HomeMy WebLinkAboutF12-0029 application.pdf
AUTOMATIC FIRE SPRINKLER SYSTEM
EQUIPMENT SUBMITTALS
FOR
ONE WILLOW BRIDGE
E. MEADOWS DR. RETAIL 2, 3 AND 4
VAIL, CO.
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional
(Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers
available in several different finishes, temperature ratings, and K-Factors to
meet design requirements. The special Polyester and Teflon® coatings
can be used in decorative applications where colors are desired. In addi-
tion, these coatings have been investigated for installation in corrosive atmos-
pheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflon® and Polyester coat-
ings as corrosion resistant.)
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class 2020
NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16
ABS Certified: Certificate 04-HS407984B-PDA
VdS Approved: Certificate G4060054, G4060056, G4880046, G4930039, and G4980020
LPC Approved: Ref. No. 096e/03, TE30401, and TE30872
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, and
0786-CPD-40171
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008
NOTE: Other International approval certificates are available upon request.
Refer to the Approval Chart on page 51d and Design Criteria on page 51e for cULus and FM approval requirements that must be
followed.
3. TECHNICAL DATA
Specifi cations:
Available since 1987.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for
use with water working pressures ranging from the minimum 7 psi
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-
sure (HP) sprinklers can be identified by locating “250” stamped on
the deflector. All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: Refer to the Approval Chart
Nominal K-Factor: Refer to the Approval Chart
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: Refer to the Approval Chart
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06661B, 06766B, 07060, and 12281. Brass UNS-C84400 for all
other sprinklers.
Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 06661B and 12281. Copper UNS-C19500 for Sprinklers
06665B, 06764B, and 07060. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw: Brass UNS-C36000
Form No. F_080488
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Sprinkler 51a
Replaces page 51a-e, dated April 25, 2008. (Updated sprinkler materials. Min. operating pressure for
LPCB and CE approval ONLY is 5 psi (0.35 bar). Added alternate frame material for Sprinklers 06661B,
06766B, 07060, and 12281. Removed VdS Approval from Sprinklers 06665B, 06764B, and 14817.)
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Pip Cap Attachment (for Sprinklers VK300 and VK325): Brass UNS-C36000
For Teflon® Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon® Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for
the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M-/W, Black Polyester = M-/B, and Black Teflon® = N
Temperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G
For example, sprinkler VK300 with a 1/2” thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 06661BAB
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/B (available since 2000)
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are available through a network
of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking
Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Sprinkler 51b
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Sprinkler 51c
Figure 1:
Standard Sprinkler Wrench 10896W/B
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating1
Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary135 °F (57 °C)100 °F (38 °C)Orange
Ordinary155 °F (68 °C)100 °F (38 °C)Red
Intermediate175 °F (79 °C)150 °F (65 °C)Yellow
Intermediate200 °F (93 °C)150 °F (65 °C)Green
High286 °F (141 °C)225 °F (107 °C)Blue
Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon®
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on
pages 51d. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through
the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the
coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester and Teflon® coatings.
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
Approval Chart
Microfast® and MicrofastHP® Quick Response
Upright and Conventional Sprinklers
Maximum 175 PSI (12 bar) WWP
Base Part
Number1 SIN Thread Size Nominal
K-Factor Overall Length Listings and Approvals3
(Refer also to Design Criteria on page 51e.)
NPTBSPU.S.metric2 InchesmmcULus4 FM7 NYC8 VdSLPCB
Upright-Standard Orifice
06661BVK3001/2”15 mm5.680.62-3/1656A2A3A2--------
07060VK345--15 mm5.680.62-3/1656--A3--A3A3B312 B314
Conventional-Standard Orifice
06766BVK3101/2”15 mm5.680.62-3/1656A3--A3--A3B312 B314
Upright-Large Orifice
06665BVK3503/4”--8.0115.22-5/1659A2A3A2--A3B312 --
14817VK350--20 mm8.0115.22-5/1659A2A3A2--A3B312 --
06764BVK3501/2”15 mm8.0115.22-5/1659A2--A2--------
Conventional-Large Orifice
06768BVK3543/4”20 mm8.0115.22-5/1659A2--A3--A3B312 --
Upright-Small Orifice10
06717B11 VK3251/2”15 mm2.840.32-3/1656A2A1A2--------
06719B11 VK3271/2”15 mm4.260.02-3/1656A2--A2--------
06931B11 VK327--10 mm4.260.02-3/1656------A3--E113 --
Maximum 250 PSI (17 bar) WWP
Upright-Standard Orifice
Base Part
Number1 SIN Thread Size Nominal
K-Factor Overall Length Listings and Approvals3
(Refer also to Design Criteria on page 51e.)
NPTBSPU.S.metric2 InchesmmcULus4 FMNYC9 VdSLPCB
12281VK3151/2”15 mm5.680.62-3/1656A2--A2--------
Upright-Small Orifice10
1228611 VK3401/2”15 mm2.840.32-3/1656A2--A2--------
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C),
and 286 °F (141°C)
B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)
C - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 286 °F (141°C)
D - 135 °F (57 °C), 155 °F (68 °C), and 175 °F (79 °C)
E - 155 °F (68 °C)
Approved Finishes
1 - Brass and Chrome-Enloy®
2 - Brass, Chrome-Enloy®, White Polyester5,6, Black Polyester5,6,
and Black Teflon®5
3 - Brass, Chrome-Enloy®, White Polyester5,6, and Black Polyester5,6
Footnotes
1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5 cULus Listed as corrosion resistant.
6 Other colors are available on request with the same Listings and Approvals as the standard colors.
7 For installation in accordance with the latest applicable FM Loss Prevention Data Sheets and Technical Advisory Bulletins.
8 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA.
9 Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16.
10 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated
wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or
internally galvanized.
11 The sprinkler orifice is bushed.
12 Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003.
13 Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40131.
14 MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
Sprinkler 51d
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Sprinkler 51e
DESIGN CRITERIA
(Also refer to the Approval Chart on page 51d)
cULus Listing Requirements:
Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in the Approval Chart for installation
in accordance with the latest edition of NFPA 13 for standard spray sprinklers, or old style (conventional) sprinklers.
Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by
the installation standards being applied, with hydraulically calculated wet systems only).
The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer
to the installation guidelines for old style (conventional) sprinklers.
•
•
FM Approval Requirements:
For installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including 2-8N) and Technical Advisory Bulletins. FM Global
Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements,
hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Wheatland’s Schedule 40 Sprinkler Pipe is a high quality sprinkler pipe offering you the
full range of assurances you require. Schedule 40 Sprinkler Pipe has passed some of the
toughest lab tests ever created for sprinkler pipe.
Wheatland’s schedule 40 Sprinkler Pipe is
made from the highest quality steel in one of
the nation’s most modern and most complete
pipe manufacturing plants. Our proprietary mill
coating offers you a clean, corrosion and heat
resistant surface that outlasts and outperforms
standard lacquer coatings. Plus, this coating
can be quickly and easily painted without special
preparation. Or it may be hot-dipped galvanized
to meet FM requirements for dry systems in
accordance with the zinc coating specifi cation of
ASTM A795. Schedule 40 is also available as
ASTM A 53 in NPS 1 - 6 and is UL & C-UL Listed
and FM Approved.
Wheatland’s Schedule 40 Standard
Wall Sprinkler Pipe meets or
exceeds the following:
UL & C-UL Listed•
FM Approved•
ASTM A795, Type E, Grade A•
Sprinkler Pipe
Specifi cations
NPS
Nominal O.DNominal I.DNominal WallNominal Weight
UL CRR*Pieces
Lift
in.mmin.mmin.mmlbs./ft.kg/m
1”1.31533.41.04926.6.1333.381.682.501.0070
1 1/4”1.66042.21.38035.1.1403.562.273.391.0051
1 1/2”1.90048.31.61040.9.1453.682.724.051.0044
2”2.37560.32.06752.5.1543.913.665.451.0030
* Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY
* The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe is
used as the benchmark (value of 1.0).
Please refer to appropriate documentation for
up-to-date listing and approval information.
Specifi cations and descriptions are accurate as
known at time of publication and are subject to
change without notice.
Wheatland’s
Made in the U.S.A. by Wheatland Tube
Company means made to the highest
standards for consistant quality.
Specifi cations and Approvals
700 South Dock Street, Sharon, PA 16146
Ph 800.257.8182 Fax 724.346.7260
www.wheatland.com
Wheatland Tube Company
0309 1.0Mrev02
Effective February 23, 2009 Coated Black Sprinkler Pipe
Page 40
D.I. THREADED FITTINGS
For fire protection services request submittal GRS 1.3
DUCTILE IRON 90 DEG. ELBOW
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.I.ABPIECE
1DB900335001.501.500.62
1 1/4DB900445001.751.750.90
1 1/2DB900555001.941.941.20
2DB900665002.252.251.85
DIMENSIONS
DUCTILE IRON STRAIGHT TEE
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.I.ABPIECE
1DT3335001.501.500.85
1 1/4DT4445001.751.751.22
1 1/2DT5555001.941.941.55
2DT6665002.252.252.45
DIMENSIONS
DUCTILE IRON RED.90 DEG. ELBOW
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.I.ABPIECE
1X1/2DB900315001.261.360.44
1X3/4DB900325001.371.450.52
1 1/4X1/2DB900415001.341.530.64
1 1/4X3/4DB900425001.451.620.72
1 1/4X1DB900435001.581.670.75
1 1/2X1DB900535001.651.800.92
1 1/2X1 1/4DB900545001.821.881.08
2X1/2DB900615001.491.881.08
2X3/4DB900625001.601.971.24
2X1DB900635001.732.021.40
2X1 1/4DB900645001.902.101.52
2X1 1/2DB900655002.022.161.65
DIMENSIONS
DUCTILE IRON COUPLING
NOMINALITEMMAX.DIMENSIONWEIGHT
SIZECODEWORKINGEACH
(INCH)#P.S.I.APIECE
1DCL0335001.670.40
1 1/4DCL0445001.930.57
1 1/2DCL0555002.150.75
2DCL0665002.531.15
DUCTILE IRON RED. COUPLING
NOMINALITEMMAX.DIMENSIONWEIGHT
SIZECODEWORKINGEACH
(INCH)#P.S.I.APIECE
1X1/2DRC0315001.690.39
1X3/4DRC0325001.690.53
DUCTILE IRON 45 DEG. ELBOW
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.I.ABPIECE
1DB450335001.121.120.46
1 1/4DB450445001.291.290.73
1 1/2DB450555001.431.430.92
2DB450665001.681.681.50
DIMENSIONS
DUCTILE IRON THREADED FITTINGS ARE UL, ULC LISTED AND FACTORY MUTUAL
APPROVED FOR 500 PSI SERVICE. DUCTILE IRON PER ASTM A 536 GRADE 65-45-
12. DIMENSIONS CONFORM TO ANSI B16.3 CLASS 150. THREADS ARE NPT PER
ANSI/ASME B1.20.1
NOTICE: DUCTILE IRON FITTINGS HAVE HIGHER TENSILE STRENGTH THEN THAT
OF STEEL PIPE. THEREFORE, OVER TIGHTENING CAN CAUSE DAMAGE TO PIPE
THREADS WHICH MAY CAUSE LEAKAGE. DUCTILE IRON
FITTINGS SHOULD BE TIGHTENED THREE TURNS BEYOND
HAND TIGHT, BUT NO MORE THAN FOUR TURNS.
A
Page 41
DUCTILE IRON REDUCING TEE
NOMINALITEMMAX.WEIGHT
SIZECODEWORKINGEACH
(INCH)#P.S.I.ABCPIECE
1X1X1/2DT3315001.261.261.360.64
1X1X3/4DT3325001.371.371.450.73
1X1/2X1DT3135001.501.361.500.71
1X3/4X1DT3235001.501.451.500.76
1X1X1 1/4DT3345001.671.671.580.98
1X1X1 1/2DT3355001.801.801.651.16
1 1/4X1X1/2DT4315001.341.261.530.82
1 1/4X1X3/4DT4325001.451.371.620.90
1 1/4X1X1DT4335001.581.501.671.00
1 1/4X1X1 1/4DT4345001.751.671.751.08
1 1/4X1X1 1/2DT4355001.881.801.821.42
1 1/4X1 1/4X1/2DT4415001.341.341.530.86
1 1/4X1 1/4X3/4DT4425001.451.451.620.92
1 1/4X1 1/4X1DT4435001.581.581.670.95
1 1/4X1 1/4X1 1/2DT4455001.881.881.821.45
1 1/4X1 1/4X2DT4465002.102.101.901.75
1 1/2X1X1/2DT5315001.411.341.660.95
1 1/2X1X3/4DT5325001.521.371.751.14
1 1/2X1X1DT5335001.651.501.801.17
1 1/2X1X1 1/4DT5345001.821.671.881.34
1 1/2X1X1 1/2DT5355001.941.801.941.45
1 1/2X1 1/4X1/2DT5415001.411.341.661.05
1 1/2X1 1/4X3/4DT5425001.521.451.751.15
1 1/2X1 1/4X1DT5435001.651.581.801.25
1 1/2X1 1/4X2DT5465002.162.102.021.90
1 1/2X1 1/2X1/2DT5515001.411.411.161.15
1 1/2X1 1/2X3/4DT5525001.521.521.751.24
1 1/2X1 1/2X1DT5535001.651.651.801.30
1 1/2X1 1/2X1 1/4DT5545001.821.821.881.48
1 1/2X1 1/2X2DT5565002.162.162.021.98
2X1X2DT6365002.252.022.252.15
2X1 1/4X2DT6465002.252.102.252.30
2X1 1/2X1/2DT6515001.491.411.881.50
2X1 1/2X3/4DT6525001.601.521.971.62
2X1 1/2X1DT6535001.731.652.021.64
2X1 1/2X1 1/4DT6545001.901.822.101.80
2X1 1/2X1 1/2DT6555002.021.942.162.00
2X1 1/2X2DT6565002.252.162.252.35
2X2X1/2DT6615001.491.491.881.60
2X2X3/4DT6625001.601.601.971.68
2X2X1DT6635001.731.732.021.85
2X2X1 1/4DT6645001.901.902.102.04
2X2X1 1/2DT6655002.022.022.162.18
2X2X2 1/2DT5565002.602.602.393.61
2 1/2X2X3/4DT7625001.741.602.322.28
DIMENSIONS
DUCTILE IRON CAP
NOMINALITEMMAX.DIMENSIONWEIGHT
SIZECODEWORKINGEACH
(INCH)#P.S.I.APIECE
1DCP0035001.160.32
1 1/4DCP0045001.280.43
1 1/2DCP0055001.330.60
2DCP0065001.450.91
DUCTILE IRON CROSS
NOMINALITEMMAX.WEIGHT
SIZECODEWORKING EACH
(INCH)#P.S.IABPIECE
1DX0335001.501.500.98
1 1/4DX0445001.751.751.50
1 1/2DX0555001.941.941.90
2DX0665002.252.252.95
1 1/4X1DX0435001.581.671.27
1 1/2X1DX0535001.651.801.48
2X1DX0635001.732.022.10
DIMENSIONS
DT667
DUCTILE IRON BUSHINGS
NOMINALITEM
SIZECODE
(INCH)#
DIMENSIONS
1x1/2DBUSH310.750.251.42OUT
1x3/4DBUSH320.750.251.42OUT
1 1/4x1DBUSH430.800.281.76OUT
1 1/2x1DBUSH530.830.312.00OUT
1 1/2x1 1/4DBUSH540.830.312.00OUT
2x1DBUSH630.880.411.95IN
2x1 1/4DBUSH640.880.342.48OUT
2x1 1/2DBUSH650.880.342.48OUT
0.22
0.17
0.28
0.44
0.30
0.66
0.72
0.61
DIMENSIONS
ABC
STYLE
WT.
EACH
D.I. THREADED FITTINGS
For fire protection services request submittal GRS 1.3
OUTSIDE HEADINSIDE HEAD
Main Office/Manufacturing Facility•1375 Sampson Ave. •Corona, CA 92879 •Ph: 909.737.5599 •Fax: 909.737.0330
Customer Service•800.786.5266
www.tolco.com
86
wwwwww..ttoollccoo..ccoomm
Revision 5/24/2001
™
®
a brand of
Fig.200 - “Trimline”Adjustable Band Hanger
Size Range — 1/2" thru 8" pipe
Material — Carbon Steel, Mil.Galvanized to G90
specifications
Function — For fire sprinkler and other general piping
purposes.Knurled swivel nut design permits hanger
adjustment after installation.
Features —
•(1/2" thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
abrasion.Captured design keeps adjusting nut
from separating with hanger.Hanger is easily
installed around pipe.
•(21/2" thru 8" Spring tension on nut holds it
securely in hanger before installation.Adjusting
nut is easily removed.
Approvals — Underwriters’Laboratories listed (1/2"
thru 8") in the USA (UL)and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8").Conforms to Federal
Specifications WW-H-171E, Type 10 and Manufacturers
Standardization Society SP-69, Type 10.
Maximum Temperature — 650°F
Finish — Mil.Galvanized.For Stainless Steel materi-
als, order TOLCO™ Fig.200WON.
Order By — Figure number and pipe size
Dimensions • Weights
Pipe Rod SizeMax.Rec.Approx.
SizeInchMetric ABLoad Lbs.Length
1/23/88mm or 10mm31/8 25/8 40011
3/43/88mm or 10mm31/8 21/2 40011
13/88mm or 10mm33/8 25/8 40012
11/4 3/88mm or 10mm33/4 27/8 40013
11/2 3/88mm or 10mm37/8 27/8 40014
23/88mm or 10mm41/2 340015
21/2 3/810mm55/8 41/8 60027
33/810mm57/8 460029
31/2 3/810mm73/8 51/4 60034
43/810mm73/8 5100035
51/212mm91/8 61/4 125066
61/212mm101/8 63/4 125073
81/212mm131/8 83/4 1250136
OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE. •CORONA, CA 92879 •PH: 951.737.5599 •FAX: 951.737.0330
CUSTOMER SERVICE•800.786.5266
www.tolco.com
66
wwwwww..ttoollccoo..ccoomm
™
®
a brand of Revision 9/22/2001
Fig.65 andFig.66
ReversibleC-TypeBeamClamps 3/4" and11/4" ThroatOpenings
Size Range — (Fig.65 and Fig.66) 3/8", 1/2" and 5/8" rod
Material — Carbon Steel with hardened cup point set screw and
jam nut
Function — Recommended for hanging from steel beam where flange
thickness does not exceed 3/4" (Fig.65) or 11/4" (Fig.66).
Features — All steel construction eliminates structural deficiencies
associated with casting type beam clamps.May be used on top or bot-
tom flange of the beam.(Beveled lip allows hanging from top flange
where clearance is limited.) May be installed with set screw in up or
down position.Offset design permits unlimited rod adjustment by
allowing the rod to be threaded completely through the clamp.Open
design permits inspection of thread engagement.
Approvals — Underwriters’Laboratories Listed in the USA (UL)and
Canada (cUL).Factory Mutual Engineering approved.Conforms to
Federal Specification WW-H-171E, Type 23 and Manufacturers
Standardization Society SP-69, Type 19.Exceeds requirements of the
National Fire Protection Association (NFPA), Pamphlet 13, 3/8" rod will
support 1/2" thru 4" pipe, 1/2" rod will support 1/2" thru 8" pipe.
Included in our Seismic Restraints Catalog approved by the State of
California Office of Statewide Health Planning and Development
(OSHPD).For additional load, spacing and placement relating to
OSHPD projects, please refer to the TOLCO Seismic Restraint
Systems Guidelines.
Finish — Plain
Note — Available in Electro-Galvanized and HDG finish.
Order By — Figure number, rod size and finish
Fig.65 Patent #4,570,885
Dimensions • Weights
Rod Size Max.Rec.Approx.
A B CDEFLoad Lbs.*Wt./100
3/813/16 3/417/16161028
1/211/2 3/419/1611/4 113055
5/811/2 3/419/1611/4 113055
* Max.loads for clamp with set screw in up or down position.
Fig.65
Dimensions • Weights
Rod Size Max.Rec.Approx.
A B CDEFLoad Lbs.*Wt./100
3/813/16 11/4 17/16161028
1/211/2 11/4 19/1611/4 113055
5/811/2 11/4 19/1611/4 113055
* Max.loads for clamp with set screw in up or down position.
Fig.66
Component of State of
California OSHPD Approved
Seismic Restraints System
Approvals Rod
Size
Part
Number Model Screw
Descriptions
Ultimate
Pullout (lbs)
UL Test
Load (lbs)
FM Test
Load
(lbs)
Min
Thick
Max
Thick
Box
Qty
Case
Qty
1/4"8024957 DSTR 100 *1/4-20 x 1" TEKS 3 1510 (20 ga.).036"-20 ga 3/16"25 125
1/4"8025957 DST 100 1/4-14 x 1" TEKS 3 446 (20 ga.).036"-20 ga 3/16"25 125
1/4"8026957 DST 150 1/4-14 x 1-1/2" TEKS 3 970 (16 ga.).036"-20 ga 3/16"25 125
1/4"8027957 DST 200 1/4-14 x 2" TEKS 3 446 (20 ga.).036”-20 ga 3/16”25 125
1/4"8030957 TEK 500 12-24 x 1-1/2" TEKS 5 3125 (3/16").187”-3/16”1/2"25 125
3/8"8038957 DSTR 1 *1/4-20 x 1" TEKS 3 1510 (20 ga.)1500 1475 .036"-20 ga 3/16"25 125
3/8"8037957 DSTR 1-1/2 *12-24 x 1-1/2" TEKS 5 1510 (3/16")1500 1475 .060”-16 ga.1/2"25 125
3/8"8039957 DSTR 516 *5/16-18 x 1-1/4" TEKS 3 2200 (20 ga.)1500 1475 .036"-20 ga 1/8"25 125
3/8"8040957 DST 10 1/4-14 x 1" TEKS 3 446 (20 ga.)
970 (16 ga.).036"-20 ga 3/16"25 125
3/8"8077925 DST 10-SS 1/4-14 x 1" TEKS 3 446 (20 ga.)
970 (16 ga.).036"-20 ga 3/16"25 125
3/8"8041957 DST 15 1/4-14 x 1-1/2" TEKS 3 446 (20 ga.)
970 (16 ga.).036"-20 ga 3/16"25 125
3/8"8078925 DST 15-SS 1/4-14 x 1-1/2" TEKS 3 446 (20 ga.)
970 (16 ga.).036"-20 ga 3/16"25 125
3/8"8042957 DST 20 1/4-14 x 2 TEKS" 3 446 (20 ga.)
970 (16 ga.).036"-20 ga 3/16"25 125
3/8"8043957 DST 25 1/4-14 x 2-1/2" TEKS 3 446 (20 ga.)
970 (16 ga.).036"-20 ga 3/16"25 125
3/8"8044957 DST 30 1/4-14 x 3" TEKS 3 446 (20 ga.)
970 (16 ga.).036"-20 ga 3/16"25 125
3/8"8045957 DST 516 5/16-18 x 1-1/4" TEKS 3 1500 (3/16")1500 1475 .125"-1/8"1/8"25 125
3/8"8046957 TEK 50 12-24 x 1-1/2" TEKS 5 3125 (3/16")1500 1475 .187”-3/16”1/2"25 125
1/2"8031925 DST 2.0 1/4-14 x 2" TEKS 3 446 (20 ga.)
970 (16 ga.).188"-3/16"1/4"25 125
1/2"8033925 DSTR 1.0 *1/4-20 x 1" TEKS 3 1510 (20 ga.).036"-20 ga 3/16"25 125
1/2"8034925 DSTR 5.16 *5/16-18 x 1-1/4" TEKS 3 2220 (20 ga.).036"-20 ga 1/8"25 125
1/2"8035925 DST 5.16 5/16-18 x 1-1/4" TEKS 3 1500 (3/16").125"-1/8"1/8”25 125
1/2"8036925 TEK 5.0 12-24 x 1-1/2" TEKS 5 3125 (3/16").187"-3/16"1/2"25 125
#14 Black
Nut Driver
Part # 8113910
#14 SW Red
Nut Driver
Part # 8114910*Includes retaining nut
Approvals Rod
Size
Part
Number Model Screw
Descriptions
Ultimate
Pullout (lbs)
UL Test
Load (lbs)
FM Test
Load (lbs)
Min
Thick
Max
Thick
Box
Qty
Case
Qty
3/8"8137957 SH-DSTR 1 *1/4-20 x 1"3220 (3/16")1500 1475 .035"3/16”25 125
#14 Black
Nut Driver
Part # 8113910
SAMMY Swivel Head® for Steel
6 For the most up to date information, visit www.sammysuperscrew.com
SAMMYS® for Steel Installs VERTICALLY into the bottom of steel structures easily and quickly!
VERTICAL MOUNT
ST
E
E
L
S
T
E
E
L
S
T
E
E
L
S
T
E
E
L
S
T
E
E
L
SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into
contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.
pre -drillingno
required
Product Features
• Made with Teks® self-drilling fasteners -
no pre-drilling required.
• Install into steel range from
22 gauge – 1/2” thicknesses.
• Saves time from traditional methods. • Reduces installation cost.
• Quick to install using the Sammy Nut
Driver with an 18V cordless drill/driver.
Product Features
• Eliminates distortion of threaded rod in
sloped roof applications.
• Accommodates 3-1/2 x 12 pitch.
• Installs into angled Z-Purlin; Allows
threaded rod to hang plumb.
• Allows 17° deflection from vertical.
(Does not comply with ROHS requirements)
Installs VERTICALLY and swivels up to 17° in steel structure
*Includes retaining nut
7 To find a distributor near you, call 800-BUILDEX
Installs VERTICALLY into the bottom of steel structures easily and quickly!
HORIZONTAL MOUNT
ST
E
E
L
S
T
E
E
L
S
T
E
E
L
S
T
E
E
L
S
T
E
E
L
SIDEWINDERS® for Steel Installs HORIZONTALLY into the side of steel structures easily and quickly!
Approvals Rod
Size
Part
Number Model Screw
Descriptions
Ultimate
Pullout (lbs)
UL Test
Load (lbs)
FM Test
Load (lbs)
Min
Thickness
Max
Thickness
Box
Qty
Case
Qty
1/4"8047957 SWD 100 1/4-14 x 1" TEKS 3 1477 (16 ga.).060"-16 ga 3/16"25 125
1/4"8049957 SWDR 100 *1/4-20 x 1" TEKS 3 1900 (20 ga.).036"-20 ga 3/16"25 125
3/8"8050957 SWD 10 1/4-14 x 1" TEKS 3 1477 (16 ga.).060"-16 ga 3/16"25 125
3/8"8080925 SWD 10-SS 1/4-14 x 1" TEKS 3 1477 (16 ga.).060"-16 ga 3/16"25 125
3/8"8051957 SWD 15 1/4-14 x 1-1/2" TEKS 3 1477 (16 ga.).060"-16 ga 3/16”25 125
3/8"8081925 SWD 15-SS 1/4-14 x 1-1/2" TEKS 3 1477 (16 ga.).060"-16 ga 3/16”25 125
3/8"8052957 SWD 20 1/4-14 x 2" TEKS 3 1477 (16 ga.).060"-16 ga 3/16”25 125
3/8"8053957 SWD 516 5/16-18 x 1-1/4" TEKS 3 2480 (20 ga.).036”-20 ga 1/8”25 125
3/8"8055957 SWDR 1 *1/4-20 x 1" TEKS 3 1900 (20 ga.)1500 1475 .036"-20 ga 3/16"25 125
3/8"8054957 SWDR 1-1/2 *12-24 x 1-1/2" TEKS 5 2375 (3/16")1500 1475 .187"-3/16"1/2"25 125
3/8"8056957 SWDR 516 *5/16-18 x 1-1/4" TEKS 3 2480 (20 ga.)1500 1475 .036"-20 ga 1/8"25 125
3/8"8057957 SWT 15 12-24 x 1-1/2" TEKS 5 237 (3/16").187"-3/16"1/2"25 125
SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into
contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.
#14 SW Red
Nut Driver
Part # 8114910
pre -drillingno
required
Ultimate Pullout Values (avg. lbs. ultimate) - SAMMYS
Fastener Steel Gauge (lbs.)
Model Dia.Pt.20 18 16 14 12 3/16 1/4
DST 1/4 #3 446 613 970 1145 1544 3190
DST 516 5/16 #3 457 568 1209 1712 2422
TEK 50 #12 #5 487 699 913 1527 3270 3593
DSTR 1-1/2”#12 #5 3270 3593
DSTR 1”1/4 #3 1510
DSTR 516 5/16 #3 2200
Ultimate Pullout Values (avg. lbs. ultimate) - SIDEWINDERS
Fastener Steel Gauge (lbs.)
Model Dia.Pt.20 18 16 14 12 3/16 1/4
SWD 1/4 #3 1477
SWDR 1-1/2”#12 #5 2375
SWDR 1”1/4 #3 1900 1900
SWDR 516 5/16 #3 2480 2480
Performance Data - Steel
Sheet Steel Gauges
Gauge No.26 24 22 20 18 16 14 12 3/16”1/4”
Nominal Decimal Equivalent .018 .024 .030 .036 .048 .060 .075 .105 .188 .250
*Includes retaining nut
Product Features
• Made with Teks® self-drilling fasteners - no pre-drilling required.
• Install into steel range from 22 gauge – 1/2” thicknesses.
• Saves time from traditional methods.
• Reduces installation cost.
• Quick to install using the Sammy Nut Driver with an 18V
cordless drill/driver.
Aluminum Curtain Wall Extrusion
Ultimate Pullout Values
(average lbs. ultimate)
Fastener Thickness
Model Dia.Pt..114 .092 .365 .132
DST 10 1/4 #3 1265 2750
SWD 10 1/4 #3 1120 1420
Installs VERTICALLY and swivels up to 17° in steel structure
OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE. •CORONA, CA 92879 •PH: 951.737.5599 •FAX: 951.737.0330
CUSTOMER SERVICE•800.786.5266
www.tolco.com
70
wwwwww..ttoollccoo..ccoomm
™
®
a brand of Revision 8/15/2005
Size Range — Secures 3/8" thru 7/8" hanger rod
Material — Carbon Steel
Function — Secures channel to hanger rod for vertical seismic bracing.
Approvals — Underwriters Laboratories Listed in the USA(UL) and
Canada (cUL).Included in our Seismic Restraints Catalog approved by
the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines
Finish — Electro Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number
Fig.98 - Rod Stiffener
Fig.99 - All ThreadRodCut to Length
Size Range — Secures 3/8" thru 7/8" rod in
1" increments
Material — Carbon Steel
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter, rod
length and finish
Fig.100 - All ThreadRodFullLengths
Size Range — Secures 3/8" thru 7/8" rod in
10’lengths
Material — Carbon Steel
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter
and finish
Dimensions • Weights
RodMax.Rec.Load Lbs.
SizeFor Service Temps
650°F750°F
3/8610540
1/211301010
5/818101610
3/427102420
7/837703360
Dimensions • Weights
Max Rec.Load Lbs.
RodFor Service TempsApprox.
Size650°F750°FWt./100
1/424021512
3/861054029
1/21130101053
5/81810161084
3/427102420123
7/837703360169
149604420222
11/4 80007140360
11/2 1163010370510
Component of State of
California OSHPD Approved
Seismic Restraints System