HomeMy WebLinkAboutB12-0382 FORD AMPHITHEATERTOWN OF VAIL%
Department of Community Development
75 South Frontage Road
Vail, CO 81657
Tel: 970 - 479 -2128
www.vailgov.com
Development Review Coordinator
BUILDING PERMIT APPLICATION
(Separate applications are required for alarm & sprinkler)
Project Street Address:
530 S. Frontage Road
(Number) (Street) (Suite #)
Building /Complex Name: Gerald R. Ford Amphitheater
Contractor Information
Business Name: TBD
Business Address:
City State: Zip:
Contact Name:
Contact Phone:
Contact E -Mail:
I hereby acknowledge that I have read this application, filled out
in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to
comply with the information and plot plan, to comply with all Town
ordinances and state laws, and to build this structure according to
the town's zoning and subdivision codes, design review ap-
proved, International Building and Residential Codes and other
ordinances of the,rfown applicable thereto.
X t-
Owner /Own,6r's Representative Signature (Required)
Applicant Information
Applicant Name: Jack Hunn, Owner's Representative
Applicant Phone: 970.390.4537
Applicant E -Mail: jackhunn @yahoo.com
Project Information
Owner Name: Vail Valley Foundation
Parcel #: 210108100002
(For Parcel #, contact Eagle County Assessors Office at (970- 328 -8640 or visit
www.eaglecounty.us/patie)
For Office Use Only
Fee Paid:
Received From:
Cash Check #
CC: Visa / MC Last 4 CC #
Auth #
exp date:
Project #: prW % �0 (D
DRB #:
Building Permit #:
Lot #: Block # Subdivision: QtJ PLfFiTE�0
Work Class: New 0 Addition O Alteration
Type of Building:
Single - Family 0 Duplex () Multi - Family 0
Commercial 1F Other 0
Work Type: Interior Q Exterior O Both I\Z
Valuation of
Work Included Plans Included Work
Electrical ('-"Yes
O)No
(F)Yes
ONo 24000
Mechanical Yes
O)No
(�i Yes
ONo 16000
Plumbing Yes
0No
G)Yes
0No 52000
Building ( Yes
O)No
Yes
ONo 350000
Value of all work being performed: $ 442000
(value based on IBC Section 109.3 & IRC Section 108.3)
Electrical Square Footage 1,050
Detailed Scope and Location of Work:
The project includes the construction of a new
accessory restroom building, and limited improvements
to the existing buildings. Site improvements to the
lawn seating areas and construction of a new terrace
are also included.
(use additional sheet if necessary)
Date Received:
AUG 21 &7v
t✓'`
TOWN OF VAIL
12- Mar-2012
COMcheck Software Version 3.9.0
Interior Lighting Compliance
Certificate
2009 IECC
Section 1: Project Information
Project Type: New Construction
Project Title : Ford Park Amphitheater Lower West Restroom
Construction Site:
Owner /Agent:
Section 2: Interior Lighting and Power Calculation
Designer /Contractor:
A
B
C
D
Area Category
Floor Area
Allowed
Allowed Watts
(ft2)
Watts / ft2
(B x C)
East Restrooms (Performing Arts Theater)
762
1.6
1219
Stage Left Restrooms (Performing Arts Theater)
1652
1.6
2643
Total Allowed Watts =
3862
Section 3: Interior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B C D E
Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
East Restrooms ( Performing Arts Theater 762 sq.ft.)
Incandescent 1: D: LED downlight / Incandescent 20W 1 19 20 380
Linear Fluorescent 1: F: Linear fluorescent perimeter / 48" T8 32W (Super T8) / Electronic 1 12 32 384
Stage Left Restrooms ( Performing Arts Theater 1652 sq.ft.)
Incandescent 2: D: LED downlight / Incandescent 20W 1 30 20 600
Linear Fluorescent 2: F: Linear fluorescent perimeter / 48" T8 32W (Super T8) / Electronic 1 40 32 1280
Total Proposed Watts = 2644
Section 4: Requirements Checklist
Lighting Wattage:
F1 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies
3862 2644 YES
Controls, Switching, and Wiring:
i] 2. Daylight zones under skylights more than 15 feet from the perimeter have lighting controls separate from daylight zones adjacent to
vertical fenestration.
❑ 3. Daylight zones have individual lighting controls independent from that of the general area lighting.
Exceptions:
❑ Contiguous daylight zones spanning no more than two orientations are allowed to be controlled by a single controlling device.
❑ Daylight spaces enclosed by walls or ceiling height partitions and containing two or fewer light fixtures are not required to have a
separate switch for general area lighting.
I] 4. Independent controls for each space (switch /occupancy sensor).
Exceptions:
Project Title: Ford Park Amphitheater Lower West Restroom Report date: 08/01/12
Data filename: P: \Current Projects \12029.00 - Ford Park Lower Bench & East Ampitheater Restrooms \Calculations \COMcheck \2012 -0801
COMCHECK.cck Page 1 of 4
❑ Areas designated as security or emergency areas that must be continuously illuminated.
❑ Lighting in stairways or corridors that are elements of the means of egress.
❑ 5. Master switch at entry to hotel /motel guest room.
❑ 6. Individual dwelling units separately metered.
❑ 7. Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
❑ 8. Each space required to have a manual control also allows for reducing the connected lighting load by at least 50 percent by either
controlling all luminaires, dual switching of alternate rows of luminaires, alternate luminaires, or alternate lamps, switching the middle
lamp luminaires independently of other lamps, or switching each luminaire or each lamp.
Exceptions:
❑ Only one luminaire in space.
❑ An occupant- sensing device controls the area.
❑ The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
❑ Areas that use less than 0.6 Watts /sq.ft.
❑ 9. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
❑ Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
❑ 10.Photocell /astronomical time switch on exterior lights.
Exceptions:
❑ Lighting intended for 24 hour use.
❑ 11.Tandem wired one -lamp and three -lamp ballasted luminaires (No single -lamp ballasts).
Exceptions:
❑ Electronic high- frequency ballasts; Luminaires on emergency circuits or with no available pair.
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2009 IECC
requirements in COMcheck Version 3.9.0 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title
Signature Date
Project Title: Ford Park Amphitheater Lower West Restroom Report date: 08/01/12
Data filename: P: \Current Projects \12029.00 - Ford Park Lower Bench & East Ampitheater Restrooms \Calculations \COMcheck \2012 -0801
COMCHECK.cck Page 2 of 4
COMcheck Software Version 3.9.0
Exterior Lighting Compliance
Certificate
2009 IECC
Section 1: Project Information
Project Type: New Construction
Project Title : Ford Park Amphitheater Lower West Restroom
Exterior Lighting Zone: 2 (Neighborhood business district)
Construction Site: Owner /Agent: Designer /Contractor:
Section 2: Exterior Lighting Area /Surface Power Calculation
A B C D E F
Exterior Area /Surface Quantity Allowed Tradable Allowed Proposed
Watts Wattage Watts Watts
/ Unit (B x C)
East Restrooms (Main entry) 6 ft of door width 20 Yes 120 60
Total Tradable Watts* = 120 60
Total Allowed Watts = 120
Total Allowed Supplemental Watts ** = 600
* Wattage tradeoffs are only allowed between tradable areas /surfaces.
** A supplemental allowance equal to 600 watts may be applied toward compliance of both non - tradable and tradable areas /surfaces.
Section 3: Exterior Lighting Fixture Schedule
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
East Restrooms ( Main entry/exit 2 ft of door width): Tradable Wattage
Incandescent 1: D: LED recessed downlight / Incandescent 20W
20 60
East Restrooms ( Main entry 6 ft of door width): Tradable Wattage
Total Tradable Proposed Watts = 60
Section 4: Requirements Checklist
Lighting Wattage:
1. Within each non - tradable area /surface, total proposed watts must be less than or equal to total allowed watts. Across all tradable
areas /surfaces, total proposed watts must be less than or equal to total allowed watts.
Compliance: Passes.
Controls, Switching, and Wiring:
❑ 2. All exemption claims are associated with fixtures that have a control device independent of the control of the nonexempt lighting.
Lj 3. Lighting not designated for dusk -to -dawn operation is controlled by either a a photosensor (with time switch), or an astronomical time
switch.
4. Lighting designated for dusk -to -dawn operation is controlled by an astronomical time switch or photosensor.
5. All time switches are capable of retaining programming and the time setting during loss of power for a period of at least 10 hours.
Exterior Lighting Efficacy:
❑ 6. All exterior building grounds luminaires that operate at greater than 100W have minimum efficacy of 60 lumen /watt.
Project Title: Ford Park Amphitheater Lower West Restroom Report date: 08/01/12
Data filename: P: \Current Projects \12029.00 - Ford Park Lower Bench & East Ampitheater Restrooms \Calculations \COMcheck \2012 -0801
COMCHECK.cck Page 3 of 4
Exceptions:
❑ Lighting that has been claimed as exempt and is identified as such in Section 3 table above.
J Lighting that is specifically designated as required by a health or life safety statue, ordinance, or regulation.
❑ Emergency lighting that is automatically off during normal building operation.
LJ Lighting that is controlled by motion sensor.
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2009 IECC
requirements in COMcheck Version 3.9.0 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title
Signature Date
Project Title: Ford Park Amphitheater Lower West Restroom Report date: 08/01/12
Data filename: P: \Current Projects \12029.00 - Ford Park Lower Bench & East Ampitheater Restrooms \Calculations \COMcheck \2012 -0801
COMCHECK.cck Page 4 of 4