HomeMy WebLinkAboutA12-0046 SCOPE OF WORK LETTERCSWC
Commercial Specialists of Western Colorado, LLC
210 Marmot Lane Unit 5B / PO Box **** Eagle, Colorado 81631
Voice (970) 328.1951 Fax (970) 328.1956
August 22, 2012
Vail Fire Department
42 West Meadow Drive
Vail, CO 81657
Attn: Mike Vaughan – Fire Marshal
Pjct : Mill Creek Court Unit 401
Re : Scope of Work for Fire Alarm System
Dear Mike,
The following is a scope of work to be performed for the remodel of unit 401 at the Mill Creek
Court Building. George Shaffer Construction is doing the remodel work in this unit. During
the construction they will be removing all the walls and ceilings in the unit, therefore our scope
of work for this unit will be to install one centrally located heat detector during construction.
We will be pulling new wire throughout the space to provide the required support of NFPA-72
and to meet the installation standards of Vail Fire department. All of the devices are going to
be reinstalled in their current locations. As a part of the multiple remodels occurring on site,
the home owners association has agreed to upgrade the existing NFS-640 fire control panel
to a new NFS2-3030 UL 9th edition panel in order to utilize the new multi-criteria smoke / heat
/ CO detectors and the new addressable sounder bases. This will allow them to change the
living room devices to the new FCO-851 and not have to install separate CO detection.
All of the existing sounder bases will be removed and changed out to the new B200S
addressable sounder base to achieve both general alarm temporal three and the required
temporal four for CO.
Once rough-in has been completed CSWC will contact Vail Fire for a rough-in inspection, and
upon completion of installation and testing CSWC will again contact Vail Fire to a final fire
alarm test of the unit.
If there are any questions or concerns about the above information, please feel free to contact
me at any time.
Sincerely,
Commercial Specialists of Western Colorado, LLC
Tim Ward
Tim Ward
General Manager