HomeMy WebLinkAboutB12-0029 Plans approved East ElectricalPROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL C VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:100A MLO TYPE: SQUARE D NQOD AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION EXTERIOR LIGHTING322 2011212030 MAIDS CLOSET FANS COMMON AREA LIGHTS 1280 20134120 900 RECEPTACLES (5)SPACE 0 56120 180CUH-3 SPACE0 780 SPACE SPACE 0 910 0 SPACE SPACE 01112 0SPACE SPACE0 13140 SPACE SPACE 0 1516 0 SPACE SPACE 01718 0SPACE SPACE0 19200 SPACE SPACE 0 2122 0 SPACE SPACE 02324 0SPACE SPACE0 25263301087 ELEV LOAD CENTER EC SPACE 0 2728 1087 "SPACE 02930 1087"LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.93 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING2030625387 RECEPTACLES1440414404 MECHANICAL25028307510 KITCHEN0000 TOTAL597218705321 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL D VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:100A MLO TYPE: SQUARE D NQOD AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION EXTERIOR LIGHTING322 2011212030 MAIDS CLOSET FANS COMMON AREA LIGHTS 1280 20134120 900 RECEPTACLES (5)SPACE 0 56120 180CUH-2 SPACE0 780 SPACE SPACE 0 910 0 SPACE SPACE 01112 0SPACE SPACE0 13140 SPACE SPACE 0 1516 0 SPACE SPACE 01718 0SPACE SPACE0 19200 SPACE SPACE 0 2122 0 SPACE SPACE 02324 0SPACE SPACE0 25263301087 ELEV LOAD CENTER ED SPACE 0 2728 1087 "SPACE 02930 1087"LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.93 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING2030625387 RECEPTACLES1440414404 MECHANICAL25028307510 KITCHEN0000 TOTAL597218705321 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK AND ASSOCIATES ENGINEER:SOH DESCRIPTION: METERBANK EXISTING UNITS 1ST SECTIONVOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:1600A MLO TYPE: SQUARE D AIC:42k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION TYPICAL EXISTING CONDO9165 10021221009165 TYPICAL EXISTING CONDO " 9165 34 9165 "TYPICAL EXISTING CONDO 91651002562100 9165TYPICAL EXISTING CONDO "9165 789165 "TYPICAL EXISTING CONDO 9165 10029102100 9165 TYPICAL EXISTING CONDO " 91651112 9165"TYPICAL EXISTING CONDO9165 1002131421009165 TYPICAL EXISTING CONDO " 9165 1516 9165 "TYPICAL EXISTING CONDO 9165100217182100 9165TYPICAL EXISTING CONDO "9165 19209165 "TYPICAL EXISTING CONDO 9165 100221222100 9165 TYPICAL EXISTING CONDO " 91652324 9165"TYPICAL EXISTING CONDO9165 1002252621009165 TYPICAL EXISTING CONDO " 9165 2728 9165 "TYPICAL EXISTING CONDO 9165100229302100 9165TYPICAL EXISTING CONDO "9165 31329165 "TYPICAL EXISTING CONDO 9165 100233342100 9765 TYP CONDO W ADD'N " 91653536 9765"TYPICAL EXISTING CONDO9165 1002373821009765 TYP CONDO W ADD'N " 9165 3940 9765 " 04142 0 LOAD CALCULATION SUMMARYNOTE: LOADS BELOW INCLUDE LOADS FROM SECOND SECTION OF METERBANK CALCULATED POWER FACTOR:0.96 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS APPLIANCES5580015541850116 LIGHTING & RECEPT.14936041454226150 MECHANICAL131750429132813433 KITCHEN OVEN 27834477166803185 TOTAL6152541769295691REF LOAD CALCS PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: MAIN DISTRIBUTION CENTER (MDC)VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS: 2,800 A MLO TYPE: PER SPECIFICATIONS AIC:TBD PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION HOUSE SERVICE83543 12003123800205085 EXISTING METERBANK " 83543 34 205085 "" 8354356 205085" 0 78 0 0 910 0 01112 0 0 13140 0 1516 0 01718 0 0 19200 0 2122 0 02324 0 0 25260 0 2728 0 02930 0 0 31320 0 3334 0 03536 0 0 37380 0 3940 0 04142 0 LOAD CALCULATION SUMMARYNOTE: PROVIDE (3) 1"C STUBBED UP TO ABOVE THE ACCESSIBLE CEILING FOR FUTURE. PROVIDE FEED THROUGH LUGS FOR SECOND SECTION. LOADS FROM THAT SECTION CALCULATED POWER FACTOR:0.94ARE INCLUDED IN THIS PANEL'S CONNECTED & DEMAND LOAD CALCULATIONS.CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS HOUSE DEMAND250628773256326792 RESI. APPLIANCES5580016341850122 RESI. LTG & REC14936041454226150 RESI. MECHANICAL131750429131750429 RESI. KITCHEN27834477161236170 TOTAL86588225505453871664 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL HOUSE VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:1200A MLO TYPE: SQUARE D I-LINE TYPE HCP AIC:25k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION PANEL H123535 20031231509717 ELEVATOR #1 (40 HP)" 23535 34 9717 S HUNT TRIP " 2353556 9717"PANEL A1716 20037831509717 ELEVATOR #2 (40 HP)" 1716 910 9717 S HUNT TRIP " 17161112 9717"PANEL B1691 1003131431509717 ELEVATOR #3 (40 HP)" 1691 1516 9717 S HUNT TRIP " 16911718 9717"PANEL C1991 1003192031509717 ELEVATOR #4 (40 HP)" 1991 2122 9717 S HUNT TRIP " 19912324 9717"PANEL D1991 1003252631008380 PANEL #10 " 1991 2728 8380 "" 19912930 8380"PANEL E5373 100331320 SPACE " 5373 3334 0 SPACE " 53733536 0SPACE SPACE0 37380 SPACE SPACE 0 3940 0 SPACE SPACE 04142 0SPACE LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.90 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING14418421441842 RECEPTACLES13180371159032 MECHANICAL156686511163974534 KITCHEN6634418466344184 TOTAL250628773256326792 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL "A"VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:100A MLO TYPE: SQUARE D NQOD NEMA 3R AIC:22k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION BOILER #1 & GF-1250 20112320422 SUPPLY FAN #1 PUMP #1 150 20134 422 "PUMP #2 89020156 422"SUPPLY FANS #2 & 31050 201780 SPACE ELEC ROOM REC(3) 540 201910 0 SPACE (RL) TIMECLOCK 10002011112 0SPACE SPACE0 13140 SPACE SPACE 0 1516 0 SPACE SPACE 01718 0SPACE SPACE0 19200 SPACE SPACE 0 2122 0 SPACE SPACE 02324 0SPACE SPACE0 25260 SPACE SPACE 0 2728 0 SPACE SPACE 02930 0SPACE LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.90 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING1000312504 RECEPTACLES74027402 MECHANICAL3407113723.7512 KITCHEN0000 TOTAL514716571418 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL B VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:100A MLO TYPE: SQUARE D NQOD AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION EXTERIOR LIGHTING322 201120 SPACE COMMON AREA LIGHTS 1280 20134120 30 MAIDS CLOSET FANS SPACE 0 56120 180CUH-4 SPACE0 780 SPACE SPACE 0 910 0 SPACE SPACE 0 1112 0SPACE SPACE0 13140 SPACE SPACE 0 1516 0 SPACE SPACE 01718 0SPACE SPACE0 19200 SPACE SPACE 0 2122 0 SPACE SPACE 02324 0SPACE SPACE0 25263301087 ELEV LOAD CENTER EB SPACE 0 2728 1087 "SPACE 02930 1087"LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.92 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING2030625387 RECEPTACLES54015401 MECHANICAL25028307510 KITCHEN0000 TOTAL507216615319 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL ELEVATOR LOAD CENTER TYPICAL "EB", "EC", "ED"VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:30A MLO TYPE: SQUARE D QO AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION HOISTWAY PIT LTS/REC(1)244 201122201096 PTAC-1 ELEV ROOM LTS/FAN/REC(1) 294 20134 1096 "ELEV CAB LTS/FAN/REC 53020156 0SPACE SPACE0 78 0 SPACE SPACE 0 910 0 SPACE SPACE 01112 0SPACE LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.89 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING42815352 RECEPTACLES54015401 MECHANICAL2292728409 KITCHEN0000 TOTAL326010391512 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL E VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:100A MLO TYPE: SQUARE D NQOD AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION EXTERIOR LIGHTING740 2011212030 MAIDS CLOSET FANS STAIR/HALL LIGHTS 1280 20134 0 SPACE SOUTH STAIR/HALL LIGHTS 48020156 0SPACE SPACE0 780 SPACE SPACE 0 910 0 SPACE RECEPTACLES (8) 14402011112 0SPACE CUH-1180 20113143201122 EXHAUST FAN #3 FIRE DOOR HOLD OPEN 200 2011516 1122 "SPACE 01718 1122"SPACE0 19203201465 CONDENSING UNIT #1 SPACE 0 2122 1465 "SPACE 02324 1465"SPACE0 25263301337 ELEV LOAD CENTER EE SPACE 0 2728 1337 "SPACE 02930 1337"LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.89 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING29289366011 RECEPTACLES2180621806 MECHANICAL110123612110.539 KITCHEN0000 TOTAL16120501795156 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK AND ASSOCIATES ENGINEER:SOH DESCRIPTION: METERBANK EXISTING UNITS 2ND SECTIONVOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:1600A MLO TYPE: SQUARE D AIC:42k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION TYP CONDO W ADD'N9765 1002122709765 EMPLOYEE APARTMENT #1 " 9765 34 9765 "TYP CONDO W ADD'N 9765100256270 9765EMPLOYEE APARTMENT #2 "9765 789765 "TYP CONDO W ADD'N 9765 1002910270 9765 EMPLOYEE APARTMENT #3 " 97651112 9765"TYP CONDO W ADD'N9765 10021314270EMPLOYEE APARTMENT #4 " 9765 1516"TYP CONDO W ADD'N PANEL LAUNDRY ""TYP CONDO W ADD'N ""TYP CONDO W ADD'N "LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.97 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS APPLIANCES19800551485041 LIGHTING & RECEPT.613601702342665 MECHANICAL4675015247812.5156 KITCHEN OVEN & DRYER11834432847338131 TOTAL246254705133426REF LOAD CALCS Quantity Volt-Amps Demand Total (VA)Residential Dwelling unit Square footage1992 General & Lighting (1st 3 KVA)1000 SF X 3X100%=3000 General & Lighting (Remainder)992 SF X 3X35%=1042 Small Appliance Circuits2 EA X1500X35%=1050 Refrigerator1 EA X1000X75%=750 Dishwasher1 EA X1200X75%=900 Oven/Range (Re:table220.19)1 EA X8000X80%=6400 Microwave1 EA X1200X75%=900 Disposal1 EA X1000X75%=750 Clothes Washer/Dryer0 EA X5000X100%=0 Steamshower0 EA X7500X75%=0 Electric Heat Heat/Light/Fan Combos3 EA X1500X100%=4500 TOTAL 19292 For 208V, 3-Phase, 4 Wire Service19292(VA) /208=93AMPS Optional Calculation NEC 220.83 Total of General Loads1 LS X21376 1st 8 kVA of General Loads1 LS X8000X100%=8000 40% of Remainder of General Loads1 LS X13376X40%=5350 100% of Electric Heat1 LS X4500X100%=4500 TOTAL 17850 For 208V, 3-Phase, 4 Wire Service17850(VA) /208=86AMPS LSLE - Condo with Loft Demand Load Calculations (Per NEC Article 220 Parts I-III)PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK ASSOCIATES ENGINEER:SOH DESCRIPTION: TYPICAL CONDO VOLTAGE:120/208V, 1P, 3W MOUNTING: RECESSED MAINS:100A MLO TYPE: QO RESIDENTIAL AIC:SERIES RATE TO 42k PHASE PHASE DESCRIPTION A BBKR PCIRCIR P BKR A BDESCRIPTION WATER HEATER2125 3021212501500 APPLIANCE CIRCUIT 212534120 50SMOKE DETECTORS RANGE4000 502561201500 APPLIANCE CIRCUIT 400078120 720BEDROOM CIRCUIT 0 9101201800 DISPOSAL & DISHWASHER SPACE 01112120 360GFI CIRCUIT SPACE0 1314120150 EXTERIOR LTG SPACE 01516 0SPACE SPACE0 1718 0 SPACE SPACE 01920 0SPACE SPACE0 21220 SPACE SPACE 02324 0SPACE SPACE0 25260 SPACE SPACE 02728 0SPACE SPACE0 29300 SPACE SPACE 03132 0SPACE SPACE0 33340 SPACE SPACE 03536 0SPACE SPACE0 37380 SPACE SPACE 03940 0SPACE SPACE0 41420 SPACE LOAD CALCULATION SUMMARYALL NEW PANELS SHALL HAVE MINIMUM AMPACITY OF 150A FOR FUTURE ADDITIONAL LOADS. NOTE: PROVIDE ARC-FAULT CIRCUIT INTERRUPTER PROTECTION AT BEDROOM RECEPTACLE CIRCUITS.CALCULATED POWER FACTOR:0.96BREAKERS MUST BE SERIES RATED WITH FEEDER BREAKER TO 42k AIC.CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS APPLIANCES1800913506 LIGHTING & RECEPT.428021344817 MECHANICAL4250205312.526 KITCHEN OVEN & DRYER800038640031 TOTAL183308816511 REF LOAD CALCS Quantity Volt-Amps Demand Total (VA)Residential Dwelling unit Square footage47342 General & Lighting (1st 3 KVA)1000 SF X 3X100%=3000 General & Lighting (Remainder)46342 SF X 3X35%=48659 Small Appliance Circuits62 EA X1500X35%=32550 Refrigerator31 EA X1000X75%=23250 Dishwasher31 EA X1200X75%=27900 Oven/Range (Re:table220.19)31 EA X8000X22%=54560 Microwave31 EA X1200X75%=27900 Disposal31 EA X1000X75%=23250 Clothes Washer/Dryer14 EA X5000X44%=30800 Future Appliance Load27 EA X8000X75%=162000 Electric Heat Heat/Light/Fan Combos68 EA X1500X100%=102000 TOTAL 535869 For 208V, 3-Phase, 4 Wire Service535869(VA) /361=1484AMPS LSLE - Meterbank w/ Future Loads Demand Load Calculations (Per NEC Article 220 Parts I-III)Quantity Volt-Amps Demand Total (VA)Residential Dwelling unit Square footage1992 General & Lighting (1st 3 KVA)1000 SF X 3X100%=3000 General & Lighting (Remainder)992 SF X 3X35%=1042 Small Appliance Circuits2 EA X1500X35%=1050 Refrigerator1 EA X1000X75%=750 Dishwasher1 EA X1200X75%=900 Oven/Range (Re:table220.19)1 EA X8000X80%=6400 Microwave1 EA X1200X75%=900 Disposal1 EA X1000X75%=750 Clothes Washer/Dryer1 EA X5000X100%=5000 Steamshower0 EA X7500X75%=0 Electric Heat Heat/Light/Fan Combos3 EA X1500X100%=4500 TOTAL 24292 For 208V, 3-Phase, 4 Wire Service24292(VA) /208=117AMPS Optional Calculation NEC 220.83 Total of General Loads1 LS X26376 1st 8 kVA of General Loads1 LS X8000X100%=8000 40% of Remainder of General Loads1 LS X18376X40%=7350 100% of Electric Heat1 LS X4500X100%=4500 TOTAL 19850 For 208V, 3-Phase, 4 Wire Service19850(VA) /208=95AMPS LSLE - Condo with Loft w Washer/Dryer Demand Load Calculations (Per NEC Article 220 Parts I-III)PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL #10 VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:100A MLO TYPE: SQUARE D NQOD AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION HOUSEKEEPING HEAT1750 302122302500 DRY #1 " 1750 34 2500 "UNKNOWN 175030256120 600TIMECLOCK "1750 782301750 UNKNOWN T: UNKNOWN 540 201910 1750 "T: HEAT - TURN OFF TGTHER 15002011112230 1750UNKNOWN T: HEAT - TURN OFF TGTHER1500 20/15113141750 "UNKNOWN 0 3021516230 1000 WASHER " 01718 1000"SPACE0 19200 SPACE SPACE 0 2122 0 SPACE SPACE 02324 0SPACE LOAD CALCULATION SUMMARYNOTE: REPLACE PANEL AS SHOWN. CALCULATED POWER FACTOR:1.00 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING60026002 RECEPTACLES54015401 MECHANICAL0000 KITCHEN24000662400066 TOTAL25140702514070 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL ELEVATOR LOAD CENTER "EE"VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:30A MLO TYPE: SQUARE D QO AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION HOISTWAY PIT LTS/REC(1)244 201122201096 PTAC-1 ELEV ROOM LTS/FAN/REC(1) 294 20134 1096 "ELEV CAB LTS/FAN/REC 53020156120 750PIT SUMP PUMP SPACE0 78 0 SPACE SPACE 0 910 0 SPACE SPACE 01112 0SPACE LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:0.88 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING42815352 RECEPTACLES54015401 MECHANICAL304210359012 KITCHEN0000 TOTAL401013466515
TAG DESCRIPTION LOAD VOLTAGE PHASE WIRE SIZE (CU)CONNECTION CIRCUIT BREAKER REMARKS THERMAL B-1BOILER #12 A1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH CU-1CONDENSING UNIT #117.9 MCA2083(4 #12, 1 #12G) 1/2"C30/320A3P THERMAL CUH-1-4CABINET HEATERS #1-41/15 HP1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH THERMAL EF-1,2EXHAUST FAN #1, 214.5 W1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH EF-3EXHAUST FAN #33 HP2083(4 #12, 1 #12G) 1/2"C30/320A3P THERMAL EF-4EXHAUST FAN #41450 W1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH FC-1FAN COIL #13.9 MCA2083(4 #12, 1 #12G) 1/2"C30/320A3P THERMAL GF-1GLYCOL FEEDER #150 W1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH THERMAL P-1SNOWMELT BOILER PUMP #1150 W1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH THERMAL P-2SNOWMELT MANIFOLD PUMP #2890 W1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH PTAC-1PACKAGED AC UNIT #115.5 MCA2081(3 #12, 1 #12G) 1/2"C30/220A2P SF-1SUPPLY FAN #11 HP2083(4 #12, 1 #12G) 1/2"C30/320A3P THERMAL SF-2SUPPLY FAN #21/4 HP1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH THERMAL SF-3SUPPLY FAN #31/6 HP1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH THERMAL SP-1SUMP PUMP #1.3 HP1201(2 #12, 1 #12G) 1/2"COVERLOAD20A1P SWITCH MECHANICAL SCHEDULE NOTE: EC TO VERIFY ELECTRICAL REQUIREMENTS FOR ALL MECHANICAL EQUIPMENT PRIOR TO ROUGH-IN.
PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL HEAT TRACE 1 "HT1"VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:150A MLO TYPE: BYLIN HECS AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION NW HEAT TRACE - 249'1494 302122301464 NE HEAT TRACE - 244'30 mA GFI 1494 34 1464 30 mA GFI NW HEAT TRACE - 227' 136230256230 1644NE HEAT TRACE - 274'30 mA GFI1362 78 1644 30 mA GFI NW HEAT TRACE - 244' 1464 302910230 984 NE HEAT TRACE - 164'30 mA GFI 1464 1112 98430 mA GFI NW HEAT TRACE - 182'1092 30213142301560 NE HEAT TRACE - 260'30 mA GFI 1092 1516 1560 30 mA GFI NW HEAT TRACE - 197' 11823021718230 1734NE HEAT TRACE - 289'30 mA GFI1182 1920 1734 30 mA GFI NW HEAT TRACE - 179' 1074 3022122230 1746 NE HEAT TRACE - 291'30 mA GFI 1074 2324 174630 mA GFI NW HEAT TRACE - 169'1014 3022526230360 N DRAIN HEAT TRACE - 60'30 mA GFI 1014 2728 360 30 mA GFI NW HEAT TRACE - 183' 10983022930 0SPACE 30 mA GFI1098 3132 0 SPACE SPACE 0 3334 0 SPACE SPACE 0 3536 0SPACE SPACE0 3738 0 SPACE SPACE 0 3940 0 SPACE SPACE 0 4142 0SPACE LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:1.00 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING0000 RECEPTACLES0000 MECHANICAL0000 KITCHEN3854410738544107 TOTAL3854410738544107 PROJECT: LIONSQUARE EAST PROJECT#:11055 CLIENT: MELICK & ASSOCIATES ENGINEER:SOH DESCRIPTION: PANEL HEAT TRACE 2 "HT2"VOLTAGE:120/208V, 3P, 4W MOUNTING: SURFACE MAINS:150A MLO TYPE: BYLIN HECS AIC:10k PHASE PHASE DESCRIPTION A B CBKR PCIRCIR P BKR A B CDESCRIPTION SW HEAT TRACE - 201'1206 302122301212 SE HEAT TRACE - 202'30 mA GFI 1206 34 1212 30 mA GFI SW HEAT TRACE - 121' 72630256230 1374SE HEAT TRACE - 229'30 mA GFI726 78 1374 30 mA GFI SW HEAT TRACE - 243' 1458 302910230 1236 SE HEAT TRACE - 206'30 mA GFI 1458 1112 123630 mA GFI SW HEAT TRACE - 227'1362 30213142301632 SE HEAT TRACE - 272'30 mA GFI 1362 1516 1632 30 mA GFI SW HEAT TRACE - 192' 11523021718230 1470SE HEAT TRACE - 245'30 mA GFI1152 1920 1470 30 mA GFI SW HEAT TRACE - 297' 1782 3022122230 1746 SE HEAT TRACE - 291'30 mA GFI 1782 2324 174630 mA GFI SPACE0 2526230540 S DRAIN HEAT TRACE - 90'SPACE 0 2728 540 30 mA GFI SPACE 0 2930 0SPACE SPACE0 3132 0 SPACE SPACE 0 3334 0 SPACE SPACE 0 3536 0SPACE SPACE0 3738 0 SPACE SPACE 0 3940 0 SPACE SPACE 0 4142 0SPACE LOAD CALCULATION SUMMARY CALCULATED POWER FACTOR:1.00 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS LIGHTING0000 RECEPTACLES0000 MECHANICAL0000 KITCHEN33792943379294 TOTAL33792943379294
TYPEDESCRIPTIONMANUFACTURERCATALOG NUMBERMOUNTINGNOLAMPVOLTSDIMENSIONSREMARKS 6" CALCULITE COMPACT FLUORESCENT OPEN PROVIDE EMERGENCY BATTERY A1DOWNLIGHT, CLEAR REFLECTOR, POLISHEDLIGHTOLIER8021 CCLP S6132BURECESSED CEILING132W TRIPLE TUBE12012-3/4" L X 10" W X 9-7/8" HBACK UP "FA EM4E" FOR FLANGE SHADED EM FIXTURES 6" CALCULITE COMPACT FLUORESCENT OPEN PROVIDE COLD WEATHER A2DOWNLIGHT, CLEAR REFLECTOR, POLISHEDLIGHTOLIER8021 CCLP S6132BU WITHRECESSED CEILING132W TRIPLE TUBE12012-3/4" L X 10" W X 9-7/8" HBALLAST. ADD COLD BATTERY FLANGE, COLD WEATHER BALLAST-20° F BALLAST BACKUP WHERE SHOWN.6" CALCULITE COMPACT FLUORESCENT OPEN PROVIDE COLD WEATHER A3DOWNLIGHT, CLEAR REFLECTOR, POLISHEDLIGHTOLIER8021 CCLP 6132BURM WITHRECESSED CEILING132W TRIPLE TUBE12012-3/4" L X 10" W X 9 -7/8" HBALLAST.FLANGE, COLD WEATHER BALLAST, REMODELER-20° F BALLAST CASCADE BRONZE CFL FULL CUT OFF WALL PROVIDE BALLAST WITH MIN E1SCONCE, BRONZE FINISH WITH AMBER HINKLEY LIGHTING1830BZ-ESWALL126W CFL1014.5" H X 8" W X 4" PROJSTART TEMP OF -20° F ETCHED ORGANIC RAIN GLASS, COLD BALLAST 2700K, 80+ CRI PROVIDE BATTERY BACKUP F11' X 4' SURFACE MOUNT FLUORESCENT BOXLIGHTOLIERPNB1SFAVA232120SOSURFACE24' 32W T812012" W X 48" L X 5 1/2" HBALLAST FOR SHADE D EM 3500K, 80+ CRIFIXTURES 4' LINEAR FLUORESCENT STRIP LIGHT,F22-LAMPLIGHTOLIERSW4S232HPFUNVSOCEILING24' 32W T812048" L X 4-1/8" W X 3-1/2" H 3500K, 80+ CRI 4' LINEAR FLUORESCENT SURFACE CLOUD,PROVIDE BATTERY BACKUP F3WHITE OPAL ARCYLIC LENSLIGHTOLIERBCW6X48 SW4S232HPFUNVHIWALL24' 32W T812050 1/2" L X 6" W X 4 1/8" HBALLAST FOR SHADED EM 3500K, 80+ CRIFIXTURES RECTANGULAR, RECESSED LED STEPLIGHT,XX IN CAT. # = FINISH PER ARCH.S1ALUMINUM FACEPLATE, GLASS LENS, DIRECTEDBEGA2384LED-XXRECESSEDN/A11.2W LED12012-1/2" W X 2-3/4" H X DOWN 3000K2-1/2" D EMERGENCY BATTERY BACKUP UNIT, 2 HEADS,PROVIDE WHERE EBU SHOWN XEBUWHITELIGHTOLIEREN125LH12WSD2 SURFACE212W, 6V HALOGEN12016.56" W X 6.15" H X 5" DAT INTERIOR ALONE OR WITH EXIT SIGN EMERGENCY BATTERY BACKUP UNIT, 2 HEADS,PROVIDE WHERE EBU SHOWN XEBURWHITE, REMOTE CAPACITY, BLACK REMOTE HEADLIGHTOLIEREN136LH12WSD2 & E NRH12BSURFACE212W, 6V HALOGEN120/616.56" W X 6.15" H X 5" DAT INTERIOR WITH REMOTE EXTERIOR HEAD WET LOCATION EMERGENCY BATTERY BACKUP PROVIDE WHERE EBU SHOWN XEBUCUNIT WITH BATTERY HEATER, BRONZELIGHTOLIERLVLBZHRSURFACE25.5W, 6V MR161207.66" W X 8.67" H X 3.72" DAT EXTERIOR HALOGEN ARCHITECTURAL LED EDGE-LIT EXIT SIGN XX IN CAT # = # OF FACES PER XITGREEN LETTERS, CLEAR BACKGROUND, WHITELIGHTOLIERLG N XX GC W SD2WALL/CEILINGN/ALEDs12014.25" W X 12.01" H X 4.5" DLOCATION O N PLAN. PROVIDE HOUSING, DIAGNOSTIC ELECTRONICS FOR INTERIOR EXIT SIGNS WET LOCATION EXIT SIGN, BLACK HOUSING AND PROVIDE FOR EXTERIOR EXIT XITESTENCIL, GREEN LEDS, -40° F OPERATIONLIGHTOLIERLWL2NUGBSD2TSURFACEN/ALEDs12013.8" W X 8.85" H X 2.4" DSIGNS.LUMINAIRE SCHEDULE NOTE: ALTERNATE EQUIVALENT LIGHTING PACKAGES ACCEPTED WITH ENGINEER'S REVIEW OF SUBMITTAL.