The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bu
l
l
e
t
i
n
0
3
4
Re
v
.
A
Bulletin 034 Rev. A
Model G5-56
Model G5-42
Quick Response Concealed
Automatic Sprinkler
UL Quick Response
FM Standard Response
Concealed Sprinkler With a
3/4” (19mm) Adjustment
Features
1. Cover plate attachment (Plain or Perforated) with
¾” (19mm) assembly adjustment.
2. Smooth aesthetic ceiling profile.
3. Factory installed protective cap.
4. Available in brass, chrome or black plated and
white painted finishes.
5. Ordinary and Intermediate temperature rating.
For K2.8 & additional Sprinklers refer to Bulletin 154
for Technical Specifi cation and Approvals
Approvals & Listings
1. Underwriters Laboratories Inc. and cULus -
Quick Response
2. Factory Mutual Research Corp. (FM) -
Standard Response (See Page 3)
• Light Hazard Occupancies -
No Limitations
• Ordinary Hazard Occupancies
Groups 1 & 2 Wet Systems Only
U.S. Patent number 6,554,077.
Product Description
The Reliable Model G5-56 and G5-42 uses a proven quick
response fusible element in a standard style sprinkler frame
with a drop-down deflector. This assembly is recessed into
the ceiling and concealed by a flat cover plate assembly. The
threaded engagement provides ¾” (19mm) of cover adjust-
ment. The flat cover plate is attached to the skirt using either
135°F (57°C) or 165°F (74°C) ordinary temperature classifica-
tion solder.
When the ceiling temperature rises, the solder holding the
flat cover plate melts, the flat cover plate released thus expos-
ing the sprinkler inside to the rising ambient temperature.
The subsequent fusing of the element opens the waterway
and causes the deflector to distribute the water. Any secure
engagement between the cover plate and cup will assure that
the drop-down deflector is properly located below the ceiling.
Application
The Reliable Model G5-56 and G5-42 are the most versatile
quick response concealed sprinklers available. It provides
the best form of fire protection while offering an attractive ap-
pearance and 3/4” (19mm) of cover adjustment for ease of
installation. The small diameter cover plate assembly is eas-
ily attached and blends into the ceiling, concealing the most
dependable fire protection available, an automatic sprinkler
system.
The Model G5-56 and G5-42 are designed for use where
aesthetic appearance is important. Offices, hospitals, motels
and restaurants are but a few of the applications where it can
be used.
The Model G5-56 and G5-42 is a UL Listed Quick Response
Concealed sprinklers intended for use in accordance with
NFPA 13. FM Approves the G5-56 sprinkler as a standard re-
sponse concealed sprinkler intended for use in accordance
with FM Loss Prevention Data Sheet 2.0.
Plain Cover Plate
Perforated Cover Plate
Installation
Do not install the G5-56 and G5-42 in ceilings which have
positive pressure in the space above.
• Cut a 25/8” inch (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model FC Wrench. The
wrench has a socket drive which is inserted into the body of
the sprinkler. When installing a sprinkler the wrench is first
positioned into the sprinkler/cup assembly until the wrench
socket engages the body of the sprinkler. The sprinkler is
then tightened into the pipe fitting. When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care should
be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRINKLER/
CUP ASSEMBLY. Install the cover plate by hand turning the
cover in the clockwise direction until it is tight against the ceil-
ing.
A protective cap is provided to protect the drop-down sprinkler
deflector from damage which could occur during construction
before the cover plate is installed. The cap is factory installed
inside the sprinkler cup. Remove cap to install sprinkler, then re-
install cap until the cover plate is installed.
Maintenance
The Model G5-56 and G5-42 should be inspected quarterly
and the sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia or
any other cleaning fluids. Remove any sprinkler that has been
painted (other than factory applied) or damaged in any way. A
stock of spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to installa-
tion, sprinklers should be maintained in the original cartons and
packaging to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.
UL Listing Category
Sprinklers, Automatic and
Open
Quick Response Sprinkler
UL Guide Number
VNIV
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested Hydrostatically to 500 psi (34.5 bar)
Temperature Rating
Classifi cationSprinkler Cover
Plate
Max. Ambient
Temp.
Ordinary165°F/74°C135°F/57°C100°F/38°C
Intermediate212°F/100°C165°F/74°C150°F/66°C
Model FC Sprinkler Wrench
Ordering Information
1. Sprinkler Model
2. Nominal Orifice
3. Flat Cover Plate
Plain or Perforated
4. Flat Cover Plate
Assembly Finish
5. Inlet Type
Cover Plate Finishes(1)
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
(2) For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
2.
Technical Data
Sprinkler
Inlet
Total
Adjustment
Nominal
Orifi ce
Nominal K Factor
ThreadApprovals Sprinkler
Identifi cation (SIN)USMetric
Non Adjustable¾” (19mm)½” (15mm)5.680½” NPT (R½)1,2RA3415
Non Adjustable¾” (19mm)7/16” (11mm)4.260½” NPT (R½)1RA3413
Notice
FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS
NOTE:
1. Testing has shown that use of a “nipple extension” will not affect the listing of the sprinkler.
2. For RETROFIT installations, per NFPA 13 (2010) section 8.15.19.4, “which allows the use of nipples as the same pipe
thread size as the existing outlet when revamping existing systems”.
3. Do not exceed 8-18 ft-lbs of torque during installation.
3.