HomeMy WebLinkAboutB12-0355 ComCheck COMcheck Software Version 3.9.1
Interior Lighting and Power
Compliance Certificate
90.1 (2007) Standard
Section 1: Project Information
Project Type: New Construction
Project Title : Gore Creek Tenant Renovation
Construction Site: Owner/Agent: Designer/Contractor:
193 East Gore Creek Drive Jeff Mullikin
Vail,CO 81657 Architectural Engineering Design Group
1900 Wazee Street,Suite#350
Denver,CO 80202
303.296.3034
Section 2: Interior Lighting and Power Calculation
A B C D
Area Category Floor Area Allowed Allowed Watts
��tz� watts i�tz �e X c�
Main Dining Area(Common Space Types:Dining Area-Family Restaurant) 1614 2.1 3389
Allowance:Decorative Appearance/Fix. ID:C 360(a) 1 360(b)
Allowance:Decorative Appearance/Fix. ID: E 400(a) 1 150(b)
Allowance:Decorative Appearance/Fix. ID:J 450(e) 1 450(b)
Allowance:Decorative Appearance/Fix. ID: L 131(a) 1 131(b)
Bar Dining Area(Common Space Types:Dining Area-Bar Lounge/Leisure) 180 1.4 252
Kitchen(Common Space Types:Food Preparation) 1172 1.2 1406
Restrooms(Common Space Types:Restrooms) 580 0.9 522
Electrical Room(Common Space Types:Electrical/Mechanical) 74 1.5 111
Bar Storage Area(Common Space Types:Active Storage) 195 0.8 156
Total Allowed Watts= 6928
(a)Area claimed must not exceed the illuminated area permitted for this allowance type.
(b) Allowance is(B x C)or the actual wattage of the fixtures given in Section 2,whichever is Iess.
(e) Additional controls/switching allowances are based on number of fixtures or wattage controlled, not floor area of allowance.
Section 3: Interior Lighting Fixture Schedule
A B C D E
Fixture ID: Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Main Dining Area(Common Space Types:Dining Area-Family Restaurant 1614 sq.ft.)
Halogen 1:A: PINSPOT RECESSED CAN/Halogen MR-16 50W 1 20 50 1000
Linear Fluorescent 1: B:2X2 RECESSED TROFFER/24"T8 17W/Electronic 3 7 54 378
Linear Fluorescent 2:C: LINEAR WALL WASHER/46"T5 28W/Electronic 2 6 66 396
Halogen 2:D: PROJECTOR LIGHT/Halogen MR-16 50W 1 27 50 1350
Incandescent 1:E: LED TAPE LIGHT(3W/LF)/Other 1 50 3 150
Compact Fluorescent 1: F: KITCHEN RECESSED DOWNLIGHT/Triple 4-pin 42W/ 1 23 45 1035
Electronic
Halogen 3:H: RECESSED DOWNLIGHT DINING RM/Halogen MR-16 50W 1 16 50 800
Halogen 4:J:SLOTTED WALL WASHER/Halogen MR-16 50W 1 24 50 1200
Linear Fluorescent 3: K: INGRADE UPLIGHT WALL WASHER/22"T5 HO 24W/ 1 5 32 Exempt
Electronic
Exemption:Retail Display Window
Halogen 5:L:RECESSED DOWNLIGHT DEC/Halogen MR-16 50W 1 9 50 450
Linear Fluorescent 4: M:VAPOR TIGHT CEILING SURFACE/48"T8 32W/Electronic 2 3 65 Exempt
Project Title: Gore Creek Tenant Renovation Report date: 08/06/12
Data filename:J:\2280.00-Gore Creek TI\Ltg Calcs\228000LCO2-Space x Space ASHRAE90_1.cck Page 1 of
Exemption:Lighting in Refrigerator/Freezer Cases
Linear Fluorescent 5: N:STORAGE STRIP LIGHTING/48"T8 32W/Electronic 2 2 65 130
Bar Dining Area(Common Space Types:Dining Area-Bar Lounge/Leisure 180 sq.ft.)
Kitchen(Common Space Types:Food Preparation 1172 sq.ft.)
Restrooms(Common Space Types:Restrooms 580 sq.ft.)
Electrical Room(Common Space Types:Electrical/Mechanical 74 sq.ft.)
Bar Storage Area(Common Space Types:Active Storage 195 sq.ft.)
Total Proposed Watts= 6889
Section 4: Requirements Checklist
Lighting Wattage:
0 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies
6928 6889 YES
0 2. Exit signs 5 Watts or less per sign.
Controls, Switching, and Wiring:
0 3. Independent manual or occupancy sensing controls for each space(remote switch with indicator allowed for safety or security).
� 4. Occupant sensing control in class rooms,conference/meeting rooms,and employee lunch and break rooms.
Exceptions:
� Spaces with multi-scene control;shop classrooms,laboratory classrooms,and preschool through 12th grade classrooms.
� 5. Automatic shutoff control for lighting in>5000 sq.ft buildings by time-of-day device,occupant sensor,or other automatic control.
Exceptions:
� 24 hour operation lighting;patient care areas;where auto shutoff would endanger safety or security.
� 6. Master switch at entry to hotel/motel guest room.
0 7. Separate control device for display/accent lighting,case lighting,task lighting,nonvisual lighting,lighting for sale,and demonstration
lighting.
� 8. Tandem wired one-lamp and three-lamp ballasted luminaires(No single-lamp ballasts).
Exceptions:
� Electronic high-frequency ballasts.
� Luminaires not on same switch.
� Recessed luminaires 10 ft.apart or surface/pendant not continuous.
� Luminaires on emergency circuits.
Voltage Drop:
� 9. Feeder conductors have been designed for a maximum voltage drop of 2 percent.
� 10.Branch circuit conductors have been designed for a maximum voltage drop of 3 percent.
r- . •- ..-
Section 5: Compliance Statement
Compliance Statement.� The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 90.1 (2007)Standard
requirements in COMcheck Version 3.9.1 and to comply with the mandatory requirements in the Requirements Checklist.
Jeff Mullikin, Principal 8/6/2012
Name-Title Signature Date
Section 5: Post Construction Compliance Statement
Record Drawings and Operating and Maintenance Manuals:
� 1. Construction documents with record drawings and operating and maintenance manuals provided to the owner.
Project Title: Gore Creek Tenant Renovation Report date: 08/06/12
Data filename:J:\2280.00-Gore Creek TI\Ltg Calcs\228000LCO2-Space x Space ASHRAE90_1.cck Page 2 of
Lighting Designer or Contractor Name Signature Date
Project Title: Gore Creek Tenant Renovation Report date: 08/06/12
Data filename:J:\2280.00-Gore Creek TI\Ltg Calcs\228000LCO2-Space x Space ASHRAE90_1.cck Page 3 of