarding the number of design sprinklers for sloped ceilings having pitch greater than (9.4°). Installation of UL Listed residential sprinklers under sloped ceilings shall be limited to a type of unobstructed construction consisting of smooth ceilings, as defined by NFPA 13, having a maximum pitch of 8/12 (33.7°). Spacing of residential sprinklers under sloped ceilings is measured along the slope when determining the distance off of walls and between sprinklers. Measure listed areas of coverage along the sloped ceiling. The actual floor coverage area will be less than the listed area. For coverage areas less than the listed coverage area shown in Tables 8, use the minimum flow requirement listed. Minimum spacing between pendent type sprinklers is 8 ft. (2.4 m). Minimum distance from a pendent type sprinkler and an adjacent wall is 4” (102 mm). Reidential sprinklers located closest to the peak of the ceiling ceiling shall have the deflectors located not more than 3 ft (1 m) vertically down from the peak. Align deflectors parallel with the ceiling slope 1” to 4” (25mm to 102mm) below the slope ceiling. 1. 2. 3. 4. 5. 6. 7. The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A 11/09 P/N 9999970245 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. CPVC PIPE CPVC FIRE SPRINKLER PRODUCTS PROGRESSIVE PRODUCTS FROM SPEARS INNOVATION & TECHNOLOGY FG-2-0700 Corrosion Resistant CPVC Material Does Not Sustain Biological Growth Unlike metal systems, FlameGuard™ CPVC products never rust, scale or pit and do not sustain biological growth -a cause of Microbiologically Influenced Corrosion (MIC) which can destroy metal fire sprinkler systems from the inside out. Superior Flow Characteristics for Lower Friction Losses The smooth-wall interior surfaces of FlameGuard™ CPVC systems result in reduced friction loss over metal systems. The design flow characteristics remain constant throughout the life of the product because there is no interior corrosion in the system due to microbiological activity. Pressure Rated to 175 psi @150° F FlameGuard™ CPVC Fittings are produced in a combination of Schedule 40 and Schedule 80 configurations conforming to ASTM F438 or F439 standards for use with SDR 13.5 CPVC fire sprinkler pipe. UL Rated working pressure is 175 psi @150° F (LPCB rated to 120°F). Easy Installation for Lower Costs FlameGuard™ CPVC system installations significantly reduce costs over conventional metal piping by virtually eliminating prefabrication. Systems can be fully installed onsite using solvent cement joining methods. UL Listed for NFPA 13, 13R & 13D Systems FlameGuard™ CPVC Fire Sprinkler Products are UL listed for Light Hazard occupancies as defined in NFPA 13, Residential occupancies up to and including 4-stories as defined in NFPA 13R, and Residential occupancies for one and two family dwellings and manufactured homes as defined in NFPA 13D. Consult Spears CPVC Fire Sprinkler Piping Products Installation Instructions and NFPA Standards for additional applications including air plenum, system risers, underground, attic, and garage installations. Full 10-Year Limited Warranty FlameGuard™ CPVC Fire Sprinkler Products are warranted for 10 years against defects in material or workmanship. Consult Spears FlameGuard™ warranty for additional details. Visit our web site: www.spearsmfg.com CORROSION RESISTANT SUPERIOR FLOW EASE OF INSTALLATION Spears FlameGuard™ CPVC Fire Sprinkler Products provide a cost effective alternative to metal systems with advantages of high corrosion resistance, improved system hydraulics, ease of installation, and quick assembly with readily available tools. CPVC Fire Sprinkler Systems are based on proven products that have been in continuous service for over 40 years. Spears FlameGuard™ products are approved by UL, FM Global, LPCB and Certified by NSF International for potable water use. Check local codes for restrictions and limitations. FlameGuardTM Pioneer in Molded-in Brass Insert Head Adapters Spears pioneered the development of the FlameGuard™ moldedin-place brass thread insert for connection of sprinkler heads to CPVC fire sprinkler systems, then refining the design to produce one of the most reliable adapters of its type. Available in straight and reducing sizes with 1/2", 3/4" and 1" Brass FIPT threads, plus 3/4" through 2" Brass FIPT threaded female adapters for metal-to-plastic transitions. Innovator of Advanced Stainless Steel Reinforced (SR) Head Adapters Spears FlameGuard™ continuous improvement program developed the technology to produce a superior patented plastic threaded fitting -the Stainless Steel Reinforced (SR) Design. This unique design incorporates a patented thermoplastic compression process that equalizes stresses generated by tapered thread joint make-up. All CPVC plastic body and threads provide a more uniform construction and improved corrosion resistance. Available in straight and reducing sizes with 1/2", 3/4" and 1" SR FIPT threads, plus 3/4" through 1-1/4" SR FIPT threaded female adapters for metal-to-plastic transitions. Full Assortment of Specialty Products & Fittings Configurations Spears FlameGuard™ provides the specialty fittings needed in today's fire sprinkler systems. Like the adjustable drop nipple for fine-tuning to finished ceiling height, side-wall tees for opposing heads, and ringed head adapter for ease of locating during installation. Plus, Spears FlameGuard™ line offers a full assortment of CPVC fire sprinkler fitting configurations including Tees, Elbows, Flanges, Couplings, Caps, Grooved Coupling Adapters and Unions, sizes 3/4" through 3". Spears Solvent Cements & Thread Sealant FlameGuard™ products should be installed using Spears FS-3 Solvent Cement & FS-1 Primer or FS-5 One-Step Solvent Cement. For threaded joints, use Spears BLUE 75™ Thread Sealant that has been tested for compatibility with FlameGuard™ CPVC Fire Sprinkler Products. Consult sprinkler head manufacturer prior to use. © Copyright 2000 Spears Manufacturing Company. All Rights Reserved. Printed in the United States of America 07/00. FG-2-0700 Spears FlameGuard™ . . . The Leader in Innovative CPVC Fire Sprinkler System Products Installation Training Available -Contact Spears Technical Services for Details FlameGuard™ Products must be installed in accordance with Spears CPVC Fire Sprinkler Piping Products Installation Instructions, National Fire Protection Association Standards 13, 13R, 13D, and in accordance with local codes. Code requirements and field conditions may differ. It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. SPEARS® MANUFACTURING COMPANY CORPORATE OFFICES 15853 Olden Street, Sylmar, CA 91342 P.O. Box 9203, Sylmar, CA 91392 (818) 364-1611 • http://www.spearsmfg.com Spears FlameGuardTM SR Sprinkler Head Adapters are available in socket or spigot by SR Thread configurations including Sprinkler Head Tees, 90° Elbows and Female Adapters. Available in 1/2" through 1-1/4" Thread Sizes Potable Water Approved Certified by NSF International, lead-free thermoplastic compounds are safe for use in drinking waer systems. All SR Sprinkler Head Adapters conform to ASTM F 439 requirements for dimensions and hydrostatic pressure test. Full ASTM Schedule 80 Conformance SR Adapters are produced from CPVC thermoplastic compound for superior chemical and corrosion resistance to system fluids. Corrosion Resistant Spears patented SR design and manufacturing process allows direct connection to fire sprinkler heads or threaded metal pipe through one simple adapter. Material thermal expansion/contraction differences are equalized by the restraining collar. You get low-cost, worry-free plastic-to-metal transitions every time. Designed for Sprinkler Heads & Plastic-to-Metal Transitions One-piece piece fitting design increases reliability and maintains system integrity. One-Piece Fitting Construction SPEARS FlameGuardTM STAINLESS STEEL REINFORCED (SR) CPVC FIRE SPRINKLER HEAD ADAPTER FITTINGS FS-2B-0200 Spears patended stainless steel reinforced (SR) Plastic female thread design is one of the most significant advancements in the use of CPVC fire sprinkler system threaded fittings. Not just an added ring, this unique precompression design compensates for expansion forces generated from tapered pipe thread joint makeup. Radial stress is no longer a problem in normal installations and easily managed in severe over-tightening situations. Tested & Approved by Underwriters Laboratories Spears FlameGuardTM Fire Sprinkler Piping Products are Listed by Underwriters Laboratories for use in: Light Hazard occupancies as defined in the Standard for Installation of Sprinkler Systems, NFPA 13; Residential occupancies as defined in the Standard for Installation of Sprinkler Systems up to Four Stories in height, NFPA 13R; Residential occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings and Mobile Homes, NFPA 13D; and Air Conditioning and Ventilation Systems, NFPA 90A. Visit our web site: www.spearsmfg.com PROGRESSIVE PRODUCTS FROM SPEARS INNOVATION & TECHNOLOGY Easy Threaded Joint Make-up Hexagonal Wrench Flats Stainless Steel Precompression Collar Provides External Reinforcement For Superior Joint Integrity Full Schedule 80 Wall Thickness Advanced Patented Technology Factory Mutual (FMRC) and UL Approved! NOT FOR USE WITH COMPRESSED AIR OR GASES Another Quality Spears Product Designed for Performance, Customer Satisfaction and Service Radial stress generated by tightening of tapered pipe threads exerts tremendous expansion forces on female plastic thread fittings. When subjected to over-tightening — even accidentally — these forces can literally split the fitting. Spears patented SR Adapter design not only alleviates this problem by containing expansion forces with its stainless steel collar, but additionally compensates for expansion stress through thermoplastic material compression. Stresses are equalized at normal joint make-up. The following graph illustrates this effect in a comparison of conventional plastic female thread fittings with Spears SR adapters when taken to failure. SPEARS Patented SR Design Contains and Compensates for Radial Stress . . . THREADED CONNECTIONS — Use a quality grade thread sealant. WARNING: SOME PIPE JOINT COMPOUNDS OR TEFLON PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING TO PLASTIC. Spears Manufacturing Company recommends the use of Spears BLUE 75TM Thread Sealant which has been tested for compatibility with Spears products. Please follow the sealant manufacturer's application/installation instructions. Choice of an appropriate thread sealant other than those listed above is at the discretion of the installer. 1 to 2 turns beyond FINGER TIGHT is generally all that is required to make a sound plastic threaded connection. Unnecessary OVERTIGHTENING will cause DAMAGE TO BOTH PIPE AND FITTING. No warranty of service is implied or expressed on the basis of this literature by Spears Manufacturing Company, Sylmar, California. All rights reserved. © Copyright 2000 Spears Manufacturing Company. All Rights Reserved. Printed in the United States of America 9/00. FS-2B-0200 SPEARS® MANUFACTURING COMPANY NORTHEAST FLORIDA MIDWEST 15853 Olden Street Sylmar (Los Angeles), CA 91342 P.O. Box 9203 Sylmar, CA 91392 (818) 364-1611 FAX: (818) 898-3774 E-mail: export@spearsmfg.com INTERNATIONAL SALES 854 Fairway Drive Bensenville (Chicago), IL 60106 (630) 773-0075 (800) 662-6330 FAX: (630) 773-0435 3445 Barlett Boulevard Orlando, FL 32811 (407) 843-1960 (800) 327-6390 FAX: (407) 425-3563 SOUTHEAST 2751 Miller Road Decatur (Atlanta), GA 30035 (770) 981-7122 (800) 662-6326 FAX: (770) 981-6106 543 Industrial Drive Lewisberry (Harrisburg), PA 17339-9532 (717) 938-8844 (800) 233-0275 FAX: (717) 938-6547 15860 Olden Street Sylmar (Los Angeles), CA 91342 P.O. Box 9203, Sylmar, CA 91392 (818) 364-1611 (800) 862-1499 FAX: (818) 367-3014 PACIFIC SOUTHWEST NORTHWEST 3902 "B" Street N.W. Auburn (Seattle), WA 98001 (253) 939-4433 (800) 347-7327 FAX: (253) 939-7557 1415 South 700 West #3 Salt Lake City, UT 84104 (801) 972-0659 FAX: (801) 972-0688 UTAH 1838 Forms Drive Carrollton (Dallas), TX 75006 (972) 245-0387 (800) 441-1437 FAX: (972) 245-4205 SOUTH CENTRAL 4880 Florence Street Denver, CO 80238 (303) 371-9430 (800) 777-4154 FAX: (303) 375-9546 ROCKY MOUNTAIN CORPORATE OFFICES 15853 Olden Street, Sylmar, CA 91342 P.O. Box 9203, Sylmar, CA 91392 (818) 364-1611 • http://www.spearsmfg.com SPEARS Spears FlameGuardTM SR Sprinkler Head Adapters are available in socket or spigot by SR Thread configurations including Sprinkler Head Tees, 90° Elbows and Female Adapters. Available in 1/2" through 1-1/4" Thread Sizes Potable Water Approved Certified by NSF International, lead-free thermoplastic compounds are safe for use in drinking waer systems. All SR Sprinkler Head Adapters conform to ASTM F 439 requirements for dimensions and hydrostatic pressure test. Full ASTM Schedule 80 Conformance SR Adapters are produced from CPVC thermoplastic compound for superior chemical and corrosion resistance to system fluids. Corrosion Resistant Spears patented SR design and manufacturing process allows direct connection to fire sprinkler heads or threaded metal pipe through one simple adapter. Material thermal expansion/contraction differences are equalized by the restraining collar. You get low-cost, worry-free plastic-to-metal transitions every time. Designed for Sprinkler Heads & Plastic-to-Metal Transitions One-piece piece fitting design increases reliability and maintains system integrity. One-Piece Fitting Construction SPEARS FlameGuardTM STAINLESS STEEL REINFORCED (SR) CPVC FIRE SPRINKLER HEAD ADAPTER FITTINGS FS-2B-0200 Spears patended stainless steel reinforced (SR) Plastic female thread design is one of the most significant advancements in the use of CPVC fire sprinkler system threaded fittings. Not just an added ring, this unique precompression design compensates for expansion forces generated from tapered pipe thread joint makeup. Radial stress is no longer a problem in normal installations and easily managed in severe over-tightening situations. Tested & Approved by Underwriters Laboratories Spears FlameGuardTM Fire Sprinkler Piping Products are Listed by Underwriters Laboratories for use in: Light Hazard occupancies as defined in the Standard for Installation of Sprinkler Systems, NFPA 13; Residential occupancies as defined in the Standard for Installation of Sprinkler Systems up to Four Stories in height, NFPA 13R; Residential occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings and Mobile Homes, NFPA 13D; and Air Conditioning and Ventilation Systems, NFPA 90A. Visit our web site: www.spearsmfg.com PROGRESSIVE PRODUCTS FROM SPEARS INNOVATION & TECHNOLOGY Easy Threaded Joint Make-up Hexagonal Wrench Flats Stainless Steel Precompression Collar Provides External Reinforcement For Superior Joint Integrity Full Schedule 80 Wall Thickness Advanced Patented Technology Factory Mutual (FMRC) and UL Approved! NOT FOR USE WITH COMPRESSED AIR OR GASES Another Quality Spears Product Designed for Performance, Customer Satisfaction and Service Radial stress generated by tightening of tapered pipe threads exerts tremendous expansion forces on female plastic thread fittings. When subjected to over-tightening — even accidentally — these forces can literally split the fitting. Spears patented SR Adapter design not only alleviates this problem by containing expansion forces with its stainless steel collar, but additionally compensates for expansion stress through thermoplastic material compression. Stresses are equalized at normal joint make-up. The following graph illustrates this effect in a comparison of conventional plastic female thread fittings with Spears SR adapters when taken to failure. SPEARS Patented SR Design Contains and Compensates for Radial Stress . . . THREADED CONNECTIONS — Use a quality grade thread sealant. WARNING: SOME PIPE JOINT COMPOUNDS OR TEFLON PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING TO PLASTIC. Spears Manufacturing Company recommends the use of Spears BLUE 75TM Thread Sealant which has been tested for compatibility with Spears products. Please follow the sealant manufacturer's application/installation instructions. Choice of an appropriate thread sealant other than those listed above is at the discretion of the installer. 1 to 2 turns beyond FINGER TIGHT is generally all that is required to make a sound plastic threaded connection. Unnecessary OVERTIGHTENING will cause DAMAGE TO BOTH PIPE AND FITTING. No warranty of service is implied or expressed on the basis of this literature by Spears Manufacturing Company, Sylmar, California. All rights reserved. © Copyright 2000 Spears Manufacturing Company. All Rights Reserved. Printed in the United States of America 9/00. FS-2B-0200 SPEARS® MANUFACTURING COMPANY NORTHEAST FLORIDA MIDWEST 15853 Olden Street Sylmar (Los Angeles), CA 91342 P.O. Box 9203 Sylmar, CA 91392 (818) 364-1611 FAX: (818) 898-3774 E-mail: export@spearsmfg.com INTERNATIONAL SALES 854 Fairway Drive Bensenville (Chicago), IL 60106 (630) 773-0075 (800) 662-6330 FAX: (630) 773-0435 3445 Barlett Boulevard Orlando, FL 32811 (407) 843-1960 (800) 327-6390 FAX: (407) 425-3563 SOUTHEAST 2751 Miller Road Decatur (Atlanta), GA 30035 (770) 981-7122 (800) 662-6326 FAX: (770) 981-6106 543 Industrial Drive Lewisberry (Harrisburg), PA 17339-9532 (717) 938-8844 (800) 233-0275 FAX: (717) 938-6547 15860 Olden Street Sylmar (Los Angeles), CA 91342 P.O. Box 9203, Sylmar, CA 91392 (818) 364-1611 (800) 862-1499 FAX: (818) 367-3014 PACIFIC SOUTHWEST NORTHWEST 3902 "B" Street N.W. Auburn (Seattle), WA 98001 (253) 939-4433 (800) 347-7327 FAX: (253) 939-7557 1415 South 700 West #3 Salt Lake City, UT 84104 (801) 972-0659 FAX: (801) 972-0688 UTAH 1838 Forms Drive Carrollton (Dallas), TX 75006 (972) 245-0387 (800) 441-1437 FAX: (972) 245-4205 SOUTH CENTRAL 4880 Florence Street Denver, CO 80238 (303) 371-9430 (800) 777-4154 FAX: (303) 375-9546 ROCKY MOUNTAIN CORPORATE OFFICES 15853 Olden Street, Sylmar, CA 91342 P.O. Box 9203, Sylmar, CA 91392 (818) 364-1611 • http://www.spearsmfg.com SPEARS Harvel Plastics, Inc. • 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • Fax: 610.253.4436 • www.harvelsprinklerpipe.com Product Specifications Harvel® Blazemaster® CPVC Fire Sprinkler Pipe Product Specifications Harvel® Blazemaster® Application: Corrosion resistant fire sprinkler pipe, IPS sizes 3/4" through 3", for use in wet automatic fire sprinkler systems. When installed in accordance with Harvel’s Installation Instructions, this pipe is Listed by Underwriters Laboratories (UL) for use in: Light Hazard Occupancies as defined in the Standard for Installation of Sprinkler systems (NFPA 13); Residential Occupancies up to and including four stories in height (NFPA 13R); and Residential Occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings and Mobile Homes (NFPA 13D). Harvel BlazeMaster‚ pipe is UL Listed for use in Return Air Plenums (NFPA 90A), System Risers per NFPA 13 Light Hazard, 13R and 13D, Exposed installations, Garages per NFPA 13R, and for use as Underground Fire Service Mains (NFPA 24) when installed in accordance with Harvel CPVC Fire Sprinkler Pipe Installation Instructions. Scope: This specification outlines minimum manufacturing requirements for Chlorinated Polyvinyl Chloride (CPVC) standard dimension ratio (SDR) 13.5 series iron pipe size (IPS) fire sprinkler pressure pipe. Pipe is intended for use in wet automatic fire sprinkler systems when installed in accordance with Harvel Plastics, Inc. CPVC Fire Sprinkler Piping Products Installation Instructions. Harvel‚ BlazeMaster‚ pipe carries a maximum working pressure of 175 psi @150°F. Pipe meets or exceeds applicable industry standards and requirements as set forth by the American Society for Testing and Materials (ASTM), the National Sanitation Foundation (NSF), and Underwriters Laboratories (UL). Harvel‚ BlazeMaster‚ fire sprinkler pipe is approved by the Factory Mutual Corporation (FM) and the Loss Prevention Certification Board (LPCB). Refer to current approval guide and installation and design manual for installation limitations. CPVC Materials: The material used in the manufacture of the pipe shall be a rigid chlorinated polyvinyl chloride (CPVC) compound, Type IV Grade I, with a Cell Classification of 23547 as defined in ASTM D1784. The compound and the finished product shall be orange in color, and shall be approved by the National Sanitation Foundation (NSF) for use with potable water. Material used shall be domestically produced BlazeMaster‚ CPVC material as provided by Noveon, Inc. (formerly the BFGoodrich Company). System Design: The CPVC sprinkler system shall be hydraulically calculated using a Hazen-Williams C factor of 150, and shall be designed in strict accordance with the Standard for Installation of Sprinkler Systems, NFPA 13 Light Hazard, NFPA 13R, and NFPA 13D as applicable. Dimensions: Harvel BlazeMaster‚ CPVC fire sprinkler pipe shall be manufactured to Standard Dimension Ratio (SDR) 13.5 dimensions in strict accordance to the requirements of ASTM F442 for physical dimensions and tolerances. Each production run of pipe manufactured in compliance to this standard, shall also meet the test requirements for materials, workmanship, burst pressure, flattening, and extrusion quality defined in ASTM F442. Furthermore, this pipe shall consistently meet or exceed the physical performance test requirements of the appropriate approval/listing agency(s) follow-up procedures established for the product. Marking: Product marking shall meet the requirements of ASTM F 442 and the Listing agency. Marking shall include: the phrase Harvel® BlazeMaster® (or the manufacturers’ trademark when privately labeled); the nominal pipe size; the type of material and material designation code; the SDR series and pressure rating for water (SDR 13.5; 175 psi @150°F); the ASTM designation F 442; the logo of the Listing and Approval agencies (UL, FM, LPCB, etc.); the independent laboratory’s seal of approval for potable water usage (NSF-pw); the date and time of manufacture; and the UL assigned control number (2N95). Installation Procedures: All installation procedures such as storage and handling, solvent cement joining techniques, pipe support spacing, bracing, allowance for thermal expansion/contraction, component assembly techniques, and testing etc. shall be in strict accordance with Harvel Plastics, Inc. Installation Instructions and the UL Listing which includes installation limitations. System Components: Fittings used shall be UL Listed CPVC fittings and shall meet or exceed the requirements of ASTM F437 (Sch 80 threaded), ASTM F437 (Sch 80 socket), or ASTM F438 (Sch 40 socket) as applicable, such as those manufactured by Spears Manufacturing Co. or equivalent. Solvent cements used shall be those referenced in Harvel Plastics, Inc. Installation Instructions (such as Spears FS-5 or equivalent), which meet or exceed the requirements of ASTM F656 and ASTM F493, and shall be approved by the National Sanitation Foundation (NSF) for use with potable water. Socket type joints, sizes 3/4" -3", shall be made up using the One-Step solvent cement joining method. The solvent cement joining method chosen shall be applied in strict accordance with the appropriate procedures as outlined in Harvel Plastics Installation Instructions. Maintenance: Maintenance shall be in accordance with the Standard for Inspection, Testing, and Maintenance of Water Based Sprinkler Systems as defined by NFPA 25. Harvel Plastics, Inc. • 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • Fax: 610.253.4436 • www.harvelsprinklerpipe.com Product Specifications Harvel® Blazemaster® CPVC Fire Sprinkler Pipe Harvel® Blazemaster® Product Specifications Limitations: • CPVC systems are intended for use at a maximum working pressure of 175 psi and ambient temperature of 150°F. • CPVC systems shall employ sprinkler heads having a maximum temperature rating of 225°F or lower, regardless of type. • CPVC products shall be installed in wet pipe systems only. • Air or compressed gas shall never be used for pressure testing. • CPVC sprinkler systems shall be hydrostatically tested for 2 hours at 200 psi, or 50 psi in excess of the maximum working pressure when the maximum working pressure exceeds 150 psi. Lines shall be slowly filled with water and the air bled from the highest and farthest sprinkler heads before test pressure is applied. • Only Teflon® tape or a thread sealant specifically approved for use with Harvel® CPVC Fire Sprinkler Products shall be used in making threaded connections. • Where freeze protection is required, only glycerin based anti-freeze solutions shall be used and installed in accordance with NFPA 13. Do not use glycol base anti-freeze solutions or contaminated glycerin solutions. • CPVC is not approved for use in combustible concealed spaces where sprinklers are required to protect these areas as defined by NFPA 13, unless certain specific application sprinklers are installed per their listing. Refer to Harvel’s current Installation Instructions for additional information. • CPVC sprinkler piping may be installed in a plenum space adjacent to, but not over, openings in the ceiling such as open ventilation grills, and require the use of schedule 80 fittings for use on 11/2" and larger pipe sizes. Refer to Installation Instructions for additional detail. • Minimum protection when installed “concealed” shall consist of: 3/8" gypsum wallboard or drywall, suspended membrane ceiling panels weighing not less less than .35 pounds per square foot, or 1/2" plywood soffits. Minimum protection for NFPA 13R and 13D systems may consist of 1/2" plywood. • Harvel‚ BlazeMaster‚ pipe is Listed for use in exposed applications with certain limitations. When installed without protection, “exposed” pipe is to be installed beneath smooth, flat, horizontal ceiling construction. Exposed categories include: standard coverage and residential pendent and sidewall sprinkler applications, light hazard extended coverage and residential sprinkler pendent and sidewall sprinkler applications, use in unfinished basements with exposed solid wood joists, light hazard upright quick response sprinklers, and system risers (in 13R & 13D occupancies). Refer to Harvel’s installation instructions for specific sprinkler head temperature ratings and spacing requirements. The product must be installed in strict accordance with NFPA 13, 13D, 13R and Harvel’s current CPVC Fire Sprinkler Piping Products Installation Instructions (HFS-3). • Harvel CPVC Fire Sprinkler Products must be installed in accordance with Harvel’s current installation instructions (HFS-3). Refer to this document for current listing limitations and installation requirements. ASTM STANDARD D1784 MATERIAL CLASSIFICATION EQUIVALENTS: Cell Classification 23447 = CPVC Type IV Grade I = CPVC 4120 PIPE SIZES SHOWN ARE MANUFACTURED IN STRICT COMPLIANCE WITH ASTM F442 Sample Specification: All CPVC fire sprinkler pipe shall be manufactured from a Type IV, Grade I Chlorinated Polyvinyl Chloride (CPVC) compound with a Cell Classification of 23547 per ASTM D1784. Pipe shall be manufactured in strict compliance with ASTM F442 to SDR 13.5 dimensions, consistently meeting the Quality Assurance test requirements of this standard with regard to material, workmanship, burst pressure, flattening, and extrusion quality. All CPVC fire sprinkler pipe shall be Listed by Underwriters Laboratories for wet pipe systems, and shall carry a rated working pressure of 175 psi @150°F. All CPVC fire sprinkler pipe shall be installed in accordance with Harvel Plastics, Inc. CPVC Fire Sprinkler Piping Products Installation Instructions. National Fire Protection Association (NFPA) Standards 13, 13D, and 13R must be referenced for design and installation requirements in conjunction with the Installation Instructions. All CPVC fire sprinkler pipe shall be manufactured in the USA by an ISO 9001 certified manufacturer and shall be FM and LPCB approved. All CPVC fire sprinkler pipe shall be packaged immediately after its manufacture to prevent damage and shall be stored indoors after production, at the manufacturing site, until shipped from factory. This pipe shall bear the logo of the listing agencies, and shall carry the National Sanitation Foundation (NSF) seal of approval for potable water applications. All CPVC fire sprinkler pipe shall be Harvel® BlazeMaster® pipe as manufactured by HARVEL® PLASTICS, INC. Harvel CPVC Fire Sprinkler Pipe Dimensions SDR 13.5 (ASTM F442) Nominal Average Min. Average Nom.Wt. Size (in.) O.D. Wall I.D. Lbs./Ft. 3/4 1.050 0.078 0.874 0.168 1 1.315 0.097 1.101 0.262 1-1/4 1.660 0.123 1.394 0.418 1-1/2 1.900 0.141 1.598 0.548 2 2.375 0.176 2.003 0.859 2-1/2 2.875 0.213 2.423 1.257 3 3.500 0.259 2.950 1.867 CAUTION This CPVC fire sprinkler product is a Life Safety Assembly and must be treated carefully. Please read the following before any activity which could contact this system: • Read and follow Harvel’s Installation Instructions prior to use. Training by an authorized representative is available and is recommended. Proof of training may be required by local authorities. • CPVC piping components may be damaged by certain substances used in construction and building maintenance. • ONLY system compatible materials including, but not limited to solvent cements, caulks, sealants, cutting oils and thread pastes as noted in Harvel’s installation instructions should be used in contact with this system. • DO NOT expose CPVC products to incompatible substances such as cutting oils, non-water based paints, packing oils, traditional pipe thread paste and dope, fungicides, termiticides, insecticides, detergents, building caulks, adhesive tape, solder flux, flexible wire/cable (with special consideration for communications cabling), and non-approved spray foam insulation materials. • DO NOT expose CPVC products to edible oils, solvents, or glycol-based anti-freeze fluids. • When combining metallic pipe and fittings with CPVC products in a system, the cutting oils should be removed prior to assembly. • DO NOT store CPVC products in containers with metal products where it may become damaged or contaminated with packing oils. • DO NOT handle CPVC products with gloves contaminated with oils (hydrocarbons) or other incompatible materials. Failure to follow this notice and Harvel’s installation instructions may cause cracks or fractures to develop in CPVC products, resulting in property damage and personal injury due to leaks or flooding. The presence of any visible cracks may require partial or full system replacement. For additional information contact: 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • www.harvelsprinklerpipe.com