HomeMy WebLinkAboutB12-0301 comment letter Date: 7/24/2012 Re: B12-0301 2477 Garmisch Drive Dear Mr. Curran RESPONSE INSTRUCTIONS ● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING COMMENTS Architectural Comments: 1. Window wells to be a minimum of 36” wide and 9 square feet. Revise plans 2. Provide complete ladder dimensions reflecting dimensional requirements of section 310.2 IRC 3. Ladder to extend the full height of the well 4. Ladder allowed to encroach only 6” into the required window well width. Revise plans 5. Minimum spacing of ladder from wall is 3” per section 310. Annotate on plans 6. CO detectors are required throughout the homes per the IRC. Annotate on plans Structural Comments: 1. See item 1 Architectural comments Plumbing Comments: 1. Plans do not reflect the gas piping changes. Revise plans Mechanical Comments: NA Electrical Comments: NA PLANNING COMMENTS Reviewed and accepted FIRE COMMENTS NA PUBLIC WORKS COMMENTS NA Sincerely, Martin A. Haeberle Chief Building Official