Date:4/20/2012
Re: B12-0097 22 W Meadow Drive
Dear Mr. Heid
RESPONSE INSTRUCTIONS
● Submit two complete sets of revised construction documents containing the requested
information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each comment.
BUILDING
COMMENTS
Architectural Comments:
Sheet A1.1
1. How is the u value of the reinstalled windows to be verified?
2. Provide details for the proposed handrail and guardrails proposed.
Structural
Comments:
Reviewed and accepted
Plumbing Comments:
Sheet A1.1
1. Provide gas piping plans to include piping isometrics
Mechanical Comments:
1. Indicate the cfm of the range hood. Note:
if it exceeds 400 cfm mechanical ventilation is to be provided and reflected on the plans.
Electrical Comments:
E1.1
1. Show that required arc faults circuits are to be installed.
2.
Indicate 50% of light fixtures to be high efficacy.
3. Plans to reflect the required smoke and CO detectors
PLANNING COMMENTS
Reviewed and accepted
FIRE COMMENTS
Reviewed and accepted
PUBLIC WORKS COMMENTS
NA
Sincerely,
Martin A. Haeberle
Chief Building Official