Loading...
HomeMy WebLinkAboutB12-0097 comment letter Date:4/20/2012 Re: B12-0097 22 W Meadow Drive Dear Mr. Heid RESPONSE INSTRUCTIONS ● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Architectural Comments: Sheet A1.1 1. How is the u value of the reinstalled windows to be verified? 2. Provide details for the proposed handrail and guardrails proposed. Structural Comments: Reviewed and accepted Plumbing Comments: Sheet A1.1 1. Provide gas piping plans to include piping isometrics Mechanical Comments: 1. Indicate the cfm of the range hood. Note: if it exceeds 400 cfm mechanical ventilation is to be provided and reflected on the plans. Electrical Comments: E1.1 1. Show that required arc faults circuits are to be installed. 2. Indicate 50% of light fixtures to be high efficacy. 3. Plans to reflect the required smoke and CO detectors PLANNING COMMENTS Reviewed and accepted FIRE COMMENTS Reviewed and accepted PUBLIC WORKS COMMENTS NA Sincerely, Martin A. Haeberle Chief Building Official