HomeMy WebLinkAboutA12-0052 Stamped approved plansWIRE AND CONDUIT CHARACTERISTICS Wire Schedule Cable / Wire Desigination Conductor size Insulation Number of Conductors Conductor Dia. (in) Conductor / Cable Area (sq-in) Conduit Size (in) Conduit ID (in) Area (sq-in) A (SLC)16AWGCABLE2 Con Cable0.1760.02431/20.6220.304 B (Strobes)14AWGTHHN20.1110.01943/40.8240.533 C (Speakers)16AWGCABLE2 Con Cable0.1780.024911.0490.864 D (24VDC)14AWGCABLE20.1110.0194 E (RS-485)16AWGCABLE2 Con Cable0.1780.02491-1/41.3801.496 G (IDC)16AWGTHHN20.0960.01451-1/21.6102.036 22.0673.356 I (Sounder Base Interconnect)16AWGTHHN10.0960.00722-1/22.7315.858 33.3568.846 Fire alarm cable for Signaling Line Circuit (SLC) type "A" shown in wire schedule is : Non Plenum 16awg, non shielded, 2cond, solid, TYPE FPLR. OD =0.176 Each B circuit consists of 2 #14 conductors Fire alarm cable for Speaker Circuit type "C" shown in wire schedule is : Non Plenum 16awg, OA shielded, 2cond, solid, TYPE FPLR. OD =0.178 Each D circuit consists of 2 #14 conductors Fire alarm cable for RS-485 Circuit type "E" shown in wire schedule is : Non Plenum 16awg, OA shielded, 2cond, solid, TYPE FPLR. OD =0.178 Each G circuit consists of 2 #16 conductors Each I circuit consists of 1 #16 conductor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alculation Column 1 Primary, Non-Fire Alarm Current (amps) Calculation Column 2 Primary, Fire Alarm Current (amps) DEVICEQTY.AMPS.TOTALQTY.AMPS.TOTAL IFC-32010.25000.250010.23000.2300 KDM-R2 DISPLAY10.10000.100010.10000.1000 ACPS-240600.12870.000000.00000.0000 BACNet Gateway00.36000.000000.36000.0000 LCD-80,LCD-80TM00.10000.000000.10000.0000 JNCA00.40000.000000.50000.0000 LDM-3200.04000.000000.0000 UZC-25600.03500.000000.08500.0000 AMG-1,AMG-E00.06000.000000.06000.0000 FFT-7,FFT-7S00.06000.000000.12000.0000 AA-300 0 AA-100,AA-1200 0 M302MJ,M502MJ00.00940.000000.09000.0000 XPIQ00.000000.0000 RPT-W,RPT-WF,RPT-F,NCM-W10.01700.017010.01700.0170 UDACT Communicator00.04000.000000.10000.0000 Notification Appliance110.00000.0000 SOUNDER BASES00.00100.000000.01500.0000 Power Supervision Relays00.02000.000000.02000.0000 DH500,DH502 Duct Detectors00.000000.0000 CHG-120 Battery Charger0 0 SLC #1 Totals10.20000.200010.20000.2000 TOTAL 0.570.55 TOTAL CURRENT - STANDBY OPERATION0.567 HOURS REQUIRED FOR OPERATION 24 BATTERY REQUIREMENTS FOR 4 HRS13.61 TOTAL CURRENT - ALARM OPERATION0.547 HOURS REQUIRED FOR OPERATION (5min)0.08 BATTERY REQUIREMENTS FOR 5 MIN0.05 TOTAL BATTERY REQUIREMENTS 13.65 BATTERY REQUIRED WITH 20% FACTOR16.38 BATTERY TO BE INSTALLED 18 AMP-HR DIGITAL AMPLIFIER DA2 BATTERY BACKUP OPERATION ON BATTERY BACKUP POWER DEVICE TYPE QTYSTAND-BY CURRENT QTYALARM CURRENT EACHTOTALEACHTOTAL DAA-5025/70 DIG. AMP.10.3800.38010.9000.900 Speaker - 1/8 watt tap80.0000.00080.0100.080 Speaker - 1/4 watt tap140.0000.000140.0200.280 Speaker - 1/2 watt tap20.0000.00020.0400.080 Speaker - 1 watt tap290.0000.000290.0802.320 Speaker - 2 watt tap00.0000.00000.1600.000 TOTAL Watts 35 TOTAL CURRENT 0.3803.660 TOTAL CURRENT - STANDBY OPERATION0.380 HOURS REQUIRED FOR OPERATION 24.00 BATTERY STANDBY REQUIREMENTS9.12 TOTAL CURRENT - ALARM OPERATION3.660 HRS REQUIRED FOR OPERATION 0.250(15 MIN) BATTERY ALARM REQUIREMENT 0.92 TOTAL BATTERY REQUIREMENTS 10.04 BATTERY REQUIRED WITH 20% FACTOR 12.04 12 AMP-HOUR BATTERIES INSTALLED WATTS OUT AVAILABLE WATTAGE50 OUT TOTAL WATTS35 OUT SPARE CAPACITY =31% Project NameSolaris Date6/25/2012 Circuit NumberRemote Power Supply #2 / RPS2-1 VoltageVoltageVoltage LocationGarage Level Partial Area 1CurrentDistanceDropCurrentDistanceDropCurrentDistanceDrop Nominal System Voltage20.41.380655 4.03 1.380655 5.767 1.380655 2.883 Minimum Device Voltage16End of Line Voltage 16.37 End of Line Voltage 14.63 End of Line Voltage 17.52 Total Circuit Current1.380WireOhm'sPercent Drop19.76%Percent Drop28.27%Percent Drop14.13% GaugePer 1000 Distance from source to 1st device190143.19 Wire Gauge for balance of circuit143.1918=7.7716=4.8914=3.1912=1.9810=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: DeviceDeviceprevious AtDrop fromPercentWire resistance is doubled in the calculations for two wires (Positive and Negative) NumberCurrentdeviceDevicesourceDropThe voltage calculated to the last device in any method must not be lower then Device 10.06019018.731.6738.20%the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 20.2207018.142.26211.09% Device 30.2207017.652.75413.50%Device ManufacturerWheelockDevice ManufacturerWheelock Device 40.2207017.253.14715.42% Device 50.22016516.563.84118.83%Candela Candela Device 60.2204516.433.96819.45%Speaker/Strobes (Wall Mount)Strobes (Wall Mount) Device 70.2204516.374.03119.76%E70-24MCW-FW150.060RSS-24MCW-FW150.060 END 16.374.03119.76%E70-24MCW-FW300.092RSS-24MCW-FW 300.092 END 16.374.03119.76%E70-24MCW-FW750.165RSS-24MCW-FW 750.165 END 16.374.03119.76%E70-24MCW-FW1100.220RSS-24MCW-FW1100.220 END 16.374.03119.76%E70-24MCWH-FW1350.300RSS-24MCWH-FW1350.300 END 16.374.03119.76%E70-24MCWH-FW1850.420RSS-24MCWH-FW1850.420 END 16.374.03119.76% END 16.374.03119.76%Speaker/Strobes (Ceiling Mount)Speaker/Strobes (Wall Mount) END 16.374.03119.76%E90-24MCC-FW150.065RSS-24MCC-FW 150.065 END 16.374.03119.76%E90-24MCC-FW300.105RSS-24MCC-FW 300.105 END 16.374.03119.76%E90-24MCC-FW750.189RSS-24MCC-FW 750.189 END 16.374.03119.76%E90-24MCC-FW950.249RSS-24MCC-FW 950.249 END 16.374.03119.76%E90-24MCCH-FW1150.300RSS-24MCCH-FW1150.300 END 16.374.03119.76%E90-24MCCH-FW1770.420RSS-24MCCH-FW1770.420 Totals1.380655End of Line Voltage 16.37 AMPS OUT AVAILABLE CURRENT3 OUT TOTAL CURRENT1.380 OUT SPARE CAPACITY =54% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point MethodEnd of Line MethodLoad Centering Method TotalsTotalsTotals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 maVoltage Current @Rated Voltage Current @Rated Voltage Model # Project NameSolaris Date6/25/2012 Circuit NumberRemote Power Supply #2 / RPS2-2 VoltageVoltageVoltage LocationGarage Level Partial Area 1CurrentDistanceDropCurrentDistanceDropCurrentDistanceDrop Nominal System Voltage20.40.885590 2.20 0.885590 3.331 0.885590 1.666 Minimum Device Voltage16End of Line Voltage 18.20 End of Line Voltage 17.07 End of Line Voltage 18.73 Total Circuit Current0.885WireOhm'sPercent Drop10.78%Percent Drop16.33%Percent Drop8.16% GaugePer 1000 Distance from source to 1st device215143.19 Wire Gauge for balance of circuit143.1918=7.7716=4.8914=3.1912=1.9810=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: DeviceDeviceprevious AtDrop fromPercentWire resistance is doubled in the calculations for two wires (Positive and Negative) NumberCurrentdeviceDevicesourceDropThe voltage calculated to the last device in any method must not be lower then Device 10.06021519.191.2145.95%the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 20.2208018.761.6358.01% Device 30.2206018.531.8679.15%Device ManufacturerWheelockDevice ManufacturerWheelock Device 40.2206018.392.0149.87% Device 50.16517518.202.19810.78%Candela Candela END 18.202.19810.78%Speaker/Strobes (Wall Mount)Strobes (Wall Mount) END 18.202.19810.78%E70-24MCW-FW150.060RSS-24MCW-FW 150.060 END 18.202.19810.78%E70-24MCW-FW300.092RSS-24MCW-FW 300.092 END 18.202.19810.78%E70-24MCW-FW750.165RSS-24MCW-FW 750.165 END 18.202.19810.78%E70-24MCW-FW1100.220RSS-24MCW-FW1100.220 END 18.202.19810.78%E70-24MCWH-FW1350.300RSS-24MCWH-FW1350.300 END 18.202.19810.78%E70-24MCWH-FW1850.420RSS-24MCWH-FW1850.420 END 18.202.19810.78% END 18.202.19810.78%Speaker/Strobes (Ceiling Mount)Speaker/Strobes (Wall Mount) END 18.202.19810.78%E90-24MCC-FW150.065RSS-24MCC-FW 150.065 END 18.202.19810.78%E90-24MCC-FW300.105RSS-24MCC-FW 300.105 END 18.202.19810.78%E90-24MCC-FW750.189RSS-24MCC-FW 750.189 END 18.202.19810.78%E90-24MCC-FW950.249RSS-24MCC-FW 950.249 END 18.202.19810.78%E90-24MCCH-FW1150.300RSS-24MCCH-FW1150.300 END 18.202.19810.78%E90-24MCCH-FW1770.420RSS-24MCCH-FW1770.420 Totals0.885590End of Line Voltage 18.20 AMPS OUT AVAILABLE CURRENT3 OUT TOTAL CURRENT0.885 OUT SPARE CAPACITY =71% Current @Rated Voltage Current @Rated Voltage Model #Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 maVoltage TotalsTotalsTotals End of Line and Load Centering Methods use only the wire guage for the first device to source This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point MethodEnd of Line MethodLoad Centering Method Project NameSolaris Date6/25/2012 Circuit NumberRemote Power Supply #2 / RPS2-3 VoltageVoltageVoltage LocationGarage Level Partial Area 1CurrentDistanceDropCurrentDistanceDropCurrentDistanceDrop Nominal System Voltage20.41.074630 2.91 1.074630 4.317 1.074630 2.158 Minimum Device Voltage16End of Line Voltage 17.49 End of Line Voltage 16.08 End of Line Voltage 18.24 Total Circuit Current1.074WireOhm'sPercent Drop14.27%Percent Drop21.16%Percent Drop10.58% GaugePer 1000 Distance from source to 1st device280143.19 Wire Gauge for balance of circuit143.1918=7.7716=4.8914=3.1912=1.9810=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: DeviceDeviceprevious AtDrop fromPercentWire resistance is doubled in the calculations for two wires (Positive and Negative) NumberCurrentdeviceDevicesourceDropThe voltage calculated to the last device in any method must not be lower then Device 10.22028018.481.9199.40%the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 20.2207518.072.32711.41% Device 30.1656017.832.57012.60%Device ManufacturerWheelockDevice ManufacturerWheelock Device 40.1654517.702.70513.26% Device 50.0924017.622.78213.64%Candela Candela Device 60.0927017.522.87714.10%Speaker/Strobes (Wall Mount)Strobes (Wall Mount) Device 70.0603017.502.90014.21%E70-24MCW-FW150.060RSS-24MCW-FW150.060 Device 80.0603017.492.91114.27%E70-24MCW-FW300.092RSS-24MCW-FW300.092 END 17.492.91114.27%E70-24MCW-FW750.165RSS-24MCW-FW 750.165 END 17.492.91114.27%E70-24MCW-FW1100.220RSS-24MCW-FW1100.220 END 17.492.91114.27%E70-24MCWH-FW1350.300RSS-24MCWH-FW1350.300 END 17.492.91114.27%E70-24MCWH-FW1850.420RSS-24MCWH-FW1850.420 END 17.492.91114.27% END 17.492.91114.27%Speaker/Strobes (Ceiling Mount)Speaker/Strobes (Wall Mount) END 17.492.91114.27%E90-24MCC-FW150.065RSS-24MCC-FW 150.065 END 17.492.91114.27%E90-24MCC-FW300.105RSS-24MCC-FW 300.105 END 17.492.91114.27%E90-24MCC-FW750.189RSS-24MCC-FW 750.189 END 17.492.91114.27%E90-24MCC-FW950.249RSS-24MCC-FW 950.249 END 17.492.91114.27%E90-24MCCH-FW1150.300RSS-24MCCH-FW1150.300 END 17.492.91114.27%E90-24MCCH-FW1770.420RSS-24MCCH-FW1770.420 Totals1.074630End of Line Voltage 17.49 AMPS OUT AVAILABLE CURRENT3 OUT TOTAL CURRENT1.074 OUT SPARE CAPACITY =64% This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point MethodEnd of Line MethodLoad Centering Method TotalsTotalsTotals Model # End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 maVoltage Current @Rated Voltage Current @Rated Voltage Model # Project NameSolaris Date6/25/2012 Circuit NumberRemote Power Supply #2 / RPS2-4 VoltageVoltageVoltage LocationGarage Level Partial Area 1CurrentDistanceDropCurrentDistanceDropCurrentDistanceDrop Nominal System Voltage20.40.360595 0.98 0.360595 1.367 0.360595 0.683 Minimum Device Voltage16End of Line Voltage 19.42 End of Line Voltage 19.03 End of Line Voltage 19.72 Total Circuit Current0.360WireOhm'sPercent Drop4.82%Percent Drop6.70%Percent Drop3.35% GaugePer 1000 Distance from source to 1st device230143.19 Wire Gauge for balance of circuit143.1918=7.7716=4.8914=3.1912=1.9810=1.24 Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors from Notes: DeviceDeviceprevious AtDrop fromPercentWire resistance is doubled in the calculations for two wires (Positive and Negative) NumberCurrentdeviceDevicesourceDropThe voltage calculated to the last device in any method must not be lower then Device 10.06023019.870.5282.59%the manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Device 20.06010019.680.7203.53% Device 30.06011519.500.8964.39%Device ManufacturerWheelockDevice ManufacturerWheelock Device 40.0603019.470.9304.56% Device 50.0604519.440.9654.73%Candela Candela Device 60.0605019.420.9844.82%Speaker/Strobes (Wall Mount)Strobes (Wall Mount) Device 7RPS32519.420.9844.82%E70-24MCW-FW150.060RSS-24MCW-FW150.060 END 19.420.9844.82%E70-24MCW-FW300.092RSS-24MCW-FW300.092 END 19.420.9844.82%E70-24MCW-FW750.165RSS-24MCW-FW750.165 END 19.420.9844.82%E70-24MCW-FW1100.220RSS-24MCW-FW 1100.220 END 19.420.9844.82%E70-24MCWH-FW1350.300RSS-24MCWH-FW1350.300 END 19.420.9844.82%E70-24MCWH-FW1850.420RSS-24MCWH-FW1850.420 END 19.420.9844.82% END 19.420.9844.82%Speaker/Strobes (Ceiling Mount)Speaker/Strobes (Wall Mount) END 19.420.9844.82%E90-24MCC-FW150.065RSS-24MCC-FW150.065 END 19.420.9844.82%E90-24MCC-FW300.105RSS-24MCC-FW300.105 END 19.420.9844.82%E90-24MCC-FW750.189RSS-24MCC-FW750.189 END 19.420.9844.82%E90-24MCC-FW950.249RSS-24MCC-FW950.249 END 19.420.9844.82%E90-24MCCH-FW1150.300RSS-24MCCH-FW1150.300 END 19.420.9844.82%E90-24MCCH-FW1770.420RSS-24MCCH-FW1770.420 Totals0.360595End of Line Voltage 19.42 AMPS OUT AVAILABLE CURRENT3 OUT TOTAL CURRENT0.360 OUT SPARE CAPACITY =88% Current @Rated Voltage Current @Rated Voltage Model #Model # Standard Wire Resistance in Ohms per 1000 feet. Enter current in amps. .150 = 150 maVoltage TotalsTotalsTotals End of Line and Load Centering Methods use only the wire guage for the first device to source This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point MethodEnd of Line MethodLoad Centering Method PS-8 BATTERY CAPACITY CALCULATION FOR RPS2 OPERATION ON BATTERY BACKUP POWER DEVICE TYPE QTYSTAND-BY CURRENT QTYALARM CURRENT EACHTOTALEACHTOTAL RPS2-110.0000.00011.3801.380 RPS2-210.0000.00010.8850.885 RPS2-310.0000.00011.0741.074 RPS2-410.0000.00010.3600.360 00.0000.00000.0000.000 00.0000.00000.0000.000 00.0000.00000.0000.000 00.0000.00000.0000.000 MAIN PC BOARD 1 0.1290.129 1 0.1290.129 Number of Slave power Supplys 0 0.0060.000 0 0.0060.000 00.000 0.000 00.000 0.000 00.000 0.000 00.000 0.000 TOTAL CURRENT 0.1293.828 TOTAL CURRENT - STANDBY OPERATION0.129 HOURS REQUIRED FOR OPERATION 24.00 BATTERY STANDBY REQUIREMENTS3.10 TOTAL CURRENT - ALARM OPERATION3.828 HRS REQUIRED FOR OPERATION 0.083(5 MIN) BATTERY ALARM REQUIREMENT 0.32 TOTAL BATTERY REQUIREMENTS 3.42 BATTERY REQUIRED WITH 20% FACTOR 4.10 7 AMP-HOUR BATTERIES INSTALLED AMPS AVAILABLE CURRENT8 TOTAL CURRENT3.828 SPARE CAPACITY 52.15%