Loading...
HomeMy WebLinkAboutF12-0013 PLANS General Notes 01. SEE THE FIRE PROTECTION EQUIPMENT DATA FOR ALL APPLICABLE MATERIALS 15. ADEQUATE DRAINAGE OF FIRE PROTECTION PIPING SHALL BE PROVIDED FOR AND EQUIPMENT INSTALLED UNDER THIS CONTRACT. PER NFPA REQUIREMENTS. 02. THIS SET OF FIRE PROTECTION PLANS AND HYDRAULIC CALCULATIONS HAVE BEEN 16. THE FIRE SPRINKLER SYSTEM HAS BEEN COORDINATED WITH ALL LIGHT FIXTURES, DESIGNED BY INTEGRITY FIRE PROTECTION DESIGN, LLC. & CENTRAL FIRE PROTECTION MECHANICAL SYSTEMS & OTHER CEILING SYSTEMS. CONTRACTORS, AND HAVE BEEN SEALED BY A NICET LEVEL IV CERTIFIED ENGINEERING 17. MAXIMUM STORAGE IS TO BE NO MORE THAN 12'-0" OR 18" BELOW FINISHED CEILING. TECHNICIAN AS REQUIRED BY THE STATE OF COLORADO. 18. SEISMIC BRACING IS NOT PART OF THIS CONTRACT. 03. THESE FIRE PROTECTION PLANS AND CALCULATIONS HAVE BEEN DESIGNED 19. CHLORINATION OF FIRE PROTECTION PIPING IS NOT PART OF THIS CONTRACT. LOT 5 WITH THE INTENT OF COMPLYING WITH MINIMUM STATE AND LOCAL CODES AND 20. PAINTING OF FIRE PROTECTION PIPING IS NOT PART OF THIS CONTRACT. A RESUBDIVISION OF LOT 1, BLOCK ,, NFPA 13. 21. FIRE EXTINGUISHERS AND CABINETS ARE NOT PART OF THIS CONTRACT. VAIL/LIONSHEAD SECOND FILING 04. ALL MATERIALS, DEVICES, AND HANGERS INSTALLED UNDER THIS CONTRACT SHALL BE 22. FIRE PROTECTION PIPING IDENTIFICATION IS NOT PART OF THIS CONTRACT. 2.710 ACRES „s,o4�.s sQ. FT. 23. CENTERING OF SPRINKLER HEADS IN CEILING TILE IS REQUIRED AS PART UL LISTED AND FACTORY MUTUAL APPROVED. 05. ALL MATERIALS, DEVICES, AND HANGERS SHALL BE INSTALLED IN ACCORDANCE WITH OF THIS CONTRACT. DOBSON icE THEIR LISTINGS AND APPLICABLE NFPA ENGINEERING STANDARDS. 24. PROTECTION OF ELECTRICAL DEVICES, SUCH AS CIRCUIT ARENA BREAKER PANELS FROM WATER DISCHARGE, SHALL BE BY OTHERS. 06. UNDER THIS CONTRACT CENTRAL FIRE PROTECTION CONTRACTORS, INC. SHALL BEGIN ITS 25. CENTRAL FIRE PROTECTION CONTRACTORS, INC. SHALL NOT BE HELD RESPONSIBLE WORK AT THE EXISTING 2" FIRE SPRINKLER SYSTEM ABOVEGROUND MAIN SUPPLY. SHOULD THE NOTED FLOW TEST VALUES NOT BE SUPPLIED AT THE POINT 07. ALL EXTERIOR UNDERGROUND PIPING, VALVES, ETC. ARE EXISTING. OF CONNECTION NOW OR IN THE FUTURE DUE TO THE POSSIBILITY OF 08. ANY AND ALL ELECTRICAL AND/OR ALARM WIRING, CONNECTIONS AND TERMINATIONS, DETERIORATING WATER SUPPLIES, SEE HYDRAULIC SOURCE NODE LOCATION. ADDITIONAL HORNS OR STROBES, SHALL BE BY OTHERS. 26. ALL REQUIRED KNOX BOXES SHALL BE PROVIDED AND INSTALLED BY OTHERS. 09. IT SHALL BE THE SOLE RESPONSIBILITY OF THE OWNER TO PROVIDE, INSTALL AND 27. ALL REQUIRED INTERIOR/EXTERIOR SIGNAGE SHALL BE PROVIDED AND MAINTAIN AN APPROVED MONITORING SYSTEM OF ALL FIRE PROTECTION SYSTEM INSTALLED BY OTHERS. ELECTRICAL COMPONENTS AND/OR ANY OTHER COMPONENTS AS REQUIRED BY THE 28. PROVISIONS FOR FLUSHING THE SPRINKLER PIPING SHALL BE PROVIDED AUTHORITY HAVING JURISDICTION. BY CENTRAL FIRE PROTECTION CONTRACTORS, INC. 10. ANY AND ALL PAINTING OR PAINT PREPARATION OF PIPING TO BE BY OTHERS. 29. PIPE NOTE ALL PIPING SHALL BE IN ACCORDANCE WITH NFPA 13 2010 EDITION 11. ANY AND ALL ACCESS PANELS FOR VALVE AND DEVICE ACCESIBILITY IS TO BE BY OTHERS. ) ' ' 12. ALL SPRINKLER PIPING PENETRATIONS THROUGH FIRE RATED ASSEMBLIES UNLESS SPECIFICALLY NOTED OTHERWISE ALL THREADED PIPING 1"-1'�" SHALL BE SHALL BE SEALED WITH AN APPROVED MATERIAL EQUAL TO THE RATING BLACK SCHEDULE 40 PIPE UTILIZING DUCTILE IRON FITTINGS. OF SUCH ASSEMBLY. ALL 2" GROOVED/WELDED PIPE SHALL BE BLACK SCHEDULE 10 PIPE 13. ALL FIRE SPRINKLER PIPING INSTALLED UNDER THIS CONTRACT SHALL BE (WITH ROLLED GROOVE JOINTS AND WELD OUTLETS UTILIZING GROOVED FITTINGS. HYDROSTATICALLY TESTED IN ACCORDANCE WITH ALL APPLICABLE NFPA ALL SCREWED FITTINGS SHALL MEET ANSI B.16.4 REQUIREMENTS ENGINEERING STANDARDS AND STATE AND LOCAL CODES. ALL FLANGED FITTINGS SHALL MEET ANSI B.16.1 REQUIREMENTS 14. UPON SUCCESSFUL INSTALLATION AND COMPLETION: ALL GROOVED FITTINGS SHALL MEET ASTM A536 REQUIREMENTS " A SPARE SPRINKLER HEAD CABINET WITH ADEQUATE SPRINKLERS AND WRENCHES ALL METHODS OF JOINING PIPE SHALL BE IN ACCORDANCE WITH NFPA 13 SECTION 6.5 � � ; SHALL BE PROVIDED AND INSTALLED PER NFPA REQUIREMENTS I� � HYDRAULIC PLACARDS, CARE AND MAINTENANCE CARDS, AND 24 HOUR 30. IT SHALL BE THE SOLE RESPONSIBILTY OF THE OWNER TO PROVIDE ADEQUATE P H O N E N U M B E R S H A L L B E P O S T E D H E A T T H R O U G H O U T T H E F A C I L I T Y W H E R E W E T P I P E S P R I N K L E R S Y S T E M S A R E ' � COMPLETE OPERATIONS AND MAINTENANCE MANUALS SHALL BE PROVIDED PRESENT, TO PREVENT FREEZING OF SPRINKLER SYSTEM COMPONENTS � � � ���� COMPLETE CONTRACTORS MATERIALS AND TEST CERTIFICATES SHALL BE (MIN 40 DEGREES F). �° PROVIDED ��Ar,� � ALL SYSTEM CONTROL VALVES SHALL BE LEFT FULLY OPEN AND IN SERVICE , �� ALL SYSTEM DEVICES SHALL BE IDENTIFIED PER NFPA REQUIREMENTS / �� V � -- . �. V � �� aa r-, Q;, _ �� a � . . . � � � a . -e � . ,. � . � i � , . .. . . � � j �� , - . , . . ��� ,\_� ' • • - . . ' . . . --� , . �,� . EXISTING --- - 4x2'hx2'/z ; FIRE DEPT. CONNECTION ���_ �`�� � � : , SEE SHEET FP2 OUTSIDE HORN TEST ���OR CONTINUATION STROBE ��� EXISTING 4"UNDERGROUNA'" ��``�� I TOR (EXISTING) L' WATER MAIN � � � � I � _ + �� � � 14 , �, � ,.; � , , , . , �,.t��a , EXISTINGMAIN FIRE �� ��� ��r� � � � SPRINKLER RISER � � ' � ' , ; �, \ i� �i (SEE DETAIL 2 THIS SHEET) �� BOR � � `� ��. ; ��, - � �� � EXISTING CITY WATER MAIN � _ � �-����� ���� M�� �� ��� RISER ROOM DETAIL LEGEND �� � "� ` ., ���, / / ITEM DESCRIPTION QTY , �_ �ti � � , � � ' �' t �°- , � ' � `, 1 EXISTING 3" FLG 90 w/4x3 REDUCER FROM EXISTING UNDERGROUND 1 � � �r�� �� � �� '" � TOWN OF VAIL LIBRARY � �` 11 2 EXISTING3" GATEVALVE 2 k, • � 2 STORY WOOD & STONE BUILDING � �? �'.' � 12 3 EXISTING 3"WYE STRAINER � FULLY FIRE SPRINKLERED � + 10 ° _° % � 4 EXISTING 3" PRESSURE REDUCING VALVE � 16,752 SF - LOWER LEVEL � ���� Y° � � 6,583 SF - MAIN LEVEL � � ��� � 5 EXISTING 3" FLxFL 90 ELL 1 15 ������ ' � )`-; � TOTAL SPRINKLERED AREA = _ � 6 ExisTiNG 3" GROOVE� so E�� 3 �g ; � / , 23,335 SF "�� � g x � 7 EXISTING 3"AMES 4000SS BACKFLOW PREVENTOR 1 � ,� I ' . = , 9 � :`a ; ,;�� „ � , ' ����������� 8 EXISTING GAUGE SET 1 ,, ` � ' -;: •• � F LO W T E ST S U M M A RY �„� 13 g EXISTING WATERFLOW SWITCH � � �� TEST DATE: 04�24�201 2 ACTUAL RESULTS: RESULTS - 1 0%: �g � � 10 EXISTING 3" GROOVED TEE 1 TEST CONDUCTED BY: STATIC: 1 50 PSI STATIC: 1 35 PSI 11 EXISTING 3" GROOVED CHECKVALVE 1 � EAGLE RIVER WATER/VAIL FIRE RESIDUAL: 145 PSI RESIDUAL: 130.5 PSI ^ � � TEST LOCATION: 22 W. MEADOW DR. FLOW: 1 353 GPM FLOW: 1 353 GPM O7 ;.r, � 12 EXISTING 3" GROOVED 90 ELL OUT TO EXISTING FIRE DEPT. CONN. 1 VAIL, CO 81 657 i 13 EXISTING MAIN DRAIN � ' � - 3., 0 3,. 6 �, � THIS FLOW TEST DATA WAS SENT BY MIKE VAUGHAN VAIL FIRE TO BE USED FOR THE - - 00 � 0 3 0 3 O � 14 EXISTING 3" GROOVED 90 ELL w/A 3x2'/z" GROOVED REDUCER 1 � O, � VAIL LIBRARY PROJECT. THIS TEST WAS CONDUCTED AT THE PROPERTY ADJACENT JUST " - u + 15 12 HEAD SPARE HEAD CABINET w/SPARE HEADS&WRENCHES 1 � - r� ., \ EAST OF THE LIBRARY. ��� � 2 SPRINKLERS OF EACH TYPE TO BE PROVIDED � BFI BFO � � The above plan shall be considered a fire-line reference plan. Refer to approved civil engineering ' construction documents for all site-related fire line routing and work. This plan has been �;�� � created for use by the Fire Department to ascertain friction loss distances, pipe sizing, fire , department connection relationships to fire hydrant(s), etc. �� The hydraulic calculations have taken into account the smallest available underground pipe 2 2 TO FLOOR DRAIN - --- diameter and conservative HWC (140) for Ductile Iron Underground Pipe. � *SEE BELOW All underground pipe & fittings are existing. Central Fire Protection Contractors, Inc. ap O - to begin installation at the existing 2" fire sprinkler system aboveground main supplies as shown � � PRI on sheets FP2 8c FP3. i,� 3 �1 O . � � � � BOR � PRO I j� � Fire Protection Site Plan � SCALE: NONE FINISHED FLOOR NORTH *FIELD VERIFY THAT THE PRESSURE REDUCING VALVE IS SET AT 150 PSI 8c ADJUST IF NECESSARY NO MODIFICATIONS HAVE BEEN MADE TO THE EXISTING FIRE SPRINKLER SYSTEM RISER. SHOWN FOR HYDRAULIC CALCULATION PURPOSES AND FOR DRAWING REFERENCE ONLY. 2 Exi stin F ire S rinkler Ri s er FP1 SCALE: NONE � RE PROTECT ON DRAW N G N DEX FP1 SITE PLAN, RISER DETAIL, & GENERAL NOTES FP2 LOWER LEVEL FIRE SPRINKLER SYSTEM LAYOUT FP3 MAIN LEVEL FIRE SPRINKLER SYSTEM LAYOUT REVISIONS I PROJECT CONTACTS � SPRINKLER SCHEDULE & LEGEND Fire Sprinkler Design Contractor: Approval: I att2St t0 tI'12 aCCUPaC�/ aI�1C+ � � � I04.23.2012I Stephanie Pelster OWNER SYM SPRINKLER MAKE, MODEL, TRIM, NPT K-Factor ORIFICE TEMP. FINISH QUANTITY . Va�l Publ�c L �,hrar Remodel � Preliminary Piping Plan for survey Town of Vail Q Tyco TY-FRB (Old Style) QR Pendent Sprinkler w/Brass 1-Piece Flush Escutcheon SIN #TY3631 5.6 1/2" 155' Brass 61 /nte / l� integrity of this document ,y P �A N I05.07.2012I Stephanie Pelster 75 S. Frontage Road 9' y vail, Colorodo 81657 � Tyco Model RFII Concealed Quick Response Sprinkler SIN #TY3531 5.6 1/2" 155' White 30 This fire s rinkler s stem 292 West Meadow Drive Vail Colorado 81657 Submit to Central Fire Protection, Shaner Life Safety, & Vail Fire Rescue Fire Protection D�sign, p y r PROJECT N0. 284212 GENERAL CONTRACTOR � Tyco TY-FRB QR Upright Sprinkler SIN #TY3131 5.6 1/2" 200' Brass 3 for approval & permit for the Library portion. w�- Evans Chaffee Construction Group LL . drawin has been Fire S rinkler Installation Contractor: 77 Metcolf Rood � Tyco TY-FRB QR Upright Sprinkler SIN #TY3131 5.6 1/2" 155' Brass 14 Marvin Heath,SET g p DRAWN BY Stephanie Pelster Avon, Colorado 81620 7694 S. Duquesne Way Central Fire Protection Contractors, Inc. SUBMITTAL DRAWING I I � Tyco TY-FRB QR Horizontal Sidewall SIN #TY3331 5.6 1/2° 155' White 5 Aurora, ColOrado 80016 NICETLevel IV1t0792o1 completed in compliance � � ►� T R,� L �I � � CHECKED BY Marvin Heath AUTHORITY HAVING JURISDICTION #1 ��; Existing Tyco Concealed Sprinkler Head 5.6 1/2" 155' White 1 Fire Protection Engineering Technology/ Vail Fire Rescue PhOne: 303.562.5205 Water-BasedSystemsLayout with NFPA, Local, & State / SCALE 1/$�� = 1'_��� 75 S. Frontage Road Q Existing Upright Sprinkler Head 5.6 1/2" 155' Brass 2 Fax: 303.400.0265 PROTECTION CONTRACTORS II \ V Vail, Colorado 81657 All existing sprinkler heads are to remain as instaiied. Stephanie M Pelster, SET Codes. � PLOT DATE May 7, 2012 � � AUTHORITY HAVING JURISDICTION #2 Fire Protection Engineering Technology C�. 80239 T 303 576-�157 F 303 'Jr76-8159 Shaner Life safety HEAD CAB'T & WRENCH(ES) PROVIDED TOTAL COUNT NEW HEADS = 113 Water-Based Systems Layout 2�� 2.�5.07 14:O�:rJB -�6���� �0775 E. 51 st Ave. Denver, � � � � 710 Summit Blvd. Nortn #�o3c TOTAL COUNT EXISTING HEADS = 3 NICET Level IV-Certification # 117390 STATE OF COLORADO FIRE SUPPRESSION REGISTRATION 004 D RAW I N G N 0. F P 1 of 3 Frisco. CO 80443 B C E � G °• • • ° '. . a . a d �r' ..,,, I _.. r_i i.... I ,. ,..,. • _ -,� .� _-_ � „ ti � Q �HILTI HDI-P CONCRETE ANCHOR 4 �FIG. 100 ALL THREAD ROD MECHANICAL ROOM 001 EXISTINCs 2�i"SUPPLY ��FIG. 200 UP?0 MAIN LEYEL � � ADJUSTABLE RING HANGER $Y$?EM IUES?OF � A?RIUM DOU�I TO EXISTINCs �� � TNE SPRINKLE 5Y5iEM LAYOUT �I�RISER LOCATION. �" C-OR TNE MECN ICAL R00�'1 5EE DETAIL SNEET FPI `�' `� WILL BE SNOUN IN TNE 2ND SUBMITTAL � ���s�� O SELF DRILLING ANCHOR, ROD AND RING ToR �� _ �Oa�O � � : � //��J�\\ N � �� � ('y N ���2 II �II 2 � 8-9 04-5 _ N FP'I � � � 5 = � �, .sTAF� � �, �,� UP?OMMLEY�LSYS?EM HANGER SPACING LEGEND PERNFPA13TAB9.2.2.1 ca� ��� � � - �����yq c��c��T NOMINALPIPE _ _ �;-i HC TOI�,E . 2�� ' ° � (L . SIZE (IN.) 3/4�� ��� 1 1/4° 1 1/2�� 2�� z vz�� 3�� 4�� 6�� 8�� FP3 FOR TINUATION �� �� 017 I�-I�I/� � STEEL PIPE (NOT / �TAFF ,, ,:���' �g THREADEDLIGHTWALL) N/A 12-0 12-0 15-0 15-0 15-0 15-0 15-0 15-0 15-0 � LOUNGE �� �. � � %-7' ��� AFF THREADEDLIGHTWALL N/A 12-0 12-0 12-0 12-0 12-0 N/A N/A N/A N/A � � I � , i�T�iG'I��,,L) / � � � ��6 I � i,�'I I��I�<�'ij, � COPPER 8-0 8-0 10-0 10-0 12-0 12-0 12-0 15-0 15-0 15-0 ��� � � � � �� / i� CPVC 5-6 6-0 6-6 7-0 8-0 9-0 10-0 N/A N/A N/A , ' �1 �j�'I i � �, �;��'� i � , ��I�� �� �� �,� BOOKKEEPING ��� ���� I � � KITCHEN �i��' 014 �� � � , ;--����� - �� ���I� ��� �� �� 01.5 � � ,°��� INDIC,4T�8 APPROXIMAt� H�4NCx�R LOGAtION - �X,4CT LOCATION TO M�ET _ 1 � i !�'� N�PA 13 l2mlm �DITION) R�QUIR�M�NTS ,4ND SP�4CINC� P�R CNART ABOV�. � � j� � � - ��''� i =� /I� �!, i�l� I � 7 �� � -- - - � 4 - � � i i -_ ��- � � - - � ' � �, II . i I I�I�� I , �,, � ���� , ' � �i i � � i� � � i , � � I i ��� � � �� � _ I,! _ 'I �i� _ i - -- - � - -- -- -- __ ��J ��, - _ ���� � � � � � - _,�-- - � - -_- -- - _ _ ; , � � � � _ i �� ; ; F i - � d'- F�� n •� 1 � il� � ( ,'Y , � /� , i _ l ��L, � % _ �% I � � �; �'�� ;" � STAFF-2 �� � i. � 013 - AcT cEiuNc �i �. �.�� �_ I � � �� � i I� � I � �11�r- +, �'-4°' AF � STAFF-1 ��� � �r;� ��� !T�r��,A�7 _ � 'i;��� / 012 � ��� ,.� I I 0 � /, / � �i ; , -1 � � � � -�I _ ----- - -- - - -- -- - - . � ��- ��'� - - �� ��� i� _ � - �,� � i - _ 9 � - - - , - -- � - � � �� CLASSROOM � - , ! � � �,. Y i ��� � I . �� ' � �� ���I � �"� � ' STORAGE i� TECH. PROCESSING � --�� , ��--�� ' �/i; , i � �i� I 1 �'� r- 009 011 � �I %- I 'i i o � � �� `� ' '� �r� �� � , WET SYSTEM , i� i '� � '� �;�� i �a, . � � � ', I �� � � � i ; i , , �_� �; CLASSROOM ;,I_ , 'i �ii� I I i �� _ 1� � 008 � / �/ � �I' I � � � , RECEIVING � � �. � � ��. � i 1 I - � 010 �� - - � , 0 �I� '� � ' - , i 1 0 � � � � I ��f � , ��� o i ' � � � / , � � i � , I_, � � „ , - - - WET I.T. NOTES: �, i.�_,��� �-�_:� � ���, �/ . : ' ---- � 1 SPRINKLER � � � l r- I� I �i �� � '' � � ' �. : : STORAGE-1 LINE 1. RUN OFF OF REMOTE _ �%' _ I �i� �� �� , � . � O -- BRANCH LINE , , �� _ . . . : . . .. . . . --- _ ---- � . •. _ ,I -� - . . �� � '�T � H� _ ,i ��� 2. RUN PIPE OUTSIDE `� F�N�SH - � � i ��'. . � �' �� �003 � � ��-�� ����r��`' WITH WALLPLATE � __ ti �_ � +i-� -4" aF AGF MODEL 1011 ASG s��FFiT i , % _ ��-4� AFF ' � � �� Z � � ' (TYP'cA�) TEST & DRAIN INSP. TEST VALVE 3. OUTLET TO BE 1'-6" �� � ELEV. �� �� � : �Y� c������-� w�PRESSURE RELIEF ABOVE FINISHED GRADE = ENTRY 005 � �'-4° AFr � �� 4. INSTALL VALVE ABOVE �' 002 � GYP cE�ur�G o0 � � � � ; %� r_��" �Fr CEILING WITH TAG - -- - - j - � a � ��, , j � ���� �, / ;�� � � �� �:� =�� � '� CHROME FNC PLATE 1 GALV 45 ELBOW - -__ -- --_� • SEAL w/GROUT w/1" G A L V W A L L P L A T E �;��P c_Eiu�ic - � J--�-_n.' - 11 _- ��� � - STAIR � ��� �I-IfJ%; �rP 004 � ��� I I��; r C� C� I I I I�I�:� � � � � � � � � � � � � STORAGE-2 2-� 007 ThdxPE I J E��v ��k.I `��T I ��I (� �,,_ ,., � -0'� ��` u� �"i„ I -0� 1 3 Inspector s Test Connection B B ' C E � G FP2 SCALE: None /� � Lower Level Fire S rinkler S stem La out FP2 SCALE: 1/8" = 1'-0" NORTH I I I I I I I I ��g" I 0 2' 4' 6' � o' � 8' 2 6' G E N E R A L N O T E S 1. THIS PROJECT CONSISTS OF PROVIDING THE FOLLOWING: 8. MAXIMUM SQUARE FOOTAGE PER STANDARD COVERAGE SPRINKLER FIR� SPRINKL�R K�1'NOTES: PROVIDE A COMPLETE FIRE SPRINKLER SYSTEM MODIFICATION AS REQUIRED HEADS IN LIGHT HAZARD AREAS IS _ 225 _ SQ. FT. PER NFPA 13 (2010) EDITION, SHANER LIFE SAFETY, & VAIL FIRE RESCUE. MAXIMUM SQUARE FOOTAGE PER 'OLD STYLE' SPRINKLER HEADS IN CON7INUOUS �R�D) PIPINCs INDIC,47�S N�W �IR� SPRINKL�R S`�S7�M PIPINCx SCOPE OF WORK INCLUDES TIEING INTO THE EXISTING FIRE SPRINKLER SYSTEM THE LIBRARY WOOD CEILING AREAS IS _�144_ SQ. FT. t0 R�MAIN AS INSTALL�D TO PROVIDE A COMPLETE FIRE SPRINKLER SYSTEM FOR THE ENTIRE EXISTING (SEE HYDRAULIC CALCULATIONS) DASN�D IC�R�EN� PIPINC� INDICAT�S EXIStINC� FIRE SPRINKLER S1'ST�M PIPINC� BUILDING AS WELL AS THE NEW ADDITION. 9. MAXIMUM SQUARE FOOTAGE PER HEAD FOR ORDINARY HAZARD AREAS TO B� R�MAIN AS INStA���p ' °' 'OLD STYLE' QR SPRINKLER HEADS ARE TO BE UTILIZED IN THE WOOD CEILING IS _ 130 _ SQ. FT. CON7INUOUS CxR�EN PIPINCz INDICATES NEW FIR� SPRINKL�R Sl'STEM PIPINC� „ AREAS OF THE LIBRARY. 10. SPRINKLER HEADS __ ARE __ TO BE LOCATED IN THE CENTER � STANDARD SPRAY QR SPRINKLER HEADS ARE TO BE USED IN ALL OTHER --- TO R�PLaC� �XISTINC� PIPINC� DU� TO SIZ� INCR�AS� FOR NEW ADD1710N L�1�lCatNS VARI' AREAS. OF CEILING TILE OR ALIGNED WITH LIGHT /OR CEILING FIXTURES. � �� THE EXISTING FIRE SPRINKLER RISER IS TO BE REUSED WITH A SEPARATE 11. TYPE OF CONSTRUCTION CONCRETE FLOORz CONCRETE_COLUMNS, X -X ,4fif INDIC,4TES G/L PIP� �L�VA710N ZONE CONTROL TO BE INSTALLED FOR THE LOWER LEVEL SYSTEM. - �II �_2 1" VARI�S _w1A_CONCRETE DECK_�NON_COMBUSTIBLE�_UNOBSTRUCTED. . o. 2. ALL PIPE SIZES FOR THE NEW SYSTEM AT THE LIBRARY IS DETERMINED FROM 12. SPRINKLER SYSTEM TO MEET ALL N. F. P. A. STANDARDS. /�' � !, NATCN�p AR�AS AR� TO R� p�SIC�sN�p � INC�Up�p IN TN� 2Np SUBMIT7A�. � ° THE TWO HYDRAULIC CALCULATIONS PERFORMED. � j � CEILINC�s 13. ALL ELECTRICAL WIRING TO BE BY OTHERS. % SPRINK� R � � ° 3. ALL AREAS ARE LIGHT HAZARD OCCUPANCY EXCEPT FOR THE STORAGE ROOMS 14. ALL PAINTING OF PIPE OR IDENTIFICATIONS OF PIPE TO BE BY OTHERS. � /, "�� LINE o WHICH ARE ORDINARY HAZARD GROUP I OCCUPANCY. P�ND�NT - � 15. MONITORING AND DETECTION OF SPRINKLER SYSTEM BY OTHERS. � tNIS AR�A IS AN OP�N-CxRID C�ILINCx ,4ND IS TO B� D�SICxN�D � INStALL�D P�R TN� SPRINKL�R 4. ALL EXISTING/NEW THREADED BRANCH-LINE PIPING TO BE SCHEDULE_40 PIPE. � R�QUIREM�N7S OF N�PA 13 (2m1(d EDITION) S�CTION 8.15.13 WITN A MAXIMUM SPRINKL�R ' '-�' '-�' ALL NEW GROOVED MAIN SUPPLY PIPING TO BE ���iEQ�L��9 PIPE. N�AD SPACING OF lmxlm W17N TNE SPRINKL�R N�AD D�FL�CTOR TO BE INSTALL�D 1g" ABOVE 7N� 80770M OF TN� OP�N-CsRID CEILINCs. I 5. ALL NEW THREADED FITTINGS 1" through 1�" TO BE DUCTILE__ TYPE FITTINGS. ALL NEW GROOVED FITTINGS TO BE SHURJOINT TYPE FITTINGS. RECESSED SPRINKLER HEADS TO BE INSTALLED 6. ALL HANGERS TO BE IN ACCORDANCE WITH N.F.P.A. #13. 2 Typical Return Bend Detail IN THE QUARTER POINTS OF THE 2x4 CEILING GRID 7. ALL MATERIAL TO MEET N.F.P.A. #13 STANDARDS. TILES AND IN THE CENTER OF THE 2x2 CEILING FP2 SCALE: None GRID TILES AS SHOWN PER THE DETAILS ABOVE REVISIONS I PROJECT CONTACTS � SPRINKLER SCHEDULE & LEGEND Fire Sprinkler Design Contractor: Approval: I dtt2St t0 t`'12 aCCUraC�/ dIICI � � � I04.23.2012I Stephanie Pelster OWNER SYM SPRINKLER MAKE, MODEL, TRIM, NPT K-Factor ORIFICE TEMP. FINISH QUANTITY . Va�l Publ�c L �,hrar Remodel � Preliminary Piping Plan for survey Town of Vail Q Tyco TY-FRB (Old Style) QR Pendent Sprinkler w/Brass 1-Piece Flush Escutcheon SIN #TY3631 5.6 1/2" 155' Brass o lnte / l� integrity of this document J/ P �A N I05.07.2012I Stephanie Pelster 75 S. Frontage Road 9' y vail, Colorodo 81657 � Tyco Model RFII Concealed Quick Response Sprinkler SIN #TY3531 5.6 1/2" 155' White o This fire s rinkler s stem 292 West Meadow Drive Vail Colorado 81657 Submit to Central Fire Protection, Shaner Life Safety, & Vail Fire Rescue Fire Protection D�sign, p y r PROJECT N0. 284212 for approval & permit for the Library portion. GENERAL CONTRACTOR � Tyco TY-FRB QR Upright Sprinkler SIN #TY3131 5.6 1/2" 200' Brass 0 Evans Chaffee Construction Group LLC. °�" drawin has been Fire S rinkler Installation Contractor: 77 Metcolf Rood � Tyco TY-FRB QR Upright Sprinkler SIN #TY3131 5.6 1/2" 155' Brass 0 Marvin Heath,SET g P DRAWN BY Stephanie Pelster Avon, Colorado 81620 7694 S. Duquesne Way Central Fire Protection Contractors, Inc. SUBMITTAL DRAWING I I � Tyco TY-FRB QR Horizontal Sidewall SIN #TY3331 5.6 1/2° 155' White � Aurora, ColOrado 80016 NICETLevel IV#079201 completed in compliance � � ►� T R,� L �I � � CHECKED BY Marvin Heath AUTHORITY HAVING JURISDICTION #1 ��; Existing Tyco Concealed Sprinkler Head 5.6 1/2" 155' White 0 Fire Protection Engineering Technotogy/ � Vail Fire Rescue PhOne: 303.562.5205 Water-BasedSystemsLayout with NFPA, Local, & State SCALE 1/$�� = 1'_��� 75 S. Frontage Road Q Existing Upright Sprinkler Head 5.6 1/2" 155' Brass 0 Fax: 303.400.0265 PROTECTION CONTRACTORS II \ V Vail, Colorado 81657 All existing sprinkler heads are to remain as instaiied. Stephanie M. Pelster, SET Codes. � PLOT DATE May 7, 2012 � � AUTHORITY HAVING JURISDICTION #2 Fire Protection Engineering Technology C�. 80239 T (303) 576-�157 F (303) 'Jr76-8159 Shaner Life safety HEAD CAB'T & WRENCH(ES) PROVIDED TOTAL COUNT NEW HEADS = 0 Water-Based S stems La out ' ' ��775 E. 51 st Ave. Denver, 710 Summit Blvd. Nortn #�o3c TOTAL COUNT EXISTING HEADS = 0 NICET Level IV-Certification #117390 2�� 2.05.07 14:0� :33 -06 00 D RAW I N G N 0. F P2 of 3 Frisco. �0 80443 STATE OF COLORADO FIRE SUPPRESSION REGISTRATION 004 A B C D E � G H J K � M �� _� _ . _�, . ,., ,�- - - � -_ _ -_ -,: -_ -� � o -� �° � - �,'� � , - � V U 1 I � I I I I I I I � I I I - - - - - - - - � - -I - - - - - - - - - - - - - I- - � - - - � � � I I . ° - - - - - - - � , , '� I I I � �� j� � I � � � � • • • . 2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - • a N ' a . � � � � , � � � � � � � I I I _� � I � � �HILTI HDI-P I � � I CONCREfE ANCHOR . I I I � I I � I I �FIG. 100 = I I I I I � I I I TECH STORAGE � a,�� rHREa,o Roo ENTRY '� � � 128 I I 1 O,� � I I � � � � H C � I � ��ADJUSTABLE RING HANGER _I _ _ I _ _ � � � � � TUTORING-1 ' � � TOILET IT RACK ° �, 3 ;i - - - - - - - I - - I - - - - - - - - - - - � - � �I ' �� I� I I I - - � STOR.-4 � I CALCULATION �� � 126 127 � 129 � I I Fii�i�H TUTORING-2 � I I - --" f � � I �Z� I LIGHT HAZARD OCCUPANCY � i 0.10 GPM�900 SQ.FT. I � CEI�ING 130 � � i� � I i i 3 �r"� I I I� � _ ' _�'�i� �� � � - � � BOOK SALES � � ACTUAL AREA CALCULATED= � � �' �' � � ? � ,Fr SELF DRILLING ANCHOR, ROD AND RING � ��L����, �Oa¢0 - , STORAGE ss4 sQ. �r. I r' � � �F � A�� TUTORING-3 � _ I I I �j/ �' � � 120 � � '-6 � � � s 131 i = - - aa � - - - - - - - - - - -- - - - - �° - - - J° - - - - � - -° - - - °- - °- - - � °- -° - - - - - - L� - - - - - - - 4 - �- ; , ; , , , � � - � -� - _ - - - - - - - - - - - - - - - - - - - - - - -- - �t�- 4 ,{ ,�� a �- � � ° -- - - � � a -! ��-- �. a � . �a � a a , � � -� i i� � --- �� , s-i E���v�, _ ,� �. ��,_ , � _ _ , _ __, Ir �I = , - �,4�� i�+l _ 8�_m„_ i � - i , a . a a a , � , a , . , oa a a � , � _ _ A�� I � I =' _ ' I I � � li I� i �� `v _ � � _ i � � ' !„ � ' i i ,�, � �� � _ � .. � � � CHILDREN S � � , �� �,��� e �� �� �� � _ ���� � � i �ii � �� � �TOR. �3 � s I I I � I I ' � ;�, il � �� ` � �/�� ,n .�i, � �@i 2-II�z_ � � �" s @ a � .. � J i � �__WOMEN i� MEN I I � � i. ' ��� :� I � � � I �� � '-I � �� � � STORAGE �� � � �z � _ �.� � _ � , � _ � ss 6-5�� _ �� 6-9ii � ao ° i �r i _ _ _ � _, _ �- -3 b-2 2 6-2� �-,, �os -, ; , �05 ,I � � � . � ��s _ � ^ � �22 � , _�_� s„ � � = � � �� - � - e @ � L � HANGER SPACING LEGEND PERNFPA13TAB9.2.2.1 ca� - � _^,I : � .1 � � I I L_ ,� I ,i � ,�,'� i + ''! , - cA � T =�. c-Eluf�i�:; NOMINAL PIPE , � , ` �_.,` ;, 4 3'_�' I-5�z 3'� I S 0 ES ' �' I • • • � ' _ � • �g ia _�i�z r � � /i ni i �i i iia° 1 1/2„ 2,. 2 v2„ 4,. 6., $„ �� i, i _ �( _ , @ ��-� � � , � �_�_� � �'� �_ �� � � _ � �s� � ��� i ��� SIZE IN. � 1 �'' N I1�4u �n I � �. 7'-6" A�F � ) ��--��;' ' � �� � � � � � - �. 3/4„ �,. 3., I I ; - ; �� j ' ,; ��� � 118 �V" � � � 1'-b I P � I � � � 3 ^ f +� 5=6 �4'-� S5 / N E W STEEL PIPE (NOT � � � I' ^ � � X��� ��RQ�N �� , � ,,i � @ � =, _ J� _ II _�� \�, _m 4I �� I I I r I r � I � O S_2 I �, 4„6 0� _ � 8'_0°,Q� � � GYP. SOFFI T THREADED LIGHTWALL) N/A 12-0 12-0 15-0 15-0 15-0 15-0 15-0 15-0 15-0 � n I I - � P D? JANITOR SI �p I-I-=� - N � - cv '- cv '�_ � ' - =I � I i � _ ,I �-4 � �' ` ' � / 7�-4" AFF THREADED LIGHTWALL N/A 12-0 12-0 12-0 12-0 12-0 N/A N/A N/A N/A � � � .: ^ � .�� .,� i � ` � , �. .�_ ... p._ � I� ��'j� , �,,� _,.� �i .. . . I = li , _�,_ �, I _ � I � �.i � i � , . . _ _ I '{.. '�� � I . J._ �. . . T '.�CH• . , � o�°% i. I'(PICAL; . � _ , �� � I IJ� FIIII , - 1 tv - - 1 - - -- � � � - - - - - - - - - - _.._ _ __. �i � ; I_.. - _ �0 I _ I '� c- COPPER 80 80 100 100 120 120 120 150 150 150 I I ;_ � ; I -2 ,s� I "� I � iud��, � : r�� � - � � 125 t � nrii ,H - G .� t. _ � R_ �:� _ � I_ I ��, � FiNi��H 0 < i � 1 - �� ���� � � p # ��-"�' , . --- - �-� P,���; Je_i- I _ _ ,_ .. 0 _ Jr, CEILII`,I(, 'Q� `_�EILINr � CPVC 5-6 6-0 6-6 7-0 8-0 9-0 10-0 N/A N/A N/A JAN. J @ 104 ��!;j�� d „�,�. ; � - �- , , ,� � � ' 1�� i� � , � " i � I _ �� 1 3,_3� _ 2" 4 _ � Ip,4�� „ I�'� ��� T; ; °,�F � � ' _. �_ � / � _ �, - M I-4 �, -II I' � �` � ~ X 1�7 I I �_ M ��� � N 0-rJ l ' � __ � - 0 � @ _ � i_ � \ , \"�� � _ � ' ^ � 2�� @ _ 61 ' S _ � _ e�- _ - ICJ-6 �r - 1�-0 �_ ' 41T0 _ r_ I % ,, - _ 9 _ a e, z�� .�*; ��� i z�� - -, zd� ��� 2�� z,�� I Iz�� I z�� . � y�� � 0 • y�� • � I z�� - �� - 16 ��� 8'-m"AFF ^ ''`� a ill � � 5 - - - - - , ; - - , _ ,- - - ' - - - - - m � � IN ICAT S A OXIMAT NAN OCA710N - XAC7 OCA710N TO M 7 -,-, � D � PPR � C��R L � L EE _ ,5 Fll.l�.ii ��� ;� � . � I � _ _ _ _ .n _ I I _ _ I n _� I u I n � � _ ���i�i,i ; ' 1 �� I ! IT CLOSET,�� � '� � ' ' ' � 3 l 6-2 I ��� S 0 .� 10 S 11-4 9-2 I �r 2 1 �r 10 (d I I 4 S 11 I ���2 � 9-4 � I�a 1�a _�"' � � ; � �- ��� _ I� �,� I � , _ � � = , I � I = , - � � : ��- , , � ��; � , , � � I , N�PA 13 l2mlm �DITION) R�QUIR�M�NTS AND SPACINC� PER CNART ,4BOVE. ;: � �� � ' '� � � s � 0-9 I � � I-9 � - - S-2 - 4-6�j1-YD� � i - � i / � G - � - _ ��F � / , , �� 11 � , -8 � i � _ e, �, � '4 4'I ,9 'I 1�Z. '?�0� �� �� II ��� 8��1� �� �,b � I � � I� � � �, = , �- �� = - � � =� ��� - - - - �p� `r�ml _ - r,, � '1 � � - _ - - � � - - - _-��I I � _ ��� �'� - ' � ' _ � � � _ .� L 6 - -- - - - - - - - ,i , �- ��, - . - - - - - - - - - - - - - - - - - - - - - - - - - - - , - - - - ;� , _ - -,��- - - - - - - - - - - - -- 6 , �I � ,���� - i-z �� a _�� - °��- I - � � _ - _ � ' � � ° � � , ��� _, � � - � i , � ��� � � + � �� -_ � �„ �' _ �� = _ � � ; ,- , ,�� � , c�a -�... . f 18 ..._ -.. _ • • .. :�.i I I •y ��i • i�, I-i :!I�_�� �� �.+�. �� T - i�� � iv � Z-II� � �� . I � � r � � ; � ; � ° �TOR.-1_ � /, I, � � � � � ���,� I C IuNI� � � �� ��� N W r �I� a � o�� �� p, �s, �� STOR.-5 ,.� � � � %; I f � 112 �, '� � Exl ?INCs 2 SUPPI.1' I � �;,, ri _ � - {- � , I -� I ' 132 � �� r � �OU������ �= c� ' �� � �� � 7-4" AFF I � � , „ �� i � , � ,' , �,. �� � �,� B'/�,' :� �� INULITION) �., I� � � "� I k / ° , � ° � T FP2 POR `� - - - `�� - � � � '� 1° a_ �� , � � _ _ � �,-' � , ; � , q i ii�� i � ,� �+1� � m� � • �t � '� � � ��� �,, • • • �-9 • ' �� ��_'�i i i � � i � , � � � � � � � ' ,' � � ,r �� ��� I , ,' � ,�. � I � � �� �� � _ bl I"� � �� � I % _ � � �� � ! ; � �„�` ��,�G� � �i _ � 2� � 2 � � �� � � �S� . _ _ _� ,� ., � ;, =,��FFIT �T� � EE � �� - �� �:, `�' ��� � - � � � 7-91 5-5� � � ,.� � i� � 1-10�i a /� �Z �� �� I-9 �% n � , � � � �"�/��, ,���! ��� .-I I-9 s s , r _ � � � __ » � �� � I �._,V�EREG ; ; � o I � �� '� �/ / /�� I-2 �' @� - � � � v �� �� _r i _ _ _ � - � 9-� � � , � � „ „ , � �r i � I � � Ii � � � �, i/ %� � � � �� � � � � I / _ � I� � ' 6, �' I I ' 2 I , ,' , , �. � ; , ; ; "�� � . ._ : , - � - - i,,' �� c" � _ �i . _ n .�_ @� � u m u-._ 0 d � @� u 0�' u �I. � . . . _ _ � . . � � - � -. 2 2 2 2 - 2 2 - � �� / - . � / HYDRAULIC SYSTEM HYDRAULIC SYSTEM - - ` -�, - - - ",�,., _, �� ,� � � _ � - �a % 7 - - j/ - f;/�! i i= � � u� � \, � ' PLACE ALL EXI�I(s I�� a C? I,<y,E 9-6 9- 2-9 6-3 9-0 9,,•(0 �0-b ; '� � - � �,' � I� �j I`J E W N,'�^,LL 1�1'_;i I I�l TEG � , COMMUNITY SPACE-1 /, ,' / ���,_ �� i��4 Pit�witNr�w2 �!�6 � � � 9,_s,,,a� _ �,� _ � _ � � i; _ �� ;� I g / �� cAeiNET AeovE I�/,,� � .�" ��� � / � � _2,, ` _ -�� I � �, �� _ _ I LOCATION NE CORNER LOCATION Main Libra 109 ,i � CO EE � '�' � ,� GALLERIA ���� � �AMPIPIt� ' � �'�� , _, � �� � , : � ,��, ;� % =_ � � ' - _ �_ _ ' � - � ' / � � � �* �* � � � � � '`- � �UUNTER PND BELUW � �; ���� ; � 113 � � � � /i'/ i � �� � � � � � � �_E�����,i�- rT,����i�_;�,�j I CALCULATION N0. 1 CALCULATION N0. 2 ���� � ���� � � «�'�,. /�� "� � � I p� p� 6l � � I � I � � � I ,_ � 103 a� � � �� I �� � � ,� ; ��' �;�� � I `� � '� " � 'I � N0. OF SPRINKLERS 11 N0. OF SPRINKLERS 9 ; , ' ��, � � , a� _ ��� ,_ � � s ��l I 5-1 _�, , � , - _� � �� � _ � _ �i � � � / ,� ° � '��/ -� � � _ _ �-��� , _ � � �. __ �� - �i � ,� �-�� _� � � ����-s°I.,aFF l � BASIS OF DESIGN BASIS OF DESIGN � � , , � , � � - � � � �� i � � I �; � - - � � � �J ���� o � _ - - , � - � , � � � � -� @ /� , - � � � � � � � � �-9 :.� � � � .n � � u'� <k � DENSITY 0.10 / q• DENSITY 0.10 / 9• GPM s ft. GPM s ft. -- , � / � , � , L , � , � , � , � � T �, JO'S OFFICE , � i ���� , , ;� �� � � � � ��-�- � �.. _� " � � � � _ @ � AREA OF DISCHARGE 964 sq.ft. AREA OF DISCHARGE 973 sq.ft. � � ' �; �' ' /. , �'j o,'� �,�� ��, �� � ,%� n �I > � � 9-3 _. � � �_ _ - � � � � ��� � �� _ � i � - � 123 GPM GPM � - - - - - - - - - - - ! ' -, � - T - - - - - - � � 8 ;� / ,,� ,�, , �, .; . , , = _ -� _ =! � , - - - - - - - - - �L - - - - - - - - - - - -- - - - �,�� � �, - - - - - _ � - - - - - - - - - - - - - - - - - - - - - g � � � ° � a � INSIDE HOSE ALLOWANCE 0 INSIDE HOSE ALLOWANCE 0 _ a � , � , � -� � �J��, s,� s,s �� s,z � �„ I � _ � OUTSIDE HOSE ALLOWANCE 100 �PM OUTSIDE HOSE ALLOWANCE 100 GPM I / ' � i I - I , � � � " � I; I_ / � ° � r _ � _ �� ' �� � �� , �� �� �� � � � � � I • � d'�UC AC _ • �-� � I _ 0-I �• _ @ -10 � I � �: � u�, � /,�i / � � � - . �/ � �� � '� . %� ��`" - ' S �. SYSTEM DEMAND SYSTEM DEMAND ��/ = m �� .���� C�F I T TO �� � � � � � � � � � ���INSPECTOR S TEST ;� ;� � �,� � j�� = �� � I '� ORI S OFFICE � _ _ _ � � � _ _ �, I�� _ _ �� EM IN � � �I � �� �-�_ �'� � � ����SEE�pETAIL 124 � GPM DISCHARGE 205.041 �PM GPM DISCHARGE 154.44 GPM I I ;� ��" ��,�, � �� , ��,��' " I � ��� , � � ' � I_ � 5-S�i-�� F�---� _ _ - , i= «�_ � -� � � � � a� � I I RESIDUAL PRESSURE AT 95.91 Ps� RESIDUAL PRESSURE AT 71.56 Ps� „ I - � � � ��� BASE OF RISER BASE OF RISER / � � � � , � � � � � �� � �-, � �� � � - � I I � �� ,i �-��l� ,I� E �i / � � �PLAGE ALL�SL�TING I° - --- � � � -� � � � � � . � � I ; ���� I I , ,_ 1 --�' � � I I ,.�� '� ; '� ,,� o �� i'%,/ � ; I ��, �/ / ,( I tI�,4°pIPEWITNNEW2" � , � _ _ . ��� � -: M-AIN LIIB-RARY •S13 � � _ � ,m.lm•� ',- � F��� I I SYSTEM DEMAND AT STREET SYSTEM DEMAND AT STREET , � , / � / < i- � MAIN PIpINCs ��� �� � , ���� - FI 15H XI �TIN�� I � / I I � � CHILDREN-1 CE uNC �oc D E u� � _ 11`� - � ,� �� I I = GPM REQUIRED 305.041 �PM GPM REQUIRED 254.44 GPM ,� � � - � , - - � COMMUNITY SPACE-2 % /' ;'i� ' /' N ' - - a y" �'-'='" - • � il ��� ���I X�=;TI����; PSI REQUIRED 101.033 PSI REQUIRED 76.13 � � s,� I - � , ; � � , I� � I � � � • • � • � • I � = ' � 3-I�� -I� I I . � , E PSI PSI ��fi1 � 110 ' , ° ' ' i ° _ � _,:_, J. i_ _ ;_ � ,. �. r��c���T Psi 24 9 � Psi 43 0 % 0 i:' �� ` ` SAFETY FACTOR 33.68 ( . ) SAFETY FACTOR 58.67 � . ) I � q�; ��� �� I � I I ��.g� � � ,� I I / � _ r r r - d r � � � i +� n u I � � � � � _ � i � -- - - � - - S14 �. i . -r - _ ..11�: � i � � � � � i � � � � � _� � � _ � • •I __, _i „ i � i �� / � � � �; % ` �-2�� � ._ _�3-PJ��4 �2-0 � i� � _ _ __ �� � • �-�� E X I `,�i; �!_�F E�� � __ �� ' �< � � u I �� � � � / �TI� ,_ � - , � � I . I�. \� I I . / I = F ��'1 I �� ��-� I�i,I II ' �II �114 "' II � - �111 2� �II I �111 - �II I �11�� N �� Ie 1) I �. ��I LI��(_. I I �i�n��H _Eiu�i_ �STOR.-2 �e _ , � � � � �� ; -_ � � � „ - 2�!I I ' f - ' � 12-0 '$-0 _ 0 6-3 4-4� 8-0 6- � I I _� AI � zo $- is _ ��' � 'PAINT� � 114 % 3- " � �� � I_ �``�'��' - , � , /��� ; pl I , � .r - i 9-4 AFF r� � � I^ � - - ,n ,n ,n ,n �n $ I 9-4 _ - - �k - - - - � �- - , . � ��� �� � �. � �� � ��_ � _ � y�. ' _ 6, = ,i, � '* j �;, = ,i, � - ,n I� � - R' I `�� I H_ � � 40 i� a � 10 - - - - - - - - - - ,- - - - - - - __�- - - ,_ --�- �- _ - � - - e �° - � � _� - - - - - - - - 1�} - - - - _ - - � - - � - - ,-_ - - _�, - - - - - - - - - - - - - - - - - ,- - - - - - - - - - - - - t - - - - - - � � Q � o � �� � _ - - , �.�, _ , - , ; , � , „ , , , � , � , � , .f �, , , �' , o -�� �� HALL-�2 -�"--�� � �., ��� � - � I • � _� • � • � � • r - � � , � a I1= ,' , / �- - - - � _ :� � � rl� ��� � _ ' I -" _ � 3 - � � � , p� - @ � _ _ '0 1'� z ,� 108 �I I° , � - �I� F I � E � o ! �;I TI f� , , / � - � - � , , , �,` ; � � � � - � 2�� , I 2�� e 2�� p�� ��' � _ � � ��FFi�I _ „_ I I _ I " � o �" � � , 2 �I � -� 0 ; _ ,� , , � , , �� / 6-2�i ��T- � -i i :�� 3-4 5- ���� I � AFF� 1 � �� _ I_ � - � _ , � o , _ 20 � � � ' ❑,, I I z � / I 3 I I �� � 6l e e _ e I � I I o ' �' i�E ti �� �� . I �, � � _ I I �� \ � � _ � U I �-�� �r� 'I I � I I CO FI�_IIFa II�?rd � I � m N N �- `-" `=, � �I L, I��If�l _, � I I w �O ELEV. � � � � � �� � I I ' � r� ii � EXI�TI � UR FI � �' � � _ 1 - -_ � -1����I��HT � � _ ' ,� 005 �'/ / TR CK VE I F � _ � �4'-b� 8'-0 8'� 4'-I�`---� - I ; , � ���, . � � � � �� � � � � � �� �r il IIE�FI1 '° If�Ti a - � '� i � _ S18 '(� �- - - � � � w 10 0 0 � � �:�� _ � I � _ _ �� � � � . � I I �� % I � % � I , I I � � , � • • I � • � � ��� ����� � E ��I`� I f I , ��� I ? � � CEILING HEIGHT, FT. � !!/� i �� i 1-b 12-P,� I .e,� i� � _ r 3-8 ' -1 (�`�F. �,EILIf�I�, I ' �)l ��a� � j �'� � - �n ��� I � _ _ � � � I I � ��'� ' I = �- (PAINT) I I I I I � � � I � I" t -�� � I" � �� � I � � `� � SYSTEM AREA REDUCTION WITH Q�R SPRINKLER HEADS I � T �'� I I I PER N.F.P.A.-13 (2010 EDITION) , SECTION 11-2.3.2.3.1 I I ° ' � 0-6 0-6 a, I I I 1. WEf PIPE SYSTEM 11 - - - - - - - - - - - - - - - - - - J - - - - - - - - - - - - - - = - - - - - � - - - - - - - - - - - - - - - - - - - - - - - - � - - - - - - - - - - - -� - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - � � 2. LIGHTHAZORORDHAZOCCUPANCY - 3. 20' MAX. CLG HGHT I I � STAIR � ' ',i I ;' � I I - 4. THERE ARE NO UNPROTECTED CEILING POCKEfS I I 004 � AS ALLOWED BY SECTION 8.6.7 & 8.8.7 EXCEEDING I I I I I CHILDREN-2 I I � � 32 sQ. �r. � 117 � I FOR CLG HGHTS GREATER THAN 10' BUT LESS THAN 20' I 4�-0" I i-�-0'� I��-�i" I Il�-0" I 'S�-!���� � '� )" � � ��'-0�� �� � I �'-0'� I WHERE x = CLG HGHT WHERE Y = PERCENT OF REDUCTION CALCULATION #2 Y= -3X + 55 2 A B B 9 C E G H LIGHT HAZARD OCCUPANCY J K L M 0.10 GPM/900 SQ.FT. ACTUAL AREA CALCULATED= 973 SQ. FT. /� � Main Level Fire S rinkler S stem La out FP3 SCALE: 1/8" = 1'-0" GENERAL NOTES FIR� SPRINK��R K�1'NOT�S: NoRTH I I I I I I I I ��8 I CONTINUOUS (RED) PIPINCx INDICAT�S N�UJ FIRE SPRINKL�R S'(St�M PIPINCx 0 2' 4' 6' 10' 18' 26' 1. THIS PROJECT CONSISTS OF PROVIDING THE FOLLOWING: 8. MAXIMUM SQUARE FOOTAGE PER STANDARD COVERAGE SPRINKLER TO R�M,41N AS INST,4���p PROVIDE A COMPLETE FIRE SPRINKLER SYSTEM MODIFICATION AS REQUIRED HEADS IN LIGHT HAZARD AREAS IS _ 225 _ SQ. FT. DASN�D �CxRE�N) PIPINCx INDIGA7�S EXISTINC�s FIR� SPRINKLER SY87EM PIPINC� PER NFPA 13 (2010) EDITION, SHANER LIFE SAFETY, & VAIL FIRE RESCUE. MAXIMUM SQUARE FOOTAGE PER 'OLD STYLE' SPRINKLER HEADS IN TO B� R�MAIN AS INSTALL�D o SCOPE OF WORK INCLUDES TIEING INTO THE EXISTING FIRE SPRINKLER SYSTEM THE LIBRARY WOOD CEILING AREAS IS _�144_ SQ. FT. fi TO PROVIDE A COMPLETE FIRE SPRINKLER SYSTEM FOR THE ENTIRE EXISTING (SEE HYDRAULIC CALCULATIONS) CONtINU0U5 CxRE�N PIPINC� INDICAT�S NEW �IR� SPRINKL�R S1'ST�M PIPINCx BUILDING AS WELL AS THE NEW ADDITION. 9. MAXIMUM SQUARE FOOTAGE PER HEAD FOR ORDINARY HAZARD AREAS 70 R�PL�4CE �XIStINCz PIPINCz DU� TO SIZ� INCREASE �OR N�UJ ,4DDITION 'OLD STYLE' QR SPRINKLER HEADS ARE TO BE UTILIZED IN THE WOOD CEILING IS _ 130 _ SQ. FT. ��� AREAS OF THE LIBRARY. X'-X" ,4FF INDICAt�S C/L PIP� �L�VATION LENCxTNB vARY STANDARD SPRAY QR SPRINKLER HEADS ARE TO BE USED IN ALL OTHER 10. SPRINKLER HEADS __ ARE __ TO BE LOCATED IN THE CENTER AREAS. OF CEILING TILE OR ALIGNED WITH LIGHT /OR CEILING FIXTURES. THE EXISTING FIRE SPRINKLER RISER IS TO BE REUSED WITH A SEPARATE j//j� NA7CN�D AR�AS ARE 70 B� D�SICxN�D � INCLUD�D IN TN� 2ND SUBMI7TAL. ��� �_2 I" VARI�S � � ZONE CONTROL TO BE INSTALLED FOR THE LOWER LEVEL SYSTEM. 11. TYPE OF CONSTRUCTION _CONCRETE FLOORi CONCRETE_COLUMNS, _w1A_CONCRETE DECK_�NON_COMBUSTIBLE,_UNOBSTRUCTED,) �� -�' -�' ---- - � ' 2. ALL PIPE SIZES FOR THE NEW SYSTEM AT THE LIBRARY IS DETERMINED FROM 12. SPRINKLER SYSTEM TO MEET ALL N. F. P. A. STANDARDS. - C�ILINCx � THE TWO HYDRAULIC CALCULATIONS PERFORMED. SPRINKL R 13. ALL ELECTRICAL WIRING TO BE BY OTHERS. � TNIS AR�A IS AN OP�N-CxRlp C�I�INCx ANp IS 70 R� p�SICxN�p � INStA���p P�R tN� ��N� 3. ALL AREAS ARE LIGHT HAZARD OCCUPANCY EXCEPT FOR THE STORAGE ROOMS R�QUIR�M�N7S OF NFPA 13 �2(I>I(d EDITION) S�CTION 8.1�.13 WITN A MAXIMUM SPRINKL�R P�ND�NT ° �-o• �-�• WHICH ARE ORDINARY HAZARD GROUP I OCCUPANCY. 14. ALL PAINTING OF PIPE OR IDENTIFICATIONS OF PIPE TO BE BY OTHERS. N�AD SPACINCx OF lmxlm W17N 7N� SPRINKL�R NEAD D�FL�CTOR TO BE INSTALLED 18" SPRINKL�R 15. MONITORING AND DETECTION OF SPRINKLER SYSTEM BY OTHERS. ABOVE TN� BOTTOM OF TH� OP�N-CxRID C�ILINC�. 4. ALL EXISTING/NEW THREADED BRANCH-LINE PIPING TO BE SCHEDULE_40 PIPE. �2 SMA�� ROOM RUL� AS p��IN�p BY N�PA 13 (2mlm �p.) SECTION 3.3.1�. ALL NEW GROOVED MAIN SUPPLY PIPING TO BE ���iEQ�1L��Q PIPE. IN SMALL ROOMS, SPRINKLERS SNALL B� P�RMITT�D TO B� LOCAT�D . " � " DUCTILE NO t MOR� T N A N 9 �T. �RO M ,4 N1' S I NG L� U J A L L P�R N�P A 13 l 2m l� �D.) Typica l Re turn Ben d De tai l R E C E S S E D S P R I N K L E R H E A D S T O B E I N S T A L L E D 5. A L L N E W T H R E A D E D F I T T I N G S 1 t h r o u g h 1/ T O B E ________ T Y P E F I T T I N G S. S�C710N 8.6.32.4. 7N� AREA OF TN� SPRINKLER SN�4LL NOT �XC��D 225 SQ. �T. IN THE QUARTER POINTS OF THE 2x4 CEILING GRID ALL NEW GROOVED FITTINGS TO BE SHURJOINT TYPE FITTINGS. • T I L E S A N D I N T H E C E N T E R O F T H E 2 x 2 C E I L I N G 2 for Center-of-Tile GRID TILES AS SHOWN PER THE DETAILS ABOVE 6. ALL HANGERS TO BE IN ACCORDANCE WITH N.F.P.A. #13. FP3 SCALE: None 7. ALL MATERIAL TO MEET N.F.P.A. #13 STANDARDS. REVISIONS I PROJECT CONTACTS � SPRINKLER SCHEDULE & LEGEND Fire Sprinkler Design Contractor: Approval: I att2St t0 tlle dCCUrdC�/ dr1CI � � � I04.23.2012I Stephanie Pelster OWNER SYM SPRINKLER MAKE, MODEL, TRIM, NPT K-Factor ORIFICE TEMP. FINISH QUANTITY . Va�l Publ�c L �,hrar Remodel � Preliminary Piping Plan for survey Town of Vail Q Tyco TY-FRB (Old Style) QR Pendent Sprinkler w/Brass 1-Piece Flush Escutcheon SIN #TY3631 5.6 1/2" 155' Brass 61 /nte / l� integrity of this document ,y P �A N I05.07.2012I Stephanie Pelster 75 S. Frontage Road 9' y vail, Colorodo 81657 � Tyco Model RFII Concealed Quick Response Sprinkler SIN #TY3531 5.6 1/2" 155' White 30 This fire s rinkler s stem 292 West Meadow Drive Vail Colorado 81657 Submit to Central Fire Protection, Shaner Life Safety, & Vail Fire Rescue GENERAL CONTRACTOR Fire Protection D�sign, p y r PROJECT N0. 284212 for approval & permit for the Library portion. � Tyco TY-FRB QR Upright Sprinkler SIN #TY3131 5.6 1/2" 200' Brass 3 � Evans Chaffee Construction Group LLC. drawin has been Fire S rinkler Installation Contractor: 77 Metcolf Rood � Tyco TY-FRB QR Upright Sprinkler SIN #TY3131 5.6 1/2" 155' Brass 14 Marvin Heath,SET g p DRAWN BY Stephanie Pelster Avon, Colorado 81620 7694 S. Du uesne Wa Central Fire Protection Contractors, Inc. SUBMITTAL DRAWING I I � Tyco TY-FRB QR Horizontal Sidewall SIN #TY3331 5.6 1/2° 155' White 5 Aurora, ColOrado 80016 NICET Level IV#079201 completed in compliance � � ►� T R,� L �I � � CHECKED BY Marvin Heath AUTHORITY HAVING JURISDICTION #1 ��; Existing Tyco Concealed Sprinkler Head 5.6 1/2" 155' White 1 Fire Protection Engineering Technology/ � Vail Fire Rescue PhOne: 303.562.5205 Water-BasedSystemsLayout with NFPA Local & State " ' " 75 S. Frontage Road Q Existing Upright Sprinkler Head 5.6 1/2" 155' Brass 2 Fax: 303.400.0265 � i SCALE 1/8 = 1 -0 �a��, Colorado 8,65� P R O T E C T I O N C O N T R A C T O R S I N C All existing sprinkler heads are to remain as instaiied. Stephanie M. Pelster, SET Codes. � PLOT DATE May 7, 2012 � � AUTHORITY HAVING JURISDICTION #2 Fire Protection Engineering Technology C�. 80239 T (303) 576-�157 F (303) 'Jr76-8159 Shaner Life safety HEAD CAB'T & WRENCH(ES) PROVIDED TOTAL COUNT NEW HEADS = 113 Water-Based S stems La out � � ��775 E. 51 st Ave. Denver, 710 Summit Blvd. Nortn #�o3c TOTAL COUNT EXISTING HEADS = 3 NICET Level IV-Certification #117390 2�� 2.�5.07 14:02:13 -06 00 D RAW I N G N 0. F P3 of 3 Frisco. �0 80443 STATE OF COLORADO FIRE SUPPRESSION REGISTRATION 004 _ _ _ Fire Prakeckian �y Compuker Design Central Fire Protection 10775 E. 51 st Ave. Denver, CO 80239 (303) 576-8157 Job Name : Vail Public Library Remodel Main Level Calc Building : FP3 Location : 292 West Meadow Drive, Vail, Colorado 81657 System : 1 Contract : 284212 Data File : Vail Public Library Remodel Main Level Calc AREA 1.wxf I attest to the accuracy and integrity of this document � Marvin Heath,SET This fire sprinkler system hydraulic calculation Central Fire Protection Contractors,���. has been com leted in com liance with NFPA, NICET LevellV#079201 p p Fire Protection Engineering Technology/ Local,&State Codes. Water-Based Systems Layout 2012.05.07 14:02:55 -06'00' Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Central Fire Protection Page 1 Vail Public Library Remodel Main Level Calc Date 05/04/2012 HYDRAULIC CALCULATIONS for Project name: Vail Public Library Remodel Location: 292 West Meadow Drive, Vail, Colorado 81657 Drawing no: FP3 Date: 05/04/2012 Design Remote area number: 1 Remote area location: NE Corner Occupancy classification: Light Hazard Density: 0.10 - Gpm/SqFt Area of application: 964 - SqFt Coverage per sprinkler: varies - SqFt Type of sprinklers calculated: QR Concealed No. of sprinklers calculated: 11 In-rack demand: 0 - GPM Hose streams: 100 - GPM Total water required (including hose streams): 305.041 - GPM @ 101.033 - Psi Type of system: Wet Volume of dry or preaction system: N/a - Gal Water supply information Date: 04/24/2012 Location: 22 West Meadow Drive, Vail, Colorado Source: Vail Fire Rescue Name of contractor: Central Fire Protection Contractors, Inc. Address: 10775 E. 51 st Ave., Denver, CO 80239 Phone number: 303-576-8157 Name of designer: Stephanie Pelster Authority having jurisdiction: Vail Fire Rescue Notes: (Include peaking information or gridded systems here.) A 10°/o reduction has been taken off of the original Static& Residual pressures of the flow test. See sheet FP1 for further information regarding the flow test. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) Central Fire Protection Page 2 Vail Public Library Remodel Main Level Calc Date 05/04/2012 City Water Supply: Demand: C1 - Static Pressure : 135 D1 - Elevation : 10.542 C2 - Residual Pressure: 130.5 D2 - System Flow : 205.041 C2 - Residual Flow : 1353 D2 - System Pressure : 101.033 Hose ( Demand ) : 100 D3 - System Demand : 305.041 Safety Margin : 33.681 150 140 2 130 P 120 R 110 p E 100 S 90 S 80 � 70 R 60 E 50 40 30 20 10 D1 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N " 1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Central Fire Protection Page 3 Vail Public Library Remodel Main Level Calc Date 05/04/2012 Fitting Legend Abbrev. Name Yz '/4 1 1'/< 1'/z 2 2Yz 3 3'/z 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90'Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90'Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Central Fire Protection Page 4 Vail Public Library Remodel Main Level Calc Date 05/04/2012 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. DP01 16.92 5.6 7.0 na 14.82 0.1 144 7.0 EQ01 17.25 6.88 na DP02 18.34 5.6 7.0 na 14.82 0.1 144 7.0 EQ02 19.34 6.64 na DP03 17.84 5.6 12.25 na 19.6 0.1 196 7.0 EQ03 18.67 11.99 na DP04 17.17 5.6 7.0 na 14.82 0.1 144 7.0 EQ04 18.0 6.7 na S5 17.34 K=K@ EQ04 7.12 na 15.28 1 17.67 8.7 na 2 19.0 13.44 na 3 19.0 16.17 na 4 19.0 17.43 na 5 19.0 25.46 na 6 19.0 36.89 na 7 19.0 38.04 na 18 8.92 45.31 na 22 8.92 55.61 na TOR 8.92 58.66 na BFO 3.71 64.84 na BFI 3.71 73.96 na PRO 3.71 75.0 na PRI 3.71 95.38 na BOR 3.71 95.91 na TEST -5.0 101.03 na 100.0 S6 17.34 K=K@ EQ04 7.91 na 16.09 S7 19.34 K=K@ EQ03 11.99 na 19.6 S8 17.34 K=K@ EQ01 10.42 na 18.23 8 17.67 12.47 na 9 17.67 13.3 na 10 19.0 13.52 na 11 19.0 13.61 na 12 19.0 15.95 na 13 19.0 16.04 na S9 17.34 K=K@ EQ01 11.44 na 19.1 S10 19.34 K=K@ EQ02 12.1 na 20.0 S2 17.34 K=K@ EQ04 9.63 na 17.76 14 17.67 12.06 na 15 19.0 14.02 na 16 19.0 17.38 na S3 17.34 K=K@ EQ04 10.95 na 18.93 S4 18.67 K=K@ EQ03 12.73 na 20.19 S1 23.5 5.6 10.75 na 18.36 0.1 144 7.0 17 19.0 17.34 na S11 19.0 5.6 14.74 na 21.5 0.1 169 7.0 20 19.0 30.67 na 21 19.0 30.26 na 19 19.0 29.72 na The maximum velocity is 18 and it occurs in the pipe between nodes 4 and 5 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 5 Vail Public Library Remodel Main Level Calc Date 05/04/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn *EQUIVALENT K'S DP01 14.82 1.049 0.0 0.330 7.000 K Factor= 5.60 to 120.0 0.0 0.0 -0.143 EQ01 14.82 0.0758 0.0 0.330 0.025 Vel = 5.50 0.0 14.82 6.882 K Factor= 5.65 DP02 14.82 1.049 0.0 1.000 7.000 K Factor= 5.60 to 120.0 0.0 0.0 -0.433 EQ02 14.82 0.0750 0.0 1.000 0.075 Vel = 5.50 0.0 14.82 6.642 K Factor= 5.75 DP03 19.60 1.049 0.0 0.830 12.250 K Factor= 5.60 to 120.0 0.0 0.0 -0.359 EQ03 19.6 0.1253 0.0 0.830 0.104 Vel = 7.28 0.0 19.60 11.995 K Factor= 5.66 DP04 14.82 1.049 0.0 0.830 7.000 K Factor= 5.60 to 120.0 0.0 0.0 -0.359 EQ04 14.82 0.0747 0.0 0.830 0.062 Vel = 5.50 0.0 14.82 6.703 K Factor= 5.72 *REMOTE HEAD TO SUPPLY S5 15.28 1.049 3E 6.0 15.750 7.125 K Factor @ node EQ04 to 120.0 0.0 6.000 -0.143 1 15.28 0.0790 0.0 21.750 1.719 Vel = 5.67 1 16.09 1.049 3E 6.0 11.750 8.701 to 120.0 0.0 6.000 -0.576 2 31.37 0.2993 0.0 17.750 5.312 Vel = 11.65 2 19.60 1.38 1 T 6.0 8.170 13.437 to 120.0 0.0 6.000 0.0 3 50.97 0.1932 0.0 14.170 2.737 Vel = 10.93 3 78.83 2.157 0.0 10.190 16.174 to 120.0 0.0 0.0 0.0 4 129.8 0.1237 0.0 10.190 1.261 Vel = 11.40 4 75.24 2.157 1 T 12.307 15.540 17.435 to 120.0 0.0 12.307 0.0 5 205.04 0.2882 0.0 27.847 8.025 Vel = 18.00 5 -80.72 2.157 1 E 6.153 93.960 25.460 to 120.0 0.0 6.153 0.0 6 124.32 0.1142 0.0 100.113 11.435 Vel = 10.92 6 0.0 2.157 1 E 6.153 3.830 36.895 to 120.0 0.0 6.153 0.0 7 124.32 0.1142 0.0 9.983 1.140 Vel = 10.92 7 80.72 2.157 0.0 10.080 38.035 to 120.0 0.0 0.0 4.366 18 205.04 0.2882 0.0 10.080 2.905 Vel = 18.00 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 6 Vail Public Library Remodel Main Level Calc Date 05/04/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 18 0.0 2.157 2E 12.307 23.460 45.306 to 120.0 0.0 12.307 0.0 22 205.04 0.2882 0.0 35.767 10.308 Vel = 18.00 22 0.0 2.635 2E 16.474 11.500 55.614 to 120.0 0.0 16.474 0.0 TOR 205.04 0.1087 0.0 27.974 3.042 Vel = 12.06 TOR 0.0 3.26 2E 18.815 5.210 58.656 to 120.0 1 Fsp 0.0 18.815 5.256 * Fixed loss = 3 BFO 205.04 0.0386 0.0 24.025 0.927 Vel = 7.88 BFO 0.0 3.26 0.0 3.170 64.839 to 120.0 0.0 0.0 9.000 * Fixed loss = 9 BFI 205.04 0.0385 0.0 3.170 0.122 Vel = 7.88 BFI 0.0 3.26 2E 18.815 6.670 73.961 to 120.0 1 G 1.344 20.159 0.0 PRO 205.04 0.0386 0.0 26.829 1.035 Vel = 7.88 PRO 0.0 3.26 0.0 10.000 74.996 to 120.0 0.0 0.0 20.000 * Fixed loss = 20 PRI 205.04 0.0386 0.0 10.000 0.386 Vel = 7.88 PRI 0.0 3.26 1 E 9.408 3.000 95.382 to 120.0 1 G 1.344 10.752 0.0 BOR 205.04 0.0385 0.0 13.752 0.530 Vel = 7.88 BOR 0.0 4.1 3E 32.783 50.000 95.912 to 120.0 1 T 21.855 56.824 3.772 TEST 205.04 0.0126 1 G 2.186 106.824 1.349 Vel = 4.98 100.00 Qa = 100.00 305.04 101.033 K Factor= 30.35 *NEW PATH S6 16.09 1.049 2E 4.0 1.750 7.908 K Factor @ node EQ04 to 120.0 1 T 5.0 9.000 -0.143 1 16.09 0.0871 0.0 10.750 0.936 Vel = 5.97 0.0 16.09 8.701 K Factor= 5.45 "NEW PATH S7 19.60 1.049 2E 4.0 1.330 11.995 K Factor @ node EQ03 to 120.0 1 T 5.0 9.000 0.147 2 19.6 0.1254 0.0 10.330 1.295 Vel = 7.28 0.0 19.60 13.437 K Factor= 5.35 *NEW PATH S8 18.23 1.049 3E 6.0 14.060 10.416 K Factor @ node EQ01 to 120.0 0.0 6.000 -0.143 8 18.23 0.1096 0.0 20.060 2.199 Vel = 6.77 8 19.10 1.38 0.0 7.580 12.472 to 120.0 0.0 0.0 0.0 9 37.33 0.1086 0.0 7.580 0.823 Vel = 8.01 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 7 Vail Public Library Remodel Main Level Calc Date 05/04/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 9 0.0 1.38 2E 6.0 1.330 13.295 to 120.0 0.0 6.000 -0.576 10 37.33 0.1086 0.0 7.330 0.796 Vel = 8.01 10 0.0 1.38 0.0 0.830 13.515 to 120.0 0.0 0.0 0.0 11 37.33 0.1084 0.0 0.830 0.090 Vel = 8.01 11 20.00 1.61 1 T 8.0 12.700 13.605 to 120.0 0.0 8.000 0.0 12 57.33 0.1134 0.0 20.700 2.347 Vel = 9.03 12 0.0 2.157 0.0 3.340 15.952 to 120.0 0.0 0.0 0.0 13 57.33 0.0272 0.0 3.340 0.091 Vel = 5.03 13 21.50 2.157 0.0 2.670 16.043 to 120.0 0.0 0.0 0.0 3 78.83 0.0491 0.0 2.670 0.131 Vel = 6.92 0.0 78.83 16.174 K Factor= 19.60 *NEW PATH S9 19.10 1.049 2E 4.0 0.830 11.440 K Factor @ node EQ01 to 120.0 1 T 5.0 9.000 -0.143 8 19.1 0.1195 0.0 9.830 1.175 Vel = 7.09 0.0 19.10 12.472 K Factor= 5.41 *NEW PATH S10 20.00 1.049 2E 4.0 1.430 12.101 K Factor @ node EQ02 to 120.0 1 T 5.0 9.000 0.147 11 20.0 0.1301 0.0 10.430 1.357 Vel = 7.42 0.0 20.00 13.605 K Factor= 5.42 "NEW PATH S2 17.76 1.049 2E 4.0 15.660 9.625 K Factor @ node EQ04 to 120.0 1 T 5.0 9.000 -0.143 14 17.76 0.1044 0.0 24.660 2.575 Vel = 6.59 14 18.93 1.38 3E 9.0 15.160 12.057 to 120.0 0.0 9.000 -0.576 15 36.69 0.1052 0.0 24.160 2.541 Vel = 7.87 15 20.19 1.38 1 T 6.0 8.170 14.022 to 120.0 0.0 6.000 0.0 16 56.88 0.2367 0.0 14.170 3.354 Vel = 12.20 16 18.36 2.157 0.0 1.310 17.376 to 120.0 0.0 0.0 0.0 4 75.24 0.0450 0.0 1.310 0.059 Vel = 6.61 0.0 75.24 17.435 K Factor= 18.02 "NEW PATH Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 8 Vail Public Library Remodel Main Level Calc Date 05/04/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn S3 18.93 1.049 2E 4.0 1.660 10.947 K Factor @ node EQ04 to 120.0 1 T 5.0 9.000 -0.143 14 18.93 0.1175 0.0 10.660 1.253 Vel = 7.03 0.0 18.93 12.057 K Factor= 5.45 *NEW PATH S4 20.19 1.049 2E 4.0 1.830 12.730 K Factor @ node EQ03 to 120.0 1 T 5.0 9.000 -0.143 15 20.19 0.1325 0.0 10.830 1.435 Vel = 7.50 0.0 20.19 14.022 K Factor= 5.39 *NEW PATH S1 18.36 1.049 5E 10.0 26.780 10.749 K Factor= 5.60 to 120.0 1 T 5.0 15.000 1.949 17 18.36 0.1111 0.0 41.780 4.641 Vel = 6.82 17 0.0 2.157 0.0 10.920 17.339 to 120.0 0.0 0.0 0.0 16 18.36 0.0034 0.0 10.920 0.037 Vel = 1.61 0.0 18.36 17.376 K Factor= 4.40 *NEW PATH S11 21.50 1.049 1 E 2.0 1.770 14.738 K Factor= 5.60 to 120.0 1 T 5.0 7.000 0.0 13 21.5 0.1488 0.0 8.770 1.305 Vel = 7.98 0.0 21.50 16.043 K Factor= 5.37 *NEW PATH 7 -80.72 2.157 3E 18.46 124.870 38.035 to 120.0 0.0 18.460 0.0 20 -80.72 -0.0514 0.0 143.330 -7.363 Vel = 7.09 20 0.0 2.157 0.0 8.000 30.672 to 120.0 0.0 0.0 0.0 21 -80.72 -0.0514 0.0 8.000 -0.411 Vel = 7.09 21 0.0 2.157 0.0 10.580 30.261 to 120.0 0.0 0.0 0.0 19 -80.72 -0.0513 0.0 10.580 -0.543 Vel = 7.09 19 0.0 2.157 1 E 6.153 64.420 29.718 to 120.0 1 T 12.307 18.460 0.0 5 -80.72 -0.0514 0.0 82.880 -4.258 Vel = 7.09 0.0 -80.72 25.460 K Factor= -16.00 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 _ _ _ Fire Prakeckian �y Compuker Design Central Fire Protection 10775 E. 51 st Ave. Denver, CO 80239 (303) 576-8157 Job Name : Vail Public Library Remodel Main Level Calc Building : FP3 Location : 292 West Meadow Drive, Vail, Colorado 81657 System : 2 Contract : 284212 Data File : Vail Public Library Remodel Main Level Calc AREA 2.wxf I attest to the accuracy and integrity of this ___ document � Marvin Heath, SET This fire sprinkler system hydraulic Central Fire Protection Contractors, ���. calculation has been completed in NICET LevellV#079201 Fire Protection Engineering Technology/ compliance with NFPA, Local, &State Codes. Water-Based Systems Layout 2012.05.07 14:03:28-06'00' Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Central Fire Protection Page 1 Vail Public Library Remodel Main Level Calc Date 05/06/2012 HYDRAULIC CALCULATIONS for Project name: Vail Public Library Remodel Location: 292 West Meadow Drive, Vail, Colorado 81657 Drawing no: FP3 Date: 05/06/2012 Design Remote area number: 2 Remote area location: Main Library Occupancy classification: Light Hazard Density: 0.10 - Gpm/SqFt Area of application: 973 - SqFt Coverage per sprinkler: varies - SqFt Type of sprinklers calculated: QR 'Old Style' Sprinklers No. of sprinklers calculated: 9 In-rack demand: 0 - GPM Hose streams: 100 - GPM Total water required (including hose streams): 254.144 - GPM @ 76.129 - Psi Type of system: Wet Volume of dry or preaction system: N/a - Gal Water supply information Date: 04/24/2012 Location: 22 West Meadow Drive, Vail, Colorado Source: Vail Fire Rescue Name of contractor: Central Fire Protection Contractors, Inc. Address: 10775 E. 51 st Ave., Denver, CO 80239 Phone number: 303-576-8157 Name of designer: Stephanie Pelster Authority having jurisdiction: Vail Fire Rescue Notes: (Include peaking information or gridded systems here.) A 10°/o reduction has been taken off of the original Static& Residual pressures of the flow test. See sheet FP1 for further information regarding the flow test. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) Central Fire Protection Page 2 Vail Public Library Remodel Main Level Calc Date 05/06/2012 City Water Supply: Demand: C1 - Static Pressure : 135 D1 - Elevation : 10.394 C2 - Residual Pressure: 130.5 D2 - System Flow : 154.144 C2 - Residual Flow : 1353 D2 - System Pressure : 76.129 Hose ( Demand ) : 100 D3 - System Demand : 254.144 Safety Margin : 58.667 150 140 2 130 P 120 R 110 E 100 S 90 S 80 � 70 R 60 E 50 40 30 20 10 D1 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N " 1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Central Fire Protection Page 3 Vail Public Library Remodel Main Level Calc Date 05/06/2012 Fitting Legend Abbrev. Name Yz '/4 1 1'/< 1'/z 2 2Yz 3 3'/z 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90'Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90'Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Central Fire Protection Page 4 Vail Public Library Remodel Main Level Calc Date 05/06/2012 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. DP01 18.42 5.6 7.0 na 14.82 0.1 144 7.0 EQ01 19.0 6.79 na DP02 18.42 5.6 7.0 na 14.82 0.1 144 7.0 EQ02 19.0 7.17 na DP03 18.42 5.6 9.54 na 17.3 0.1 173 7.0 EQ03 19.0 9.85 na DP04 18.42 5.6 7.96 na 15.8 0.1 158 7.0 EQ04 19.0 7.93 na S12 19.0 K=K@ EQ01 8.37 na 16.45 S13 19.0 K=K@ EQ02 9.29 na 16.87 S14 19.0 K=K@ EQ03 11.99 na 19.09 19 19.0 13.72 na 5 19.0 17.09 na 6 19.0 21.17 na 7 19.0 21.58 na 18 8.92 27.66 na 22 8.92 33.74 na TOR 8.92 35.54 na BFO 3.71 41.34 na BFI 3.71 50.41 na PRO 3.71 51.02 na PRI 3.71 71.25 na BOR 3.71 71.56 na TEST -5.0 76.13 na 100.0 20 19.0 13.84 na 21 19.0 13.68 na S15 19.0 K=K@ EQ01 8.44 na 16.51 S16 19.0 K=K@ EQ02 9.71 na 17.25 S18 19.0 K=K@ EQ02 8.94 na 16.55 S17 19.0 K=K@ EQ02 10.04 na 17.54 S19 19.0 K=K@ EQ04 8.74 na 16.59 S20 19.0 K=K@ EQ03 9.85 na 17.3 The maximum velocity is 13.53 and it occurs in the pipe between nodes 7 and 18 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 5 Vail Public Library Remodel Main Level Calc Date 05/06/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn *EQUIVALENT K'S DP01 14.82 1.049 0.0 0.580 7.000 K Factor= 5.60 to 120.0 0.0 0.0 -0.251 EQ01 14.82 0.0741 0.0 0.580 0.043 Vel = 5.50 0.0 14.82 6.792 K Factor= 5.69 DP02 14.82 1.049 1 T 5.0 0.580 7.000 K Factor= 5.60 to 120.0 0.0 5.000 -0.251 EQ02 14.82 0.0747 0.0 5.580 0.417 Vel = 5.50 0.0 14.82 7.166 K Factor= 5.54 DP03 17.30 1.049 1 T 5.0 0.580 9.544 K Factor= 5.60 to 120.0 0.0 5.000 -0.251 EQ03 17.3 0.0995 0.0 5.580 0.555 Vel = 6.42 0.0 17.30 9.848 K Factor= 5.51 DP04 15.80 1.049 1 E 2.0 0.580 7.960 K Factor= 5.60 to 120.0 0.0 2.000 -0.251 EQ04 15.8 0.0841 0.0 2.580 0.217 Vel = 5.87 0.0 15.80 7.926 K Factor= 5.61 *REMOTE HEAD TO SUPPLY S12 16.45 1.049 1 E 2.0 8.080 8.372 K Factor @ node EQ01 to 120.0 0.0 2.000 0.0 S13 16.45 0.0906 0.0 10.080 0.913 Vel = 6.11 S13 16.86 1.049 0.0 8.080 9.285 K Factor @ node EQ02 to 120.0 0.0 0.0 0.0 S14 33.31 0.3345 0.0 8.080 2.703 Vel = 12.37 S14 19.09 1.38 1T 6.0 2.500 11.988 K Factor @ node EQ03 to 120.0 0.0 6.000 0.0 19 52.4 0.2033 0.0 8.500 1.728 Vel = 11.24 19 18.83 2.157 1 E 6.153 64.420 13.716 to 120.0 1 T 12.307 18.460 0.0 5 71.23 0.0408 0.0 82.880 3.378 Vel = 6.25 5 0.0 2.157 1 E 6.153 93.960 17.094 to 120.0 0.0 6.153 0.0 6 71.23 0.0408 0.0 100.113 4.080 Vel = 6.25 6 0.0 2.157 1 E 6.153 3.830 21.174 to 120.0 0.0 6.153 0.0 7 71.23 0.0408 0.0 9.983 0.407 Vel = 6.25 7 82.91 2.157 0.0 10.080 21.581 to 120.0 0.0 0.0 4.366 18 154.14 0.1699 0.0 10.080 1.713 Vel = 13.53 18 0.0 2.157 2E 12.307 23.460 27.660 to 120.0 0.0 12.307 0.0 22 154.14 0.1700 0.0 35.767 6.081 Vel = 13.53 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 6 Vail Public Library Remodel Main Level Calc Date 05/06/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 22 0.0 2.635 2E 16.474 11.500 33.741 to 120.0 0.0 16.474 0.0 TOR 154.14 0.0641 0.0 27.974 1.794 Vel = 9.07 TOR 0.0 3.26 2E 18.815 5.210 35.535 to 120.0 1 Fsp 0.0 18.815 5.256 * Fixed loss = 3 BFO 154.14 0.0228 0.0 24.025 0.547 Vel = 5.92 BFO 0.0 3.26 0.0 3.170 41.338 to 120.0 0.0 0.0 9.000 * Fixed loss = 9 BFI 154.14 0.0227 0.0 3.170 0.072 Vel = 5.92 BFI 0.0 3.26 2E 18.815 6.670 50.410 to 120.0 1 G 1.344 20.159 0.0 PRO 154.14 0.0227 0.0 26.829 0.610 Vel = 5.92 PRO 0.0 3.26 0.0 10.000 51.020 to 120.0 0.0 0.0 20.000 * Fixed loss = 20 PRI 154.14 0.0228 0.0 10.000 0.228 Vel = 5.92 PRI 0.0 3.26 1 E 9.408 3.000 71.248 to 120.0 1 G 1.344 10.752 0.0 BOR 154.14 0.0228 0.0 13.752 0.313 Vel = 5.92 BOR 0.0 4.1 3E 32.783 50.000 71.561 to 120.0 1 T 21.855 56.824 3.772 TEST 154.14 0.0075 1 G 2.186 106.824 0.796 Vel = 3.75 100.00 Qa = 100.00 254.14 76.129 K Factor= 29.13 "NEW PATH 7 -82.92 2.157 3E 18.46 124.870 21.581 to 120.0 0.0 18.460 0.0 20 -82.92 -0.0540 0.0 143.330 -7.738 Vel = 7.28 20 33.90 2.157 0.0 8.000 13.843 to 120.0 0.0 0.0 0.0 21 -49.02 -0.0205 0.0 8.000 -0.164 Vel = 4.30 21 67.84 2.157 0.0 10.580 13.679 to 120.0 0.0 0.0 0.0 19 18.82 0.0035 0.0 10.580 0.037 Vel = 1.65 0.0 18.82 13.716 K Factor= 5.08 *NEW PATH S15 16.51 1.049 1 E 2.0 12.000 8.435 K Factor @ node EQ01 to 120.0 0.0 2.000 0.0 S16 16.51 0.0913 0.0 14.000 1.278 Vel = 6.13 S16 17.25 1.049 1T 5.0 6.570 9.713 K Factor @ node EQ02 to 120.0 0.0 5.000 0.0 21 33.76 0.3428 0.0 11.570 3.966 Vel = 12.53 0.0 33.76 13.679 K Factor= 9.13 *NEW PATH Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Central Fire Protection Page 7 Vail Public Library Remodel Main Level Calc Date 05/06/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn S18 16.55 1.049 0.0 12.000 8.940 K Factor @ node EQ02 to 120.0 0.0 0.0 0.0 S17 16.55 0.0917 0.0 12.000 1.100 Vel = 6.14 S17 17.54 1.049 1T 5.0 5.430 10.040 K Factor @ node EQ02 to 120.0 0.0 5.000 0.0 21 34.09 0.3489 0.0 10.430 3.639 Vel = 12.66 0.0 34.09 13.679 K Factor= 9.22 *NEW PATH S19 16.59 1.049 0.0 12.000 8.742 K Factor @ node EQ04 to 120.0 0.0 0.0 0.0 S20 16.59 0.0922 0.0 12.000 1.106 Vel = 6.16 S20 17.30 1.049 1 T 5.0 6.570 9.848 K Factor @ node EQ03 to 120.0 0.0 5.000 0.0 20 33.89 0.3453 0.0 11.570 3.995 Vel = 12.58 0.0 33.89 13.843 K Factor= 9.11 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 CENTRAL FIRE PROTECTION CONTRACTORS, INC. 107'�5 EAST 51`��� AVENUE DFN`'�R. CO 80�39 303-5��-81 ��"7 T�AX 303—�'7C�-8159 State RegiStration � 004 c�_f�c:(�?c_fpc. ta_s Job ,��' �84�1� Vail Public Libr�r°y Rerriodel �92 West Meadow Drive Vail, Colorado 8"165�7 Product Manufacturer Description 1. Sprinkler Heads: Tyco TY3631 TY FRB QR Old ct.yle Pendent, w� 1 Piece Flush Escut�heon Tyco TY�531 RFII Concealed Pendent Tyco TY�1�1 TY FRB �R Upright Tyc�o TY33�1 TY—FRB QR HS�N 2. Pipe: Allied Tube Schedule 40�Schedule 10 3. Fittings: Shurjoint Grooced �'ittings Shurjoint Grooved Couplings Smith Cooper Ductile Iron Thread Fit,tings Smith Cooper Weld Outlets 1 4. Valves: AGF Moclel 1011 Te�t 8c Drain Ames Mode]_ 40005�� Reduced Pressure Backflow (Existing - included for Hydraulic Reference only� PressLlre Reducing Valve (Fxi�ting - included for Hydraulic Reference on1y� 5. Hangers: Tol�o ;�?00 Rin� H�ngers Tolco ,�100 All Thread Rod Hilt.i HDI P Drop Tn Anchors 2 �'��+� �ir�� c�'c ��i��'ir�� �������� Technical Services: Tel: (800) 381-9312/Fax: (800) 791-5500 Series TY-FRB — 5.6 and 8.0 K-factor Conventional (Old Style) Sprinklers Quick Response cable approval agencies, the testing is General not representative of all possible cor- �Y�y . . rosive atmospheres. Consequently, it � Descr�pt�on is recommended that the end user be �.,�,� consulted with respect to the suitability 4+� !� The Series TY-FRB, 5.6 and 8.0 K-fac- of these coatings for any given corro- tor, Conventional Sprinklers described sive environment.The effects of ambi- in this data sheet are quick response- ent temperature, concentration of �: standard coverage, decorative 3 mm chemicals, and gas/chemical velocity, -. glass bulb type spray sprinklers. should be considered, as a minimum, � ' These sprinklers are intended to be along with the corrosive nature of the +,��� installed either pendent or upright,and chemical to which the sprinklers will be ��'� in either position, they produce a exposed. �� spherical water discharge pattern with approximately 50% of the discharge directed upwards and approximately 50% of the discharge directed down- WARNINGS � wards. The Series TY-FRB Sprinklers de- TeChI1ICaI scribed herein must be installed and Conventional sprinklers are generally maintained in compliance with this Data used with Ordinary and Extra High document, as well as with the applica- Hazard Class Systems, as defined by ble standards of the National Fire Pro- the automatic sprinkler system instal- tection Association, in addition to the Approvals lation rules of the country and authority standards ofany otherauthorities hav- UL and C-UL Listed. having jurisdiction.The NFPA permits ing jurisdiction. Failure to do so may LPCB, VdS and NYC Approved. the use of"Old Style Sprinklers"where impair the performance of these de- �Refer to Table A for complete approval special construction features require a vices. information including corrosion resis- unique water distribution; for the pro- tant status.) tection of fur vaults; or, the replace- The owneris responsible formaintain- Maximum Working Pressure ment of similar sprinklers that had �ng theirfire protection system and de- 175 psi (12,1 bar) been installed prior to 1955. vices in proper operating condition. The installing contractor or sprinkler Discharge Coefficient Corrosion resistant coatings, where manufacturer should be contacted K=5.6 GPM/psi1i2 (80,6 LPM/bar��2) applicable, are utilized to extend the with any questions. K=8.0 GPM/psi1�2(115,2 LPM/bar��2) life of copper alloy sprinklers beyond that which would otherwise be ob- Temperature Ratings tained when exposed to corrosive at- Refer to Table A mospheres. Although corrosion resis- MOdeI�SpI�II1kIeP Finishes tant coated sprinklers have passed the Sprinkler: Refer to Table A standard corrosion tests of the appli- 'dentification Physical Characteristics Frame . . . . . . . . . . . . Bronze IMPORTANT Numbers Button . . . . . . . . Brass/Copper Y Always refer to Technical Data Sealing Assembly . . . . . . . . . . � TY3631 - 5.6K,1/2"NPT . Beryllium Nickel w/Teflont E Sheet TFP700 for the `7NSTALLER • • • • • �, TY4631 - 8.OK,3/4"NPT WARN/NG" that provides cautions Bulb . . . . . . . . . . . . . . Glass � with respect to handling and instal- Compression Screw . . . . . Bronze � lation of sprinkler systems and com- Deflector . . . . . . . . . . . Copper � ponents. Improper handling and in- �' stallation can permanently damage � a sprinkler system or its compo- o� nents and cause the sprinkler to fail o to operate in a fire situation orcause a it to operate prematurely. o � Page 1 of 4 JULY, 2004 TFP666 Page 2 of 4 TFP666 ESCUTCHEON 7/16"(11,1 mm) ESCUTCHEON 1/2"(12,7 mm) PLATE SEATING NOMINAL PLATE SEATING NOMINAL SURFACE 1�2 ** MAKE-IN SURFACE 3�4 ** MAKE-IN � NPT � i NPT � g* � — � g* � I 5 I I - 5 2-3/16" � 2-1/4" � (55,6 mm) � 4 (57,2 mm) � 4 1-1/2" 2 1-1/2" 2 (38,1 mm) � � (38,1 mm) � V � � , �• � � 3 � / 3 i I WRENCH '� � � � WRENCH - FLATS 1 FLATS 1 SHOWN CROSS SECTION SHOWN CROSS SECTION PENDENT SHOWN UPRIGHT PENDENT SHOWN UPRIGHT 1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2-Button Assembly 5-Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 SERIES TY-FRB 5.6 K-FACTOR(TY3631)AND 8.0 K-FACTOR(TY4631) QUICK RESPONSE CONVENTIONAL SPRINKLERS Operation Installation , The glass Bulb contains a fluid which The Series TY-FRB Sprinklers must be � WRENCH RECESS expands when exposed to heat.When installed in accordance with the follow- ; (Ervo��a��USED FOR the rated temperature is reached, the ing instructions: -� v2"NPT MODELS) fluid expands sufficiently to shatter the - glass Bulb, allowing the sprinkler to NOTES � activate and water to flow. Do not install any bulb type sprinkler if WRENCH RECESS the bulb is cracked or there is a loss of (END��8��USED FOR liquid from the bulb. With the sprinkler 3/4��NPT MODELS) - held horizontally, a small air bubble FIGURE 2 Des�g n should be present. The diamefer of the w TYPE 6 SPRINKLER Cr�te� � air bubble is approximately 1/16 inch WRENCH r�a (1,6 mm) for the 135°F/57°C to 3/32 inch (2,4 mm) for the 286°F/141°C The Series TY-FRB Conventional temperature ratings. Sprinklers are intended for fire protec- tion systems designed in accordance Aleaktightl/2inchNPTsprinklerjoint with the standard installation rules rec- should be obtained with a torque of 7 ognized by the applicable Listing or to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- Approval agency (e.g., UL Listing is mum of 21 ft. Ibs. (28,5 Nm) of torque based on NFPA 13 requirements).The may be used to install sprinklers with Series TY-FRB Conventional Sprin- 1/2 NPT connections. A leak tight 3/4 klers are only for non-recessed appli- inch NPT sprinkler joint should be ob- cations. tained with a torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). A maximum of 30 ft.lbs. (40,7 Nm)of torque is to be used to install sprinklers with 3/4 NPT con- nections. Higher levels of torque may distort the sprinkler inlet and cause leakage or impairmenf of the sprinkler. Step 1. With pipe thread sealant ap- plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 2). With reference to Figure 1,the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. TFP666 Page 3 of 4 SPRINKLER FINISH(See Note 6) TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD LIQUID BRASS PLATED POLYESTER COATED 5.6K 135°F/57°C Orange CONVENTIONAL 155°F/68°C Red (TY3631) 1,2,3,4,5 1,2,4 or 175°F/79°C Yellow 8.OK 200°F/93°C Green CONVENTIONAL (TY4631) 286°F/141°C Blue NOTES: 1.Listed by Underwriters Laboratories, Inc.(UL)as Quick Response. 2.Listed by Underwriters Laboratories, Inc.for use in Canada(C-UL)as Quick Response. 3.Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06&007k/04)as Quick Response. 4.Approved by the City of new York under MEA 354-01-E. 5.VdS Approved(For details contact Tyco Fire&Building Products, Enschede, Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377). 6.Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. `* 150°F/66°C Maximum Ceiling Temperature. "'Frame and defiector only.Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS Care and ommended to be initially performed for corrosion resistant coated sprinklers, . after the installation has been com- Ma�ntenance pleted,to verify the integrity of the cor- rosion resistant coating. Thereafter, The Series TY-FRB Sprinklers must be annual inspections per NFPA 25 maintained and serviced in accord- should suffice; however, instead of in- ance with the following instructions: specting from the floor level,a random sampling of close-up visual inspec- NOTES tions should be made, so as to better Before closing a fire protection system determine the exact sprinkler condi- main control valve for maintenance tion and the long term integrity of the work on the fire protection system that corrosion resistant coating, as it may it controls,permission to shut down the be affected by the corrosive conditions affected fire protection system mustbe present. obtained from the proper authorities and all personnel who may be affected The owner is responsible for the in- by this action must be notified. spection, testing, and maintenance of Sprinklers that are found to be leaking their fire protection system and de- or exhibiting visible signs of corrosion vices in compliance with this docu- must be replaced. ment, as well as with the applicable standards of the National Fire Protec- Automatic sprinklers must never be tion Association (e.g., NFPA 25), in painted, plated, coated or otherwise addition to the standards of any other altered after leaving the factory. Modi- authorities having jurisdiction. The in- fied sprinklers must be replaced. stalling contractor or sprinkler manu- Sprinklers that have been exposed to facturershouldbecontactedrelativeto corrosive products of combustion, but any questions. have not operated, should be replaced if they cannot be completely cleaned It is recommended that automatic by wiping the sprinkler with a cloth or sprinkler systems be inspected, by brushing it with a soft bristle brush. tested, and maintained by a qualified Inspection Service in accordance with Care must be exercised to avoid dam- local requirements and/or national age to the sprinklers - before, during, code. and after installation. Sprinklers dam- aged by dropping, striking, wrench twisUslippage, or the like, must be re- placed.Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). Frequent visual inspections are rec- Page 4 of 4 TFP666 P/N 57 - XXX - X - XXX TEMPERATURE RATING SPRINKLER MODEL/SIN 135 135°F/57°C 373 5.6K CONVENTIONAL TY3631 1 NATURAL BRASS 155 155°F/68°C 393 8.OK CONVENTIONAL TY4631 9 CHROME PLATED 175 175°F/79°C 4 WHITE POLYESTER 200 200°F/93°C 3 WHITE(RA�9010)* 286 286°F/141°C 7 LEAD COATED `Eastern Hemisphere sales only. TABLE B PART NUMBER SELECTION SER/ES TY-B CONVENTIONAL SPRINKLERS Limited PRODUCTS BE LIABLE, IN CON- Ordering TRACT,TORT,STRICT LIABILITY OR UNDER ANY OTHER LEGAL THE- PrOCP.dI.II�P. Warranty ORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL Products manufactured by Tyco Fire DAMAGES, INCLUDING BUT NOT �Nhenplacinganorder,indicatethefull Products are warranted solely to the LIMITED TO LABOR CHARGES, RE- product name. Refer to the Price List original Buyer for ten (10) years GARDLESS OF WHETHER TYCO for complete listing of Part Numbers. against defects in material and work- FIRE PRODUCTS WAS INFORMED Contact your local distributor for avail- manship when paid for and properly ABOUT THE POSSIBILITY OF SUCH ability. installed and maintained undernormal DAMAGES, AND IN NO EVENT use and service.This warranty will ex- SHALL TYCO FIRE PRODUCTS' LI- Sprinkler Assemblies with NPT pire ten (10) years from date of ship- ABILITY EXCEED AN AMOUNT Thread Connections: ment by Tyco Fire Products. No war- EQUAL TO THE SALES PRICE. Specify: (Specify Model/SIN), Quick ranty is given for products or THE FOREGOING WARRANTY IS Response, (specify K-factor), (specify components manufactured by compa- nies not affiliated by ownership with MADE IN LIEU OF ANY AND ALL temperature rating), Series TY-FRB Tyco Fire Products or for products and OTHER WARRANTIES EXPRESS OR Conventional Sprinkler with (specify components which have been subject IMPLIED,INCLUDING WARRANTIES type of finish or coating), P/N (specify to misuse, improper installation,corro- OF MERCHANTABILITY AND FIT- from Table B) sion, or which have not been installed, NESS FOR A PARTICULAR PUR- maintained,modified or repaired in ac- POSE. Sprinkler Wrench: cordance with applicable Standards of Specify: W-Type 6 Sprinkler Wrench, the National Fire Protection Associa- P/N 56-000-6-387. tion, and/or the standards of any other Authorities Having Jurisdiction. Mate- rials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products' sole option. Tyco Fire Products neither as- sumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. IN NO EVENT SHALL TYCO FIRE TYCO FIRE PRODUCTS,451 North Cannon Avenue,Lansdale, Pennsylvania 19446 �`L�CO Fire & Building Products Technical Services: Tel: (800) 381-9312 / Fax: (800)791-5500 Style 65 One-Piece Flush Escutcheon Style 401 Two-Piece Deep Escutcheon 1/2 Inch and 3/4 /nch NPT General WARNINGS The Style 65 and 401 Escutcheons de- Descr�n�/�/'� scribed herein must be installed and � I�+ maintained in compliance with this The Tyco°Style 65 and 401 Escutch- document, as well as with the applica- - � eon Plates illustrated in Figures 1 and 2 ble standards of the National Fire Pro- are designed for use with pendent and tection Association, in addition to the � horizontal sidewall automatic sprin- standards of any other authorities hav- - klers in fire protection systems where ing jurisdiction. Failure to do so may the piping is installed above a ceiling �mpair the performance of these or behind a wall. They are used to im- devices. STYLE 65 prove the overall appearance of the in- The owner is responsible for maintain- ONE-PIECE ESCUTCHEON stallation by concealing the clearance ing their fire protection system and de- holes required for the connecting pip- vices in proper operating condition. ing and fittings to the sprinkler. The installing contractor or sprinkler The Escutcheon Plates are available manufacturer should be contacted in two styles: Style 65 flush one-piece with any questions. �, (non-adjustable),and Style 401 deep two-piece(adjustable). rechnical � The flush one-piece (non-adjustable) '� � 1 Style 65 Escutcheon Plates(Fig. 1)are Data � used where the position of the sprin- kler "escutcheon plate seating sur- Approvals face"(relative to the ceiling line or wall) With reference to NFPA 13, listings/ap- � � can be fixed by adjusting the length of provals are not required for metallic the interconnecting piping. escutcheons used for non-recessed ` - - The two-piece Style 401 Escutcheon applications. Plates(Fig.2)are used where it is nec- Finishes STYLE 401 essary to position the sprinkler away Chrome, White, or Brass from the ceiling/wall surface so that Material TWO-PIECE ESCUTCHEON spray will not be adversely affected by Carbon Steel protruding obstructions such as light fixtures and HVAC diffusers. The adjustment provided by the Style 401 Escutcheon Plates reduces the ac- curacy to which the length of the fixed pipe drops or horizontal pipe runs to the sprinklers must be cut, and it pro- vides additional flexibility in the inter- connecting pipe. The separable, two-piece design of the Style 401 allows installation of the sprinklers and pressure testing of the fire protection system/evaluation of leak tightness prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling. They also permit the removal of suspended ceiling panels, for access to building service equipment, without having to first shut down the fire protection sys- tem and remove sprinklers. Page 1 of 4 DECEMBER, 2007 TFP777 Page 2 of 4 TFP777 3-1/2"DIA. 2-13/16" DIA. �- (8g,0 mm) � (71,4 mm) � 2" DIA. 2-1/2" DIA. y (50,8 mm) (63,5 mm) 2-1/4"DIA. (57,2 mm) CEILING CEILING SURFACE SURFACE 11 � � SKIRT * 2-7/8" MAX. � (73,0 mm) FRICTION MIN.1-7/8" 1�2 FIT (47,6 mm) 1/2"OR (12,7 mm) 3/4" NPT CUP* � OPENING ESCUTCHEON PLATE SEATING 1/2"OR SHOWN WITH SURFACE 3/4" NPT SERIES TY-FRB OPENING ESCUTCHEON 5.6 K-FACTOR PLATE SEATING PENDENT SPRINKLER SHOWN WITH SURFACE FOR REFERENCE SERIES TY-FRB 5.6 K-FACTOR PENDENT SPRINKLER *ORDERED FOR REFERENCE SEPARATELY FIGURE 1 FIGURE 2 STYLE 65 ONE-PIECE STYLE 401 TWO-PIECE DEEP FLUSH ESCUTCHEON ADJUSTABLE ESCUTCHEON TFP777 Page 3 of 4 Installation Step 4. Using the appropriate sprin- kler wrench, tighten the sprinkler into NOTES the fitting. A leak tight 1/2 inch NPT sprinkler joint Step 5. After a suspended ceiling has should be obtained with a torque of 7 been installed or the finish coat has to 14 ft.lbs. and 10 to 20 ft.lbs. should been applied to a wall or fixed ceil- be sufficient for a 3/4 inch NPT sprin- ing (as appropriate), align the detents kler. Higherlevels of torque may distort in the skirt over those in the cup and the sprinkler orifice seat with conse- then slide the cup over the skirt until quent leakage. it comes in contact with the mount- ing surface. Do not push the skirt such Do not attempt to make-up for insuf- that it will lift a ceiling tile out of its nor- ficient adjustment in an Escutcheon mal position. Plate by under- or over-tightening the Holding the skirt in contact with the sprinkler. Readjust the position of the mounting surface, rotate the skirt ap- sprinkler fitting to suit. proximately 1/8-turn in relation to the Style 65 cup creating a friction fit between the The pipe connected to the sprinkler skirt detents and the cup wall, to hold fitting must be cut so that the "es- the Escutcheon Plate firmly together. cutcheon plate seating surface" is at the proper nominal distance in front Care and of the wall or below the ceiling. Man- ufacturing variations in the take-out of Maintenance the fittings as well as the make-in of the sprinklers (as permitted by ANSI The following inspection procedure B1.20.1) may require that trial cuts of must be performed as indicated, in the connecting pipe be made. addition to any specific requirements Proceed with the assembly as follows: of the NFPA.Any impairments must be Step 1. Insert the threaded end of immediately corrected. the sprinkler through the Escutcheon The owner is responsible for the in- Plate. spection, testing, and maintenance of Step 2. Apply pipe thread seal- their fire protection system and devic- ant sparingly to the sprinkler threads es in compliance with this document, only. Use of a non-hardening type of as well as with the applicable stan- Teflon based pipe thread sealant is dards of the National Fire Protection recommended. Association(e.g., NFPA 25), in addition Step 3. Hand tighten the sprinkler with to the standards of any authority hav- the attached Escutcheon Plate into the ing jurisdiction. The installing contrac- sprinkler fitting. tor or product manufacturer should be Step 4. Using the appropriate sprin- contacted relative to any questions. kler wrench, tighten the sprinkler into It is recommended that automatic sprin- the fitting. kler systems be inspected, tested, and Style 401 maintained by a qualified Inspection The pipe connected to the sprinkler fit- Service in accordance with local re- ting must be cut so that the "escutch- quirements and/or national codes. eon plate seating surface" is at the After placing a fire protection system proper nominal distance in front of the in service, notify the proper authorities wall or below the ceiling. and advise those responsible for mon- Proceed with the assembly as follows: itoring proprietary and/or central sta- Step 1. Separate the two pieces of tion alarms. the Escutcheon Plate and screw the cup onto the sprinkler until the plate is engaged onto the last thread of the sprinkler. Step 2. Apply a brush-on pipe thread sealant sparingly to the sprinkler threads only. Use of a non-hardening type of Teflon based pipe thread seal- ant is recommended. Step 3. Hand tighten the sprinkler with the attached inner plate into the sprin- kler fitting. Page 4 of 4 TFP777 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire When placing an order, indicate the full & Building Products (TFBP) are war- product name. Contact your local dis- ranted solely to the original Buyer for tributor for availability. ten (10)years against defects in mate- Style 65 rial and workmanship when paid for Specify: Style 65 Flush One-Piece Es- and properly installed and maintained cutcheon with (1/2 or 3/4) NPT Open- under normal use and service. This ing and (Chrome, White, or Brass) Fin- warranty will expire ten(10)years from ish, P/N (specify). date of shipment by TFBP. No warran- ty is given for products or components Style 65 One-Piece Escutcheon manufactured by companies not af- 1i2"Chrome...................... P/N 1153 filiated by ownership with TFBP or for 3/4�°Chrome...................... P/N 1152 products and components which have 1i2"White........................ P/N 1174 been subject to misuse, improper in- 3ia��White........................ P/N 1175 stallation, corrosion,or which have not 1i2;;Brass........................ P/N 1150 been installed,maintained,modified or 3/4 Brass........................ P/N 1184 repaired in accordance with applicable Style 401 Cup* Standards of the National Fire Protec- Specify:Style 401 Cup with(1/2 or 3/4) tion Association, and/or the standards NPT Opening and (Chrome, White, or of any other Authorities Having Juris- grass) Finish, P/N (specify). diction. Materials found by TFBP to be defective shall be either repaired or re- styie aoi cUp placed, at TFBP's sole option. TFBP 1i2„Cup.Chrome ................. P/N 1192 neither assumes, nor authorizes any 3/4 Cup.Chrome ................. P/N 1193 person to assume for it, any other ob- �i2"Cup.White ................... P/N 1196 ligation in connection with the sale of 3/4��Cup.White ................... P/N 1197 products or parts of products. TFBP 1i2"Cup.Brass ................... P/N 1194 shall not be responsible for sprinkler 3ia��Cup.Brass ................... P/N 1195 system design errors or inaccurate or Style 401 Skirt* incomplete information supplied by Specify: Style 401 Skirt with (Chrome, Buyer or Buyer's representatives. White,or Brass)Finish, P/N(specify). In no event shall TFBP be liable, in Style401 Skirt contract, tort, strict liability or under Chrome.......................... P/N 1198 any other legal theory, for incidental, White............................P/N 1200 indirect,special or consequential dam- Brass............................ Pirv iiss ages, including but not limited to labor �The Cup and Skirt are ordered sepa- charges, regardless of whether TFBP rately for the Style 401 Escutcheon. was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties of inerchantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale Pennsylvania 19446 co 800-381-9312 TechnicalServices +1-401-781-8220 www.tyco-fire.com Series RFII — 5.6 K-factor ��Royal Flush ll" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General tective Cap can be used to mark the center of the ceiling hole into plaster Description board or ceiling tiles by gently push- �—� ing the ceiling product against the Pro- The TYCO Series RFII Quick Response tective Cap. When ceiling installation `�,. �� (3-mm bulb) and Standard Response is complete, the Protective Cap is re- y -���,� (5-mm bulb), 5.6 K-Factor, "Royal moved and the Cover Plate/Retainer ` �s-� Flush IP' Concealed Pendent Sprin- Assembly is installed. 9_ -� � klers are decorative sprinklers featur- As an option, the Series RFII Standard ing a flat cover plate designed to con- Response(5-mm bulb) "Royal Flush II" ceal the sprinkler.These sprinklers are Concealed Pendent Sprinklers can be optimal for architecturally sensitive ar- fitted with a silicone Air and Dust Seal. eas such as hotel lobbies, office build- (Refer to Figure 5.) The Air and Dust ings,churches,and restaurants. Seal is intended for sensitive areas Each sprinkler includes a Cover Plate/ Where it is desirable to prevent air and Sprinkler Retainer Assembly and a Sprinkler/ dust from the area above the ceiling to Support Cup Assembly. The separa- pass through the cover plate. ,dentification ble, two-piece assembly design pro- � Number (SIN) vides the following benefits: • Allows installation of the sprinklers The Series RFII Concealed Pendent TY3531 — 3 mm bulb and pressure testing of the fire pro- Sprinklers described herein must be tection system prior to installation of installed and maintained in compli- TY3551 — 5 mm bulb a suspended ceiling or application of ance with fhis document and with the the finish coating to a fixed ceiling. applicable standards of the National Fire Protection Association, in addi- • Permits the removal of suspended tion to the standards of any authori- ceiling panels for access to building ties having jurisdiction. Failure to do so service equipment without having may impair the performance of these to first shut down the fire protection devices. system and remove sprinklers. The owner is responsible for maintain- • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de- vertical adjustment to allow a mea- vices in proper operating condition. sure of flexibility in determining the The installing contractor or sprinkler length of fixed piping to cut for the manufacturer should be contacted sprinkler drops. with any questions. The Series RFII Sprinklers are shipped with a Disposable Protective Cap.The Protective Cap is temporarily removed during installation and replaced to help protect the sprinkler during ceiling in- stallation or finish. The tip of the Pro- I MPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 SEPTEMBER 2011 TFP181 TFP181 Page2of6 Technical 1/2" NPT_ SEALING �-_ ASSEMBLY Data - -- � Sprinkler Approvals / Approvals apply only to the service FRAME conditions indicated in the Design �� / ` �� � �; �CAP Criteria section. � • TY3531 (3-mm Bulb) is UL Listed, SUPPORT C-UL Listed, VdS Approved (Certif- CUP wITH — BU�B icate No. G4090007), and NYC Ap- RO�L FORMED — proved (MEA 353-01-E) as Quick THREADS '�� — Response. • TY3531 (3-mm Bulb) is FM and _ COMPRESSION LPCB Approved (Ref. No. 094a/10) _ _— -- SCREW Approved as Standard Response. GUIDE �— Factory Mutual and LPCB do not PiNS(2) _ approve any concealed sprinklers for quick response. DEFLECTOR � (DROPPED • TY3551 (5-mm Bulb) is UL Listed, DEFLECTOR ; � �� �� �- POSITION) GUL Listed, FM Approved, LPCB °_�---_-_z_._ Approved (Ref. No. 094a/9), and L-� ��' ' NYC Approved (MEA 353-01-E) as i SPRINKLER/SUPPORTCUP � Standard Response. ASSenns�Y Approvals for Air and Dust Seal THREAD INTO RETAINER UL and C-UL Listed for use with the SUPPORT CUP WITH THREAD RFII Standard Response Concealed UNTIL MOUNTING O � � DIMPLES Sprinkler(TY3551). SuRFACE IS FLUSH WITH EJECTION Maximum Working Pressure CEI�ING Maximum 250 psi (17,3 bar) by UL, SPRING GUL,and NYC \ Maximum 175 psi (12,1 bar) by FM, VdS, and LPCB _ Temperature Rating / 155°F(68°C) Sprinkler with So�DER J -----_J COVER 139°F(59°C) Plate TABS(3) COVER PLATE/RETAINER PLATE 200°F(93°C) Sprinkler with ASSEMBLY 165°F(74°C) Plate Discharge Coefficient FIGURE 1 K=5.6 GPM/psi�i2 (80,6 LPM/bar�i2) MODEL RFII CONCEALED SPRINKLER Adjustment ASSEMBLY 1/2 inch (12,7 mm) Finishes See the Ordering Procedure section. Physical Characteristics Frame. . . . . . . . . . . . . . . . . . . Bronze Support Cup. . . . . . . . . . . . . .Chrome Plated Steel Guide Pins . . . . . . . . . Stainless Steel Deflector. . . . . . . . . . . . . . . . . Bronze Compression Screw. . . . . . . . . Brass Bulb . . . . . . . . . . . . . . . . . . . . . .Glass Cap. . . . . . . . . . . . .Bronze orCopper Sealing Assembly. . . . . . . . .Beryllium Nickel w/TEFLON Cover Plate. . . . . . . . . . . . . . . . Brass Retainer . . . . . . . . . . . . . . . . . . Brass Ejection Spring. . . . . . Stainless Steel TFP181 Page 3 of 6 FACE OF CLEARANCE HOLE Design �SPRWKLER 'I� DIAMETER Criteria FITTING DIMENSION C � The TYCO Series RFII Concealed Pen- SPRwKLER =_-- dent Sprinklers are intended for fire SuPPORT CuP � protection systems designed in ao- ASSEMBLY ���j cordance with the standard instal- '� lation rules recognized by the appli- 1/2"(12,7 mm) cable Listing or Approval agency; for THREADED - example, UL Listing is based on NFPA p ADJUSTMENT�� - 13 and VdS Approval is based on the - CEA 4001. FACE OF CEILING, - For more information on LPCB and RETAINING RWG — VdS Approvals, contact Tyco Fire Sup- MOUNTING I SuRFACE — pression & Building Products at the ---- following office: , Enschede, Netherlands Telephone:31-53-428-4444 � Fax:31-53-428-3377 � The Series RFII Concealed Pendent \ �-i-I�- -J � -� Sprinklers are only listed and approved --T--z_s- 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE with the Series RFII Concealed Cover (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER Plates having a factory applied finish. REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY � • COVER PLATE COVER PLATE Do not use the Series RFII in applica- PROFILE DEPTH � DIAMETER — t10nS where the air pressure above DIMENSION B DIMENSION A the ceiling is greater than that be- low. Down drafts through the Sprin- kler/Supporf Cup Assembly can delay A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) sprinkler operation in a fire situation. B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) Operation FIGURE 2 When exposed to heat from a fire, the SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Cover Plate, normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup Assembly. The Deflector—supported by the Guide Pins—then drops down to its operational position. The glass Bulb contains a fluid that ex- pands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, activating the sprinkler and allowing water to flow. TFP181 Page4of6 CLEARANCE HOLE FRAME ARM SUPPORT CUP // 7/8"(23 mm) � SQUARE ALIGN �J `� ARROWS WITH � FIGURE 4 i � � � DISPOSABLE PROTECTIVE CAP FRAME ARMS � � al l � I I � ACCEPTS � � � � O 1/2"SOCKET �-r DRIVE FIGURE 3 RFII SPRINKLER WRENCH SUPPORT --= SPRINKLER FACEOF ORIENT CUP - TFP181 Page 5 of 6 Installation � Absence of the Cover Plate/Retainer Assembly can delay sprinkler opera- The TYCO Series RFII must be in- As long as ihe Protective Cap remains tion in a fire situation. stalled in accordance with the follow- in place, the system is considered in instructions. `Out of Service". When properly installed, there is a g nominal 3/32 inch (2,4 mm) air gap be- Step 6.After the ceiling has been com- tween the lip of the Cover Plate and the .� pleted with the 2-1/2 inch(63,5 mm)di- ceiling, as shown in Figure 2. Do not install any bulb-type sprinkler if ameter clearance hole and in prepa- the bulb is cracked or there is a loss ration for installing the Cover Plate/ This air gap is necessary for proper of liquid from the bulb. With the sprin- Retainer Assembly, remove and dis- operation of the sprinkler. If the ceil- kler held horizontally, a small air bub- card the Protective Cap.Verify that the ing requires repainting after sprinkler ble should be present. The diameter Deflector moves up and down freely. installation, ensure that the new paint of the air bubble is approximately 1/16 If the Sprinkler is damaged and the does not seal off any of the air gap. inch (1,6 mm) for the 155°F/68°C and Deflector does not move up and down Do not pull the Cover Plate relative to 3/32 inch (2,4 mm) for fhe 200°F/93°C freely, replace the entire Sprinkler. the Enclosure. Separation may result. temperature ratings. Do not attempt to modify or repair a Replace sprinklers that: damaged sprinkler. Obtain a 1/2 inch NPT sprinkler joint • are leaking or exhibiting visible signs by applying a minimum to maximum Step 7.When installing an Air and Dust of corrosion. torque of 7 to 14 ft.-Ibs. (9,5 to 19,0 Seal, refer to Figure 5; otherwise, pro- Nm). Higher levels of torque can dis- ceed to Step 8. To attach the Air and • were modified or over-heated. tort the sprinkler Inlet with consequent Dust Seal, verify the angle of the out- Never paint, plate, coat, or otherwise leakage or impairment of the sprinkler. side edge of the seal is oriented ac- alter automatic sprinklers after they cording to Figure 5. Start the edge of leave the factory. Never repaint facto- Do not attempt to compensate for in- the Retainer in the grooved slot of the ry-painted Cover Plates. If necessary, sufficient adjustment in the Sprinkler Air and Dust Seal and continue around replace them with factory-painted by under-or over-tightening the Sprin- the retainer until the entire Air and Dust units. Non-factory applied paint can kler/Support Cup Assembly. Re-adjust Seal is engaged. adversely delay or prevent sprinkler the position of the sprinkler fitting to Step 8. Screw on the Cover Plate/ operation in the event of a fire. suit. Retainer Assembly until the Retainer Step 1. Install the sprinkler only in the (shown in Figure 2)or the Air and Dust Exercise care to avoid damage to pendent position with the center-line Seal (shown in Figure 5) contacts the sprinklers before, during, and after in- of the sprinkler perpendicular to the ceiling. Do not continue to screw on stallation. Replace sprinklers damaged mounting surface. the Cover Plate/Retainer Assembly by dropping, striking, wrench twisting, so that it lifts a ceilin anel out of its Wrench slipping, or the like. Also, re- Step 2. Remove the Protective Cap. g p place any sprinkler that has a cracked Step 3. With pipe thread sealant ap- normal position. If you cannot engage bulb or that has lost liquid from its plied to the pipe threads, hand-tighten the Cover Plate/Retainer Assembly bulb. (Refer to the Installation section.) the sprinkler into the sprinkler fitting. With the Support Cup or you cannot engage the Cover Plate/Retainer As- If you must remove a sprinkler, do not Step 4. Wrench-tighten the sprinkler sembly sufficiently to contact the ceil- reinstall it or a replacement without re- using only the RFII Sprinkler Wrench. ing, you must reposition the Sprinkler installing the Cover Plate/Retainer As- (Refer to Figure 3.) Apply the RFII Fitting. sembly. If a Cover Plate/Retainer As- Sprinkler Wrench to the Sprinkler as sembly becomes dislodged during shown in Figure 3. service, replace it immediately. Step 5. Replace the Protective Cap Care and Responsibility lies with sprinkler own- by pushing it upwards until it bottoms Maintenance out against the Support Cup. (Refer ers for the inspection, testing, and to Figure 4.) The Protective Cap helps maintenance of their fire protection prevent damage to the Deflector and The TYCO Series RFII must be system and devices in compliance Arms during ceiling installation and/or maintained and serviced in accordance with this document, as well as with the finish. You can also use the Protective With the following instructions. applicable standards of the National Cap to locate the center of the clear- Fire Protection Association (for exam- � ple, NFPA 25), in addition to the stan- ance hole by gently pushing the ceiling dards of any other authorities having material up against the center point of Before closing a fire protection sys- jurisdiction. Contact the installing con- the Protective Cap. tem main control valve formaintenance tractor or sprinkler manufacturer re- work on the fire protection system that garding any questions. it controls, obtain permission to shut down the affected fire protection sys- Automatic sprinkler systems should be tem from the proper authorities and no- inspected,tested,and maintained by a tify all personnel who may be affected qualified Inspection Service in accor- by this action. dance with local requirements and/or national code. TFP181 Page6of6 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for Protection Products (TFPP) are war- availability. When placing an order, ranted solely to the original Buyer for indicate the full product name. ten (10) years against defects in ma- terial and workmanship when paid for Sprinkler/Support Cup Assembly and properly installed and maintained Specify: (SIN), (temperature rating under normal use and service. This from below) Series RFII Concealed warranty will expire ten (10)years from pendent Sprinkler, P/N (specify). date of shipment by TFPP. No warran- ty is given for products or components 155°Fisa°c 2oo°F/93°c manufactured by companies not df- TY3531 51-792-1-155 51-792-1-200 filiated by ownership with TFPP or for TY3551 51-790-1-155 51-790-1-200 products and components which have been subject to misuse, improper in- Separately Ordered Cover Plate/ stallation, corrosion, or which have not Retainer Assembly: been installed,maintained,modified or Specify: (temperature rating from be- repaired in accordance with applicable low) Series RFII Concealed Cover Standards of the National Fire Protec- Plate with(finish), P/N(specify). tion Association, and/or the standards of any other Authorities Having Juris- 139°F/59°c(a) iss°F/74°c(b) diction. Materials found by TFPP to be Brass..........56-792-1-135 56-792-1-165 defective shall be either repaired or re- cnrome........ssasz-s-is5 56-792-9-165 laced, at TFPP's sole o tion. TFPP Brushed p p , Chrome........56-792-8-135 56-792-8-165 neither assumes, nor authorizes any Signal White person to assume for it, lfly Otll@I'OI�- (RAL 9003)....56-792-4-135 56-792-4-165 ligation in connection with the sale of Grey White pYOdUCtS OY parts of products. TFPP (RAL 9002)....56-792-0-135 56-792-0-165 shall not be responsible for sprinkler Pure White(c) system design errors or inaccurate or �RAL9010)....56-792-3-135 56-792-3-165 incomplete information supplied by Custom........56-792-X-135 56-792-X-165 Buyer or Buyer's representatives. (a� For use witn 1s5°F/68°C sprinklers. In no event shall TFPP be liable, in �b) For use with 200°F/93°C sprinklers. (c) Eastern Hemisphere sales only. contract, tort, strict liability or under any other legal theory, for inciden- Sprinkler Wrench tal, indirect, special or consequential Specify: RFII Sprinkler Wrench, damages, including but not limited to p�N 56-000-1-075. labor charges, regardless of whether TFPP was informed about the possibil- q�r and Dust Seal ity of such damages, and in no event Specify:Air and Dust Seal, shall TFPP's liability exceed an amount p�N 56-908-1-001. equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties of inerchantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Copyright O 2008,2011 Tyco Fire Protection Products.All rights reserved. t�C� TEFLON is trademark of The DuPont Corporation. �'���Q Fire & Building Products Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500 Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-factor Uprighf, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage tained when exposed to corrosive at- Ge ne ra 1 mospheres. Although corrosion resis- �. _._ tant coated sprinklers have passed the � � D e s c ri p t i o n standard corrosion tests of the appli- ��Y •,��'� cable approval agencies,the testing is " � � . The Tyco° Series TY-FRB, 2.8, 4.2, not representative of all possible cor- � 5.6,and 8.0 K-factor, Upright and Pen- rosive atmospheres. Consequently, it ' �� ? , dent Sprinklers described in this data is recommended that the end user be 4_ � sheet are quick response - standard consulted with respect to the suitability coverage, decorative 3 mm glass bulb of these coatings for any given corro- � '. . _ type spray sprinklers designed for use sive environment.The effects of ambi- � in light or ordinary hazard, commercial ent temperature, concentration of - 4�-�`0' occupancies such as banks, hotels, chemicals, and gas/chemical velocity, ` - - ' ��� shopping malls, etc. should be considered, as a minimum, The recessed version of the Series along with the corrosive nature of the TY-FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be �� plicable, is intended for use in areas exposed. — with a finished ceiling. It uses either a An intermediate level versions of the "�" �"` two-piece Style 10 (1/2 inch NPT) or Series TY-FRB Pendent Sprinklers ��� `�;. Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet ! � cutcheon with 1/2 inch (12,7 mm) of TFP356,and Sprinkler Guards are de- recessed ad'ustment or u to 3/4 inch �� 1 P tailed in Technical Data Sheet TFP780 (19,1 mm)oftotal adjustmentfrom the +��,� `r� flush pendent position, or a two-piece WARN/NGS _ � �� Style 20(1/2 inch NPT)or Style 30(3/4 The Series TY-FRB Sprinklers de- inch NPT) Recessed Escutcheon with scribed herein must be installed and � -��' � 1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica- total adjustment from the flush pen- ble standards of the National Fire Pro- dent position. The adjustment pro- tection Association, in addition to the vided by the Recessed Escutcheon re- standards ofany other authorities hav- M�d e��S n�-�n k�e�- duces the accuracy to which the fixed ing jurisdiction. Failure to do so may 1" pipe drops to the sprinklers must be impair the performance of these de- 'd e n t i fi c a t i o n cut. vices. Corrosion resistant coatings, where The owneris responsible formaintain- N UI�be I�S applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2"NPT that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2"NPT manufacturer should be contacted TY2131 - Upright 4.2K, 1/2"NPT with any questions. TY2231 - Pendent 4.2K, 1/2"NPT IMPORTANT TY3131 - Upright 5.6K, 1/2"NPT Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2"NPT Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.OK, 3/4"NPT WARN/NG" that provides cautions TY4231 - Pendent 8.OK, 3/4"NPT with respect to handling and instal- TY4831- Upright 8.OK, 1/2"NPT lationofsprinklersystemsandcom- TY4931- Pendent 8.OK, 1/2"NPT ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation orcause it to operate prematurely. Page 1 of 10 AUGUST, 2007 TFP171 Page 2 of 10 TFP171 ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED * SURFACE NPT �-IN ESCUTCHEON DEF�ECTOR � 6 5 � 7/16" 2-1/4" (11,1 mm) 4 (57,2 mm) NOMINAL MAKE-IN 2 1-9/16" � 2-3/16" 3 (39,7 mm) WRENCH 55,6 mm FLATS ( ) 1 1 7 SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. - 1/2"NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2-Button Assembly 5-Compression 7-Bushing orifiCe Seat on frame. Screw F/GURE 1 QU/CK RESPONSE SER/ES TY-FRB UPR/GHT(TY1131)AND PENDENT(TY1231)SPR/NKLERS 2.8 K-FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED * SURFACE NIPT MA�E-IN ESC�TCHEON DEFLECTOR 1 6* � 7/16" 5 2-3/16" —_ � I (11,1 mm) (55,6 mm) i NOMINAL 4 MAKE-IN 1-1/2° -- 2-3/16,� i, 2 (38,1�mm) WRENCH � J_ (55,6 mm) 3 FLATS � �� � 1 SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. � 1/2"NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2-Button Assembly 5-Compression orifice seat on frame. Screw FIGURE 2 QUICK RESPONSE SER/ES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231) SPR/NKLERS 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 3 of 10 ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED * SURFACE ��2 MAKE-IN ESCUTCHEON SSU I N�PT � / DEFLECTOR �� -- 6* � 7/16" = 5 2-3/16" � (11,1 mm) (55,6 mm) i r NOMINAL 4 MAKE-IN 1-1/2" � -� -- I 2-3/16" 2 (38,1I mm) WRENCH � (55,6 mm) FLATS 3 1 1 — i � � SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. � 1/2"NPT � PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2-Button Assembly 5-Compression orifice seat on frame. Screw F/GURE 3 QU/CK RESPONSE SER/ES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2"(12,7 mm) STYLE 30 or 40 PLATE SEATING NOMINAL RECESSED * SURFACE 3�4 MAKE-IN ESCUTCHEON SSU NPT � DEFLECTOR � _ ' 6� � 1/2" 5 2-5/16" � (12,7 mm) (58,7 mm) � I � NOMINAL 4 MAKE-IN i �2 1-9/16" � 2-1/4" ' (39,7 mm) � WRENCH � (57,2 mm) �' FLATS I 3 1 SSP DEFLECTOR* � 2-7/8"(73,0 mm)DIA. �� 3/4"NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2-Button Assembly 5-Compression o1'ifiCe seat on frame. Screw F/GURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPR/NKLERS 8.0 K-FACTOR, 3/4 INCH NPT Page 4 of 10 TFP171 7/16"(11,1 mm) ��2„ NOMINAL SSU* NPT MAKE-IN DEFLECTOR � * 6 � 5 2-1/4" � 2-3/16" (57,2 mm) � (55,6 mm) 4 1-9/16" WRENCH 2 (39,7 mm) FLATS 3 SSP* 1 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2-Button Assembly 5-Compression orifice seat on frame. Screw F/GURE 5 QU/CK RESPONSE SER/ES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT Technical Operation Da ta The glass Bulb contains a fluid which expands when exposed to heat.When Approvals the rated temperature is reached, the UL and C-UL Listed. fluid expands sufficiently to shatter the FM, LPCB, and NYC Approved. glass Bulb, allowing the sprinkler to (Refer to Table A and B for complete activate and water to flow. approval information including corro- sion resistant status.) De sign Maximum Working Pressure Refer to Table C. Crite ria Discharge Coefficient K- 2.8 GPM/psi��2 (40,3 LPM/bar�i2) The Series TY-FRB Pendent and Up- K-4.2 GPM/psi�i2 (60,5 LPM/bar�i2) right Sprinklers are intended for fire K- 5.6 GPM/psi�i2 (80,6 LPM/bar�i2) protection systems designed in ac- K-8.0 GPM/psi��2(115,2 LPM/bar�i2) cordance with the standard installation rules recognized by the applicable Temperature Ratings Listing or Approval agency (e.g., UL Refer to Table A and B Listing is based on the requirements of Finishes NFPA 13, and FM Approval is based Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre- Recessed Escutcheon:White Coated, vention Data Sheets ). Only the Style Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch- eon, as applicable, is to be used for recessed pendent installations. Y Physical Characteristics m Frame . . . . . . . . . . . . . Bronze � Button . . . . . . . . . Brass/Copper � Sealing Assembly . . . . . . . . � . Beryllium Nickel w/Teflont � Bulb . . . . . . . . . . . . . . . Glass �, Compression Screw . . . . . Bronze N Deflector . . . . . . . Copper/Bronze � Bushing (K=2.8) . . . . . . . Bronze � 0 a � 0 � TFP171 Page 5 of 10 SPRINKLER FINISH(See Note 7) K TYPE TEMP. BULB NATURAL CHROME WHITE*"" LIQUID BRASS PLATED POLYESTER 135°F/57°C Orange PENDENT 155°F/68°C Red (TY1231) 1,2,3,5 and 175°F/79°C Yellow UPRIGHT 200°F/93°C Green 2$ (TY1131) 286°F/141°C Blue 1/2" NPT 135°F/57°C Orange RECESSED 155°F/68°C Red PENDENT (TY1231)* 175°F/79°C Yellow Figure 6 200°F/93°C Green 1,2,5 135°F/57°C Orange RECESSED 155°F/68°C Red PENDENT (TY1231)"" 175°F/79°C Yellow Figure 7 200°F/93°C Green 135°F/57°C Orange PENDENT 155°F/68°C Red (TY2231) and 175°F/79°C Yellow UPRIGHT 200°F/93°C Green 4.2 �TY2131) 286°F/141°C Blue � 2 1/2" NPT 135°F/57°C Orange RECESSED 155°F/68°C Red PENDENT (TY2231)* 175°F/79°C Yellow Figure 8 200°F/93°C Green 135°F/57°C Orange RECESSED 155°F/68°C Red PENDENT (TY2231)"" 175°F/79°C Yellow Figure 9 200°F/93°C Green NOTES: 1.Listed by Underwriters Laboratories, Inc. (UL)as Quick Response Sprinklers. 2.Listed by Underwriters Laboratories, Inc.for use in Canada(C-UL)as Quick Re- sponse Sprinklers. 3.Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprin- klers. 5.Approved by the City of New York under MEA 354-01-E. 7.Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprin- klers are UL and C-UL Listed as Corrosion Resistant Sprinklers. " Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon, as applicable. " Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon, as applicable. '"` Frame and Deflector only. Listings and approvals apply to color(Special Order). N/A: Not Available TABLE A LABORATORY L/ST/NGS AND APPROVALS 2.8 AND 4.2 K-FACTOR SPR/NKLERS Page 6 of 10 TFP171 SPRINKLER FINISH(See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE*"� LEAD LIQUID BRASS PLATED POLYESTER COATED 135°F/57°C Orange PENDENT 155°F/68°C Red (TY3231) 1,2,3,4,5,6,7 1,2,3,5 and 175°F/79°C Yellow UPRIGHT 200°F/93°C Green 5.6 �TY3131) 286°F/141°C Blue 1/2" NPT 135°F/57°C Orange RECESSED 155°F/68°C Red PENDENT 1,2,4,5 N/A (TY3231)* 175°F/79°C Yellow Figure 10 200°F/93°C Green 135°F/57°C Orange RECESSED 155°F/68°C Red PENDENT 1,2,3,4,5 N/A (TY3231)"" 175°F/79°C Yellow Figure 11 200°F/93°C Green 135°F/57°C Orange PENDENT 155°F/68°C Red (TY4231) 1,2,5 and 175°F/79°C Yellow 1,2,3,4,5,6,7 UPRIGHT 200°F/93°C Green $p (TY4131) 286°F/141°C Blue 3/4" NPT 135°F/57°C Green RECESSED 155°F/68°C Orange PENDENT 1,2,4,5 N/A (TY4231)* 175°F/79°C Red Figure 12 200°F/93°C Yellow 135°F/57°C Orange RECESSED 155°F/68°C Red PENDENT 1,2,3,4,5 N/A (TY4231)"" 175°F/79°C Yellow Figure13 200°F/93°C Green 135°F/57°C Orange PENDENT 155°F/68°C Red TY4931 $2� and 175°F/79°C Yellow 1,2,4,5,6 1 2 5 NPT UPRIGHT 200°F/93°C Green (TY4831) 286°F/141°C Blue NOTES: 1.Listed by Underwriters Laboratories, Inc. (UL)as Quick Response Sprinklers. 2.Listed by Underwriters Laboratories, Inc.for use in Canada(C-UL)as Quick Response Sprinklers. 3.Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4.Approved by the Loss Prevention Certification Board(LPCB Ref. No.007k/04)as Quick Response Sprinklers; however,the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5.Approved by the City of New York under MEA 354-01-E. 6.VdS Approved(For details contact Tyco Fire&Building Products, Enschede, Netherlands,Tel. 31-53-428-4444/Fax 31-53-428-3377). 7.Approved by the Loss Prevention Certification Board(LPCB Ref. No.094a/06)as Quick Response Sprinklers. 8.Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. � Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon, as applicable. '" Installed with Style 20(1/2"NPT)or Style 30(3/4" NPT) 1/2"Total Adjustment Recessed Escutcheon, as applicable. �"Frame and Deflector only. Listings and approvals apply to color(Special Order). N/A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K-FACTOR SPR/NKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED PENDENT(TY3231) and 2.8 UPRIGHT(TY3131) 175 PSI(12,1 BAR) N/A ��2 RECESSED PENDENT NPT (TY323) PENDENT(TY4231) and q 2 UPRIGHT(TY4131) 175 PSI(12,1 BAR) N/A 3/4" RECESSED PENDENT NPT (TY4231) PENDENT(TY3231) and 250 PSI(17,2 BAR) 175 PSI(12,1 BAR) 5.6 UPRIGHT(TY3131) OR ��2 RECESSED PENDENT 175 PSI(12,1 BAR) NPT (TY3231) N/A (SEE NOTE 1) PENDENT(TY4231) and 175 PSI(12,1 BAR) 175 PSI(12,1 BAR) g.p UPRIGHT(TY4131) 3/4" RECESSED PENDENT NPT (TY4231) N/A 8.0 PENDENT(TY4931) 1/2" and 175 PSI(12,1 BAR) 175 PSI(12,1 BAR) NPT UPRIGHT(TY4831) NOTES: 1.The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc. (UL);the Listing by Underwriters Laboratories, Inc.for use in Canada(C-UL);and ,the Approval by the City of New York. TABLE C, MAX/MUM WORKING PRESSURE tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting. 1 nsta Ila fion (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the ft.lbs. (40,7Nm)of torque is to be used sprinkler fitting using only the W-Type The Series TY-FRB Sprinklers must to install sprinklers with 3/4 NPT con- be installed in accordance with the fol- nections. Higher levels of torque may 6 Sprinkler Wrench (Ref. Figure 14). lowing instructions: distort the sprinkler inlet and cause With reference to Figures 1, 2, 3, 4, leakage orimpairmentofthe sprinkler. and 5,the W-Type 6 Sprinkler Wrench NOTES is to be applied to the sprinkler wrench Do not install any bulb type sprinkler if Do not attempt to make-up for insuffi- flats. the bulb is cracked or there is a loss of cient adjustment in the escutcheon The Series TY-FRB Recessed Pen- liquid from the bulb. With the sprinkler p�ate by under- or over-tightening the dent Sprinklers must be installed in held horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc- should be present. The diameter of the sprinkler fitting to suit. tions. air bubble is approximately 1/16 inch The Series TY-FRB Pendent and Up- Step A. After installing the Style 10. (1,6 mm) for the 135°F/57°C to 3/32 right Sprinklers must be installed in 20, 30,or 40 Mounting Plate,as appli- inch (2,4 mm) for the 286°F/141°C accordance with the following instruc- cable, over the sprinkler threads and temperature ratings. tions. with pipe thread sealant applied to the A leak tighf 1/2 inch NPT sprinklerjoint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin- should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting. to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the mum of 21 ft. Ibs. (28,5 Nm)of torque the upright position. sprinkler fitting using only the W-Type may be used to install sprinklers with 7 Recessed Sprinkler Wrench (Ref. 1/2 NPT connections. A leak tight 3/4 Step 2. With pipe thread sealant ap- Figure 15).With reference to Figure 1, inch NPT sprinkler joint should be ob- plied to the pipe threads, hand tighten 2 3, and 4, the W-Type 7 Recessed Page 8 of 10 TFP171 2-7/8"DIA. i 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2" 12,7 mm 1/2±1/8" � ) (15,9±6,4 mm) 2_1/4"DIA. yi 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. y� 1/4"(6,4 mm) FACE OF I ~ (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER � pLATE FITTING FITTING 1/8" 1/8" � (3,2 mm) 1 I i (3,2 mm) � 1 ' �� , / �� � � MOUNTING � f MOUNTING / � SURFACE I SURFACE i � � � i � CLOSURE SERIES 1-5/16"(33,3 mm)� CLOSURE SERIES 1-5/16"(33,3 mm)� TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) F/GURE 6 FIGURE 7 SERIES TY-FRB RECESSED PENDENT SER/ES TY-FRB RECESSED PENDENT W/TH TWO-P/ECE 3/4/NCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2/NCH NPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 2-7/8"DIA. 5/8±1/4" (73,0 mm) � 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) (15,9±6,4 mm) � 2_1/4"DIA. y 1/4"(6,4 mm) (12,7±3,2 mm) � 2_1/4"DIA. y 1/4°(6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING � FITTING / 1/8" % 1/8" - -- (3,2 mm) - I (3,2 mm) % � ��� ' � l �G � MOUNTING � � SURFACE � � SURFACE� � � / � CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES _1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) TY-FRB �"(25,4 mm) FIGURE 8 FIGURE 9 SER/ES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-P/ECE 3/41NCH TOTAL ADJUSTMENT WITH TWO-P/ECE 1/2/NCH TOTAL ADJUSTMENT STYLE 1 D RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2/NCH NPT 4.2 K-FACTOR, 1/2 INCH NPT Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi- the sprinkler wrench flats. itcontrols,permission toshutdown the fied sprinklers must be replaced. Step C. After the ceiling has been in- affected fire protection system mustbe Sprinklers that have been exposed to stalled or the finish coat has been ap- obtained from the proper authorities corrosive products of combustion, but plied, slide on the Style 10, 20, 30, or and all personnel who may be affected have not operated,should be replaced 40 Closure over the Series TY-FRB by this action must be notified. if they cannot be completely cleaned Sprinkler and push the Closure over The owner must assure that the sprin- by wiping the sprinkler with a cloth or the Mounting Plate until its flange klers are not used for hanging of any by brushing it with a soft bristle brush. comes in contact with the ceiling. objects; otherwise, non-operation in Care must be exercised to avoid dam- theeventofafireorinadvertentopera- age to the sprinklers - before, during, Ca re a n d tion may result. and after installation. Sprinklers dam- Absence of an escutcheon, which is aged by dropping, striking, wrench used to cover a clearance hole, may twist/slippage, or the like, must be re- M a i n t e n a n c e delay the time to sprinkler operation in p�aced. Also, replace any sprinkler The Series TY-FRB S rinklers must a fire situation. that has a cracked bulb or that has lost P liquid from its bulb. (Ref. Installation be maintained and serviced in accord- Sprinklers that are found to be leaking Section). ance with the following instructions: or exhibiting visible signs of corrosion must be replaced. Frequent visual inspections are rec- NOTES ommended to be initially performed for Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers, main control valve for maintenance painted, plated, coated or otherwise after the installation has been com- TFP171 Page 9 of 10 2-7/8"DIA. 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2" 12,7 mm 1/2±1/8" � ) (15,9±6,4 mm) 2_1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) FACE OF (57,2 mm) ~ MOUNTING FACE OF (57,2 mm) ~ MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" � 1/8" — - (3,2 mm) (3,2 mm) = � ;- _ ��'� � „ , � � �� i MOUNTING SURFACE � SURFACE � / � SERIES 1-1/4"(31,8 mm) � SERIES 1-1/4"(31,8 mm) CLOSURE TY-FRB CLOSURE TY-FRB 3/4"(19,1 mm) 1"(25,4 mm) F/GURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-P/ECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-P/ECE 1/21NCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE ZO RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2/NCH NPT 5.6 K-FACTOR, 1/2/NCH NPT 2-7/8"DIA. 2-7/8"DIA. � (73,0 mm) 3/4"(19,1 mm) (73,0 mm) � 1/2"(12,7 mm) 5/8±1/4" _ 1/2±1/8" _ (15,9±6,4 mm) � 2-1/4"DIA. � 1/4"(6,4 mm) (12,7±3,2 mm) � 2-1/4"DIA. y 1/4"(6,4 mm). FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING � 1/8" 1/8„ � (3,2 mm) (3,2 mm) � ii, � � /� � /i � � MOUNTING � MOUNTING � � SURFACE SURFACE � � / � � - CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 12 F/GURE 13 SER/ES TY-FRB RECESSED PENDENT SER/ES TY-FRB RECESSED PENDENT W/TH TWO-P/ECE 3/4/NCH TOTAL ADJUSTMENT WITH TWO-P/ECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4/NCH NPT 8.0 K-FACTOR, 3/4 INCH NPT pleted,to verify the integrity of the cor- wRENCH rosion resistant coating. Thereafter, RECESS annual inspections per NFPA 25 \ should suffice; however, instead of in- / WRENCH RECESS � specting from the floor level,a random � (END"A"USED FOR � sampling of close-up visual inspec- 1/2"NPT MODELS) � � tions should be made, so as to better � determine the exact sprinkler condi- � tion and the long term integrity of the �� - corrosion resistant coating, as it may WRENCH RECESS PUSH WRENCH be affected by the corrosive conditions (END"B"USED FOR IN TO ENSURE present. 3/4"NPT MODELS) ENGAGEMENT The owner is res onsible for the in- FIGURE 14 WITH SPRINKLER P WRENCHING AREA spection, testing, and maintenance of W-TYPE 6 SPR/NKLER their fire protection system and de- WRENCH F/GURE 15 vices in compliance with this docu- W-TYPE 7 RECESSED ment, as well as with the applicable facturer should be contacted relative SPRINKLER WRENCH standards of the National Fire Protec- to any questions. tion Association (e.g., NFPA 25), in Inspection Service in accordance with addition to the standards of any other It is recommended that automatic local requirements and/or national authorities having jurisdiction. The in- sprinkler systems be inspected, codes. stalling contractor or sprinkler manu- tested, and maintained by a qualified Page 10 of 10 TFP171 P/N 57 - XXX - X - XXX TEMPERATURE MODEL/SIN RATING SPRINKLER 330 2.8K UPRIGHT(1/2"NPT) TY1131 135 135°F/57°C 331 2.8K PENDENT(1/2"NPT) TY1231 1 NATURAL BRASS 155 155°F/68°C 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 WHITE POLYESTER 175 175°F/79°C 341 4.2K PENDENT(1/2"NPT) TY2231 3 WHITE(RAL9010)� 200 200°F/93°C 370 5.6K UPRIGHT(1/2"NPT) TY3131 9 CHROME PLATED 286 286°F/141°C 371 5.6K PENDENT(1/2"NPT) TY3231 7 LEAD COATED 390 8.OK UPRIGHT(3/4"NPT) TY4131 391 8.OK PENDENT(3/4"NPT) TY4231 �Eastern Hemisphere sales oniy. 360 8.OK UPRIGHT(1/2"NPT) TY4831' 361 8.OK PENDENT(1/2"NPT) TY4931' TABLE D PART NUMBER SELECT/ON SER/ES TY-FRB PENDENT AND UPR/GHT SPR/NKLERS In no event shall TFBP be liable, in Lim ite d contract, tort, strict liability or under Ordering any other legal theory, for incidental, Wa rra n t y indirect,Spe��a�or�onseqUent�a�dam- Pro c e d ure ages, including but not limited to labor Products manufactured by Tyco Fire& charges, regardless of whether TFBP When placing an order, indicate the Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price ranted solely to the original Buyer for such damages, and in no event shall List for complete listing of Part Num- ten (10)years against defects in mate- TFBP's liability exceed an amount bers. rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail- and properly installed and maintained under normal use and service. This The foregoing warrantv is made in lieu ability. warranty will expire ten (10) years of any and all other warranties. ex- from date of shipment by TFBP. No press or implied. including warranties Sprinkler Assemblies with NPT warranty is given for products or com- of inerchantability and fitness for a par- Thread Connections: ponents manufactured by companies ticular�urr�ose. Specify: (Specify Model/SIN), Quick not affiliated by ownership with TFBP This limited warranty sets forth the ex- Response, (specify K-factor), (specify or for products and components which clusive remed for claims based on temperature rating), Series TY-FRB y (specify Pendent or Upright) Sprinkler have been subject to misuse,improper failure of or defect in products, materi- installation, corrosion, or which have als or com onents, whether the claim With (specify type of finish or coating), p P/N (specify from Table D). not been installed, maintained, modi- is made in contract, tort, strict liability fied or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon: plicable Standards of the National Fire S ecif St le 10, 20, 30, or 40 Re- Protection Association, and/or the This warranty will apply to the full ex- p Y� Y � ) standards of any other Authorities tent permitted by law.The invalidity, in cessed Escutcheon with (specify�)fin- Having Jurisdiction. Materials found Whole or part, of any portion of this ish, P/N (specify ). by TFBP to be defective shall be either Warranty will not affect the remainder. repaired or replaced, at TFBP's sole 'Refer to Technical Data Sheet TFP770. option. TFBP neither assumes, nor Sprinkler Wrench: authorizes any person to assume for it, Specify: W-Type 6 Sprinkler Wrench, any other obligation in connection with P/N 56-000-6-387. the sale of products or parts of prod- ucts.TFBP shall not be responsible for Specify: W-Type 7 Sprinkler Wrench, sprinkler system design errors or inac- P/N 56-850-4-001. curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 �'���Q Fire & Building Products Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500 Series TY-FRB — 5. 6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage ment provided by the Recessed Es- Ge ne ra 1 cutcheon reduces the accuracy to - which the fixed pipe nipples to the � De s c ri ption sprinklers must be cut. ,�� : ,� The Series TY-FRB, 5.6 K-Factor, Corrosion resistant coatings, where applicable, are utilized to extend the w�r �'` ' ° Horizontal and Vertical Sidewall Sprin- � +� klers described in this data sheet are life of copper alloy sprinklers beyond ?r � � quick response - standard coverage, that which would otherwise be ob- � � decorative 3 mm glass bulb type spray tained when exposed to corrosive at- � sprinklers designed for use in light and mospheres. Although corrosion resis- tant coated sprinklers have passed the `�"`F, ordinary hazard,commercial occupan- - cies such as banks, hotels, shopping standard corrosion tests of the appli- malls, etc. They are designed for in- cable approval agencies,the testing is stallation along a wall or the side of a not representative of all possible cor- beam and just beneath a smooth ceil- rosive atmospheres. Consequently, it ing. Sidewall sprinklers are commonly is recommended that the end user be y� - R�� used instead of pendent or upright consulted with respect to the suitability sprinklers due to aesthetics or building of these coatings for any given corro- ,.,,�' construction considerations, where sive environment.The effects of ambi- � piping across the ceiling is not desir- ent temperature, concentration of �' able. chemicals, and gas/chemical velocity, '¢ should be considered, as a minimum, �� The recessed version of the Series along with the corrosive nature of the ��� � TY-FRB Horizontal Sidewall Sprinkler chemical to which the sprinklers will be is intended for use in areas with a exposed. finished wall. It uses a two-piece Style � 10 Recessed Escutcheon with 1/2 inch WARN/NGS � (12,7 mm) of recessed adjustment or The Series TY-FRB Sprinklers de- �' up to 3/4 inch(19,1 mm)of total adjust- scribed herein must be installed and ment from the flush sidewall position, maintained in compliance with this or a two-piece Style 20 Recessed Es- document, as well as with the applica- T e c h n i c a 1 cutcheon with 1/4 inch (6,4 mm) of ble standards ofthe National Fire Pro- recessed adjustment or up to 1/2 inch tection Association, in addition to the Da ta (12,7 mm)of total adjustment from the standards ofany otherauthorities hav- flush sidewall position. The adjust- ing jurisdiction. Failure to do so may Approvals impair the performance of these de- UL and C-UL Listed. vices. FM, LPCB, and NYC Approved. The owner is responsible for maintain- (Refer to Table A for complete ap- ing their fire protection system and de- proval information including corrosion IMPORTANT vices in proper operating condition. resistant status.) The installing contractor or sprinkler Maximum Working Pressure Always refer to Technical Data manufacturer should be contacted Sheet TFP700 for the "INSTALLER with any questions. Refer to Table B. WARN/NG" that provides cautions Discharge Coefficient with respect to handling and instal- A/� K= 5.6 GPM/psi��2 (80,6 LPM/bar�iz) lation of sprinkler systems and com- ►�/, Q(�e��S p/'��n�{�e/"' ponents. Improper handling and in- Temperature Ratings stallation can permanently damage 1 d e n t i fi c a t i o n Refer to Table A. a sprinkler system or its compo- Finishes nents and cause fhe sprinkler to fail N um be rs Sprinkler: Refer to Table A. to operate in a fire situation orcause Recessed Escutcheon:White Coated, it to operate prematurely. TY3331 - Horizontal Chrome Plated, or Brass Plated. TY3431 - Vertical Page 1 of 6 APRIL, 2006 TFP176 Page 2 of 6 TFP176 SPRINKLER FINISH(See Note 11) K TYPE TEMP. BULB NATURAL CHROME WHITE*"" LEAD LIQUID BRASS PLATED POLYESTER COATED 135°F/57°C Orange HORIZ. 155°F/68°C Red SIDEWALL 1,2,3,4,9, 10 1,2,3,9 1,2,3,9 (TY3331) 175°F/79°C Yellow 200°F/93°C Green 5.6 2g6°F/141°C Blue 1/2" NPT RECESSED 135°F/57°C Orange HORIZ. 155°F/68°C Red SIDEWALL 1,2,4,9, 10 1,2,9 N/A (TY3331)* 175°F/79°C Yellow Figure 3 200°F/93°C Green RECESSED 135°F/57°C Orange HORIZ. 155°F/68°C Red SIDEWALL 1,2,3,4,9 N/A (TY3331)** 175°F/79°C Yellow Figure 4 200°F/93°C Green VERTICAL 135°F/57°C Orange SIDEWALL 155°F/68°C Red 5.6 (TY3431) 5,6,7,8,9 5,6,7,9 ��2�� Installed 175°F/79°C Yellow NPT Pendent 200°F/93°C Green or Upright 286°F/141°C Blue NOTES: 1.Listed by Underwriters Laboratories, Inc. (UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)top of deflector to ceiling distance. 2.Listed by Underwriters Laboratories Inc.for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 3.Approved by Factory Mutual Research Corporation (FM)as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)top of deflector to ceiling distance. 4.Approved by the Loss Prevention Certification Board (LPCB Ref. No.007a/04)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5.Listed by Underwriters Laboratories, Inc.as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6.Listed by Underwriters Laboratories for use in Canada (C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7.Approved by Factory Mutual Research Corporation (FM)as Quick Response Sprinklers for use in Light Hazard Occupancies. 8.Approved by the Loss Prevention Certification Board (LPCB Ref. No.094a/06&007a/04)as Quick Response Sprinklers. 9.Approved by the City of New York under MEA 354-01-E. 10.Approved by the Loss Prevention Certification Board(LPCB Ref. No.094a/06)at a 4 to 6 inch (100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11.Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. " Installed with Style 10(1/2"NPT)3/4"Total Adjustment Recessed Escutcheon. "�Installed with Style 20(1/2"NPT) 1/2"Total Adjustment Recessed Escutcheon. "*'Frame and deflector only. Listings and approvals apply to color(Special Order). TABLE A LABOR.4TORY LISTINGS AND APPROVALS Y Physical Characteristics �° Frame . . . . . . . . . . . . . Bronze Ope ra tion � Button . . . . . . . . . Brass/Copper � Sealing Assembly . . . . . . . . . . The glass Bulb contains a fluid which . . . . . Beryllium Nickel w/Teflont expands when exposed to heat.When a Bulb . . . . . . . . . . . . . . . Glass the rated temperature is reached, the �' � Compression Screw . . . . . Bronze fluid expands sufficiently to shatter the �� HSW Deflector . . . . . . . . Bronze glass Bulb, allowing the sprinkler to � VSW Deflector . . . . . . . . Copper activate and water to flow. o Patents a � U.S.A. 5,810,263 0 � TFP176 Page 3 of 6 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED HORIZONTAL SIDEWALL 250 PSI (17,2 BAR) (TY3331) OR 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) 5.6 RECESSED HORIZ. ��2�� SIDEWALL(TY3331) (SEE NOTE 1) N/A NPT VERTICAL SIDEWALL (TY3431) 175 PSI (12,1 BAR) NOTES: 1.The maximum working pressure of 250 psi (17,2 bar)only applies to the Listing by Underwriters Laboratories, Inc. (UL);the Listing by Underwriters Laboratories, Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE B, MAX/MUM WORK/NG PRESSURE De sign * Temperature rating is DEFLECTOR indicated on deflector or HAT 5 Cri t e ria adjacent to orifice seat _ on frame. The Series TY-FRB Horizontal and **Pipe thread Vertical Sidewall Sprinklers are in- connections per ISO 7/1 tended for fire protection systems de- can be provided on \ signed in accordance with the stand- special request. * , \ ard installation rules recognized by the 6 4 2 3 1 applicable Listing or Approval agency WRENCH 1/2"** (e.g., UL Listing is based on the re- 9/16" quirements of NFPA 13, and FM Ap- (14,3 mm) FLATS NPT proval is based on the requirements of � / FM's Loss Prevention Data Sheets). — Only the Style 10 or 20 Recessed Es- cutcheon, as applicable, is to be used ��� -- -- for recessed horizontal installations. 1-13/16" 7/16" (46,0 mm) (11,1 mm) CENTERLINE NOMINAL OF SPRINKLER MAKE-IN WATERWAY 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) 1 -Frame STYLE ESCUTCHEON 2-Button � PLATE SEATING 3-Sealing 10 or 20 — Assembly RECESSED SURFACE 4-Bulb ESCUTCHEON 5-Compression Screw 6-Deflector 2-7/8"DIA. (73,0 mm) FIGURE 1 5.6 K-FACTOR QUICK RESPONSE SER/ES TY-FRB HOR/ZONTAL S/DEWALL (TY3331)SPRINKLERS Page 4 of 6 TFP176 1 nsta Ila tion ARROW MUST POI NT AWAY The Series TY-FRB Sprinklers must 7/16" FROMAND BE 0 be installed in accordance with the fol- ESCUTCHEON (11,1 mm) PERPENDICULAR lowing instructions: PLATE SEATWG ** NOMINAL TO THE BACK / SURFACE NPT MAKE-IN WALL SURFACE � NOTES Do not install any bulb type sprinkler if *6 the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler - � 5 held horizontally, a small air bubble 2-3/16" � � 2-3/16" should be present. The diameter of the (55,6 mm) � I (55,6 mm) 4 air bubble is approximately 1/16 inch (1,6 mm) for the 135°F/57°C to 3/32 �_�/z�� WRENCH � Z inch (2,4 mm) for the 286°F/141°C 3s,1 mm temperature ratings. � I > FLATS � 3 A leak tight 1/2 inch NPT sprinklerjoint �' should be obtained with a torque of 7 � to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- SHOWN SHOWN CROSS mum of21 ft. Ibs. (28,5 Nm)of torque PENDENT UPRIGHT SECTION may be used to install sprinklers with 1/2 NPT connections. Higher levels of torque may distort the sprinkler and 1 -Frame 3-Sealing 4-Bulb 6-Deflector cause leakage or impairment of the Z-Button Assembly 5-Compression 7-Ejection Spring sprinkler. screw Do not attempt to make-up for insuffi- Cient 8djustment in the eSCUtcheon * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. plate by under- or over-tightening the **Pipe thread connections per ISO 7/1 can be provided on special request. sprinkler. Readjust the position of the sprinkler fitting to suit. F/GURE 2 The Series TY-FRB Horizontal and 5.6 K-FACTOR QU/CK RESPONSE Vertical Sidewall Sprinklers must be SERIES TY-FRB VERTICAL SIDEWALL (TY3431)SPRINKLERS installed in accordance with the follow- ing instructions. Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of water- Step B.After installing the Style 10 or Ca re a n d way perpendicular to the back wall and 20 Mounting Plate over the sprinkler parallel to the ceiling.The word"TOP" threads, hand tighten the sprinkler into Ma in te na n c e on the Deflector is to face towards the the sprinkler fitting. ceiling. Step C. Tighten the sprinkler into the The Series TY-BFR Sprinklers must Vertical sidewall sprinklers are to be sprinkler fitting using only the W-Type be maintained and serviced in accord- installed in the pendent or upright po- 7 Recessed Sprinkler Wrench (Ref. ance with the following instructions: sition with the arrow on the Deflector Figure 6). With reference to Figure 1, pointing away from the wall. the W-Type 7 Recessed Sprinkler NOTES Step 2. With pipe thread sealant ap- Wrench is to be applied to the sprinkler gefore closing a fire protection system plied to the pipe threads, hand tighten Wrench flats. main control valve for maintenance the sprinkler into the sprinkler fitting. Step D. After the ceiling has been in- work on the fire protection system that Step 3. Tighten the sprinkler into the stalled or the finish coat has been ap- it controls, permission to shut down sprinkler fitting using only the W-Type plied, slide on the Style 10 or 20 Clo- the affected fire protection system 6 Sprinkler Wrench (Ref. Figure 5), sure over the Series TY-FRB Sprinkler must be obtained from the proper With reference to Figure 1 or 2, the and push the Closure over the Mount- authorities and all personnel who may W-Type 6 Sprinkler Wrench is to be ing Plate until its flange comes in con- be affected by this action must be no- applied to the wrench flats. tact with the ceiling tified. The Series TY-FRB Recessed Hori- The owner must assure that the sprin- zontal Sidewall Sprinklers must be klers are not used for hanging of any installed in accordance with the follow- objects; otherwise, non-operation in ing instructions. theeventofafireorinadvertentopera- tion may result. Step A. Recessed horizontal sidewall Absence of an escutcheon, which is sprinklers are to be installed in the used to cover a clearance hole, may horizontal position with their centerline delay the time to sprinkler operation in of waterway perpendicular to the back a fire situation. wall and parallel to the ceiling. The word "TOP" on the Deflector is to face Sprinklers that are found to be leaking towards the ceiling. or exhibiting visible signs of corrosion TFP176 Page 5 of 6 5/8±1/4" (15,9±6,4 mm) , FACE OF � WRENCH RECESS MOUNTING SPRINKLER � ��2�NPrMO��s) SURFACE FITTING FIGURE 5 CLOSURE W-TYPE 6 SPR/NKLER WRENCH 2-7/8"DIA. (73,0 mm) WRENCH SERIES RECESS TY-FRB 2-1/4" DIA. � (57,2 mm) MOUNTING � PLATE ��_J �/g" PUSH WRENCH (3,2 mm) IN TO ENSURE ENGAGEMENT 1-1/4"(31,8 mm) 3/4"(19,1 mm) WITH SPRINKLER WRENCHING AREA 3/4"(19,1 mm) 1/4"(6,4 mm) FIGURE 3 F/GURE 6 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER W-TYPE 7 RECESSED WITH TWO-P/ECE 3/4/NCH TOTAL ADJUSTMENT SPR/NKLER WRENCH STYLE 10 RECESSED ESCUTCHEON �/2±1/8" must be replaced. (12,7±3,2 mm) Automatic sprinklers must never be painted, plated, coated or otherwise MOUNTING FACE OF altered after leaving the factory. Modi- SURFACE SPRINKLER fied sprinklers must be replaced. FITTING Sprinklers that have been exposed to corrosive products of combustion, but have not operated,should be replaced CLOSURE if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. 2-7/8"DIA. (73,0 mm) Care must be exercised to avoid dam- SERIES age to the sprinklers - before, during, TY-FRB 2-1/4" DIA. and after installation. Sprinklers dam- (57,2 mm) aged by dropping, striking, wrench � twist/slippage, or the like, must be re- placed. Also, replace any sprinkler MOUNTING that has a cracked bulb or that has lost PLATE liquid from its bulb. (Ref. Installation Section). � Frequent visual inspections are rec- ��8„ ommended to be initially performed for (3,2 mm) corrosion resistant coated sprinklers, after the installation has been com- 1-1/4"(31,8 mm) 1/2"(12,7 mm) p�eted,to verify the integrity of the cor- rosion resistant coating. Thereafter, 1"(25,4 mm) 1/4"(6,4 mm) annual inspections per NFPA 25 should suffice; however, instead of in- FIGURE 4 specting from the floor level, a random SER/ES TY-FRB RECESSED HOR/ZONTAL S/DEWALL SPR/NKLER sampling of close-up visual inspec- W/TH TWO-P/ECE 1/2 INCH TOTAL ADJUSTMENT tions should be made, so as to better STYLE 20 RECESSED ESCUTCHEON determine the exact sprinkler condi- tion and the long term integrity of the Page 6 of 6 TFP176 P/N 57 - XXX - X - XXX SPRINKLER TEMPERATURE MODEL/SIN RATING 378 HORIZONTAL SIDEWALL TY3331 1 NATURAL BRASS 135 135°F/57°C 375 VERTICAL SIDEWALL TY3431 4 WHITE POLYESTER 155 155°F/68°C 3 WHITE RAL9010)* 175 175°F/79°C 9 CHROME PLATED 200 200°F/93°C 7 LEAD COATED 286 286°F/141°C TABLE C `Eastern Hemisphere sales only. PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL S/DEWALL SPR/NKLERS corrosion resistant coating, as it may standards of any other Authorities Ordering be affected by the corrosive conditions Having Jurisdiction. Materials found present. by TFBP to be defective shall be either repaired or replaced, at TFBP's sole Procedure The owner is responsible for the in- option. TFBP neither assumes, nor spection, testing, and maintenance of authorizes any person to assume for it, When placing an order, indicate the their fire protection system and de- any other obligation in connection with full product name. Refer to the Price vices in compliance with this docu- the sale of products or parts of prod- List for complete listing of Part Num- ment, as well as with the applicable ucts.TFBP shall not be responsible for bers. standards of the National Fire Protec- sprinkler system design errors or inac- Contact your local distributor for avail- tion Association (e.g., NFPA 25), in curate or incomplete information sup- ability. addition to the standards of any other plied by Buyer or Buyer's repre- authorities having jurisdiction. The in- sentatives. Sprinkler Assemblies with NPT stalling contractor or sprinkler manu- In no event shall TFBP be liable, in Thread Connections: facturer should be contacted relative contract, tort, strict liability or under Specify: (Specify Model/SIN), Quick to any questions. any other legal theory, for incidental, Response, (specify K-factor), (specify It is recommended that automatic indirect,special orconsequential dam- temperature rating), Series TY-FRB sprinkler systems be inspected, ages, including but not limited to labor (specify Horizontal Sidewall orVertical tested, and maintained by a qualified charges, regardless of whether TFBP Sidewall) Sprinkler with (specify type Inspection Service in accordance with was informed about the possibility of of finish or coating), P/N (specify from local requirements and/or national such damages, and in no event shall Table C). codes. TFBP's liability exceed an amount equal to the sales price. Recessed Escutcheon: Specify: Style (10 or 20) Recessed Lim ite d The fore�oing warranty is made in lieu Escutcheon with (specify*) finish, P/N of any and all other warranties. ex- (specify*). Wa rra n t y press or implied, includin� warranties of inerchantability and fitness for a� *Refer to Technical Data Sheet TFP770. Products manufactured by Tyco Fire& ticular purpose. Building Products (TFBP) are war- This limited warranty sets forth the ex- Sprinkler Wrench: ranted solely to the original Buyer for clusive remedy for claims based on Specify: W-Type 6 Sprinkler Wrench, ten (10)years against defects in mate- failure of or defect in products, materi- P/N 56-000-6-387. rial and workmanship when paid for als or components, whether the claim Specify: W-Type 7 Sprinkler Wrench, and properly installed and maintained is made in contract, tort, strict liability p/N 56-850-4-001. under normal use and service. This or any other legal theory. warranty will expire ten (10) years from date of shipment by TFBP. No This warranty will apply to the full ex- warranty is given for products or com- tent permitted by law.The invalidity, in ponents manufactured by companies whole or part, of any portion of this not affiliated by ownership with TFBP warranty will not affect the remainder. or for products and components which have been subject to misuse,improper installation, corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale, Pennsylvania 19446 l■i� ■ � � ' f� ■ � .� �� ,� _ .� �` Schedule-10/Schedule-40 - ABFII Submittal Data Sheet > Fully Listed and FM Approved Sprinkler Pipe -� � NPS Nominal I.D. Wt. Wt.(H20 Filled) CRR When you specify Schedule-10/Schedule-40-ABFII sprinkler pipe from Allied Tube& �n;mm in;mm Lbs/Ft;kg/m Lbs/Ft;kg/m - Conduit,you get UL listed and FM approved products.Although these products do not t" 1.049 1.680 z.o5 � require separate approvals,Schedule-10/Schedule-40-ABFII gives you the extra quality z5 26.6 z.5 3.05 - assurance you demand.Our Sch-10(1-1/4"-8") pipe and Sch-40(1"-2-1/2") pipe t�/4" 1.380 z.z�o 2.93 � have passed the same thorough lab testing as our other listed pipe products,and receive 3z 35.1 436 4.36 - periodic mill inspections from both UL and FM agents to ensure consistent quality. �'/z" 1.610 z.�zo 3.61 � 40 40.9 4.0 5.37 - � GaIVa111Z2C1 Plpe Schedule-10/Schedule-40-ABFII product can be "hot-dip" Z" z.o6� 3.650 5.13 � galvanized to meet FM requirements. 50 52.5 5.4 7.63 - 2'/z" 2.469 5J90 7.86 1 > Superior Coating our advanced formula mill coating offers a clean,durable 65 6z.� a.6 11.73 - surface that is also paintready for custom color applications without special preparation. � .- . The internal surface of all black Fire Sprinkler pipe up to 4.5000" in diameter shall be NPS Nominal I.D. .Wt. Wt.(H20 Filled) cRR coated with Allied Tube &Conduit Antibacterial Formula "ABF". i,,;mm i,,;mm Lbs/Ft;kg/m Lbs/Ft;kg/m - 1'/4" 1.442 1.810 2.525 7.0955 > American MadeAb�e to meet"BuyAmerican" requirements,and is available 3z 36.6 z.7 3.75 - through distributors in the USA, Canada, Mexico and Latin America. ��/�" �.ssz z.oso 3.04 5.6570 40 42.7 3.1 4.52 - � SpeCIflCat10115 & ApprOVaIS Schedule-10-ABFII pipe is in compliance Z�� Z.�S� Z640 4.zz 4.5827 with ASTM A135,Type E Grade A, and NFPA 13.Schedule-40-ABFII pipe is in compliance 50 54.8 3.9 S.ZS - with ASTM A135/A795,Type E Grade A,and NFPA 13. Both pipe products have a working Zyz�� 2.635 3.530 5.89 3.5196 pressure rating of 300 psi maximum and also meet the stringent requirement for the 65 66.9 5.3 s.77 - following tests:Welded Outlets, Hydrostatic Pressure, Side Wall Rupture,Vibration Test. 3" 3.z6o 4330 7.94 2.5550 75 82.8 6.4 11.82 - 4" 4.260 5.610 11.78 1.6020 100 108.2 83 17.53 - 5" 5.295 7.77 1733 1.4874 125 134.5 11.56 25.80 - 6" 6.357 9.290 23.03 1.0251 150 161.5 13.8 34.27 - 8" 8.249 16.490 40.15 1.8365 200 Z09.5 24.5 59.75 - �L C �L F M APPROVED Project: Sprinkler Contractor: Date: Engineer: Specification Reference: System Type: Locations: Comments: /���III�� Customer Service (800) 88Z-5543 Fax: (800) 659-7730 www.alliedtube-sprinkler.com �T� • 16100 S Lathrop Ave. • 11350 Norcom Rd. •2525 N Z7th Ave. •600 Dean Sievers Place TUBE & CONDUIT° Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009 Morrisville,PA 19067 A PART O=�atkore 002011 Atkore International,Inc.All Rights Reserved. STP-S5-4-1111 � �HUR,JCIIl�T�� . • - • • • � wwtiv sfiu r�aint.cam MODEL 7110 90° ELBOW, REGULAR RADIUS C u` u� � F� vds usr€o aQa�n 7111 45° ELBOW, REGULAR RADIUS 7112 22-1/2° ELBOW 7113 11-1/4° ELBOW � - �-�., �� �-� � Ee•_ -11� Ii��.'ll:+ ??.I '_"IJi���,� 11-I'�'E-1h<xv _ r _ ! � 1 I i.. -'___ . � {-I i i-I f I i i_ � _ + L -. '� i _ _ -'liti I�it�.. 'li: J�r��. il_' VI -1i.� 'xi E_Ih�+u d> i_[Ixn. ,.'-I ; I Ilr��u I I I 1 Flhui, r1���ld cRrltics'1;� • • - I • • Nominal Pipe P'ipe #7110 90� EJboenS #7111 45o �bovvs 7112 72-1/2� Obows #7113 11-1/4� EJbo�nS Sl'ze O.D. GE VUeigFrt GE V1kigM GE Vlkight GE Vlkight mn rrrri rrrn Kgs rrrri Kgs rrrri Kgs rrm Kgs f_1„ !!x> i i 25 33.4 57 0.3 45 0.2 - - - - 32 42.2 70 0.5 45 0.3 45 0.3 35 0.2 t 25 1.6� 2.75 1.� 1 J5 0.7 1 JSSW 0.7 �.38SW 0.4 40 48.3 70 0.7 45 0.4 45 0.6 35 0.3 1.5 1.900 2J5 1.5 1 J5 0.9 1 J5 1.3 1.38SW 0 7 50 60.3 83 0.9 51 0.7 48 0.8 35 0.8 2 2375 3.25 2.0 2� 15 1.88 1.8 1.38 1.8 65 73.0 95 1.2 57 0.9 51 1.0 38 1.0 25 2875 3.75 26 225 20 201 22 150 22 65 76.1 95 1.4 57 1.0 51 1.0 38 1.0 25 3.�0 3J5 3.1 225 22 2G1 22 150 22 80 88.9 108 2.1 64 1.3 57 1.4 38 1.1 3 3..500 4.25 4.6 2.50 2.9 2 25 3.1 1.50 2.4 90 101.6 114 2.5 - - - - - - 35 4.� 450 5.6 100 114.3 127 2.8 76 2.0 73 2.0 45 1.5 4 4 x�0 5 Gi 6 2 3 rXi i.? 'SS'i =2.I 9; 3 3 100 108.0 127 3.5 76 2.0 - - - - 4 >S:i �G:'; ,7 3 L't,; _ _ 125 141.3 140 5.0 83 3.5 73 3.3 51 2.7 5 5.5fx3 5.50 ��.0 325 77 23S 7.3 2L'(�S;/✓ 5.9 125 133.0 140 4.1 83 2.7 - - - - 5 5250 5.50 9 0 325 5 9 125 139.7 140 5.0 83 3.5 73 3.3 51 2.7 5 5.500 5.50 11.0 325 7J 2 88 7 3 2�SW 5.9 150 168.3 165 6.4 89 4.4 79 5.0 51 3.4 6 6.G25 650 14.1 350 9.7 312 11.0 2� Z5 150 159.0 165 6.0 89 3.8 - - - - 0 6.250 6.50 132 3.50 8.4 150 165.1 165 5.7 89 4.4 79 5.0 51 3.4 6 6..500 6.50 12 5 3.50 9.7 3.12 11.0 2� Z 5 200 219.1 197 12.5 108 9.0 98 10.0 51 5.5 B ��J ��J '�.�J -�'.?r tLii 2.� �2� 200JIS 216.3 197 12.5 108 9.0 98 10.0 - - 8 i 6 7J5 27 5 �J5 `�Y. �'9 - - 250 273.0 229 24.0 121 17.0 111 13.6 54 6.6 r0 10750 9.� 528 4.75 3Z4 4�.38 299 213 14.5 250.11S 267.4 229 24.0 121 17.0 111 13.6 54 6.6 10 1Q528 9.� 528 475 3Z4 4.38 29.9 2.13 94.5 300 323.9 254 35.0 133 22.5 124 18.3 57 8.5 12 1 Z 750 10.00 77 0 525 49.5 4 88SW 4Q 3 225 18 7 300JIS 318.5 254 35.0 133 ?2.5 124 18.3 57 8.5 i2 12�39 10.00 77.0 5.25 49.5 4.88SW 40.3 225 1SJ 350 355.6 280 35.0 152 22.0 127 21.0 89 14.6 14 14 IX� 11.CO T/0 6.� 48.4 S.00SW 46 2 3.50SW 321 400 406.4 305 43.0 184 44.0 127 24.0 102 19.0 16 16.G1�0 12.00 94.6 725 96.8 5.00SW 528 4.00SW 41.8 450 457.2 394 75.0 203 46.6 140 30.0 114 24.0 18 18.� 15.50 165.0. 8.� 102 5 5.50SW 66.0 4.50SW 528 E-02-1/3 Rev.B 20070911 � �H iJR,JCI�Il�T`� . . - • • • � u�wtiv.shurjaint_com • • - 1 • • Nominal Pipe P'ipe #7110 90° Elbows #7111 45° Obows 7112 22-1/20 �bo�n5 #7113 11-1/4� EJbo�nS Size O.D. GE V1ki ht GE V1ki ht GE Vlkight GE Vlkight rrrri rrm rrrri Kgs rrm Kgs rrm Kgs rrm Kgs i� ii�� in IJ�s ii� �zs ri� ll�s ii� IJ�s 500 508.0 438 92.0 229 47.6 152 36.3 127 30.0 20 2G�X: 1Z 25 202.4 9.� 104'J 6�S�.N 79.J 5.0!JSU'd tS6� 550 558.8 508 129.0 280 80.0 178 51.0 152 46.0 22 22� 20.00SW 283 8 11.�SW 176 0 Z 00.SVV 112 2 6.00SW 1012 600 609.6 508 129.0 280 80.0 178 51.0 152 46.0 24 CXYJ 20.00 283.8 11.� 176_0 7.COSW 9'12.2 6.00 SW 101.2 SV�i.Segment-�n,elded steel. MODEL 7112G 22-1/2° ELBOW, Goose Neck Design The use of two 22-1/2°goose neck elbows and a coupling 5 x .�� works as a universal joint and is ideal for instances where a 4- _ pipe line and or system is in indeed of a slight adjustment �F �-� c �! us ,�g FM usren na�Arnhn � • • - • • • • �l Nominal Pipe Pipe 7112 72-1/2� Elbo�n5 ,� Size O.D. E-E Vlkight rrrri rrrri rrrri Kgs , ir i Llzs 40 48.3 95 G 0.6 � ' 7.5 1.Xb 375 7.3 ,�j 50 60.3 95 G 0.8 2 2.375 3J5 1.3 65 73.0 102 G 1.0 25 - 400 22 65 76.1 102 G 1.0 25 3 CP'J 4 Ql 22 I�-E: � ��9 114G 1.4 3 3.5� 4 50 3 1 100 114.3 127 G 2.0 �; ,.7 �a_� 5� �t.a l�l��. a I I� 125 141.3 127G 3.3 ' ` :z 563 �i(r� 7:; �', �,'i F=�f�+.}'�'` 125 139.7 127G 3.3 55 ,^:�� 5(Xl Z3 150 168.3 159 G 5.0 G c.6`1'� G.25 1 i.0 150 165.1 159 G 5.0 6 F'�� 6.25 11.0 200 219.1 197 G 10.0 7; 720 200JIS 216.3 197 G 10.0 8 Z 75 22 0 MATERIAL SPECIFICATIONS Ftting body: •SurFaoe Fnish: Ductile Ira�toPSTMA536,Gr.65�45-12,Nin.tensile strerigth Orar�ge odor pair�ted a-red RAL3000 odor pairited. aasn���,000 p��>. ❑ Hot dip galvanized(Option). ❑ Carbon stcel Sch.40 pi pe to ASTM A53 or 9.5mm ❑ Epo>ry coeted in red RAL3000 a-other cdors (0.375')wall pipe ofASTMA234 Gr.WPB. (Option) E-02-2/3 Rev.B 20070911 � �HUR,J[]Il�T�' . . - • • • � ww�,v sfiu r�aint.cam G21leCa��2S: • Pressure ratings listed are CV�P(cdd water pressure)or rr�udmum v�aiiang pressure v�ithin the seivice terrperature rar�ge of the gasket used in the coupling.This rating rr�y occasionally differ from rr�dmum v�,oricing pressures listed arKVor approved by UL,ULC,arxVor FM as testing coriditions and test pipes differ.For additional inforrration oontact Shurjoint.. • IV}�dmum Nroii<ing pressures arid end loeds listed are total of ir�e�rial and extemal pressures ar�d loads based on Sch.40 steel pipe with rdl growes to ANSI/AVUNA C60Fr97 speafications.Fa-ir�famation on other pipe schedules contact Shurjoint.. • For one time field test only the ma�dmamjar�v�roii<ing pressure rriay be ir�a-eased 1-1/2 times the figures shov�m. • V1�ming:�iping syst�s must always be depressurized and drained befa-e attempting disassembly and or removal of any oorrponents. • Shurjoint reserves the right to char�ge speafications,designs and a-star�dard equiprrent witha.it notice ar�d without irxurring ar�y obligatia�.s. E-02-3�3 Rev.B 20070911 � SHIIRJ+�]INT� • • - • • • � uvw�w.shur�oint.cam e �L us ,�p�g, F�II 1,�d� �isxea araem�n MODEL 7120 TEE 7135 CROSS �, `� � ,� 7130 45° LATERAL - '� T-` - � #. f. � � -- C:-E -� i�:-E`. Fi�. ?1?0 Ie� Fis. '�3� C�r�ss _ _ � y �� i ' f;. � �: � � ��.! t � `r �C�-E-� - C-E F'a• '1'C' Fia, ?1'Q FiQ. ;13� -�>�Lat�ral Tee ���relcC�ec�j Cross f����lEi�s��lj . • - 1 ' • 1 • • - • Norririal P'ipe P'ipe #7120 #7135 #7130 Size O.D. Tee Qross 45°Later�al rrm rrm GE Kgs GE Kgs GLE CSE Kgs in !�'�s iJ�s 1J�s 25 33.4 57 0.4 57 SW 0.6 - - - 1 �.315 225 Cl9 2.2� 9.3 32 42.2 70 0.7 70 SW 1.0 146 SW 64 1.1 125 2 G 0 2J5 %.(� 2 75 2 5 75 2��� 2 4 40 48.3 70 0.9 70 S1N 1.1 159 SW 70 1.6 �;a r' 2 7.5 2 7s 6� °i's 50 60.3 83 1.3 83 1.7 178 70 2.3 2 2;i 3.2`; 'Lti` �1 65 73.0 95 2.2 95 2.8 197 76 2.8 2'i �ni5 3J5 +.c 3.%� 8.2 i.7;i 3.i1� 6.2 65 76.1 95 2.3 95 2.8 197 76 2.8 2 5 3 L1�`J 3.75 5.l 3J5 G 2 7J5 3 00 6.2 80 88.9 108 3.1 108 4.8 216 83 4.2 3 3.� 4.25 6.8 4.25 1Q6 8;,G 325 9.2 100 114.3 127 4.6 127 72 267 95 8.0 4 45(X) 5.� 10.1 5.� 15.9 1Q� 3J5 l76 100 108.0 127 4.1 - - - - - 4 4.250 5.� 9.0 - 125 141.3 140 6.5 140 9.1 318 102 12.5 5 5.5G3 5.50 14.3 5.50 20.0 12:�i 400 2Z5 125 133.0 140 6.0 - - - - - 5 5.250 5.50 13.2 125 139.7 140 6.5 140 9.0 318 102 12.5 5.5(X� 5.50 143 5.50 198 �250 4.00 2Z5 150 168.3 165 10.0 165 12.7 356 114 18.5 6 6.625 6.50 /�(� 6 50 27,9 94.00 4�) �,7 150 159.0 165 8.6 - - - - - �; r�.v7 6.50 i£;�) . - 150 165.1 165 8.5 165 12.0 356 114 18.5 G c.�a;cJ 6.50 18.7 Ez�) 264 i% iJ7 200 219.1 197 20.0 197 22.0 457 152 32.0 8 t3 6�5 7J5 44.0 7J5 48.4 18.00 6.00 70 4 200A 216.3 197 20.0 197 21.0 457 152 32.0 8 8 516 Z 75 44.0 7J5 46.2 18.00 6.Cd 70.4 250 273.0 229 31.0 229 SW 32.0 521 165 47.6 10 ?0 750 9.� 68.2 9.� 70.4 Z1J.50 6 50 104.7 E-05-1/2 Rev.A 20070929 � SHUI�.J+DINT�' • • - • • • � uvww.shu r�pint.com • • - 1 ' • 1 • • ' • IVomirial P'ipe Pipe #7120 #7135 #7130 Size O.D. Tee Cross 45�Lateral mn rrm GE Kgs GE Kgs GLE GSE Kgs �i, in U,s Lbs Lbs 250A 267.4 229 31.0 229 SW 32.0 521 165 47.6 ?0 1U52S J-U� 682 9.� 70.4 20.50 6'� 14�J 300 323.9 254 45.0 254 SW 50.0 584 178 75.0 12 12J;�(i 10.� 99.0 1Q� ?10.0 23.00 7.00 1650 300A 318.5 254 45.0 254 SW 50.0 584 178 75.0 I� 12�39 ^9.Cf< <tir; 90.Gt% G'i7i? <<�' 7%k:i 5r50 350 355.6 280 54.0 280 SW 91.0 673 SW 191 125.0 ak; +; T 1.in) s2 2 `16.50 >7a 0 400 406.4 305 66.0 305 SW 113.8 737 SW 203 156.0 �F�.(Xk� i 2 C;�) i45� 12(IG 25L'4 �i IXi 343.2 450 457.2 394 SW 124.3 394 SW 1657 813 SW 216 195.0 i>i i`c.iXti? 15:xi 273 5 �5 a'l 364.5 32!Xl 42�J 0 500 508.0 438 SW 153.9 438 SW 205.2 889 SW 229 227.0 2Q Gt� 1 z?5 9 z cs -7.? 35�! ',9 4 550 558.8 483 SW 150.0 483 SW 242.8 965 SW 241 280.0 �% 220� '�'.ib 3t:;.,7 9C� 1.2 30.00 ?1�0 600 609.6 508 SW 215.1 508 SW 286.8 1016 SW 254 324.0 �; r;, �;', o ,; v SW.Segrn�t v�elded stcel. - MATERIAL SPECIFICATIONS Ftting body: Dudile Iron toPSTMA536,Gr.65-45-12,Nin.tensile strerigth 448NPa(65,000 psi). ❑ Carbon stcel Sch.40 pi pe to ASTM A53 a-9.5mm (0.378')wall pipe ofl�.STMA234 Gr.WPB. •SurFace Fnish: Orar�ge cola-pair�ed a-red RAL300o cda-pair�ed. ❑ Hot dip galvanized(Option). ❑ Epwry caated in red RAL3000 or other cdas (Option) Ger�-al Notes: • Pressure ratirigs listed are CU�P(cdd water pressure)or ma�drrum v�,oiidng pressure�n�ithin the service temperature range of the gasket used in the coupling.This rating rr�y occasionally differ from rr�dmum v�,orking pressures listed arKVor approved by UL,ULC,arxVor FM as testing coriditions arid test pipes differ.For additional infarration oontact Shurjoint.. • fN}a�dmum woricing pressures and end loads listed are total of ir�e�rial and extemal pressures arid loads based on Sch.40 steel pipe v�,ith rdl grooves toANSI/AVUNAC�OCr97 speafications.For ir�farr�tion on other pipe�dules contad SJ�urjoint.. • For one time field test only the ma�dmamjar�v�roricing pressure rriay be iria-eased 1-1/2 times the figures sYiov�n. • V1�ming:Rping systerrs must always be depressurized ar�d drained befa-e attempting disassembly and or re�rioval of any corrponents. • Shurjoint reserves the right to char�ge speafications,designs and or star�dard equiprrent witha.it notice ar�d without irxumng ar�y obligatia�.s. E-05-7J2 Rev.A 20070929 � �HURJ�IIVrT�� � � ww°w.shurja�int.eQm MODEL Z05 RIGID COUPLING e«U�o�s AP RWFD -Angle-Pad Design - The Shurjoint Model Z05 is an angle-pad design rigid coupling for - =�-�,� moderate pressure piping services including fire mains, long straight � �` � runs and valve connections. The angle-pad design allows the coupling '` : � housings to slide along the bolt pads when tightened. The result is an offset clamping action which provides a rigid joint which resists so called `snaking' of a long straight run. Support and hanging requirements correspond to ANSI B31.1, 631.9 and NFPA 13. With the 's removal of only one bolt you can make a fast and easy "swing-over" � installation. � The Shurjoint Model Z05 is available with a standard "C" shaped or GapSealO gasket in a variety grades to meet your specific service requirements. Sizes available: 32mm-200mm/1-1/4"-8" Working Pressure: Up to 24 bar/350 psi 1 ItiF• .un�;lf• �,,�rl �I�=ti,�ra .,Ifi:nl� 1�,r I.1�1 .,��! u.►ey� .�, �:F-o-,�„r�r u,slall,ti�w-rn .� � _� .- �_� -� ��� ..�. �� - .,, "�: �. � � y . _ . � � � II I � �_ � 4• � / MODEL Z05 RIGID COUPLING . • - 1 . . . . . Nla�c. Nkvc Axial Norririal Pipe V�bridng Erid displace- Dimension Bolt Size OD Pressure Load ment A B C Size Vlkight rrm rrm Bar kN rrm rrm rrm rrm � rrm Kgs 32 42.2 24 3.37 0-12 66 102 46 2 M10 x 55 0.6 40 48.3 24 4.42 0-12 72 109 46 2 M10 x 55 0.7 15 1.9M ;;r7 9iJG 0-0.05 2a3 4tJ 1&1 3/Sx2-1/F; ?� 50 60.3 24 6.90 0-1.7 85 117 47 2 M10 x 70 0.8 2 2375 350 1550 0-0.07 3.35 4.61 9.F3� 3Bx2-y4 7] 65 73.0 24 10.11 0-1.7 98 132 47 2 M10 x 70 0.9 2�5 2 875 3li'J 2270 �-0.07 '.f?6 5.20 7.£i5 3�8 x 2-�/4 21 65 76.1 24 11.01 0-1.7 100 136 47 2 M10 x 70 1.0 25 3-(X�7 3.50 2475 0�0 07 3-94 5.35 1.5a 3i8 x 2-3�4 22 80 88.9 24 14.99 0-1.7 113 148 48 2 M10 x 70 1.2 3 3� s:�l 3365 0-0 07 �� 5.83 1.F38 3�8 x 2-3�4 26 100 108.0 24 22.11 0-4.1 142 176 54 2 M10 x 70 1.6 4 4.250 3:� 4'9G; 0-0.16 5 t;G 6 93 213 3i8 x 2-3i4 £<r 100 114.3 24 24.77 0-4.1 146 182 53 2 M10 x 70 1.9 4a�J0 3xJ :;*!;� 0-016 575 Z97 2(19 ✓ox2-:v4 41 125 133.0 20 28.91 0-4.1 170 224 54 2 M12 x 75 2.3 5.250 3� 649'i 0-0.l6 6.&9 8 82 213 7i 2 x 3 51 125 139.7 20 31.72 0-4.1 173 227 53 2 M12 x 75 2.6 5.� 3Gb 7125 0-0.16 6.89 8.94 2.09 1Y2 x 3 5 7 125 141.3 20 32.45 0-4.1 175 229 53 2 M12 x 75 2.6 5 55G3 30;; i�xr� 0-0.16 6&3 90[ 2.(k� Z�? 57 150 159.0 20 40.98 0-4.1 198 250 54 2 M12 x 75 2.8 �> 6�'SJ 3i U f;`�i3 0_0 96 /'riil 9�i 2.13 `t�2 x 3 Fi, G0.'�1 Rev B20W0911 � �HL1RJ+[J�IIVrT�' � � ww°w.shur�oint.eQm • • - 1 • • • • • Nlax IVlax Axial Nomirial Pipe V1kMidng Em! displace- Dimension Bolt S1ze oD Pressure Load ment A B C Si� Vlkight rrrri rrrri Bar kN rrrri rrrri rrrri rrrri � rrrri Kgs 150 165.1 20 44.30 0--4.1 200 246 54 2 M12 x 75 3.1 150 168.3 20 46.02 0—4.1 203 249 54 2 M12 x 75 3.1 8 G625 30t; ?i�°4i,� 0-0.16 SiX� 980 2.1� ';�x? 6c 200 219.1 20 78.00 0—4.8 264 330 64 2 M16 x 135 6.1 8 8625 3GYl 17525 0-0.19 ?0.4v ?29� 252 5"c'x�5�1� ?34 200 JIS 216.3 20 76.08 0—4.8 260 340 64 2 MZO x 120 7.4 t� �516 3(YJ 17079 0—0 99 10 24 13-39 2 50 3�4 x 43.' ?&2 MODEL Z05 MATERIAL SPECIFICATIONS . �j terrperature,fluid medium(air,watex,air with water...etc.)and �� the continuous or ir�terrriitter�t use of the em For Duc�ile Iron toASTMP536,Gr.6.5-45-12,min.tensile strength ���� ������i� speafic applications over 200°F(93°C),please oonsult Shurjoint for recorrrr�endatia�s. •SurFace Fnish: ❑ �opt�a,�c��m'Nitrile(Cdor code:Orange stripe) Standard pairrted finish�es in a-arx�e or RAL3000 red. Recomrr�rxied fa-petrdeum products,air with al vapa-s, ❑ Hot dip anc galvanized(Optional). vegetable and rrineral als within the speafied terrperature ❑ Epo�ry Coatings in RAL3000 red or other cdas rarxx�ee. Also good for water services under+66bC (Optia�al) (+150°�. Tenpei-ature rarxae:-29°C to+82°C(-20°F to+180°�. • F�ubber Gasket: �o�c�fo�-Hor wa��+ss�c�+��o��o�- To assure rr�xi mum I ife for the service ir�terided,proper gaslcet �T�'°'�R above+60°C(+140°F) seledion and speafication in orclaing is esseritial. Failure to � p�he�.o�ions:Q.ade��d�_Flua.celastar�. seled the proper gasket corrpound rray result in pc�-sor�l injury, Q-�"L"-Silicone. property darrege,jant leakage orjar�failure. trade"E"EPDM(Cdor code:Green stripe)Good for odd&hot For dry systerrs we recorrrr�ends the use of the Shurjoint vuater up to+230°F(+110°C).Also good for services for water �p Seal gasket. with acid,water v�ith chlaine,deionized water,seauvater and For additia�al details contact Shurjoint. waste wat�,dilute acids,al-free air arid rr�ny d�erricals.Not recan�r�ended for petroleum als,rrinerals als,sdvents and arorr�tic hydrocarbons. Ma�dmum Tenperature Range:-29�F(-34°C)to+23(PF • BOItS&IV�S: (+110'C)� Heat treated carbon rrnriganese steel track bdts to ASTM *Fa-hot water application betv�en Z00°F-230°F extrerrie A44,�83a(or A183 tr.2),rrinimum tensile strength 758 NPa caution sha.ild be�ed as the life of the gasket can be gre�atly (110,000 psi),Zinc electroplated,with heavy�luty hexagorial nuts reduoed by incx-erriental ina-eases in terrperature. Additional to/�.STMA563. factas that affed gasket life and perfarrance indude Ger�eral Notes: • Pressure ratings listed are CWP(cdd water pressure)or rr�drrum v�,orking pressure within the service terrperature rarx�e of the gasket used in the coupling.This rating rr�y oa�sionally differ from ma�dmum working pressures listed arxVor ap�xoved by UL,ULC,arxVor FM as testing coriditions arid test pipes differ.For additional ir�forrration c�ontad Shurjoint.. • Ma�dmum vwricing{xessures arid erid loads listed are total of ir�emal arid exterr�al pressures arid loads based on Sch.40 steel pipe v�,ith rdl grooves toANSI/AVUNAC60G97 speaficatia�s.For irifarr�tion on otl�er pipe schedules c�ntad Shurjoint.. • For one time field test only the ma�drrumjar�v�a�kirx,�pressure rr�y be incxeased 1-1/2 times the figures shwvr�. • Waming:�iping systems must always be depressurized and drained before atterrpting disasserr�bly arid or removal aF arry c�rponents. • Shurjoint reseives the right to char�ge specifications,designs and or staridard equiprrient witha.it notice arid without incurring any obligatia�s. G0.'�2 Rev B 20W0911 ,��I ����� � ���I���. S�I INTERNATIONAL Ductile Iron Threaded Fittings C, u� u� *ALL FITTINGS 100%AIR TESTED *ASME/ANSI B16.3 *ISO 9001:2000 MANUFACTURER *ASTM A536 Grade 65,45,12 F� LISTED '�LISTED/APPROVED AT 500 PSI *ASME/ANSI B 1.201 pRPROVEO Ductile Iron 90°Elbow Ductile Iron Cou lin Fi re 35E Size A W t Fi re 35CP Size A W t �A� 1/2 1.13 0.24 1/2 1.38 0.18 3/4 1.31 0.40 3/4 1.63 0.26 1 1 1.50 0.64 1 1 1.75 0.44 AI 1-1/4 1.75 0.95 A 1-1/4 2.00 0.54 , i 1-1/2 1.94 1.24 � 1-1/2 2.19 0.71 2 2.25 1.74 2 2.62 1.15 2-1/2 2.70 3.28 2-1/2 3.00 2.29 Ductile Iron Reducin 90°Elbow Ductile Iron Ca Fi re 35RE Size A B Wgt Fi ure 35C Size A W t 3/4 x 1/2 1.22 1.20 0.33 1/2 0.87 0.15 1 x 1/2 1.36 1.26 0.44 3/4 0.97 0.22 1 x 3/4 1.45 1.38 0.53 � 1 1.16 0.33 1-1/4 x 1/2 1.53 1.34 0.64 A 1-1/4 1.28 0.54 1-1/4 x 3/4 1.63 1.45 0.75 i 1-1/2 1.33 0.68 1-1/4 x 1 1.67 1.58 0.77 2 1.45 0.96 ~A� 1-1/2 x 1/2 1.75 1.52 0.90 2-1/2 1.70 1.80 } 1-1/2 x 3/4 1.75 1.52 0.95 B 1-1/2 x 1 1.80 1.65 0.99 Ductile Iron Hex Bushin 1 1-1/2 x 1-1/4 1.88 1.82 1.14 Fi ure 35HS Size A Wgt 2 x 1/2 1.97 1.60 1.35 1 x 1/2 1.06 0.22 2 x 3/4 1.97 1.60 1.39 1 x 3/4 1.06 0.18 2 x 1 2.02 1.73 1.58 4 1-1/4 x 1 1.19 0.31 2 x 1-1/4 2.10 1.90 1.62 � 1-1/2 x 1 1.25 0.53 2 x 1-1/2 2.16 2.02 1.67 1-1/2 x 1-1/4 1.25 0.35 2-1/2 x 1-1/2 2.51 2.16 2.32 � 2 x 1 1.38 0.75 2-1/2 x 2 2.60 2.39 3.01 2 x 1-1/4 1.38 0.69 2 x 1-1/2 1.38 0.62 Ductile Iron Brass Seat Union Fi re 35U Size A Wgt Ductile Iron 45°Elbow 1/2 1.88 0.47 Fi re 35F Size A Wgt � 3/4 2.00 0.66 � 1/2 0.88 0.22 A 1 2.19 1.08 �A 3/4 0.98 0.33 l1-1/4 2.50 1.54 1 1.13 0.48 1-1/2 2.62 2.03 1-1/4 1.29 0.73 2 3.12 3.15 � 1-1/2 1.44 0.93 A 2 1.69 1.55 Ductile Iron Tee i 2-1/2 1.95 2.70 Fi ure 35T Size A Wgt �A��A� 1/2 1.13 0.33 Ductile Iron Beam Clam s 3/4 1.31 0.50 Figure 35SP 1 1 1.50 0.85 Size A Wgt A 1-1/4 1.75 1.30 � 3/8 0.75 0.31 � 1-1/2 1.94 1.63 + 1/2 0.75 0.54 2 2.25 2.63 2-1/2 2.70 4.55 �,�I �����I( � C���I�I�IE�. �,�I INTERNATIONAL I�I� Ductile Iron Threaded Fittings C '�L �S �'ALL FITTINGS 100%AIR TESTED *ASME/ANSI B16.3 F� *ISO 9001:2000 MANUFACTURER *ASTM A536 Grade 65,45,12 LISTED *LISTED/APPROVED AT 500 PSI *ASME/ANSI B 1.20.1 qRPROVED Ductile Iron Bull Head Tee Ductile Iron Reducin Tee Fi re 35RT �B��A� Size A B C Wgt 1 3/4 x 3/4 x 1/2 1.20 1.20 1.22 0.46 Figure 35BT l 1 x 1/2 x 1 1.50 1.36 1.50 0.70 • 1 x 3/4 x 3/4 1.38 1.31 1.45 0.68 1 x 3/4 x 1 1.50 1.45 1.50 0.77 Size A B C Wgt 1 x 1 x 1/2 1.26 1.26 1.36 0.66 3/4 x 3/4 x 1 1.45 1.45 1.37 0.68 1 x 1 x 3/4 1.38 1.38 1.45 0.73 1 x 1 x 1-1/4 1.67 1.67 1.58 0.97 1-1/4 x 1/2 x 1-1/4 1.75 1.53 1.75 1.04 1 x 1 x 1-1/2 1.80 1.80 1.65 1.14 1-1/4 x 3/4 x 1-1/4 1.75 1.62 1.75 1.09 1-1/4 x 1 x 1-1/2 1.88 1.80 1.82 1.43 1-1/4 x 1 x 1/2 1.34 1.26 1.53 0.81 1-1/4 x 1-1/4 x 1-1/2 1.88 1.88 1.82 1.52 1-1/4 x 1 x 3/4 1.45 1.38 1.63 0.90 1-1/4 x 1-1/4 x 2 2.10 2.10 1.90 2.00 1-1/4 x 1 x 1 1.58 1.50 1.69 1.03 1-1/2 x 1-1/4 x 2 2.16 2.10 2.02 1.94 1-1/4 x 1 x 1-1/4 1.75 1.69 1.75 1.10 1-1/2 x 1-1/2 x 2 2.16 2.16 2.02 2.00 1-1/4 x 1-1/4 x 1/2 1.34 1.34 1.53 0.87 2 x 2 x 2-1/2 2.60 2.60 2.39 3.67 1-1/4 x 1-1/4 x 3/4 1.45 1.45 1.62 0.96 1-1/4 x 1-1/4 x 1 1.58 1.58 1.67 1.10 Ductile Iron Hex Reducin Cou lin 1-1/2 x 1/2 x 1-1/4 1.81 1.56 1.88 1.37 Fi re 35RC Size A Wgt 1-1/2 x 1/2 x 1-1/2 1.94 1.66 1.94 1.42 1 x 1/2 1.69 0.40 1-1/2 x 3/4 x 1-1/4 1.94 1.66 1.88 1.42 1 1 x 3/4 1.69 0.38 1-1/2 x 3/4 x 1-1/2 1.94 1.75 1.94 1.47 A 1-1/4 x 3/4 2.06 0.53 1-1/2 x 1 x 1/2 1.44 1.25 1.69 0.97 1 2 x 1(not hex) 2.81 0.53 1-1/2 x 1 x 3/4 1.50 1.44 1.75 1.14 1-1/2 x 1 x 1 1.65 1.50 1.80 1.14 1-1/2 x 1 x 1-1/4 1.82 1.67 1.88 1.47 Ductile Iron Cross &Reducin Cross 1-1/2 x 1 x 1-1/2 1.94 1.80 1.94 1.52 Fi re 35X Size A B Wgt 1-1/2 x 1-1/4 x 1/2 1.41 1.34 1.66 1.03 1 1.50 1.50 0.97 1-1/2 x 1-1/4 x 3/4 1.52 1.45 1.75 1.10 4 A �-�' � ' 1-1/4 1.75 1.75 1.59 1-1/2 x 1-1/4 x 1 1.65 1.58 1.80 1.31 , � 1-1/2 1.94 1.94 1.89 1-1/2 x 1-1/4 x 1-1/4 1.82 1.75 1.88 1.52 e 2 2.25 2.25 2.93 1-1/2 x 1-1/4 x 1-1/2 1.94 1.88 1.94 1.50 ; Figure 35RX 1-1/2 x 1-1/2 x 1/2 1.41 1.41 1.66 1.14 � Size A B Wgt 1-1/2 x 1-1/2 x 3/4 1.52 1.52 1.75 1.23 ' 1-1/4 x 1 1.67 1.58 1.25 1-1/2 x 1-1/2 x 1 1.65 1.65 1.80 1.38 1-1/2 x 1 1.80 1.65 1.48 1-1/2 x 1-1/2 x 1-1/4 1.82 1.82 1.88 1.50 2 x 1 2.02 1.73 2.64 2 x 1 x 2 2.25 2.02 2.25 2.18 2x1-1/4x2 2.25 2.10 2.25 2.31 Ductile Iron Plu s 2 x 1-1/2 x 1/2 1.49 1.41 1.88 1.50 Fi ure 35SP Size A Wgt 2 x 1-1/2 x 3/4 1.60 1.52 1.97 1.61 1/2 0.94 0.10 2 x 1-1/2 x 1 1.73 1.65 2.02 1.65 � 3/4 1.12 0.18 2 x 1-1/2 x 1-1/4 1.90 1.82 2.10 2.03 A 1 1.25 0.28 2 x 1-1/2 x 1-1/2 2.02 1.94 2.16 2.37 I 1-1/4 1.37 0.50 2 x 1-1/2 x 2 2.25 2.16 2.25 2.53 � 1-1/2 1.44 0.70 2 x 2 x 1/2 1.49 1.49 1.88 1.50 2 1.50 0.90 2 x 2 x 3/4 1.60 1.60 1.97 1.67 2 x 2 x 1 1.73 1.73 2.02 1.91 2 x 2 x 1-1/4 1.90 1.90 2.10 2.05 2x2x1-1/2 2.02 2.02 2.16 2.11 �,,�I ���°�I� � ���I���.� ��I � � � � � � � � � � � � � Cooplet° Weld Outlets *ISO 9002 MANUFACTURER *ASTM A106 C �L US �LISTED/APPROVED AT 300 PSI *ANSI B 1.20.1 F� *LISTED/APPROVED ON FLOW PIPE,THREADABLE THINWALL, ARRRfyVED LISTED SCH.10,SCH.40 (SEE COMPLETE LISTING ATTACHED) Female Threaded Coo let Fi ure 61FT � A i Size A Wgt/Ibs. Run Sizes Available 1/2 1.063 0.15 1"to 1-1/2", 2" to 2-1/2", 3"to 8" 3/4 1.125 0.20 1"to 1-1/2", 2" to 2-1/2", 2-1/2", 3"to 8" 1 1.250 0.25 1-1/4"to 1-1/2", 2"to 2-1/2", 2-1/2", 3"to 4", 5"to 8" 1-1/4 1.375 0.30 1-1/2", 2", 2-1/2", 3"to 4", 5"to 8" 1-1/2 1.625 0.55 2", 2-1/2", 3", 4"to 5", 6"to 8" 2 1.750 0.85 2-1/2", 3", 4"to 5", 6"to 8" 2-1/2 2.215 1.45 3", 4"to 5", 6", 8" 3 2.500 2.75 4"to 5", 6", 8" 4 3.000 4.20 6", 8" Sch.40 Cut Grooved Coo let Fi ure 62CG � A � Size A Wgt/Ibs. Run Sizes Available 1-1/4 3.00 0.65 1-1/2", 2", 2-1/2", 3", 4"to 5", 6", 8" 1-1/2 3.00 0.65 2", 2-1/2", 3", 4"to 5", 6", 8" 2 3.00 0.85 2-1/2", 3", 4"to 5", 6", 8" 2-1/2 3.00 1.50 3", 4"to 5", 6", 8" 3 3.00 1.90 4"to 5", 6", 8" 4 4.00 3.70 6", 8" 6 4.00 6.30 6", 8" 8 4.00 11.0 8" SIZE-ON-SIZE GROOVED OUTLETS AVAILABLE, NOT LISTED OR APPROVED ��� ����� � �������° I N T E R N A T I O N A L 2867 Vail Avenue, Commerce, CA 90040 Phone: 323-890-4455 Fax: 323-890-4456 SCI Cooplets are UL Listed, FM Approved for use on the following types of sprinkler pipe: Dyna-Threado steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. Central-Thread� steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. XL-II� steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. Dyna-Flow� steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. Super 40� steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. Super-Flo� steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. TL� steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. Central 7� steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. BLT� steel sprinkler pipe manufactured by Allied Tube and Conduit Corp. Eddylite� steel sprinkler pipe manufactured by Bull Moose Tube Co. Eddy Flowo steel sprinkler pipe manufactured by Bull Moose Tube Co. Eddy Thread 40o steel sprinkler pipe manufactured by Bull Moose Tube Co. EZ-Flow� steel sprinkler pipe manufactured by Northwest Pipe & Casing Co. WLSO steel sprinkler pipe manufactured by Wheatland Tube Company. Mega-Flowo steel sprinkler pipe manufactured by Wheatland Tube Company. MLT� steel sprinkler pipe manufactured by Wheatland Tube Company. Steady Flowo steel sprinkler pipe manufactured by AMS Tube Corp. Steady Thread0 steel sprinkler pipe manufactured by AMS Tube Corp. Fire-Floc� steel sprinkler pipe manufactured by Youngstown Tube Co. EZ-Thread� steel sprinkler pipe manufactured by Youngstown Tube Co. Fire Line Flow� steel sprinkler pipe manufactured by Western International Forest Products Inc. Rapid Thread� steel sprinkler pipe manufactured by Western International Forest Products Inc. Rapid-Threado steel sprinkler pipe manufactured by Western International Forest Products Inc. Tex-FlowO steel sprinkler pipe manufactured by Tex-Tube International Schedule 10 steel sprinkler pipe made by any manufacturer Schedule 40 steel sprinkler pipe made by any manufacturer MODF11011 U� � � � � FM I , —�� � � � TE�� :� � . �;� �� .,�,+� ' ..,,�.� _ , , �, n..�,..� s� ����` 39 y � �' y �; - � `� � � a�E� �K ��'�„ � �:� . . ..�� ;�.F�k w+'p ,-��;�,!„�r +� e?,i.�ce� ,'}°d. . ,r+�"�`o��{'�'�������^����'j��'3�+'r� USA PATENT AND OTHER PATENTS PENDING ❑ IT�eAGFManufacturing Inc.Mode11011 MatchesAll -fhe FeaturesAnd BenefitsOfOur Model 1000 by Providing Both l�he Test Function And lf�e Express Drain Function In A Multistory Installation,With lhe Added Feature OfAn Integral Model 7000 Pressure ReliefValve With Drainage Piping. ❑ Available In A Full Range Of9zesFrom 3/a"To 2", NPT& BSP1;With All Specifiable Orifice �zes3/s", �I16��, 1�2�� 17�32��,5�8�� ��0�,8c 3�4���E�R�. ❑ Zhe Model 1011 CompliesWith The RequirementsOfNFPA 13, 13R,& 13D,Which Stipulate A Pressure ReliefValve Be Installed On All Gridded 9�rstemsAnd Downstream OfAll Pressure Reducing Valves. ❑ li�e Mode11011 IsA �ngle Handle BaIIValvelYiatlsLightweightAnd Compact,Which Includes ATamperResistantTestOrifice, IntegralTamperResistant�ghtGlass,And Is300PSIRated. ❑ lhe Included UUFfVI Mode1 7000 Pressure ReliefValve FeaturesA Flushing Handle And IsFactory SetAt 175 PSI,OtherPressure SettingsAre Also Available. ❑ Designed To Relieve E�ccess9�rstem Pressure Caused By SurgesOrTemperature ChangesAs Well AsSolve Zhe Difficult Problem Of Providing The ReliefValve With A Drainage-Piping Outlet. ❑ The Unit ComesSiipped In A Semi-Assembled State With lhe ReliefValve And li�e By p a ss D ra i n Fb rts PI u g g e d.lFi i s I s D o n e To Ea se Pre ssu re Te sti n g li�e 9�r ste m. o�t pur New AutoC e�V� visit us '9p .� on the InTernet �'� G at �?i 8/01 MODEL 1011 � o �l FM , MOD�� .�: . �JL LISTED/FM APPROVED) BRONZE BALL VALVE MODEL 7000 (UL LISTED/FM APPROVED) PRESSURE RELIEF VALVE FACTORY SET AT 175 PSI WITH OTHER SETfINGS AVAILABLE. FRONT VIEW - MODEL 1011 PLAN VIEW � INLET A� � � A� t E� f � � B � I - 1 �� ♦ I IIDRAIN j �� �D' - � � � = 0 � � I TO DRAIN � _ � c � G �� � � , � I � From the February 1 , 1999 Edition of NFPA 13: Chapter 4-1.2 Requires ALL GRIDDED SYSTEMS be provided with a relief valves Chapter 5-14.1.2.3 Requires a relief valve be installed downstream of all pressure-reducing valves ORIFICE SIZESAVAILABLE -3ia, �hb, �i2, ��is2, E�ocsis)*, ESFR(3�4)* DIMENSIONS- INCHES OVERALL LENGTH �0�� ���� s�zE a B c o E F G H MATERIAL LIST 3�4�� 7 9�16� � 1�2 2 3�16� 3 5�8 3 3�8� � 13�16� 4 g�16� 6 g�s� 191.30mm 37.SSmm 55.65mm 9323mm 85.88mm 45.30mm 117.12mm 162.42mm PART: MATERIAL: '��� 7 9�16� � ��2� Z 3�16� 3 5�8� 3 3�8� � 13�16� 4 g�16� 6 3�si 191.30mm 37.58mm 55.65mm 93.23mm 85.88mm 45.30mm 117.12mm 162.42mm HANDLE STEEL ,� ��4� 7 15/16� � ���16� 2 9�16� 4 ��4 3 5�16� � 15�16� 'rJ g�1fi� �j �/2' STEM RODBRASS 201mm 42.70mm 65.36mm 108.36mm 82.84mm 50.89mm 141.39mm 19228mm BALL C.P.BRONZE BODY BRONZE 1 �� �� 8 15�16� � 13�16� 3 ��4� 'rJ ��16� 3 ��8� 2 5�8� H ��4� �� ��8� VALVE SEAT IMPREGNATED TEFLON 2 226.68mm 45.50mm 81.50mm 127mm 99.18mm 66.97mm 206.63mm 273.60mm INDICATOR PLATE STEEL 2n H 15�16� � 13�16� 3 ��4� 'rJ ��16� 3 ��8� 2 5�8� H ��4� �� ��8� BYPASSFITfINGS BROSZE 226.68mm 45.50mm 81.50mm 127mm 99.18mm 66.97mm 206.63mm 273.60mm gYPASSTUBING NYLOBRAID 'Available on 1 �/a"to 2"size unitsonly. USA PATENT AND OTHER PATENTS PENDING `' ' � ��'' ' . UL LISTING EX4019(N)&EX4533(NJ AGFMANUFACIURING COMPANY JOB NAME: 100 Qua ker La ne ARCH ITECT: Malvern,PA 19355 USA Telephone:(610)240-4900 ENGINEER: Fax:(610)240-4906 www.testandrain.com MAOE�N�.s.A. CONTRACTOR: ES-A-4000SS . � Ser�es 4000SS A M E S Reduced Pressure Zone Assemblies FIRE&WATERWORKS& Sizes: 2'/�" — 10" (65 —250mm) 3 i � � 4000SS OSY Features �#� • Stainless steel construction provides long `" � term corrosion resistance and maximum strength • Stainlesssteelbodyishalftheweightofcom- - " petitive designs reducing installation&ship- ping costs • Short end-to-end dimensions makes retrofit easy • Cam-check assembly provides maximum flow at low pressure drop • No special tools required for servicing Series4000SSReducedPressureZoneAssembliesaredesignedtoprovideprotectionofthepota- • Compact construction allows for smaller blewatersupplyinaccordancewithnationalcodes.Thisseriescanbeusedwhereapprovedbythe enclosures local authority having jurisdiction on health hazard cross connections. • Stainlesssteelreliefvalvefeaturesabalanced Series4000SSfeaturesshortlaylength,lightweightstainlesssteelbody,corrosiveresistantstainless rollingdiaphragmtoeliminateslidingsealsand steel relief valve,and patented cam-check assembly. lower maintenance costs Available Models Specifications AReduced PressureZoneAssemblyshall be installed ateach cross-connectionto prevent backsi- Suffix: phonageandbackpressureofhazardousmaterialsintothepotablewatersupply.Theassemblyshall NRS- non-rising stem resilient seated consist of a pressure differential relief valve located in a zone between two positive seating cam- gate valves checkassemblies.Themainvalvebodyshallbemanufacturedfrom300Seriesstainlesssteelforcor- OSY- UUFM outside stem and yoke resilient rosionresistance.Thecam-checkassemblyshallbeofthermoplasticconstructionwithstainlesssteel seated gate valves "OSYFxG- flanged inlet gate connection and hingepins,camarm,andcambearing.Thecam-checkassemblyshallutilizeasingletorsionspring grooved outlet gate connection designtominimizepressuredropthroughtheassembly.Thecam-checkassemblyshallbemodular "OSY GxF-grooved inlet gate connection and andshallsealtothemainvalvebodybytheuseofan0-ring.Thereshallbenobrassorbronzeparts flanged outlet gate connection usedwithinthecheckassemblyorreliefvalve.Theuseofseatscrewstoretainthecheckvalveseat "OSY GxG- grooved inlet gate connection and is prohibited.All internal parts shall be accessible through a single cover on the valve assembly grooved outlet gate connection securely held in place by atwo-bolt grooved coupling.The differential relief valve shall be of stain- LG- less gates less steel construction and shall utilize a rolling diaphragm and no sliding seals.The relief valve Available with grooved NRS gate valves-consult shall be bottom mounted and supplied with a steel reinforced sensing hose.The assembly shall factory"' includetworesilientseatedshutoffvalves&fourballtypetestcocks.Theassemb�yshallbeanAmes Post indicator plate and operating nut available- Company Series 4000SS. consult factory" �`Consult factory for dimensions Standards Note:Theinstallationofadrainlineisrecommended. AWWAC511-92 When installing a drain line,an air gap is necessary. The4000SSshouldbeinstalledwithaminimumclear- AppY'OVa1S ance of 12" between lowest point of the assembly and the floor drain or grade. �°"SS�F,``o Note:When installing a drain line on Series 'The wetted surface of this product contacted by A55E s P� FM � UL us 4000SS backflow preventer,use air gap. consumablewatercontainslessthanonequarterof c us APProved one percent(0.25%)of lead by weight. iols B64.5 sizes 2Yz��-io��, OSY OSY only See Literature ES-A-AG/EUTC for atlditional oniy information. �ob Name Vail Library Remodel Contractor Central Fire Protection Contractors Job Location Approval Engineer Contractor's P.O. No. Approval Representative Ames product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Ames Technical Service. Ames reserves the right to change or modify product design, construction, specifications, or materials without prior notice antl without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Materials Pressure — Temperature All internal metal parts:300 Series stainless steel Temperature Range:33°F-110°F(5°C-43°C) Main valve body:300 Series stainless steel Maximum Working Pressure:175psi(12.06 bar) Check assembly:Noryl° Flange dimension in accordance with AWWA Class D 6"(150mm) kPa psi * 145 21 ** Capaci� y 124 18 Series4000SSperformanceasestablishedbyanindependenttestinglabo- � �03 15 ratory(1996 UL). UL certified flow characteristics. y $3 �z Documented flow characteristics(including shutoff valves). � 41 6 "UL Rated ""UL Tested 2� 3 0 250 500 750 1000 1250 1500 gpm 0 950 1900 2850 3800 4750 57001pm kPa p � ZYz"(65mm) Flow Rate si * 145 21 ** kPa psi 8��(200mm) 124 18 * ** y 138 20 ..°,103 15 124 18 y $3 12 � 110 16 ` 62 9 °f 96 14 5 � 41 6 ; 83 12 21 3 � 69 10 0 100 200 300 400 500 600 gpm 0 380 760 1140 1520 1900 22801pm 55 8 Flow Rate 0 400 800 1200 1600 2000 2400 gpm 0 1520 3040 4560 6080 7600 91201pm 3"(80mm) Flow Rate kPa psi * ** 145 21 kPa ps� 1�°(250mm) 124 18 �t ** �103 15 138 20 124 18 � 83 12 0 110 16 d 62 9 d 96 14 � 41 6 y 83 12 21 g a 69 10 0 100 200 300 400 500 600 gpm 55 $0 500 1000 1500 2000 2500 3000 gpm 0 380 760 1140 1520 1900 22801pm Flow Rate 0 1900 3800 5700 7600 9500 114001pm Flow Rate kPa psj 4°(100mm) 145 21 ** * y 124 18 ' �103 15 G I _ --°_�-- c� C(open) � 83 12 � = d 62 9 ` � 41 6 21 3 0 100 200 300 400 500 600 700 gpm � 0 380 760 1140 1520 1900 2280 26601pm Flow Rate ----------- ------- L---------- . . ---------------------------- A ----------------------- Dimensions — Weig tS Note: Strainer sold separately � � A C(OSY) C�NRS) D F L w/Gates wPo Gates f in. mm in. mm in. mm in. mm in mm in. mm in. mm Ib. kg. Ib. kq. o � o 0 0 2Yz 65 37 940 163/a 416 93/s 238 10'/z 267 7 178 22 559 148 67 60 27 d'� a� 3 80 38 965 18'/e 479 10'/a 260 10Yz 267 7Yz 191 22 559 226 103 62 28 �a�� °� 4 100 40 1016 223/a 578 123hs 310 10'/z 267 9 229 22 559 235 107 65 30 ° ° '� 6 150 48'h 1232 30'/s 765 16 406 11 Y2 292 11 279 27Yz 699 380 172 110 50 8 200 52Yz 1334 373/a 959 19'S/is 506 12Yz 318 13Yz 343 29'h 749 571 259 179 81 10 250 55'/z 1410 453/a 1162 2313/ie 605 12'/z 318 16 406 29'h 749 773 351 189 86 F Noryl°is a registered trademark of General Electric Company � IMPORTANT:Inquire with governing authorities for local installation requirements. �,�� A M E S ��V% • 9001-2008 F,RE&W,,TERWORKSP' www.amesfi rewater.com c e R r�F�e o A Watts Water Technologies Company USA: Backflow- Sacramento,CA•Tel.(916)928 0123•Fax(916)928 9333 Control Valves- Houston,TX•Tel.(713)943-0688•Fax(713)944-9445 Canada: Burlington,ON•Tel.(905)332-4090•Fax(905)332-7068 ES-A-4000SS 1114 �O 2011 Ames Fire&Waterworks tyco Fire & Building Products Technical Services: Tel: (800)381-9312/Fax: (800)791-5500 Model PRV-1 Pressure Reducing Valve 2 thru 8 Inch (DN50 fhru DN200), 250 psi (17,2 bar) Pilot Operated, Globe and Angle Body Styles General .�y,� Description � � � ��� �� �. � � �� �'�. �� ���'. The Tyco� 2 thru 8 inch (DN50 thru �� � '�. ���.' . ,,._. `�`?� i DN200) Model PRV-1 Pressure Re- '' � ,� ° :, . . � �' P ducing Valves are factory assembled �a � ,' F ' and fully trimmed valve arrangements � � ;� � � �, ' for pressure control. They are used on '�` ��; S,�.- �'+ � .�`'� � water filled pipe where it is necessary �� a�� �+ ` '?; to reduce a higher inlet pressure to .;�-� � a lower delivery pressure under static `-'�' ` and/or residual flowing conditions.The � PRV-1 is intended to automatically ��*'- I. �, maintain the outlet "set pressure" ' �" �� �j (static and residual) within a close "-� �+' range, regardless of fluctuations in the higher pressure inlet line or varying flow rates. The PRV-1 is provided with a factory NORTH AMERICA outlet "set pressure" of 125 psi (8,6 Available Body Styles, End Connections&Sizes bar); however it may be field set to a nominal outlet "set pressure" of 80 to Nominal Valve Size 225 psi (5,5 to 15,5 bar) per its FM BOdy End Connection Approval or 80 to 150 psi (5,5 to 10,3 Style 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch bar) per its UL Listing. (DNSO) (DN80) (DN1o0) (DN150) (DN200) Thread x Thread � N/A N/A N/A N/A Typical applications are as follows: �ioae Groove x Groove � • • � N/A I i Within the main header(Ref. Figure Flange x Flange N/a N/a • • • 1) supplying wet pipe, dry pipe, del- uge, or preaction system risers, � =Available N/A=NotAvailable and/or a standpipe system supply- ing hose connections. SOUTH AMERICA, CENTRAL AMERICA&EASTERN HEMISPHERE i i As part of a sectional floor control Available Body Styles, End Connections&Sizes assembly (Ref. Figure 2) supplying sprinkler systems, and/or hose sta- Nominai vaive size tions. Style End Connection 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch FeStUPeS 81'e 85 fOIIOWS: (DN50) (DN80) (DN100) (DN150) (DN200) I I C8f1 be IIlSt811ed Ill afly OflefltatlOfl. Thread x Thread � � N/A N/A N/A i I Eliminates any required bleeding of Globe Groove x Groove • • • • N/A trapped air from the diaphragm chamber during installation. Fiange x Fian9e N/A • • • • � �Globe or angle pattern. Tnread x Tnread • • N/A N/A N/A i i Accurate pressure control. An9ie Groove x Groove • • • • N/A � �Standard nylon coated internal and eXternal. Flange x Flange N/A � � � N/A (continued) � =Available N/A=Not Available Page 1 of 16 NOVEMBER, 2007 TFP1580 Page 2 of 16 TFP1580 i�One piece, one moving part dia- WET PIPE DRY PIPE phl"2g1T1. SPRINKLER SPRINKLER RISER RISER ❑ In-line service. MAIN MAIN I I One pilot valve sub-assembly pro- �RAiN vides for any outlet "set pressure", DRAIN i.e., 80 to 225 psi (5,5 to 15,5 bar). MAIN CONTROL WARNING PRV-1 VALVE RELIEF CO TIROL HOSE The Model PRV-1 Pressure Reducing MAIN \ — VALVE VALVE STATIONS Valves described herein must be in- HEADER stalled and maintained in compliance with this document, as well as with the applicable standards of the National PRV-1 Fire Protection Association,in addition to the standards of any other authori- ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- F/GURE 1 ing their fire protection system and de- TYPICAL MAIN HEADER APPLICATION vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Due to the flow regulating charac- teristic of this device, its impact on system hydraulics should be carefully considered, especially when retrofit- ted into existing systems. ������ ���� ����,�.� �� Downstream pressure adjustment RELIEF VALVE is only to be performed by experi- enced personnel who understand the impact of adjusting the down- ~ stream pressure and who take full PRV-1 responsibility of the readjustment � SPRINKLERS from the factory setting. The Pilot SECTIONAL � Valve is provided with a Tamper Cap, CHECK which upon removal for purposes of FLOOR I vA�vE RISER downstream adjustment will provide CONTROL SECTIONAL MANIFOLD an indication that the PRV-1 may have HOSE CONTROL OR been altered from its factory setting. VALVE VALVE ZONE " CHECK ���, � ��� RELIEF VALVE ~ Z PRV-1 SPRINKLERS SECTIONAL CHECK FLOOR i va�vE CONTROL SECTIONAL HOSE CONTROL VALVE VALVE ��� �, FIGURE 2 TYP/CAL SECTIONAL FLOOR CONTROL APPUCAT/ON TFP1580 Page 3 of 16 VALVE PARTS � DIAPHRAGM OUTLET CHAMBER NO. DESCRIPTION QTY. Refer to Kit PRESSURE 3 1 Valve Body ........... 1 NR GAUGE �' 2 2 Diaphragm ........... 1 (a) ° / 3 Handhole Cover ....... 1 NR 4,5,6 4 Flat Washer, 2 Inch Valve,M12 ......4 CH � 3&4 Inch Valves,M16 ..4 CH � 6&8 Inch Valves,M16 ..8 CH $ � � 5 Hex Bolt, i �8 2 Inch Valve,M12 x 35 ..4 CH y 3&A Inch Valves, � M16x55 .............4 CH 11� �/' / 6 Inch Valve,M16 x 45 ..8 CH 8 Inch Valve,M16 x 55 ..8 CH ___ __ INLET 6 Hex Nut,M16, DOWNSTREAM PRESSURE 4 Inch Valve Only.......4 CH OUTLET CAVITY— GAUGE 7 Pilot Valve ............ 1 (b) � 8 Water Pressure Gauge ..2 (c) 9 Strainer .............. 1 (d) PRESSURE UPSTREAM 10 Pressure Sensor Insert .. 1 (e) SENSOR INSERT L� �--� 11 Tubing and Fittings ..... 1 (f) (SEE DETAIL) INLET CAVITY REPLACEMENT PARTS NO. DESCRIPTION P/N STRAINER � (a) Diaphragm, (SEE DETAIL) � Fits Either Body Style, Includes Item 2 only: GLOBE BODY STYLE 2 Inch Valves ............. 92-570-2-011 3 Inch Valves ............. 92-570-2-012 INTERIOR INTERIOR 4 Inch Valves ............. 92-570-2-013 6 Inch Valves ............. 92-570-2-014 OF OUTLET VALVE OF INLET VALVE 8 Inch Valves ............. 92-570-2-015 SENSOR CAVITY gODY CAVITY gODY (b) PilotValve ............... 92-570-2-200 INLETFACES � ` (c) Water Pressure Gauge ..... 92-570-2-201 TO TO (d) Strainer: DOWNSTREAM TRIM TRIM 2,3,&4 Inch Valves ....... 92-570-2-202 � 6&8 Inch Valves.......... 92-570-2-209 10 9 (e) Pressure Sensorinsert: 2 Inch Valve.............. 92-570-2-203 PRESSURE SENSOR STRAINER 3 Inch Valve.............. 92-570-2-204 INSERT DETAIL DETAIL 4 Inch Valve.............. 92-570-2-205 6 Inch Valve.............. 92-570-2-206 8 Inch Valve.............. 92-570-2-207 OUTLET DIAPHRAGM (f) Tubing and Fitting Kit, PRESSURE 7 CHAMBER Excludes Items 7,8,9,and 10 GAUGE � Globe Style Valve: � 2 Inch Valve.............. 92-570-3-001 ° 3 3 Inch Valve.............. 92-570-3-002 2 4 Inch Valve.............. 92-570-3-003 6 Inch Valve.............. 92-570-3-004 8 Inch Valve.............. 92-570-3-005 1 � 4,5,6 Angle Style Valve: $ � 2 Inch Valve.............. 92-571-3-001 3 Inch Valve.............. 92-571-3-002 � i 4 Inch Valve.............. 92-571-3-003 6 Inch Valve.... ..... 92-571-3-004 11� �/' / � 8 NOTES: 1. NR-Not Replaceable DOWNSTREAM �� INLET 2. CH-Common Hardware OUTLET CAVITY PRESSURE GAUGE PRESSURE L� SENSORINSERT DOWNSTREAM DOWNSTREAM (SEE DETA�L) � � OUTLET FLOW OUTLET FLOW � � � DIAPHRAGM � � � � � O 0 O O TAB IS ORIENTED i � 0 0 � PERPENDICULAR TO \ O 0 O O OUTLET FLOW STRAINER UPSTREAM (SEE DETAIL) INLET CAVITY GLOBE ANGLE ANGLE BODY STYLE FIGURE 3 MODEL PRV-1 PRESSURE REDUC/NG VALVE —ASSEMBLY— Page 4 of 16 TFP1580 Te c h n i c a 1 Factory Outlet "Set Pressure": End Connections: 125 psi (8,6 bar) Threaded end connections are avail- Da ta Field Outlet"Set Pressure" Range: able NPT threaded or threaded per ISO 7/1. Flanged end connections Approvals: 80 to 225 psi (5,5 to 15,5 bar)per its are available drilled per Table A. FM Approval, or 80 to 150 psi (5,5 to Grooved end connections are per in- UL Listed. FM Approved. 10,3 bar) per its UL Listing dustry standard groove specifica- The UL Listing is based on Pressure Loss With Inlet Pressure tions. I:I Installation requirements refer- Above "Set Pressure" Construction (Ref. Figure 3): enced in the Standard for Installa- The inlet pressure minus the outlet Body. Rilsan* blue coated ductile tion of Sprinkler Systems, NFPA "set pressure" equals pressure loss. iron per ASTM A536-77, Grade 65- 13, or the Standard for Installation For example:assumimg that the inlet 45-12. of Standpipe and Hose Valves, flowing pressure is 225 psi(15,5 bar) Handhole Cover. Rilsan* blue NFPA 14, as applicable. and the field outlet "set pressure" is coated ductile iron per ASTM A536- ❑ Inspection, testing, and mainte- 130 psi (9,0 bar), the pressure loss 77, Grade 65-45-12. nance requirements referenced in is 95 psi (6,5 bar). the Standard for Inspection, Test- Pressure Loss with Inlet Pressure Diaphragm. Nylon fabric reinforced, ing, and Maintenance of Water- Below "Set Pressure" natural rubber per ASTM D2000. Based Fire Protection Systems, Refer to Graphs A thru E. (These Diaphragm Cover Fasteners. Gal- NFPA 25. vanized carbon steel. graphs are a requirement of UL and I-I The Model PRV-1 being field setto should be used as reference only.) Pilot Valve. Brass and stainless provide the required outlet pres- steel with nylon fabric reinforced, sures and flows for the given appli- Rated Flowing Range: natural rubber per ASTM D2000 dia- cation. 2 inch (DN50): 0 to 250 GPM phragm. ❑The Model PRV-1 being tested af- �0 to 946 LPM) Strainer. Brass and stainless steel. ter installation in accordance with 3 inch (DN80): 0 to 550 GPM pressure Gauges. 2-1/2 inch (65 NFPA 13 and/or NFPA 14 as appli- (0 to 2080 LPM) cable. mm) diameter, stainless steel case, 4 inch (DN100): 0 to 1000 GPM 0 to 350 psi (25 bar). I I The Model PRV-1 being tested pe- (0 to 3785 LPM) Tube, Fittings, and Needle Valve. riodically thereafter in accordance 6 inch (DN150): 0 to 2200 GPM Copper, brass, and stainless steel. with NFPA 25. (0 to 8325 LPM) �Rilsan is a registered trademark of Maximum Inlet Pressure: 8 inch (DN200): 0 to 4000 GPM ATOFINA Chemicals, Inc. (The Ril- 250 psi (17,2 bar) (0 to 15140 LPM) san coating is a polyamide (Nylon 11)coating.) Flange Drilling Specification Nominal Dimensions in Inches and(mm) Nominal ANSI B16.1 ' ISO 7005-2 ISO 7005-2 JIS B 2210 AS 2129 Valve (Class 125) (PN10)Z (PN16)3 (10K) (Table E) Size Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. A B N A B N A B N A B N A B N 31nch 6.00 0.75 4 6.30 0.75 $ 5.90 0.59 $ 5.75 0.71 4 (DN80) (152,4) I (19,0) (160,0) (19,0) (150,0) (15,0) (146,0) (18,0) 41nch 7.50 0.75 $ ISO 005-2 �•09 0.75 $ 6.89 0.59 8 7.00 � 0.71 $ (DN100) (190,5) (19,0) (PN16) (180,0) (19,0) (175,0) (15,0) (178,0) (18,0) 61nch 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87 (DN150) (241,3) (22,2) $ (240,0) (23,0) $ (240,0) (19,0) $ (235,0) (22,0) $ 8 Inch 11.75 0.88 $ 11.61 0.91 $ 11.61 0.91 �2 11.42 0.75 �2 11.50 0.87 $ (DN200) (298,5) (22,2) (295,0) (23,0) (295,0) (23,0) (290,0) (19,0) (292,0) (22,0) 'Same drilling as forANSI 616.5(Class 150)and ANSI B16.42(Class 150). Dim.A Qty.N 2 Same drilling as for BS 4504 Section 3.2(PN10)and DIN 2532(PN10). Bolt Circle—� � Number of 3 Same drilling as for BS 4504 Section 3.2(PN16)and DIN 2532(PN16). Diameter ��� Bolt Holes �o—o� Dim.B ''��� � BoIY Hole����� Diameter �—� TABLE A DIMENS/ONAL SPECIFICAT/ON FOR SELECTION OF FLANGE DRILLING TFP1580 Page 5 of 16 TAMPER ADJUSTING CAP � SCREW OUTLET PRESSURE = LOCKNUT GAUGE P I LOT -� VALVE NEEDLE VALVE C� � (FACTORY SET, � REGULATING DIAPHRAGM DO NOT READJUST) � � SPRING CHAMBER ♦ EXIT FLOW SUPPLY LINE � � � INLET PRESSURE PILOT � � GAUGE VALVE SYSTEM SEAT WATER SUPPLY C� PRESSURE OUTLET CAVITY � INLET CAVITY ♦ SENSWG � LIN E \ II INTERIOR � INTERIOR VALVE OF OUTLET / � VALVE OF INLET BODY CAVITY SENSOR BODY CAVITY � � INLET FACES PRV-1 PRV-1 � i " UPSTREAM DIAPHRAGM SEAT / TO � TO TRIM PRESSURE TRIM STRAINER SENSORINSERT FIGURE 4 MODEL PRV-1 PRESSURE REDUCING VALVE —OPERAT/ON— low the "set pressure" of the spring, I I As the flow demand continues down- O p e ra t i o n exit flow from the Diaphragm Chamber stream of the PRV-1 and the "set through the Pilot Valve to the PRV-1 pressure" is met, the Pilot Valve With reference to Figure 4,the system outlet cavity resumes and pressure in Seat closes.As the Pilot Valve Seat water supply pressure from the inlet the Diaphragm Chamber decreases. closes to reduce the opening, pres- cavity of the PRV-1 enters the Dia- sure is trapped in the Diaphragm phragm Chamber through a Strainer The regulated flow through the Pilot Chamber at a point that allows the and Needle Valve. The factory set Valve decreases and increases the Diaphragm to remain lifted from the Needle Valve provides the required pressure in the diaphragm chamber to PRV-1 Seat to retain the down- orifice size for the supply line to the sufficiently open and close the PRV-1, stream "set pressure". Diaphragm Chamber to optimize per- as required, to regulate the down- formance. stream "set pressure". I_I Should the downstream pressure Exitflowfrom the Dia hra m Chamber The operation sequence is as follows: start to fall below the"set pressure", p g the Pilot Valve Seat re-opens to al- through the Pilot Valve is controlled by u When there is no flow demand low for a decrease in pressure in the a regulating spring that is factory set, downstream of the PRV-1, the Diaphragm Chamber to allow the and subsequently field adjustable, to PRV-1 Seat is closed and the Pilot PRV-1 to open further and then once the desired downstream"set pressure" Valve Seat is closed. With the Pilot again establish the downstream"set that is to be maintained.A sensing line Valve Seat closed, pressure is pressure". connects the outlet of the Pilot Valve trapped in the Diaphragm Chamber to the system piping downstream of to seat the Diaphragm and the [1 When the downstream pressure is at the PRV-1 via the Pressure Sensor PRV-1 remains closed. or above the "set pressure" and as- Insert in the outlet cavity. suming there is a flow demand �When there is a flow demand down- downstream of the PRV-1, the Pilot When the downstream pressure rises stream of the PRV-1 and the PRV-1 Valve Seat is closed to trap a suffi- above the"set pressure"of the spring, outlet pressure drops below the"set cient pressure in the Diaphragm exit flow from the Diaphragm Chamber pressure,the Pilot Valve Seat opens Chamber to allow the PRV-1 to re- through the Pilot Valve to the PRV-1 to relieve pressure from the Dia- main open to provide the "set pres- outlet cavity is stopped and pressure phragm Chamber allowing the sure". increases in the Diaphragm Chamber. PRV-1 to open. When downstream pressure falls be- Page 6 of 16 TFP1580 facilitate a flow test at the sprinkler or multiple hose valves, as required, Design system demand. will be necessary to simulate hose C o n s i d e ra t i o n s stream demand. For the purposes of the following in- The following items must be consid- struction, the opening of a "flow test ered and applied accordingly for an 1 nsta Ila tion valve" simulates either fhe sprinkler installation that will be using the Model demand or hose stream demand, as PRV-1 Pressure Reducing Valve: The Tyco�Model PRV-1 Pressure Re- applicable. The sprinkler demand or ducing Valve must be installed with the hose stream demand must be at least I I The PRV-1 may be installed verti- flow arrow located on the Diaphragm 50 GPM (190 LPM) for 2 to 6 inch cally or horizontally and in any orien- Cover pointing in the intended direc- (DN50 to DN150) valves and at least tation without affecting its operating tion offlow.Installation dimensions are 100 GPM (380 LPM) for 8 inch efficiency. When planning the posi- provided in Figures 5 and 6. (DN200) valves. tioning of the PRV-1, it is recom- mended that consideration be given Before the PRV-1 is installed, pipe There is no need to vent any trapped to the viewing of the pressure lines should be flushed of all chips, air from the Diaphragm Chamber. gauges. Consideration should also scale and foreign matter.Care must be Filling The System: be given to positioning the PRV-1 so exercised to assure that the trim is not that the diaphragm cover is facing damaged during installation. Do Not Step 1. Verify that downstream drain up.With the cover facing up,internal Lift The Valve By Its Trim. valves are closed and that there are no access is more easily achieved. leaks. NOTES Step 2.Partially open a valve or valves n The PRV-1 must be in an area that The inlet and outlet connections must at the end of the system (e.g., an in- is easily accessible for maintenance be made based on the direction offlow ur oses, not sub ect to freezin spector's test connection on a wet pipe p P 1 9 arrow provided on the handhole cover. system)to allow trapped air to escape temperatures, and not subject to The valve cannof operate if connected When filling the system. physical damage. backwards. Step 3. Slowly and partially open the I�The valve is designed for fresh water po not alter the trim. Altering the trim Water supply control valve feeding the service. When corrosive atmos- may render the valve ineffective and pRV-1. pheres and/or contaminated water impair the system operation. supplies are present, it is the Step 4. After the system fills with owner's responsibility to verify com- water, close the valve or valves that patibility with the pressure reducing had been partially opened in Step 2. valve, pilot valve, and trim. PI a C I rI g T h e Step 5. Completely open the main I I The difference between the water water supply control valve feeding the supply pressure and the desired out- V a 1 ve 1 n S e rvi c e PRV-1. let (downstream) pressure must be Downstream Pressure Adjustment: 25 psi (1,7 bar)or greater per its FM Steps 1 through 12 are to be per- Approval or 50 psi (3,4 bar) or formed when placing the Model PRV-1 Step 6. Remove the Tamper Cap from greater per its UL Listing.The differ- Pressure Reducing Valve in service. the Pilot Valve by first loosening its set ential maintains accuracy control of screw and then unscrewing the Tam- the discharging pressure over the WARNING per Cap. full rated flowing range. Downstream pressure adjustment is on/y to be performed by experi- Step 7. Open the "flow test valve" to i i Cavitation may occur when the inlet enced personnel who understand simulate either the desired sprinkler pressure is greater than twice the the impact of adjusting the down- demand or hose stream demand. "set pressure". For this case, the stream pressure and who take full pressure should be reduced in two responsibility of the readjustment NOTE steps by using two PRV-1's in se- from the factory setting. The Pilot �f surging flow occurs,attempt fo bleed ries. Valve is provided with a Tamper Cap, trapped air from the system via the which upon removal for purposes of inspector's test valve and any other I I When reducing pressure for a sprin- downstream adjustment will provide valve that can vent trapped air. kler system,a relief valve of not less than 1/2 inch (DN15)in size shall be an indication that the PRV-1 may have Step 8. Loosen the locknut on the ad- located downstream of the PRV-1. been altered from the factory setting. justing screw of the Pilot Valve. The relief valve shall be set at a Adjustment of the Needle Valve is Step 9. Turn the adjusting screw pressure equal to the lowest pres- factory set and must not be altered. clockwise to increase outlet pressure sure rated component downstream The Needle Valve is provided with a or counterclockwise to decrease outlet of the PRV-1. NOTE:FMApproval is tamper indication, which upon removal pressure. based on the use of the 1/2 inch, for purposes of any adjustment will Ste 10. After achievin the desired Watts Regulator, Series 530C Pres- provide an indication that the PRV-1 per ormance, tighten the locknut on sure Relief Valve. may have been altered from the fac- i i When reducing pressure for a sprin- tory setting. the adjusting screw. kler system, a listed indicating valve Step 11. Close the "flow test valve". shall be provided on the inlet side of NOTES Observe the outlet pressure gauge the PRV-1. Per the requirements of NFPA 13, a and compare to the required "set means shall be provided downstream pressure". If the required "set pres- I I When reducing pressure for a sprin- of the PRV-1 to simulate the sprinkler sure° is not achieved, repeat Step 8 kler system, means shall be pro- system demand. In the case of hose and proceed accordingly. vided downstream of the PRV-1 to stations, the opening of a hose valve TFP1580 Page 7 of 16 Step 12. Replace the Tamper Cap and first be obtained from the proper L im i t e d tighten its set screw. authorities and all personnel who may The pressure reducing valve is now be affected by this decision must be wa rra n ty set for service. notified. The Model PRV-1 Pressure Reducing products manufactured by Tyco Fire& NOTES Valve requires no lubrication, packing guilding Products (TFBP) are war- Due to the spring tolerance within the or preventative maintenance; how- ranted solely to the original Buyer for Pilot Valve, it may be necessary to ever, replacement of the diaphragm ten (10)years against defects in mate- alternate back and forth between re- every five years is recommended. rial and workmanship when paid for sidual and static conditions to achieve Flow Tests. Flow tests per NFPA are and properly installed and maintained the desired "set pressure"for both re- required every five years, at which under normal use and service. This sidual and static conditions. point the outlet pressure is compared warranty will expire ten (10) years After any downstream pressure ad- to previous tests. If necessary the from date of shipment by TFBP. No justment, fhe following items are to be PRV-1 can be readjusted following the warranty is given for products or com- recorded on a tag attached to the Placing The Valve In Service section. ponents manufactured by companies valve: If the desired pressure cannot be not affiliated by ownership with TFBP - Valve installation location achieved, the Diaphragm and/or Pilot or for products and components which Valve should be replaced. have been subject to misuse,improper -Inlet static pressure Diaphragm Replacement. Prior to re- installation, corrosion, or which have not been installed, maintained, modi- - Outlet static pressure placing the Diaphragm, the PRV-1 fied or repaired in accordance with ap- -Inlet residual pressure must be taken out of service and com- plicable Standards of the National Fire pletely drained. With reference to Fig- protection Association, and/or the - Outlet residual pressure ure 3, the Diaphragm Tab is oriented standards of any other Authorities -Intended outlet flow perpendicular to the outlet flow. When Having Jurisdiction. Materials found reinstalling the Diaphragm Cover, the by TFBP to be defective shall be either The tag is not to be removed until after Diaphragm Cover Fasteners must be repaired or replaced, at TFBP's sole the system has been accepted by the uniformly and securely tightened option. TFBP neither assumes, nor Authority Having Jurisdiction. It is rec- using a cross-draw sequence. After authorizes any person to assume for it, ommended that the tag not be re- tightening, double check to make cer- any other obligation in connection with moved even after acceptance by the tain that all of the Diaphragm Cover the sale of products or parts of prod- Authority Having Jurisdiction unless fasteners are securely tightened. ucts.TFBP shall not be responsible for another means of record keeping is pilot Valve Replacement. Prior to re- sprinkler system design errors or inac- maintained. moving the Pilot Valve, the PRV-1 curate or incomplete information sup- must be taken out of service and com- plied by Buyer or Buyer's repre- pletely drained.When installing the re- sentatives. placement Pilot Valve,the trim compo- In no event shall TFBP be liable, in nents must be replaced exactly as they contract, tort, strict liability or under Ca re a n d were. After reinstalling the Pilot Valve any other legal theory, for incidental, and before returning the PRV-1 into indirect,special or consequential dam- Ma i n t e n a n c e service, completely unscrew the Ad- ages, including but not limited to labor justing Stem of the replacement Pilot charges, regardless of whether TFBP Inspection, testing, and maintenance Valve so as to obtain a minimum outlet Was informed about the possibility of must be performed in accordance with "set pressure". Then proceed to use such damages, and in no event shall the requirements ofthe NFPA,and any the instructions under Placing The TFBP's liability exceed an amount impairment must be immediately cor- Valve In Service section to place the equal to the sales price. rected. PRV-1 in service. The foregoing warranty is made in lieu The owner is responsible for the in- NOTES of any and all other warranties. ex- spection, testing, and maintenance of The Pilot Valve is not field repairable. press or implied. including warranties their fire protection system and de- Attempting to repair the Pilot Valve of inerchantability and fitness for a a�r- vices in compliance with this docu- may render the valve ineffective and ticular purpose. ment, as well as with the applicable impair the system operation. standards of any authorities having ju- This limited warranty sets forth the ex- risdiction. The installing contractor or Completely unscrewing the Adjusting clusive remedy for claims based on product manufacturer should be con- Stem of the replacement Pilot Valve failure of or defect in products, materi- tacted relative to any questions. will help to avoid an accidental over als or components, whether the claim Automatic sprinkler systems should be Pressurization of the system piping is made in contract, tort, strict liability ins ected,tested,and maintained b a Prior to achieving the desired "set or any other legal theory. p y pressure". This warranty will apply to the full ex- qualified Inspection Service in accord- ance with local requirements and/or tent permitted by law.The invalidity, in national codes. whole or part, of any portion of this warranty will not affect the remainder. NOTE Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls,permission to shut down the affected fire protection systems must Page 8 of 16 TFP1580 Thread x Thread End Connections Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve Ibs. Sizes A B C D E F k 2" 7.51 1.49 7.32 6.41 8.18 2.36 15.2 (DN50) (191) (38) (186) (163) (208) (60) (6,9) 3" 11.14 1.77 8.19 7.48 9.25 3.93 30.6 DN80 283 45 208 190 235 100 13,9 i � Groove x Groove End Connections � � F Nominal Nominal Installation Dimensions in Inches and(mm) Weight � Valve Sizes A B C D E F Ibs. E k O I 2" 7.51 1.49 7.32 6.41 8.18 2.36 15.2 � (DN50) (191) (38) (186) (163) (208) (60) (6,9) 3" 11.14 1.77 8.19 7.48 9.25 3.93 30.6 � � � (DN80 283) 45 208 190 �235)__100 �13,9 4" 13.62 4.37 8.70 7.91 9.68 4.52 45.2 C (DN100) (346) (111) (221) (201) (246) (115) (20,5) � 6" 17.79 3.30 9.88 6.73 11.49 5.90 118.0 � DN150 452 84 251 171 292 150 53,5 G� � Flange x Flange End Connections g Nominal Nominal Installation Dimensions in Inches and(mm) Weight � A _ � Valve Ibs. Sizes A B C D E F k 3" 11.14 3.93 8.19 7.48 9.25 3.93 46.3 (DN80) (283) (100) (208) (190) (235) (100) (21,0) 4" 12.00 2.24 8.70 7.91 9.68 4.52 65.0 (DN100) (305) (57) 221 (201) (246) _(115) (29,5) 6" 15.98 5.59 9.88 6.73 11.49 5.90 118.0 (DN150) (406) (142) (251) (171) (292) (150) (53,5) 8" 18.50 6.69 11.14 7.16 12.55 6.96 166.5 DN200 470 170 283 182 319 177 75,5 FIGURE 5 MODEL PRV-1 PRESSURE REDUC/NG VALVE -GLOBE STYLE INSTALLATION DIMENSIONS- TFP1580 Page 9 of 16 Thread x Thread End Connections Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve Ibs. Sizes A B C D E F G k 2" 3.54 3.18 7.32 6.41 8.18 2.40 2.40 15.9 (DN50) (90) (81) (186) (163) (208) (61) (61) (7,2) 3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 34.1 DN80 154 115 208 190 235 100 100 15,5 Groove x Groove End Connections 1. � � F Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve Ibs. f Sizes A B C D E F G k E 2" 3.54 3.18 7.32 6.41 8.18 2.40 2.40 15.9 � � (DN50) (90) (81) (186) (163) (208) (61) (61) (7,2) 3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 34.1 (DN80) (154) (115) (208) (190) (235) (100) (100) (15,5) D � � �G 4" 6.33 4.56 8.70 7.91 9.68 4.52 4.52 44.0 C (DN100) (161) (116) (221) (201) (246) (115) (115) (19,9) _L 6" 8.89 6.69 9.88 6.73 11.49 5.90 5.90 89.3 DN150 226 170 251 171 292 150 150 40,5 � � Flange x Flange End Connections B Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve � Sizes A B C D E F G Ibs. � ��A k 3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 35.1 (DN80) (154) (115) (208) (190) (235) (100) (100) (15,9) 4" 6.33 4.56 8.70 7.91 9.68 4.52 4.52 67.3 (DN100) (161) (116) (221) (201) (246) (115) (115) (30,5) 6" 8.89 6.69 9.88 6.73 11.49 5.90 5.90 116.2 DN150 226 170 251 171 292 150 150 52,7 FIGURE 6 MODEL PRV-1 PRESSURE REDUCING VALVE -ANGLE STYLE INSTALLAT/ON DIMENS/ONS- Page 10 of 16 TFP1580 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=70 PSI INLET PRESSURE " B=50 PSI INLET PRESSURE v 120 z w 110 � � 100 C7 � 90 � w a 80 � Z 70 � � 60 A � z W 50 � _ � 40 B � � 30 � w 20 J � 10 O 0 0 25 50 75 100 125 150 175 200 225 250 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH A-1 2 INCH(DN50)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference on/y.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A= 140 PSI INLET PRESSURE �- B=100 PSI INLET PRESSURE v 120 A C=50 PSI INLET PRESSURE z W 110 � - — – � 100 c� � 90 B � w a 80 � Z 70 � a 60 z w 50 � � 40 cn C � 30 a w 20 J � 10 O 0 0 25 50 75 100 125 150 175 200 225 250 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH A-2 2 INCH(DN50)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) TFP1580 Page 11 of 16 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=70 PSI INLET PRESSURE -- B=50 PSI INLET PRESSURE U 120 z W 110 � � 100 c� � 90 � w a 80 � Z 70 � a 60 z A W 50 � _ — � 40 v� — B — — � 30 a W 20 J � 10 O 0 0 50 100 150 200 250 300 350 400 450 500 550 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH B-1 3 INCH(DN80)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference on/y.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=140 PSI INLET PRESSURE B= 100 PSI INLET PRESSURE V �2� A C=50 PSI INLET PRESSURE z W 110 � � 100 C7 � 90 g � w d 80 � z 70 � a 60 z w 50 � � 40 � C � 30 a W 20 � � 10 O 0 0 50 100 150 200 250 300 350 400 450 500 550 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH B-2 3 INCH(DN80)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) Page 12 of 16 TFP1580 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=70 PSI INLET PRESSURE -- B=50 PSI INLET PRESSURE U 120 z W 110 � � 100 c� � 90 � w a 80 � z �� � � 60 A a z W 50 � � 40 g � � � 30 a W 20 J � 10 O 0 0 100 200 300 400 500 600 700 800 900 1000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH C-1 4/NCH(DN100)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference on/y.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A V 120 z W ��p A=140 PSI INLET PRESSURE � B= 100 PSI INLET PRESSURE � 100 C=50 PSI INLET PRESSURE C7 B � 90 � w d 80 � z 70 � a 60 z w 50 � 40 C � � 30 a W 20 � � 10 O 0 0 100 200 300 400 500 600 700 800 900 1000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH G2 4/NCH(DN100)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) TFP1580 Page 13 of 16 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=70 PSI INLET PRESSURE -- B=50 PSI INLET PRESSURE U 120 z W 110 � � 100 c� � 90 � w a 80 � z �� � a 60 z A W 50 � . — � 40 � B � 30 a W 20 J � 10 O 0 0 250 500 750 1000 1250 1500 1750 2000 2250 2500 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH D-1 6/NCH(DN150)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference on/y.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=140 PSI INLET PRESSURE B= 100 PSI INLET PRESSURE V �2� A C=50 PSI INLET PRESSURE z W 110 � � 100 C7 � 90 B � w d 80 � z 70 � a 60 z w 50 � � 40 � C � 30 a W 20 � � 10 O 0 0 250 500 750 1000 1250 1500 1750 2000 2250 2500 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH D-2 6/NCH(DN150)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) Page 14 of 16 TFP1580 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A=70 PSI INLET PRESSURE -- B=50 PSI INLET PRESSURE U 120 z W 110 � � 100 c� � 90 � w a 80 � Z 70 � A a 60 z W 50 � — ---. _ — � 40 B � � 30 a W 20 J � 10 O 0 0 500 1000 1500 2000 2500 3000 3500 4000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH E-1 8/NCH(DN200)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI (This graph is a requirement of UL and should be used as reference on/y.) 1 PSI=0,06895 BAR 1 GPM=3,785 LPM 140 a 130 A A=140 PSI INLET PRESSURE -- B= 100 PSI INLET PRESSURE V �2� C=50 PSI INLET PRESSURE z W 110 � � 100 C7 � 90 B � w d 80 � z 70 � a 60 z w 50 � � 40 C � � 30 a W 20 � � 10 O 0 0 500 1000 1500 2000 2500 3000 3500 4000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH E-2 8/NCH(DN200)PRESSURE REDUC/NG VALVE OUTLET PRESSURE VERSES FLOW SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI (This graph is a requirement of UL and should be used as reference only.) TFP1580 Page 15 of 16 Ordering Ordering Procedure Procedure North America South America, Pressure Reducing Valve: CenfCa�A117@CICa 8c Specify: Globe Type, (specify size), 125 psi Outlet "Set Pressure"with(T Ea s te rn H e m is h e re x T, G x G, or F x F) Connection, P/N p (specify from below). Pressure Reducing Valve: P/N's for GLOBE BODY STYLE Specify: (Globe or Angle)Type, (spec- AVAILABLE IN AMERICAS ify size), 125 psi Outlet"Set Pressure" with (specify) Connection (and for 2 Inch T x T flanged valves specify flange drilling), NPT................ P/N 52-570-5-060 P�N (specify from complete listing on 2 Inch G x G Page 16). 2.37 inch(60,3 mm) Groove O.D........... P/N 52-570-8-920 f I VaIV2 Typ2 & SIZ@ (Globe, 2, 3, 4, 6, or 8 Inch) 3 Inch G x G (Angle, 2, 3, 4, or 6 Inch 3.50 inch(88,9 mm) Groove O.D.. ........ P/N 52-570-8-922 I I 125 psi Outlet"Set Pressure" Pressure 4 Inch G x G [1 Connection Type 4.50 inch(114,3 mm) Groove O.D. ......... P/N 52-570-8-923 (Threaded, Grooved, Flanged) 4 Inch F x F For threaded, specify NPT or ISO ANSI Flange......... P/N 52-570-8-023 6 Inch G x G For grooved, specify O.D. Pipe Size s.s2�r,cn��ss,s mm) -2 inch (DN50): Groove O.D. ......... P/N 52-570-8-925 2.gg inch (60,3 mm) O.D. 6 Inch F x F ANSI Flange. ........ P/N 52-570-8-025 - 3 IIICh �DN80�: 8 Inch F x F 3.50 inch (88,9 mm) O.D. ANSI Flange......... P/N 52-570-8-026 -4 IIICh ��N����: Pressure Relief Valve: 4.50 inch (114,3 mm) O.D. Specify: 1/2 inch (DN15)Watts Regu- -6 inch (DN150): lator, Series 530C Pressure Relief 6.62 inch (168,3 mm) O.D. or Valve for use downstream of a PRV-1 6.50 inch (165,1 mm) O.D. being used for reducing pressure in _g inch (DN200): sprinkler system, P/N 92-570-2-208. g.62 inch (219,1 mm) O.D. Replacement Valve Parts: For flanged, specify flange drilling Specify: (description) for use with per (specify) size Model PRV-1 Pressure Reducing Valve, P/N (see Figure 3). -ANSI B16-1 (Class 125) - ISO 7005-2 (PN16) - ISO 7005-2 (PN10), 8 inch valve only -JIS 62210 (10K) -AS 2129 (Table E) NOTES Refer to Table A for flange drilling di- mensional specifications. Pressure Relief Valve: Specify: 1/2 inch (DN15)Watts Regu- lator, Series 530C Pressure Relief Valve for use downstream of a PRV-1 being used for reducing pressure in sprinkler system, P/N 92-570-2-208. Replacement Valve Parts: Specify: (description) for use with (specify) size Model PRV-1 Pressure Reducing Valve, P/N (see Figure 3). Page 16 of 16 TFP1580 P/N's for GLOBE BODY STYLE P/N's for ANGLE BODY STYLE 21nchTxT 21nchTxT NPT................ P/N 52-570-8-060 NPT................ P/N 52-571-8-060 21nchTxT 21nchTxT ISO ................ P/N 52-570-8-160 ISO................ P/N 52-571-8-160 21nchGxG 21nchGxG 2.37 inch(60,3 mm) 2.37 inch(60,3 mm) Groove O.D........... P/N 52-570-8-920 Groove O.D.. ........ P/N 52-571-8-920 31nchTxT 31nchTxT NPT................ P/N 52-570-8-062 NPT................ P/N 52-571-8-062 31nchTxT 31nchTxT ISO ................ P/N 52-570-8-162 ISO................ P/N 52-571-8-162 31nchGxG 31nchGxG 3.50 inch(88,9 mm) 3.50 inch(88,9 mm) Groove O.D.. ........ P/N 52-570-8-922 Groove O.D.......... P/N 52-571-8-922 3 Inch F x F 3 Inch F x F ANSI Flange......... P/N 52-570-8-022 ANSI Flange......... P/N 52-571-5-022 3 Inch F x F 3 Inch F x F ISO(PN16)Flange.... P/N 52-570-8-112 ISO(PN16)Flange ... P/N 52-571-8-112 31nchFxF 31nchFxF JIS Flange........... P/N 52-570-8-722 JIS Flange .......... P/N 52-571-8-722 3 Inch F x F 3 Inch F x F AS Flange........... P/N 52-570-8-522 AS Flange........... P/N 52-571-8-522 41nchGxG 41nchGxG 4.50 inch(114,3 mm) 4.50 inch(114,3 mm) Groove O.D. ......... P/N 52-570-8-923 Groove O.D. ........ P/N 52-571-8-923 4 Inch F x F 4 Inch F x F ANSI Flange......... P/N 52-570-8-023 ANSI Flange ........ P/N 52-571-8-023 4 Inch F x F 4 Inch F x F ISO(PN16)Flange.... P/N 52-570-8-113 ISO(PN16)Flange ... P/N 52-571-8-113 4 Inch F x F 4 Inch F x F JIS Flange........... P/N 52-570-8-723 JIS Flange .......... P/N 52-571-8-723 41nchFxF 41nchFxF AS Flange........... P/N 52-570-8-523 AS Flange........... P/N 52-571-8-523 61nchGxG 61nchGxG 6.62 inch(168,3 mm) 6.62 inch(168,3 mm) Groove O.D. ......... P/N 52-570-8-925 Groove O.D. ........ P/N 52-571-8-925 61nchGxG 61nchGxG 6.50 inch(165,1 mm) 6.50 inch(165,1 mm) Groove O.D. ......... P/N 52-570-8-945 Groove O.D. ........ P/N 52-571-8-945 6 Inch F x F 6 Inch F x F ANSI Flange......... P/N 52-570-8-025 ANSI Flange ........ P/N 52-571-8-025 61nchFxF 61nchFxF ISO(PN16)Flange.... P/N 52-570-8-115 ISO(PN16)Flange ... P/N 52-571-8-115 61nchFxF 61nchFxF JIS Flange........... P/N 52-570-8-725 JIS Flange .......... P/N 52-571-8-725 61nchFxF 61nchFxF AS Flange........... P/N 52-570-8-525 AS Flange........... P/N 52-571-8-525 8 Inch F x F ANSI Flange......... P/N 52-570-8-026 8 Inch F x F ISO(PN10)Flange.... P/N 52-570-8-116 SlnchFxF ISO(PN16)Flange.... P/N 52-570-8-126 SlnchFxF JIS Flange........... P/N 52-570-8-726 8 Inch F x F AS Flange........... P/N 52-570-8-526 O 2007 TYCO FIRE 8�BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446 � � II � � . - � - •'° - . �� Fig. 200 - "Trimline" Adjustable Band Hanger � �� �S�,STEo Size Range— 1/2" thru 8" pipe A�MD Material —Carbon Steel, Mil. Galvanized to G90 specifications Function — For fire sprinkler and other general piping � purposes. Knurled swivel nut design permits hanger adjustment after installation. Features— • (1/2" thru 2") Flared edges ease installation for � all pipe types and protect CPVC plastic pipe from ' i abrasion. Captured design keeps adjusting nut _ ; B - �� from separating with hanger. Hanger is easily B � �" installed around pipe. ��/ ' • (2'/z" thru 8") Spring tension on nut holds it A A securely in hanger before installation. Adjusting nut is easily removed. Approvals — Underwriters' Laboratories listed (1/2" thru 8") in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4�� thru 8��). Conforms to Federal 1/2 THRU 2 INCH PIPE 2 1/2 THRU 8 INCH PIPE Specifications WW-H-171 E, Type 10 and Manufacturers Standardization Society SP-69, Type 10. Maximum Temperature— 650°F Finish — Mil. Galvanized. For Stainless Steel materi- � als, order TOLCOT"' Fig. 200WON. Order By— Figure number and pipe size II + Dimensions •Weights Pipe Rod Size Max. Rec. Approx. Size Inch Metric A B Load Lbs. Wt./100 1/2 3/8 8mm or 10mm 3�/a 25/a 400 11 3/4 3/8 8mm or 10mm 3�/a 2�/2 400 11 1 3/8 8mm or 10mm 33/a 25/a 400 12 1�/a 3/8 8mm or 10mm 33/a 2�/a 400 13 1�/z 3/8 8mm or 10mm 3�/a 2�/a 400 14 2 3/8 8mm or 10mm 4�/z 3 400 15 2�h 3/8 10mm 55/a 4�/a 600 27 3 3/8 10mm 5�/a 4 600 29 3�/z 3/8 10mm 73/e 5�/a 600 34 4 3/8 10mm 73/a 5 1000 35 5 1/2 12mm 9�/a 6'/a 1250 66 6 1/2 12mm 10�/a 63/a 1250 73 8 1/2 12mm 13�/s 83/a 1250 136 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE•CORONA,CA 92879•PH: 951 J37.5599•fAX: 951 J37.0330 �1 CUSTOMER SERVICE•800J86.5266 www.tolco.com � � � • � . . . - , – •� . • ��. Fig. 98 - Rod Stiffener Component of Sta�tp of �OUS LISTED California OSHPD A roved V Seismic Restraints System Size Range—Secures 3/8" thru 7/8" hanger rod Material —Carbon Steel "a k:_; �_; Function — Secures channel to hanger rod for vertical seismic bracing. r-,; t--: Approvals— Underwriters Laboratories Listed in the USA (UL) and "r =' �;,.,_ Canada (cUL). Included in our Seismic Restraints Catalog a�proved �� � ��_:;; � � �_:.. bv the State of California Office of Statewide Health Planning and ', � " r`'�' Development (OSHPD). For additional load, spacing and placement \\ ', ` �h " , information relating to OSHPD projects, please refer to the TOLCO ', 1�\; , Seismic Restraint Systems Guidelines ' � � '' ' Finish — Electro Galvanized ', Note—Available in HDG finish or Stainless Steel materials. ' .,,✓ Order By— Figure number Fig. 99 - All Thread Rod Cut to Length Size Range— Secures 3/8" thru 7/8" rod in Dimensions 1" increments Rod Max. Rec. Load Lbs. Material —Carbon Steel Size For Service Temps Maximum Temperature—750°F 650°F 750°F Finish — Plain 3/s sio 540 1/2 1130 1010 Note—Available in Electro-Galvanized and 5/s 1810 1610 HDG finish or Stainless Steel materials. 3/a 2�10 2a2o Order By— Figure number, rod diameter, rod �/8 3��0 3360 length and finish Fig. 100 - All Thread Rod Full Lengths Size Range—Secures 3/8" thru 7/8" rod in 10' lengths Material —Carbon Steel Maximum Temperature—750°F Finish — Plain Note—Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By— Figure number, rod diameter and finish i Dimensions •Weights Max Rec. Load Lbs. Rod For Service Temps Approx. Size 650°F 750°F Wt./100 1/4 240 215 12 3/8 610 540 29 1/2 1130 1010 53 5/8 1810 1610 84 3/4 2710 2420 123 7/8 3770 3360 169 1 4960 4420 222 1�/a 8000 7140 360 1�/2 11630 10370 510 m OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE•CORONA,CA 92879•PH: 951 J37.5599•fAX: 951 J37.0330 CUSTOMER SERVICE•800J86.5266 www.tolco.com 4.3.9 HDI-P Drop-In Anchor 4.3.9.1 Product Description 4.$.9.7 Product Description 4.3.9.2 Material Specifications The Hilti HDI-P Drop-In anchor is an Guide Specifications 4.3.9.3 Technical Data internally threaded,flush mounted Expansion Anchor Expansion anchors 4.3.9.4 Installation Instructions expansion anchor for solid and shall be flush or shell type and zinc 4.3.9.5 Ordering Information hollow concrete. plated in accordance with ASTM B 633, Product Features SC 1,Type III. Anchors shall be Hilti �,..;,.�� • Optimized 3/4" anchor length to HDI-P anchors as supplied by Hilti. allow reliable fastenings in hollow Installation Install shell or flush type core panels, precast plank&post "�'�'�� tensioned slabs anchors in holes drilled with Hilti carbide Shallow drilling enables fast tipped drill bits. Install anchors in ��;�'. • installation accordance with manufacturer's '� Lip provides flush installation, recommendations. . � consistent anchor depth and easy rod alignment Listings/Approvals • Setting tool leaves mark on flange ICC-ES(International Code Council) when anchor is set properly to ESR-1291 enable inspection&verification of COLA(City of Los Angeles) proper expansion Research Report No.25350 Factory Mutual(FM) 4.3.9.2 Material Specifications Pipe Hanger Components for Automatic Sprinkler Systems The HDI-P is manufactured from mild carbon steel, which is zinc plated for corrosion protection in accordance with ASTM B 633, SC 1,Type III 4.3.9.3 Technical Data HDI-P Specification Table Average Ultimate Loads,Ib(kN) Allowable Loads,Ib(kN) 4000 psi Concrete Hollaw Core 4000 psi Concrete Hollow Core Length Bit Size� (27.6 MPa) (Spancrete) (27.6 MPa) (Spancrete) Desc. in.(mm) in. Tension Shear Tension Shear Tension Shear Tension Shear HDI-P 3/8 3/4(19.1) 1/2 1900(8.5) 3000(13.3) 2100(9.3) 4000(17.8) 380(1.7) 600(2.7) 420(1.9) 800(3.6) 1 For Hilti matched tolerance carbide Yipped drill bits,see section 8.4.1. 4.3.7.4 Installation Instructions J� \ �\ � ,:, ��� ' �� ���� � ���� � � � � �� ��� °°� ��� ������� � �� �� �� �� I �� • �� �� �� �� * � � * . 1.Set depth 2. Hammer-drill 3.Clean hole. 4. Insert anchor. 5.Insert setting 6.Collar of set- gauge on drill. hole. tool and strike ting tool will with hammer leave an until anchor is indentation fully set. on flange of 4.3.9.5 Ordering Information anchor when HDI-P AnChOr properly expanded. Item No. Description Box�ty 00283611 HDI-P 3/8 100 Setting Tools for HDI-P Anchors Item No. Description 00283611 HSD-G 3/8"—3/4"Setting Tool w/hand guard 00253784 HST-P 3/8"—3/4"Setting Tool 256 Hilti,Inc.(US)1-800-879-8000 I www.us.hilti.com I en espanol 1-800-879-5000 I Hilti(Canada)Corp.1-800-363-4458 I www.ca.hilti.com I Product Technical Guide 2006