HomeMy WebLinkAboutB12-0016_17 comment letter Date: 2/09/2012 Re: B12-0016 and B12-0017 549/ 551 E Lionshead Circle Dear Mr. Stewart, RESPONSE INSTRUCTIONS ● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified showing compliance with the Town of Vail building codes. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Plumbing Comments: 1. Plans to be sealed and signed by an engineer licensed in the State of Colorado per section 106.3.1 IPC. 2. Provide actual flow rates for each fixture to be discharged through the grease interceptor. 3. Include on plans all fixtures required to be discharged to the grease interceptor per section 1003.3.1 IPC. 4. Plans do not reflect the required flow controls per section 1003.3.4.2 IPC. Revise plans. 5. Provide plumbing isometric showing waste/ vent piping installation showing compliance with the plumbing code. Reference section 106.3.1 IPC Sincerely, Martin A. Haeberle Chief Building Official