Vail Fire & Emergency Services 42 West Meadow Drive Vail, Colorado 81657 970-479-2250
B06-0352
P 0.0.1 Piping to gas meters must be approved by Excell Energy. Provide valve tags and separate feed to emergency generator.
E 0.0.10 – 14 Electrical panels seem to include breakers for fire and smoke dampers, exits signs and related elements scattered through out. Please explain the intent. Are these panels
remotely located per floor or designed to accommodate functions per floor?
L 300 Locks on pool gates must provide fire dept access. Submit spec’s on fire pit and 100% shut off valve location.
A 0.1.0 Boiler room L116 exit door is blocked by parking space.
Elevator lobby L 104 and Trash room L 103 cannot share common space.
A 0.1.1 I did not find sheet Axxxx for detail on fire extinguishers. Locate per NFPA 10 at a minimum.
L 133 A is too close to chemical cleaning. Chemical cleaning should not be common to the laundry. Specify the type and
volume of chemicals.