HomeMy WebLinkAboutA12-0033 CUT SHEETS �
' #
FIRE ALARM SUBMITTALS
PRO�ECT: Lion Sq ua re Lodge South
ELECTRICAL CONTRACTOR: New Electric Inc.
41199 Highway 6/ P.O. Box 957
Avon, CO 81620
CONTACT: 7ay VanVoorst
PHONE: 970-949-4651
� ` , �
� / �
Commercial Specialists
of
Western Colorado, LLC
LIONS SQUARE LODGE - INFILL
PROJECT
Fire Alarm System
Manufacturers Data Sheet
• FAPT-851 -ANALOG ADDRESSABLE SMOKE DETECTOR
• FRM-1 -ADDRESSABLE RELAY MODULE
• PC2W- CEILING MOUNT HORN/STROBE WHITE
• FM-998 SERIES- SURFACE MOUNT MAGNETIC DOOR HOLDERS
• PAM-1 - MULTI-VOLTAGEAUXILLARYRELAY
� .
��, �. �+'� s�,�,��ar� �,n�d enc��r�ag�� NI�E�' cer��?e�t�+��r
.
210 Marmot Lane Unit 85—PO Box 3913
Eagle, Co 81631
Phone:970.328.1951 Fax:970.328.1956
DN-6937:D
FAPT-851 (A) � N OT 1 F 1 E R°
Acclimate0 PIusT'" Multi-Sensor J
Low-Profile Intelligent Detector by H o n eywe I I
- - - - � - -
General
The Notifier FAPT-851(A) AcclimateOO PIusT"' detector is an -
intelligent, addressable, multi-sensing, low-profile detector ,
designed for use with Notifier Notifier Onyx and CLIP series � ,:� °-. '
Fire Alarm Control Panels(FACPs). '` '
The Acclimate Plus detector uses a combination of photoelec-
tric and thermal sensing technologies to increase immunity to
false alarms. Unlike traditional intelligent detectors, the Accli- ��
mate Plus detector has a microprocessor in the detector head
that processes alarm data. As a result, the Acclimate Plus *
detector adjusts its sensitivity automatically, without operator o
intervention or control panel programming. i���� m
Areas where the Acclimate Plus detector is especially useful ��,� 3
include office complexes, schools, college campuses, manu- �
facturing and industrial facilities, and anywhere else the use of FAPT-851(A) in B210LP(A) Base `
a particular area may change. The Acclimate Plus detector
automatically adjusts its sensitivity to the environment.
FlashScanOO (U.S. Patent 5,539,389) is a communication pro-
tocol developed to greatly enhance the speed of communica-
tion between analog intelligent devices and compatible Specifications
systems. Intelligent devices communicate in a grouped fash- Sensitivity: auto-adjusting levels: 1 to 2%/ft. and 2 to 4%/ft.
ion. If one of the devices within the group has new information, ,�,�ith classic CLIP systems; 1 to 2, 2 to 3, and 3 to 4%/ft. with
the panel's CPU stops the group poll and concentrates on sin- systems; fixed-sensitivity levels: 1, 2, and 4%/ft. with classic
gle points. The net effect is response speed greater than five CLIP systems;0.5, 1,2,3,and 4%/ft.with FlashScan systems.
times that of earlier designs.
Size:2.0"(5.3 cm) high;base determines diameter.
F@atl1P@S -B210LP(A): 6.1" (15.5 cm)diameter.
• Automatically adjusts sensitivity levels without operator -B501(A):4.1" (10.4 cm)diameter.
intervention or programming. Sensitivity increases with -B200S(A):6.875" (17.46 cm)diameter.
heat. -B200SR(A):6.875" (17.46 cm)diameter.
• Microprocessor-based, combination photo and thermal _B224RB(A):6.2" (15.748 cm)diameter.
technology. Shipping weight:5.2 oz. (147 g).
• Compatible with all Notifier Onyx and CLIP series Fire
Alarm Control Panels(FACPs). Operating temperature:0°C to 38°C(32°F to 100°F).
• Addressable-analog communication. UL-Listed velocity range: 0-4000 ft./min. (1219.2 m/min.),
• Sleek, low-profile design. suitable for installation in ducts.
• Two-wire SLC connection. Relative humidity: 10%-93%noncondensing.
• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 Thermal sensing rating: fixed-temperature setpoint 135°F
on FlashScan systems). (57°C)•
• Addresses can be viewed and changed without electronic ELECTRICAL SPECIFICATIONS
programmers.
• Dual bi-color LED design provides 360°viewing angle. Voltage range: 15-32 volts DC peak.
• LEDs lock red when in alarm. In FlashScan, LEDs flash Standby current(max.avg.):300 uA.
green in standby for normal condition. Loop resistance: 50 ohms maximum; varies according to
• Built-in tamper-resistant feature. control panel used. Refer to panel installation manuals.
• Constructed of off-white fire-resistant plastic, designed to LED current(max.):6.5 mA @ 24 VDC("ON").
commercial standards,and offers an attractive appearance.
• SEMS screws for wiring of the separate base. Installation
• Several base options, including relay, isolator,and sounder. The FAPT-851(A) plug-in detector uses a separate base to
• Built-in functional test switch activated by external magnet. simplify installation, service, and maintenance. A special tool
• Listed to UL 268. allows maintenance personnel to plug-in and remove detec-
Capable of heat-only alarm mode, enabled by a special tors without using a ladder. Suitable mounting base boxes
� include:
command from the panel. Smoke alarms are ignored.
• Low-temperature signal at 45°F +/- 10°F (7.22°C +/-
5.54°C).
DN-6937:D•12/07/2011—Page 1 of 2
• 4.0" (10.16 cm)square box. ACCESSORIES
• 3.5" (8.89 cm)or 4.0" (10.16 cm)octagonal box. F110: Retrofit flange to convert B210LP to match the 6710LP
• Single-gang box(except relay or isolator base). profile,or to convert older high-profile bases to low-profile.
NOTE: The FAPT-851(A) detector has the unique ability to adjust F110BP: Bulk pack of F110;package contains 15.
sensitivity according to the environment, based on heat and F210: Replacement flange for B210LP(A)base.
smoke levels.Avoid installing these detectors in locations that are
susceptible to rapid and high temperature changes.An example of RA100Z(A): Remote LED annunciator. 3—32 VDC. Fits U.S.
an incorrect application would be near or in line with the output of a single-gang electrical box. Supported by B210LP(A) and
self-contained heater. B501(A)bases only.
Agency Listings and Approvals SM6600: Surface mounting kit for use with B210LP(A).
M02-04-00:Test magnet.
These listings and approvals apply to the modules specified in
this. In some cases, certain modules or applications may not M02-09-00:Test magnet with telescoping handle.
be listed by certain approval agencies,or listing may be in pro- XR2B: Detector removal tool. Allows installation and/or
cess. Consult factory for latest listing status. removal of FlashScanOO Series detector heads from base in
• UL Listed: S1115. high ceiling installations.
• ULC Listed: S1115. T55-127-010: Detector removal tool without pole.
• MEA Listed:225-02-E. XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524
• FM Approved. m)sections.
• CSFM: 7272-0028:0206.
• U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0
(NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).
• Lloyd's Register: 1 1/60001 3 (NFS2-640, NFS-320/NFS-
320C,excluding B210LP(A)).
• Maryland State Fire Marshal: Permit#2122.
Ordering Information
NOTE:"A"suffix indicates ULC Listed model.
FAPT 851: Low-profile intelligent multi-sensor detector.
FAPT 851 A: Same as FAPT-851 but with ULC Listing.
INTELLIGENT BASES
NOTE:"A"suffix indicates ULC Listed model.
NOTE: For details about intelligent bases and their mounting, see
DN-60054.
B210LP(A): Plug-in detector base; standard U.S. flanged low-
profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501(A): Flangeless mounting base.
B5016P: Bulk pack of B501; package contains 10.
B200S(A): Intelligent, programmable sounder base capable of
producing sound output in high or low volume with ANSI Tem-
poral 3, ANSI Temporal 4, continuous tone, marching tone,
and custom tone.
B200SR(A): Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone.
Replaces B501 BH series bases in retrofit applications.
B224RB(A): Relay base Screw terminals: up to 14 AWG (2.0
mm2). Relay type Form-C. Rating: 2.0 A@ 30 VDC resistive;
0.3 A@ 110 VDC inductive; 1.0 A@ 30 VDC inductive.
B224BI(A): Isolator base. Maximum: 25 devices between iso-
Iat01'baSeS. NotifierOO,ONYXO,FlashScanO,and Acclimate0 are registered trademarks
and Acclimate PIusT"^is a trademark of Honeywell International Inc.
�02011 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
I�O 9001 This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
_ We cannot cover all specific applications or anticipate all requirements.
EN6INEERIN6 8 MANUFACTURIN& All specifications are subject to change without notice.
QUALITY SYSTEMS MadeintheU.S.A.
For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118.
www.notifier.com
Page 2 of 2—DN-6937:D•12/07/2011
DN-6724:B3
FCM-1 (A) & FRM-1 (A) �1 N OT 1 F 1 E R�
Series ►�
Control and Relay Modules by H o n eywe I I
- - - - � - -
General
FCM-1(A)Control Module: The FCM-1(A)Addressable Con-
trol Module provides Notifier intelligent fire alarm control pan- �
els a circuit for Notification Appliances (horns, strobes,
speakers, etc.). Addressability allows the FCM-1(A)to be acti- � �,�
vated, either manual�y or through panel programming, on a l `
select(zone or area of coverage) basis. '�' � G �' 1
FRM-1(A)Relay Module: The FRM-1(A) Addressable Relay � "'E°""'a'' � „�;o Ea�,emE„;°
Module provides the system with a dry-contact output for acti- . T10E„PwR,,, _��,.,.,
vating a variety of auxiliary devices, such as fans, dampers,
control equipment,etc.Addressability allows the dry contact to '°'•' _",.,'� ^
be activated, either manually or through panel programming, a `""", iPULTOM9
on a select basis. "`°°°°'_°°`°°"`°°"'�`°
FlashScanO (U.S. Patent 5,539,389) is a communication pro- e��
tocol developed by NOTIFIER Engineering that greatly , � -
enhances the speed of communication between analog intelli- ""� `� � �'"� '
gent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new infor- `� , \ � . -- ;- I°
mation, the panel CPU stops the group poll and concentrates 'ff�'
.,
on single points.The net effect is response speed greater than _ _,
five times that of other designs.
FCM-1(A)
Features
• Built-in type identification automatically identifies these ' The FCM-1(A)is configured for a single Class B(Style Y)or
devices to the control panel. Class A(Style Z) Notification Appliance Circuit.
• Internal circuitry and relay powered directly by two-wire ' The FRM-1(A) provides two Form-C dry contacts that
SLC loop.The FCM-1(A) module requires power(for horns, switch together.
strobes,etc.),or audio(for speakers).
• Integral LED "blinks" green each time a communication is Operation
received from the control panel and turns on in steady red Each FCM-1(A)or FRM-1(A)uses one of 159 possible module
when activated. addresses on a SLC loop (99 on CLIP loops). It responds to
• LED blink may be deselected globally(affects all devices). regular polls from the control panel and reports its type and
• High noise immunity(EMF/RFI). status, including the open/normal/short status of its Notifica-
The FCM-1(A) may be used to switch 24-volt NAC power, tion Appliance Circuit (NAC). The LED blinks with each poll
• audio(up to 70.7 Vrms). received. On command, it activates its internal relay. The
FCM-1(A) supervises Class B (Style Y) or Class A (Style Z)
• Wide viewing angle of LED. notification or control circuits.
• SEMS screws with clamping plates for wiring ease. Upon code command from the panel, the FCM-1(A) will dis-
• Direct-dial entry of address 01- 159 for FlashScan loops, connect the supervision and connect the external power sup-
01 -99 for CLIP mode loops. ply in the proper polarity across the load device. The
• Speaker, and audible/visual applications may be wired for disconnection of the supervision provides a positive indication
Class B or A(Style Y or Z). to the panel that the control relay actually turned ON. The
external power supply is always relay isolated from the com-
Applications munication loop so that a trouble condition on the external
power supply will never interfere with the rest of the system.
The FCM-1(A) is used to switch 24 VDC audible/visual power, Rotary switches set a unique address for each module. The
high-level audio (speakers). The FRM-1(A) may be pro- address may be set before or after mounting. The built-in
grammed to operate dry contacts for applications such as door TYPE CODE (not settable)will identify the module to the con-
holders or Air Handling Unit shutdown, and to reset four-wire trol panel, so as to differentiate between a module and a sen-
smoke detector power. sor address.
NOTE: Refer to the SLC Manual (PN 51253) for details regarding
releasing applications with the FCM-1(A). Refer to the FCM-I-REL Specifications for FCM-1(A)
datasheet(DN-60390)for new FlashScanO releasing applications.
Normal operating voltage: 15 to 32 VDC.
Construction Maximum current draw: 6.5 mA(LED on).
• The face plate is made of off-white heat-resistant plastic. Average operating current: 350 NA direct poll,375 NA group
• Controls include two rotary switches for direct-dial entry of poll with LED flashing, 485 �A Max. (LED flashing, NAC
address(01-159). shorted.)
DN-6724:63•2/17/2011—Page 1 of 2
Maximum NAC Line Loss: 4 VDC. Contact Ratings for FRM-1(A�
External supply voltage(between Terminals T10 and
T11): Maximum (NAC): Regulated 24 VDC; Maximum Current Maximum Load Application
(Speakers):70.7 V RMS,50W. Rating Voltage Description
Drain on external supply: 1.7 mA maximum using 24 VDC 3 A 30 VDC Resistive Non-Coded
supply;2.2 mA Maximum using 80 VRMS supply. 2 A 30 VDC Resistive Coded
Max NAC Current Ratings: For class B wiring system, the g A 110 VDC Resistive Non-Coded
current rating is 3A; For class A wiring system,the current rat-
ing is 2A. .9 A 125 VDC Resistive Non-Coded
Temperature range: 32°F to 120°F(0°C to 49°C). ,5 A 30 VDC Inductive Coded
(L/R=5ms)
Humidity range: 10%to 93%non-condensing.
1 A 30 VDC Inductive Coded
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x (L/R-2ms)
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm)deep box. .3 A 125 VAC Inductive Non-Coded
(PF=0.35)
Accessories: SM6500 Electrical Box; C6500 Barrier
Inductive
Specifications for FRM-1(A) 1.5 A 25 VAC (PF=0.35) Non-Coded
Normal operating voltage: 15 to 32 VDC. Inductive
Maximum current draw: 6.5 mA(LED on). ��A 70.7 VAC (PF=0.35) Non-Coded
Average operating current: 230 uA direct poll;255 uA group
poll. Inductive
2 A 25 VAC (PF=0.35) Non-Coded
EOL resistance: not used.
Temperature range: 32°F to 120°F(0°C to 49°C). NOTE:Maximum(Speakers):70.7 V RMS,50 W
Humidity range: 10%to 93%non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x Product Line Information
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x NOTE:"A"suffix indicates ULC Listed model.
2.125" (53.975 mm)deep box.
FCM-1(A): Intelligent Addressable Control Module.
Accessories: SMB500 Electrical Box; CB500 Barrier
FRM-1(A): Intelligent Addressable Relay Module.
Agency Listings and Approvals A2143-20: Capacitor, required for Class A (Style Z) operation
of speakers.
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac- SMB500: Optional Surface-Mount Backbox.
tory for latest listing status. CB500: Control Module Barrier—required by UL for separat-
• UL: S635 ing power-limited and non-power limited wiring in the same
• ULC: S3705(A version only) junction box as FCM-1(A).
• FM Approved NOTE: For installation instructions,see the following documents:
• CSFM: 7300-0028:0219 • FCM-1(A)Installation document 156-1169.
• MEA: 14-00-E • FRM-1(A)Installation document 156-3502.
• FDNY:COA#6067,#6065 • Notifier SLC Wiring Manual,document 51253.
Notifier0 and FlashScanO are registered trademarks of Honeywell
International Inc.
�02011 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
I�O 9001 This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
_ We cannot cover all specific applications or anticipate all requirements.
EN6INEERIN6 8 MANUFACTURIN& All specifications are subject to change without notice.
QUALITY SYSTEMS MadeintheU.S.A.
For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118.
www.notifier.com
Page 2 of 2—DN-6724:B3•2/17/2011
DN-7087:C1
SpectrAlert� Advance N OT 1 F 1 E R°
Selectable Output ��
Notification Appliances by Honeywell
� . .�_ � - -
General � _
System SensorOO SpectrAlertOO Advance selectable-output
horns, strobes and horn/strobes are rich with features guaran- �, �='�'F• -
teed to cut installation times and maximize profits. The Spec- � �
trAlert Advance series of notification appliances is designed to �` �„
simplify your installations, with features such as: plug-in �
designs, instant feedback messages to ensure correct installa- Indoor Ceiling Outdoor Ceiling
tion of individual devices, and eleven field-selectable candela Horn/Strobe Strobe
settings for wall and ceiling strobes and horn/strobes.
More specifically, when installing Advance products, first °� �-
attach a universal mounting plate to a four-inch square, four- ;�_r��rw �;p�
inch octagon, or double-gang junction box. The two-wire �_!'� � '
mounting plate attaches to a single-gang junction box. - "- �
� �' �" �
Then, connect the notification appliance circuit wiring to the � - �'�
SEMS terminals on the mounting plate. Indoor Wall Indoor Ceiling
Finally, attach the horn, strobe, or horn/strobe to the mounting Horn/Strobe Strobe
plate by inserting the product's tabs in the mounting plate's
grooves. The device will rotate into position, locking the prod-
uct's pins into the mounting plate's terminals. The device will ��° ,.
temporarily hold in place with a catch until it is secured with a - �-''
captured mounting screw.
•
SpectrAlert Advance products allow you to choose: r
• 12 or 24 volts. Indoor Wall Outdoor Wall^
• 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, or 185 can- Horn Strobe
dela by way of a rear-mounted slide switch and front view- • Outdoor products rated from-40°F and 151°F (-40°C and
ing window. 66°C).
• Horn tones and volume by way of a rotary switch. • Outdoor products rainproof per UL50 (NEMA 3R) and
• The SpectrAlert Advance series includes outdoor notifica- Weatherproof per NEMA 4X, IP56
tion appliances. Outdoor strobes and horn/strobes (two- • Minimal intrusion into the backbox.
wire and four-wire) are available for wall or ceiling. Outdoor • Horn rated at 88+dbA at 16 volts.
horns are available for wall only.All System Sensor outdoor . Rotary switch for tone selection.
products are rated between -40°F and 151°F (-40°C and
66°C) in wet or dry applications. • Three horn volume settings.
Models available: • Electrically compatible with existing SpectrAlert products.
• Indoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire Engineering Specifications
horn/strobe.
• Indoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire SpectrAlert Advance horns, strobes, and horn/strobes shall
horn/strobe. mount to a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81
Outdoor wall-mount: horn, strobe, 2-wire horn/strobe, 4- cm) backbox,4.0" (10.16 cm)octagonal backbox, or a double-
• wire horn/strobe. gang backbox.Two-wire products shall also mount to a single-
gang 2.0"x 4.0"x 1.875" (5.08 x 10.16 x 4.763 cm)backbox.A
• Outdoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire universal mounting plate shall be used for mounting ceiling
horn/strobe. and wall products. The notification appliance circuit wiring
shall terminate at the universal mounting plate. Also, Spec-
Features trAlert Advance products, when used with the Sync•CircuitT"'
Plug-in design. Module accessory, shall be powered from a non-coded notifi-
� cation appliance circuit output and shall operate on a nominal
• Same mounting plate for wall-and ceiling-mount units. 12 or 24 volts. When used with the Sync•Circuit Module, 12-
• Shorting spring on mounting plate for continuity check volt rated notification appliance circuit outputs shall operate
before installation. between 9 and 17.5 volts; 24-volt rated notification appliance
• Captive mounting screw. circuit outputs shall operate between 17 and 33 volts. Indoor
SpectrAlert Advance products shall operate between 32°F and
• Tamper-resistance capability. 120°F (0°C and 49°C)from a regulated DC, or full-wave-recti-
• Field-selectable candela settings on wall and ceiling units: fied, unfiltered power supply. Strobes and horn/strobes shall
15, 15/75,30,75, 95, 110, 115, 135, 150, 177, 185. have field-selectable candela settings including 15, 15/75, 30,
• Automatic selection of 12 or 24 volt operation at 15 and 15/ 75,95, 110, 115, 135, 150, 177, 185.
75 candela.
• Outdoor wall and ceiling products.
DN-7087:C1 •11/9/11—Page 1 of 4
STROBE Operating Specifications
The strobe shall be a System Sensor SpectrAlert Advance . Standard operating temperature: 32°F to 120°F (0°C to
Model listed to UL 1971 and shall be approved for fire 49oC�
protective service.The strobe shall be wired as a primary-sig- K Series operating temperature: —40°F to 151°F (-40°C
naling notification appliance and comply with the Americans � to 66°C).
with Disabilities Act requirements for visible signaling appli-
ances, flashing at 1 Hz over the strobe's entire operating volt- • Humidity range: 10% to 93% non-condensing (indoor
age range.The strobe light shall consist of a xenon flash tube products).
and associated lens/reflector system. • Strobe flash rate: 1 flash per second.
HORN/STROBE COMBINATION • Nominal voltage: regulated 12 VDC/FWR or regulated 24
VDC/FWR. NOTE: Full Wave Rectified (FWR) voltage is a
The horn/strobe shall be a System Sensor SpectrAlert non-regulated, time-varying power source that is used on
Advance Model listed to UL 1971 and UL 464 and some power supply and panel outputs.
shall be approved for fire protective service. The horn/strobe � pperating voltage range: 8 V to 17.5 V(12 V nominal);or
shall be wired as a primary-signaling notification appliance 16 V to 33 V(24 V nominal). NOTE: P, S, PC,and SC prod-
and comply with the Americans with Disabilities Act require- ucts will operate at 12 V nominal only for 15 cd and 15/75
ments for visible signaling appliances,flashing at 1 Hz over the
strobe's entire operating voltage range. The strobe light shall cd.
consist of a xenon flash tube and associated lens/reflector sys- • Input terminal wire gauge: 12 to 18 AWG (3.31 to 0.821
tem.The horn shall have three audibility options and an option mmz).
to switch between a Temporal 3 pattern and a Non-Temporal • Ceiling-mount dimensions (including lens): 6.8" diame-
(continuous) pattern.These options are set by a multiple posi- ter x 2.5"deep(17.3 cm diameter x 6.4 cm deep).
tion switch.On four-wire products,the strobe shall be powered . N/all-mount dimensions(including lens):5.6" H x 4.7"W
independently of the sounder.The horn on horn/strobe models x 2.5" D(14.2 cm H x 11.9 cm W x 6.4 cm D).
shall operate on a coded or non-coded power supply.
• Horn dimensions: 5.6" H x 4.7" W x 1.3" D (14.2 cm H x
OUTDOOR PRODUCTS 11.9 cm W x 3.3 cm D).
SpectrAlert Advance outdoor horns, strobes and horn/strobes
shall be listed for outdoor use by UL and shall operate Agency Listings and Approvals
between —40°F and 151°F (-40°C and 66°C). The products The listings and approvals below apply to SpectrAlert Advance
shall be listed for use with a System Sensor outdoor/weather- Selectable Output Notification Devices. In some cases,certain
proof backbox with half-inch and three-fourths-inch conduit modules may not be listed by certain approval agencies, or
entries. listing may be in process. Consult factory for latest listing sta-
SYNCHRONIZATION MODULE tus.
The module shall be a System Sensor Sync•Circuit MDL3R or ' UL Listed: S4011 (HR_, HW_, P2_, P4_, PC2_,
MDL3W listed to UL 464 and shall be approved for fire protec- PC4_ models); S5512 (models SCR, SCRH, SCW,
tive service.The module shall synchronize SpectrAlert strobes SCWH, SR, SRH, SW, SWH); S3593 (SCRHK, SCRK,
at 1 Hz and horns at Temporal 3. Also, while operating the SRHK,SRK).
strobes, the module shall silence the horns on horn/strobe • ULC Listed: S4011 (HRA, HRKA); S5512 (typically "A"
models over a single pair of wires. The module shall mount to models, with exception of outdoor strobes). See Canadian
a 4.688"x 4.688"x 2.125" (11.906 x 11.906 x 5.398 cm)back- data sheet for listings and specifications.
box. The module shall also control two Style Y (class B) cir- . FM approved
cuits or one Style Z (Class A) circuit. The module shall MEA:452-05-E
synchronize multiple zones. Daisy-chaining two or more syn- �
chronization modules together will synchronize all the zones • CSFM: 7125-1653:0186 (SCR, SCRH, SCW, SCWH, SR,
they control. The module shall not operate on a coded power SRH, SW, SWH);7300-1653:0188(P2_, P4_, PC2_, PC4_
supply. modules); 7135-1653:0189 (HR, HRK, HW); 7300-
1653:0187(SCRHK, SCRK, SRHK,SRK).
Strobe Current Draw, Horn Current Draw,
UL Maximum (mA RMS) UL Maximum (mA RMS)
8-17.5V 16-33V Sound $-17.5V 16-33V
Candela Pattern dB
DC FWR DC FWR DC FWR DC FWR
15 123 128 66 71 Temporal High 57 55 69 75
15/75 142 148 77 81 Temporal Medium 44 49 58 69
Standard 30 NA N/A 94 96 Temporal Low 38 44 44 48
Candela 75 NA NA 158 153 Non-temporal High 57 56 69 75
Range g5 NA NA 181 176 Non-temporal Medium 42 50 60 69
110 NA NA 202 195 Non-temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
135 NA NA 228 207 Coded Medium 44 51 56 69
High 150 NA NA 246 220 Coded Low 40 46 52 50
Candela
Range 177 NA NA 281 251
185 NA NA 286 258
Page 2 of 4—DN-7087:C1•11/9/11
Horn and Horn/Strobe Horn and Horn/Strobe Output (dBA)
Rotary Switch Setting
8-17.5V 16-33V
Setting Repetition Rate dB Level Switch Sound dB
Position Pattern DC FW DC FW
1 Temporal horn High R R
2 Temporal horn Medium 1 Temporal High 78 78 84 84
3 Temporal horn Low 2 Temporal Medium 74 74 80 80
4 Normal horn High 3 Temporal Low 71 73 76 76
5 Normal horn Medium 4 Non-temporal High 82 82 88 88
6 Normal horn Low 5 Non-temporal Medium 78 78 85 85
7' Externally coded High 6 Non-temporal Low 75 75 81 81
8' Externally coded Medium 7" Coded High 82 82 88 88
9' Externally coded Low 8" Coded Medium 78 78 85 85
"NOTE:Settings 7, 8, and 9 are not available 9" Coded Low 75 75 81 81
on 2-wire horn/strobe. *NOTE:Settings 7, 8, and 9 are not available on 2-wire horn/strobe.
7tivo-Wire Horn/Strobe, STANDARDCandela Range (15 - 115 cd),
UL Maximum Current Draw (mA RMS)
Input, Sound Pattern, dB $-17.5 V 16—33 V
Level 15 15/75 15 15/75 30 75 95 110 115
DC Input,Temporal, High 137 147 79 90 107 176 194 212 218
DC Input,Temporal, Medium 132 144 69 80 97 157 182 201 210
DC Input,Temporal, Low 132 143 66 77 93 154 179 198 207
DC Input,Non-temporal, High 141 152 91 100 116 176 201 221 229
DC Input,Non-temporal, Medium 133 145 75 85 102 163 187 207 216
DC Input,Non-temporal,Low 131 144 68 79 96 156 182 201 210
FWR Input,Temporal, High 136 155 88 97 112 168 190 210 218
FWR Input,Temporal, Medium 129 152 78 88 103 160 184 202 206
FWR Input,Temporal,Low 129 151 76 86 101 160 184 194 201
FWR Input, Non-temporal, High 142 161 103 112 126 181 203 221 229
FWR Input, Non-temporal,Medium 134 155 85 95 110 166 189 208 216
FWR Input, Non-temporal,Low 132 154 80 90 105 161 184 202 211
Two-Wire Horn/Strobe, H/GHCandela Range (135 - 185 cd),
UL Maximum Current Draw (mA RMS)
16-33V 16-33V
DC Input FWR Input
135 150 177 185 135 150 177 185
DC,Temporal, High 245 259 290 297 FWR,Temporal, High 215 231 258 265
DC,Temporal, Medium 235 253 288 297 FWR,Temporal, Medium 209 224 250 258
DC,Temporal, Low 232 251 282 292 FWR,Temporal,Low 207 221 248 256
DC, Non-temporal, High 255 270 303 309 FWR, Non-temporal, High 233 248 275 281
DC, Non-temporal,Medium 242 259 293 299 FWR, Non-temporal,Medium 219 232 262 267
DC, Non-temporal,Low 238 254 291 295 FWR, Non-temporal,Low 214 229 256 262
7087dim12009.tif
�" � 6.8„
�
� �
�
� 2.5
5.6" �
� �
� I
I�2.5„
DN-7087:C1 •11/9/11—Page 3 of 4
Ordering Information
Model Description Model Description
WALL HORN/STROBES CEILING HORN/STROBES
P2R 2-wire horn/strobe,standard cd,red. PC2R 2-wire horn/strobe,standard cd, red.
P2RH 2-wire horn/strobe,high cd,red. PC2RH 2-wire horn/strobe,high cd,red.
P2RK 2-wire horn/strobe,standard cd,red,outdoor. PC2RK 2-wire horn/strobe,standard cd,red,outdoor.
P2RHK 2-wire horn/strobe,high cd,red,outdoor. PC2RHK 2-wire horn/strobe,high cd,red,outdoor.
P2W 2-wire horn/strobe,standard cd,white. PC2W 2-wire horn/strobe,standard cd,white.
P2WH 2-wire horn/strobe,high cd,white. PC2WH 2-wire horn/strobe, high cd,white.
P4R 4-wire horn/strobe,standard cd,red. PC4R 4-wire horn/strobe,standard cd,red.
P4RH 4-wire horn/strobe,high cd,red. PC4RH 4-wire horn/strobe, high cd,red.
P4RK 4-wire horn/strobe,standard cd,red,outdoor. PC4RK 4-wire horn/strobe,standard cd,red,outdoor.
P4RHK 4-wire horn/strobe,high cd,red,outdoor. PC4RHK 4-wire horn/strobe,high cd,red,outdoor.
P4W 4-wire horn/strobe,standard cd,white. PC4W 4-wire horn/strobe,standard cd,white.
P4WH 4-wire horn/strobe,high cd,white. PC4WH 4-wire horn/strobe, high cd,white.
WALL STROBES CEILING STROBES
SR Strobe,standard cd,red. SCR Strobe,standard cd,red.
SRH Strobe,high cd,red. SCRH Strobe,high cd,red.
SRK Strobe,standard cd,red,outdoor. SCRK Strobe,standard cd,red,outdoor.
SRHK Strobe,high cd,red,outdoor. SCRHK Strobe,high cd, red,outdoor.
SW Strobe,standard cd,white. SCW Strobe,standard cd,white.
SWH Strobe,high cd,white. SCWH Strobe,high cd,white.
A CCESSOR/ES HORNS
BBS-2A Backbox skirt,wall, red. HR Horn, red.
BBSW-2A Backbox skirt,wall,white. HRK Horn, red,outdoor.
BBSC-2A Backbox skirt,ceiling,red. HW Horn,white.
BBSCW-2A Backbox skirt,ceiling,white. ACCESSORIES,continued
SA-WBB Weatherproof backbox,wall. TR-HS Trim Ring,wall,red,package of 5
SA-WBBC Weatherproof backbox,ceiling. TRW-HS Trim Ring,wall,white, package of 5
WTP Weatherproof,flush mount plate,red TRC-HS Trim Ring,ceiling,red,package of 5
WTPW Weatherproof,flush mount plate,white TRCW-HS Trim Ring,ceiling,white, package of 5
NOTE: "High cd" refers to strobes that include 135, 150, 177, and 185 candela settings. "Standard cd" refers to strobes that
include 15, 15/75,30,75,95, 110,and 115 candela settings.
NOTE: For strobes and horn/strobes,add suffix"F"for French or"B"for Bilingual.
NOTE: All outdoor models("K(A)"suffix)include a plastic weatherproof backbox.
NOTE: Add"-R"to models for weatherproof replacement device (no back box included). Only for use with weatherproof outdoor
flush mounting plate,WTP and WTPW.
NOTE: Add"P"to model for plain housing. (No"FIRE"marking on cover.)
Sync•CircuitTM is a trademark and NOTIFIEROO and SpectrAlertOO are
registered trademarks of Honeywell International Inc.
�02011 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
I�O 9001 This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
ENGINEERING&MANUFACTURINC All specifications are subject to change without notice.
QUALITY SYSTEMS
For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118.
www.notifier.com
Page 4 of 4—DN-7087:C1•11/9/11
DN-5286:A1 •K-225
FM Series � N OT 1 F 1 E R°
Electromagnetic Door Holders �
by H o n eywe I I
General
FM Series electromagnetic door holders are designed for vir-
tually any remote door release application. They are primarily '
used to hold fire and smoke barrier doors open until released
by a remote smoke detector or other switching device. The
complete assembly consists of: an armature contact plate with � � - _ _ _
adjustable pivot mounting for installation in the door, and a
heavy-duty electromagnet, in a durable plastic enclosure,
mounted on the wall or floor behind the door.A separate clos-
ing device is required. �
Features
• All models support 12 VDC,24 VAC/VDC,or 120 VAC. ��` �
Improperly applied voltage does not damage the unit. SzasPn,.;P9 �
• Spacing kit for odd angles. �
• 25 to 40 pounds(11.3 kg)holding power.
• Magnet protected against transients and surges up to 600
volts(AC models). FM996
• Fail-safe operation; power failure releases door to close.
• Positive release button initiates closing motion.
• Two-year warranty. Ordering Information
• Floor-and wall-mount models. FM980: Surface floor-mount model for single door; 12 VDC,
24 VACNDC, 120 VAC.
Installation FM996: Surface wall-mount model; 12 VDC, 24 VACNDC,
• Used in hospitals, schools, offices, nursing homes, and 120 VAC.
public buildings. FM998: Flush wall-mount model; 12 VDC, 24 VAC/VDC, 120
• Install where required by code,where doors may be used to VAC.
confine smoke or fire, or wherever remote control or auto- FM900: Extension kit.
matic closing doors are required.
• Ensure that door hardware and trim projections are compat- FM900-Z: Extension kit,90°.
ible with total projection of door release. FM900-50: Spacer, 1/2" (1.27 cm).
• Anchor the electromagnet firmly, as the wall portion will FM900-75: Spacer,3/4"(1.905 cm).
function as a doorstop.
• Locate magnet approximately 6" (15.24 cm)in from the lock FM900-100: Spacer, 1" (2.54 cm).
stile at the door. Wall magnets should be mounted approxi-
mately two to four feet(0.61 to 1.22 meters)above the floor
for optimum performance.
• Door-mounted contact plate includes hardware for thrubolt-
ing or concealed mounting.
• Spotting template included with unit assures correct align-
ment.
• 14 AWG (2.0 mm2) maximum wire size.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases,certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
• UUULC Listed: R4869
• MEA Listed:447-00-E
• CSFM: 3550-0028:210
DN-5286:A1 •8/3/10—Page 1 of 2
• Concealed wiring.
43/4"(120.65 mm) 5"(127.00 mm) �_S�g
— �n�.z�s mm�--� �-sia" • Total floor space required: 6-5/8" (168
� (4445) mm).
� ---- • Mounting requirements: Conduit con-
— + — 3-1/8" – – 2-17132" _
(79.375) Isn.z+a� _ nects directly to floor plate.
I ----- • UL-Listed door holder.
�
• Voltage/current:
Model 980 szasmsaouf 120 VAC,60 Hz,0.020 amp.
FIOOr-MOUnt 24 VAC/VDC,60 Hz,0.020 amp.
Single DOOr 12 VDC,0.040 amp.
• Shipping weight:4 Ibs. (1.8 kg).
• Total projection: 4-1/8" (105 mm).
� �-���" �ss�as4,m� • Mounting requirements: 1-1/2" (38 mm) deep
�ss.s m�»� �atz�s� adapter housing.
j1 '� �aaas� • UL-Listed door holder.
� � � ______ • Shipping weight: 3 Ibs. (1.4 kg).
4-5�g 2-"�32" I Voltage/Current:
— �,n.a�emm� ' (2a2sa) _ '
� + ----- 120 VAC,60 Hz,0.020 amp.
O+
24 VACNDC,60 Hz,0.020 amp.
12 VDC,0.040 amp.
Model 996 5286m996tif
Wall Mount
Surface Wiring
• Total projection: 3-5/8" (92 mm).
� r��z5aomm� (e985mm) • Mounting requirements: 2" x 4" x 1-3/4"
j — vsis° (51 x 102 x 45 mm)outlet box.
1 16a6�s) �4445�� Wall must be properly reinforced and outlet
� f ______ • box adequately fastened.
a-eia° a��isz° _ _ i • UL-Listed door holder.
(117.475 mm) (24294) �
� � + --
January 20,2000 DN-6755• K-150
N OT 1 F 1 E R� PAM-� and PAM-2
F/RE SYSTEMS Multi-Voltage Relay Modules
Section: Miscellaneous
GENERAL
Air Products&Controls, Inc.PAM-1 and PAM-2 Multi-Volt- M EA � California
a e Rela Modules are enca sulated multi-volta e de- � State Fire
9 Y p 9 c� 73-92-E f ;:���� Marshal
vices. The PAM-1 relay provides 10.0 Amp Form-C con- VoL XXI � �; 7300-1004:101
tacts and may be energized by one of three input voltages: S3403
24 VAC, 24 VDC, or 115 VAC. The PAM-2 relay provides
7.0 Amp Form-C contacts and may be energized by one of
two input voltages: 12 VDC or 24 VDC. �
A red LED is provided on both models. When illuminated, `�
it indicates the relay coil is energized. �r{
Either model may be mounted by using the double-sided � ' ��`,� � �
�
adhesive tape,the self-drilling screw, or by placing loosely �� .:� �
in a backbox. �
� -= �_, �,
PAM-1 and PAM-2 Relay Modules are ideal for applica- U
tions where remote relays are required for control or status
feedback. They are suitable for use with HVAC,tempera- a �
ture control,fire alarm, security, energy management, and r �,,
lighting control systems. � �f .��`
SPECIFICATIONS _ ,�
Power requirements: for PAM-1: 0.015 Amps per posi- ..» �"�-- --- �
tion @ 24 VDC, 24 VAC, 115 VAC; for PAM-2: 0.015
Amps per position @ 12 VDC or 24 VDC.
Re�ay: u�-recognized SP�T. PRODUCT LINE INFORMATION
Contact rating, PAM-1: 10.0 A@ 115 VAC; 7.0 A@ 28 PAM-1 Single SPDT relay with LED, double-sided
VDC; 250 �aA @ 5 VDC. adhesive tape, mounting screw, 12" (304.8
mm)leads and six wire-nuts. Powerrequire-
Contact rating, PAM-2: 7.0 A@ 115 VAC; 7.0 A@ 28 ments: 0.015 Amps per position @ 24 VDC,
VDC; 250 �A @ 5 VDC. 24 VAC, 115 VAC. Contact rating: 10.0 A
Ambient temperature range: —58°F to+185°F(-50°C to @ 115 VAC, 7.0 A@ 28 VDC, 250 �A @ 5
+85°C). VDC.
Dimensions: 1.500" (38.100 mm) high x 1.000" (25.400 PAM-2 Single SPDT relay with LED, double-sided
mm)wide x 0.875"(22.225 mm)deep,with 12"(304.8 mm) adhesive tape, mounting screw, 12" (304.8
wire leads @ 18 AWG (0.75 mmz). mm)leads and six wire-nuts. Powerrequire-
ments: 0.015 Amps per position @ 12 VDC
WIRING DIAGRAMS or 24 VDC. Contacf rating: 7.0 A@ 115
VAC; 7.0 A@ 28 VDC; 250 NA @ 5 VDC.
Relay-Energized LED
1
(-) N N wHT p I i BLU C ' AT LEFT: Installation wiring
�„� BLK � YEL NC 10.0 Amp forPAM-1 model.
Contacts
�+� C RED �_ ORG N� �OW: Installation wiring
for PAM-2 model.
� � '� 115VAC@0.015Amp
3 24 VAC @ 0.015 Amp Relay-Energized LED
� 24 VDC @ 0.015 Amp �V �_� wHT � �' , BLU C
O I _
� 3 +24V GRY � YEL NC 7.0 Amp
Contacts
� +12V RED � � ORG NO
This document is not intended to be used for installation purposes. We try to keep our I�O �oo�
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information,contact NOTIFIER. Phone:(203)484-7161 FAX:(203)484-7118 _ ,
�j� N OTI FI E R 12 Clintonville Road, Northford, Connecticut o6472 ENGINEERING&MANUFACTURING
DN-6755•01/20/00 — Page 1 of 1