HomeMy WebLinkAboutB12-0211 - CR1 - 062712 TOV COMMENT RESPONSES
June 15, 2012
Mark Donaldson
Victor Mark Donaldson Architects
RE: Graham Residence
Town of Vail Comments
Dear Mark:
The enclosed is the Architectural Engineering Consultants (AEC) response to the Town of Vail plan
comments. We have been asked to verify the roof drain sizes shown on Sheet A1.5 due to the
expansion of the deck at Unit 4.
The existing deck size is 474 square feet and will be expanded by 58 square feet to a total
proposed size of 532 square feet. Per the 2009 International Plumbing Code (IPC) Section 1106.2,
vertical pipes serving the roof drains shall be a minimum of 2.” Per the 2009 IPC Section 1106.3,
horizontal pipes serving the roof drains shall be a minimum of 3.” Any vertical pipe connected
downstream of the horizontal pipes shall be the same size as the horizontal pipe or larger.
Contractor to verify pipe sizes in field.
Please let me know if you have any questions.
Architectural Engineering Consultants
David G. Denio, E.I.T