Bulletin 034 Rev. A
Model G5-56
Model G5-42
Quick Response Concealed
Automatic Sprinkler
UL Quick Response
FM Standard Response
Concealed Sprinkler With a
3/4” (19mm) Adjustment
Features
1. Cover plate attachment (Plain or Perforated) with
¾” (19mm) assembly adjustment.
2. Smooth aesthetic ceiling profile.
3. Factory installed protective cap.
4. Available in brass, chrome or black plated and
white painted finishes.
5. Ordinary and Intermediate temperature rating.
For K2.8 & additional Sprinklers refer to Bulletin 154
for Technical Specifi cation and Approvals
Approvals & Listings
1. Underwriters Laboratories Inc. and cULus -
Quick Response
2. Factory Mutual Research Corp. (FM) -
Standard Response (See Page 3)
• Light Hazard Occupancies -
No Limitations
• Ordinary Hazard Occupancies
Groups 1 & 2 Wet Systems Only
U.S. Patent number 6,554,077.
Product Description
The Reliable Model G5-56 and G5-42 uses a proven quick
response fusible element in a standard style sprinkler frame
with a drop-down deflector. This assembly is recessed into
the ceiling and concealed by a flat cover plate assembly. The
threaded engagement provides ¾” (19mm) of cover adjust-
ment. The flat cover plate is attached to the skirt using either
135°F (57°C) or 165°F (74°C) ordinary temperature classifica-
tion solder.
When the ceiling temperature rises, the solder holding the
flat cover plate melts, the flat cover plate released thus expos-
ing the sprinkler inside to the rising ambient temperature.
The subsequent fusing of the element opens the waterway
and causes the deflector to distribute the water. Any secure
engagement between the cover plate and cup will assure that
the drop-down deflector is properly located below the ceiling.
Application
The Reliable Model G5-56 and G5-42 are the most versatile
quick response concealed sprinklers available. It provides
the best form of fire protection while offering an attractive ap-
pearance and 3/4” (19mm) of cover adjustment for ease of
installation. The small diameter cover plate assembly is eas-
ily attached and blends into the ceiling, concealing the most
dependable fire protection available, an automatic sprinkler
system.
The Model G5-56 and G5-42 are designed for use where
aesthetic appearance is important. Offices, hospitals, motels
and restaurants are but a few of the applications where it can
be used.
The Model G5-56 and G5-42 is a UL Listed Quick Response
Concealed sprinklers intended for use in accordance with
NFPA 13. FM Approves the G5-56 sprinkler as a standard re-
sponse concealed sprinkler intended for use in accordance
with FM Loss Prevention Data Sheet 2.0.
Plain Cover Plate
Perforated Cover Plate
Installation
Do not install the G5-56 and G5-42 in ceilings which have
positive pressure in the space above.
• Cut a 25/8” inch (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model FC Wrench. The
wrench has a socket drive which is inserted into the body of
the sprinkler. When installing a sprinkler the wrench is first
positioned into the sprinkler/cup assembly until the wrench
socket engages the body of the sprinkler. The sprinkler is
then tightened into the pipe fitting. When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care should
be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRINKLER/
CUP ASSEMBLY. Install the cover plate by hand turning the
cover in the clockwise direction until it is tight against the ceil-
ing.
A protective cap is provided to protect the drop-down sprinkler
deflector from damage which could occur during construction
before the cover plate is installed. The cap is factory installed
inside the sprinkler cup. Remove cap to install sprinkler, then re-
install cap until the cover plate is installed.
Maintenance
The Model G5-56 and G5-42 should be inspected quarterly
and the sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia or
any other cleaning fluids. Remove any sprinkler that has been
painted (other than factory applied) or damaged in any way. A
stock of spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to installa-
tion, sprinklers should be maintained in the original cartons and
packaging to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.
UL Listing Category
Sprinklers, Automatic and
Open
Quick Response Sprinkler
UL Guide Number
VNIV
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested Hydrostatically to 500 psi (34.5 bar)
Temperature Rating
Classifi cationSprinkler Cover
Plate
Max. Ambient
Temp.
Ordinary165°F/74°C135°F/57°C100°F/38°C
Intermediate212°F/100°C165°F/74°C150°F/66°C
Model FC Sprinkler Wrench
Ordering Information
1. Sprinkler Model
2. Nominal Orifice
3. Flat Cover Plate
Plain or Perforated
4. Flat Cover Plate
Assembly Finish
5. Inlet Type
Cover Plate Finishes(1)
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
(2) For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
2.
Technical Data
Sprinkler
Inlet
Total
Adjustment
Nominal
Orifi ce
Nominal K Factor
ThreadApprovals Sprinkler
Identifi cation (SIN)USMetric
Non Adjustable¾” (19mm)½” (15mm)5.680½” NPT (R½)1,2RA3415
Non Adjustable¾” (19mm)7/16” (10mm)4.260½” NPT (R½)1RA3413
Notice
FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS
NOTE:
1. Testing has shown that use of a “nipple extension” will not affect the listing of the sprinkler.
2. For RETROFIT installations, per NFPA 13 (2010) section 8.15.19.4, “which allows the use of nipples as the same pipe
thread size as the existing outlet when revamping existing systems”.
3. Do not exceed 8-18 ft-lbs of torque during installation.
3.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 04/12 P/N 9999970421
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F1FR56 Series
Quick Response
Standard Spray
Bu
l
l
e
t
i
n
0
1
4
R
e
v
.
G
Bulletin 014 Rev. G
Model F1FR56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model F1FR56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP
Horizontal Sidewall
Model F1FR56 Concealed Sprinkler Types
Standard Pendent
Listing & Approvals
1. Underwriters Laboratories Inc. and Certified for
Canada (cULus).
2. Factory Mutual Approvals (FM)
3. Loss Prevention Council (LPCB, UK)
4. VdS Schadenverhütung GmbH
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Models F1FR56 Series Sprinklers are quick re-
sponse sprinklers which combine the durability of a stan-
dard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models F1FR56 Series Recessed automatic sprin-
klers utilize a 3.0 mm frangible glass bulb. These sprin-
klers have demonstrated response times in laboratory tests
which are five to ten times faster than standard response
sprinklers. This quick response enables the Model F1FR56
Series sprinklers to apply water to a fire much faster than
standard sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Pendent
Conventional
Recessed
Pendent/F1/F2
Upright
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflec-
tor style and sprinkler type are in accordance with the lat-
est published standards of the National Fire Protection As-
sociation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
Vertical Sidewall
Horizontal Sidewall
Recessed
Horizontal Sidewall
Recessed
Pendent/FP
Concealed
Pendent
2.
Pendent ConventionalUpright
Model F1FR56 Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifi ce
Thread
Size
Nominal K Factor Sprinkler
Height
Approval
Organization
Sprinkler Identifi cation Number
(SIN)
USMetricUprightPendent
Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position
½” (15mm)½” NPT(R½) 5.6802.25” (57mm)1, 2, 3, 4RA1425(1)RA1414 (1)(2)
Conventional-Install in Upright or Pendent Position
15mm(1)½” NPT(R½) 5.68057mm3,4RA1475
(1) cULus listed corrosion resistant (Polyester coated) sprinkler.
(2) Polyester coated FM approved sprinkler.
Model F1FR56/F1 or F2
Model F1FR56 Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orifi ce
Thread
Size
K Factor Sprinkler
Height
Sprinkler Identifi cation Number
(SIN)USMetric
½” (15mm)½” NPT(R½)5.6802.25” (57mm)RA1414
(1) Refer to escutcheon data table for approvals and dimensions.
Model F1FR56/FP
3.
Model F1FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal
Orifi ce Thread Size
Nominal K Factor Sprinkler
Height
Approval
Organizations
Sprinkler
Identifi cation
Numbers (SIN)USMetric
½” (15mm)½” NPT (R1/2)5.68.02.25” (57mm)1,2,3,4 RA1485(2)
15mm½” NPT (R1/2)5.68.02.25” (57mm)4(1)
(1) LPC Approval is for pendent position only.
(2) cULus Listed corrosion resistant (Polyester coated) sprinkler.
Sprinkler TypeDefl ector to Ceiling Distance
(Min. - Max.)
Upright4” (102mm) - 12” (305mm)
Pendent4” (102mm) - 12” (305mm)
Model F1FR56 Quick Response Horizontal Sidewall Sprinkler
Defl ector: HSW
Installation Wrench: Model D Sprinkler Wrench
Installation Data: Horizontal Sidewall
Nominal Orifi ceThread Size
Nominal K Factor Sprinkler
Height
Approval Organizations
and Type of Approval Sprinkler
Identifi cation
Numbers (SIN)USMetricLight Hazard Ordinary
Hazard
½” (15mm)½” NPT (R1/2)5.6802.63” (67mm)1,21RA1435(1)
(1) cULus Listed corrosion resistant (Polyester coated) sprinkler.
Horizontal Sidewall
Vertical Sidewall
Note: For Recessed HSW Sprinklers use installation wrench GFR2.
Model F1FR56 Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model RC1 Sprinkler Wrench
Technical Data:
Nominal
Orifi ce
“K” Factor Thread
Size Model
Temp. RatingMax.
Ambient
Temp
Bulb
Color Approvals
Sprinkler
Identifi cation
Number(SIN)USMetricSprinklerCover
½” (15mm)5.680½” NPTF1FR135°F/57°C135°F/57°C100°F/38°COrange1RA1414
½” (15mm)5.680½” NPTF1FR155°F/68°C135°F/57°C100°F/38°CRed1, 4(1)RA1414
½” (15mm)5.680½” NPTF1FR175°F/79°C165°F/74°C100°F/38°CYellow1RA1414
½” (15mm)5.680½” NPTF1FR200°F/93°C165°F/74°C150°F/65°CGreen1RA1414
(1) For VdS only = 155°F/68°C Norbulb and 1/2” [12,7mm] adjustment.
Figure 1 Figure 2
Installation Aid
A protective cap is included for use during installation.
Important: The F1FR56 Sprinkler with Model CCP cover
plate is not an FM Approved combination.
Installation
Quick response sprinklers are intended for installation
as specified in NFPA 13. Quick response sprinklers and
standard response sprinklers should not be intermixed.
The Model F1FR56 Recessed Quick Response Sprin-
klers are to be installed as shown. The Model F1 or F2 Es-
cutcheons illustrated are the only recessed escutcheons
to be used with the Model F1FR56 Sprinklers. The use
of any other recessed escutcheon will void all approvals
and negate all warranties.
When installing Model F1FR56 Sprinklers, use the Mod-
el D Sprinkler Wrench. Use the Model GFR2 Wrench for
installing F1FR56 Recessed Pendent Sprinklers. Any
other type of wrench may damage these sprinklers.
NOTE: A leak tight ½” NPT (R1/2) sprinkler joint can
be obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m).
Do not tighten sprinklers over maximum recommended
torque. It may cause leakage or impairment of the sprin-
klers.
The Model F1FR56/ CCP Concealed Sprinkler uses the
½” orifice, ½” NPT (R1/2), 135°F (57°C), 155°F (68°C),
175°F (79°C) or 200°F (93°C) Model F1FR56 Pendent
Sprinkler with a threaded Model CCP cup which is fac-
tory attached to the sprinkler. The assembly is complet-
ed by the installation of the attractive, low profile, 135°F
(57°C) or 165°F (74°C) rated Model CCP push on cover
plate assembly. The cover plate and sprinkler cup as-
semblies are joined using a cover plate skirt with flexible
tabs for threaded engagement. A choice of two cover
plate assemblies provide either ½” (13mm) or 5/16” (8mm)
of cover adjustment.
Do not install these sprinklers in ceiling which have
positive pressure in the space above.
After a 25/8” (67mm) diameter hole is cut in the ceil-
ing, the sprinkler is easily installed with the Model RC1
Wrench. A Teflon* based thread sealant should be
applied to the sprinkler threads only. The Model RC1
Wrench is then used to engage the sprinkler wrenching
surfaces and to install the sprinkler in the fitting. When
inserting or removing the wrench from the sprinkler/cup
assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART
OF THE SPRINKLER. The cover plate is then pushed
onto the cup. Final adjustment is made by hand turning
the cover plate until the skirt flange makes full contact
with the ceiling. Cover plate removal requires turning in
the counter clockwise direction.
4.
*DuPont Registered Trade Mark
5.
After installation, inspect all sprinklers to ensure that
there is a gap between the cover plate and ceiling and
that the four cup slots are open and free from any air flow
impediment to the space above.
Concealed cover plate/cup assemblies are listed only
for use with specific sprinklers. The use of any other con-
cealed cover plate/cup assembly with the Model F1FR56
Pendent Sprinkler or the use of the Model CCP Concealed
cover plate assembly on any sprinkler with which it is not
specifically listed my prevent good fire protection and will
void all guarantees, warranties, listings and approvals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and
installation. REMOVE THIS PROTECTION AT THE TIME
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR
FIRE PROTECTION. Removal of the protectors before this
time may leave the bulb vulnerable to damage. RASCO
wrenches are designed to install sprinklers when covers
are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THE PROTECTORS.
Temperature Ratings
Classifi cation
Sprinkler
Temperature Max. Ambient
Temp.Bulb Color
°C°F
Ordinary
Ordinary
Intermediate
Intermediate
High (1)
57
68
79
93
141
135
155
175
200
286
100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)
225°F (107°C)
Orange
Red
Yellow
Green
Blue
(1) Not available for recessed sprinklers.
Escutcheon Data (1)
Escutcheon
Model ApprovalsAdjustment “A”
Dimension
Face of Fitting to
Ceiling or Wall
Dimension
F11, 3, 4 Max Recess
Min Recess
1½” (38.1mm)
3/4” (19.1mm)
3/16” - 15/16”
(5mm - 24mm)
F21, 2, 3, 4 Max Recess
Min Recess
1 ½” (38.1mm)
1” (25mm)
3/16” - 11/16”
(5mm - 17mm)
FP Push-on/
Thread-off 1, 4 Max Recessed
Min Recessed
7/16” (11mm)
15/16 (24mm)
11/2” (38.1mm)
1” (25.4mm)
(1) SIN RA1435 – cULus permits use with F1, F2 or FP escutcheons for “light
hazard” only, while FM limits use for same hazard with F2 escutcheon only.
Maintenance
The Models F1FR56 and F1FR56 Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler which has
been painted (other than factory applied) or damaged
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or oper-
ated sprinklers. Prior to installation, sprinklers should be
maintained in the original cartons and packaging to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finishes (1)
Standard Finishes
SprinklerEscutcheonCover plate
Bronze
Chrome Plated
Polyester
Coated (4)(5)
Brass
Chrome
Plated
White Painted
Chrome
White
Special Application Finishes
SprinklerEscutcheonCover plate
Bright Brass (3)
Black Plated
Black Paint (2)
Off White (2)
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Satin
Off White
Black Paint
Black Plated
(1) Other finishes and colors are available on special order.
Consult the factory for details.
(2) cULus Listed only.
(3) 200°F (93°C) maximum.
(4) cULus listed “corrosion resistance” applies to SIN Numbers RA1435
(HSW), RA1485(VSW), RA1425 (Upright) and RA1414 (Pendent) in
standard black or white.
(5) FM Approvals finish as “Polyester coated” applies to SIN Number
RA1414 (Pendent) in standard black or white.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
9. Cover plate Model
10. Cover plate Thread size
11. Cover plate Temperature
12. Cover plate Adjustment
13. Cover plate Finish
Note: When Model F1FR56 Recessed sprinklers are ordered, the sprin-
klers and escutcheons are packaged separately.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A 08/11 P/N 9999970300
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection